Ontario Fire Code SECTION 5.10 COMBUSTIBLE DUST PRODUCING PROCESSES. Illustrated Commentary. Office of the Ontario Fire Marshal

Similar documents
DUST COLLECTION TRAINING. Revision 2013

Objectives. NFPA Dust Specific Documents. Combustible Dust Process Hazard Safety Overview of NFPA Standards for Combustible Dusts

Combustible Dust Issues

Fire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY

Special Occupancy Requirements

Progressive Safety Services LLC 1

Prevention of Fires and Explosions in Wood Pellet Facilities. Allen Wagoner, FLAMEX, Inc.

1303 Trans Canada Way SE Medicine Hat, AB T1B 3Z9 Phone

COMBUSTIBLE DUST HAZARD MITIGATION

The correlating committee has revised the numbering in these sections to provide clarity for the next edition of the document.

INTRODUCTION TO DUSTS AND THEIR EXPLOSIVE PROPERTIES

Property risk solutions

Making sense of risk Risk engineering. Metalworking operations

NFPA 33 Standard for Spray Applica4on Using Flammable or Combus4ble Materials

ELECTRICAL SAFETY Information Bulletin

APPLICATION PROFILE EXPLOSIONS IN CEMENT PLANTS EXPLOSIONS IN CEMENT PLANTS CEMENT PLANT EQUIPMENT WITH HIGHEST EXPLOSION POTENTIAL. Form No.

FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION

Understanding. Combustible Dust Hazards: Basic Measures to Ensure the Safety of Combustible Dust Handling Operations

FLAMMABLE FINISHES CHAPTER 24

GASEOUS HYDROGEN SYSTEMS

Specifying a Dust Collector For a School Wood Shop

Demolition Permit Application (Please print and complete ENTIRE form)

Aluminum Dust Management in a Metallizing Facility

Dust Explosion Hazard Overview

Kice Dust Control System Design and Maintenance Basics Design, Maintenance, & Operation

COMBUSTIBLE DUST SAFETY PROGRAM

Industrial Dust Aspiration Solutions. For optimal protection of plant and environment.

(h) Pesticide Application.

AQ Translated English of Chinese Standard: AQ WORK SAFETY INDUSTRY STANDARD

ELECTRICAL SAFETY Information Bulletin

By Authority Of THE UNITED STATES OF AMERICA Legally Binding Document

Flammable and Combustible Liquids

LIMESTONE HANDLING AND LIME MILLING SYSTEM

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2000 EDITION

ADMINISTRATIVE SERVICES MANUAL

Introduction Airflow and filtration area General design practices Cleaning system

AUTOMATIC FIRE SUPPRESSION SYSTEMS

50 Years of Quality. Specifying a Dust Collector For a School Wood Shop

Prevention of Fires and Dust Explosions within the Biomass Handling Process. PFI July 20, 2015

First Revision No. 15-NFPA [ Chapter 2 ]

Combustible Dust Hazard Recognition and Control NFPA Standards for Combustible Dusts

General Design Practices in Reducing Risk in Grain Handling Facilities

CLEACOM Engineered System Solutions. Established 24/7 technology for the separation of dust and fume during compounding processes

Handling Petroleum Products & Static Ignition Hazards Introduction

Combustible Dust Hazards- Awareness

HeatExchangerSpares.com Ltd HRS Heat Exchangers Ltd HRS Hevac Ltd HRS Hevac Engineering Ltd HRS International Ltd HRS Investments Ltd

Hot Work Permit. Can this job be avoided? Is there a safer alternative? Permit No.:

Spray Painting and Coating

PRELIMINARY REVIEW OF APPLICABLE CODES AND STANDARDS, PROCESS HAZARD ANALYSIS AND OPERATIONAL FIRE SAFETY PLAN

ROTARY DRYER CONSTRUCTION

REFERENCES TO ICC ELECTRICAL CODE - ADMINISTRATIVE PROVISIONS IN THE INTERNATIONAL BUILDING CODE

Conducting a NFPA 652 Dust Hazard Analysis (DHA): Practical Tips & Approaches

Overview of Hazardous Locations as They Relate to Solenoid Valves

PRIMATECH WHITE PAPER PROCEDURE FOR DUST HAZARD ANALYSIS (DHA)

c SAFETY CONSIDERATIONS FOR USING POWDER COATINGS

Camden County Fire Rescue Office of the Fire Marshal 125 N. Gross Road, Kingsland, GA

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST

This Second Correlating Revision effects correct usage. This also addresses one of the Affirmative Comments to Second Revision No. 28.

Safe Operating Procedure

venting method will work for all pressure conveying systems, analyzing your available equipment, your material s characteristics, and your conveying c

Introduction. Program Description. Section C.20 University of South Carolina Safety Program Guide FLAMMABLE AND COMBUSTIBLE LIQUIDS

The AST Dryer

FX5 Series Explosion-Proof Electric Air Heaters

Fire Hazard Identification Checklist 1

ELECTRICAL SAFETY Information Bulletin

Flammable and Combustible Liquids Checklist

DuPont Formacel Z-2. Safety and Handling of DuPont Formacel Z-2: Thermoplastic* Foam Extrusion Applications FOAM EXPANSION AGENT TECHNICAL INFORMATION

Notable Changes in the Mechanical Codes

OBC INDUSTRIAL CLASSIFICATION OBOA ANNUAL MEETING AND TRAINING SESSIONS LONDON ON OCTOBER 4, 2011

FlexFilter EX A state of the art filter system to meet your current and future needs

Industrial Explosion Suppression Technology

Part I Extraction Process Equipment

1.2 To ensure the safety of all persons working in or occupying a building where a hot work operation is performed.

M E M O R A N D U M. The Technical Correlating Committee on Boiler and Combustion Systems Hazards

Above Ground Fuel Tank Requirements

Explosion Prevention & Suppression James Maness JEM Safety Consulting Rehoboth, DE.

WATER WASH BOOTHS PUMP TYPE PUMPLESS TYPE

Fire Hazard Identification Checklist 1

OUTDOOR INSTALL NO RETURN AIR SINGLE MODULE COLLECTORS OUTDOOR INSTALL WITH RETURN AIR SINGLE MODULE COLLECTORS

Introduction to the Exhaust Fan Interceptor Commercial Exhaust Fans from a Service Perspective

10 Considerations for Pneumatic Conveying System Design: What Most Engineering Schools Didn t Teach You

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

INSTALLATION INSTRUCTIONS FOR THROUGH-THE-WALL VENTING COMPONENTS

The element is closed at one end and open at the other, and it s bolted onto the explosion vent opening on the equipment so that its open end overlaps

Clean. Easy. COMPLIANT.


ALUMINUM REPAIR CERTIFICATION EQUIPMENT. Eliminate hazardous aluminum dust with a Eurovac system. BODY REPAIR CERTIFICATION EII Wet Mix Dust Collector

CE Unit is suitable for material transport. The transported gas may be up to 80 C.

Engineering and Work Practice Control Methods

Efficient Vacuum Conveyors Deliver Cost-Effective Solutions Pick-up, conveying and feeding of powders, granules and other bulk materials

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

Reducing the Cost and Risk of Dust Collection in Coal

Wood Dust Mitigation and Control Audit Auditor Worksheet, Questionnaire and Guideline

Dust Collectors. Unique Design & Engineering Approaches for Dust Collection and Pneumatic Conveying

Integrated Ventilation System

EUTECTIC EC-10DV Series

Understanding and Applying the Science: A Case Study in Eliminating Process Fires. K. Gerry Phillips, P.Eng, MCIC NOVA Chemicals Corporation

Managing Combustible Dust

Chapter FUEL GAS CODE*

TABLE OF CONTENTS PART 4 - HAND TOOLS AND POWER DRIVEN PORTABLE TOOLS

Transcription:

Ontario Fire Code SECTION 5.10 COMBUSTIBLE DUST PRODUCING PROCESSES Illustrated Commentary Office of the Ontario Fire Marshal

Combustible Dust Illustrated Commentary 1 Mechanical Exhaust Systems 5.10.1.1. Machinery that produces, agitates or conveys combustible dusts shall have or be connected to a mechanical exhaust system to the outside atmosphere and dust-tight casings or enclosures. The intent of this Article is covered by Article 5.10.1.3. Combustible dust means dust and particles ignitable and liable to explode when mixed with air.

2 Illustrated Commentary Combustible Dust Mechanical Exhaust Systems 5.10.1.2.(1) Building and machinery surfaces shall be kept clean by a vacuum apparatus listed and labelled for use in atmospheres containing combustible dusts. (2) The vacuum cleaning machine required in Sentence (1) and ancillary piping, suction hose and tools shall be electrically conductive and grounded. (3) Compressed air or other compressed gases shall not be used to blow dust from surfaces inside buildings. Surfaces in buildings and on machinery must be cleaned with a vacuum which is listed and labeled for use in atmospheres with combustible dusts. If you are unable to tell the colour of the surface, it needs to be cleaned often. If dust deposits are thicker than a paperclip (1/8 ), the surfaces need to be cleaned. Vacuums, ancillary piping, suction hose and tools must be electrically conductive and grounded. Inside buildings, the dust on surfaces must be cleared without the use of compressed air or other compressed gases. Under no circumstances should dust be blown off surfaces. Yes No Do not use compressed air or other compressed gases Building means any structure used or intended for supporting or sheltering any use or occupancy. Combustible dust means dust and particles ignitable and liable to explode when mixed with air. Compressed gas means any contained mixture or material with either an absolute pressure exceeding 275.8 kpa at 21ºC or an absolute pressure exceeding 717 kpa at 54ºC, or both, or any liquid having an absolute vapour pressure exceeding 275.8 kpa at 37.8ºC. Listed means equipment or materials included in a list published by a certification organization accredited by the Standards Council of Canada.

Combustible Dust Illustrated Commentary 3 Dust-Collecting Equipment 5.10.1.3. Dust-collecting equipment shall be installed where necessary to keep the accumulation of dust at a safe concentration in the interior of the building. In order to reduce the fire and explosion hazards associated with combustible dust, dust collecting equipment consisting of suction ducts and inlets, air moving equipment, feeders, discharge ducts and outlets, collecting equipment, vaults, and other receptacles designed to collect powdered, ground, and finely divided combustible material shall be provided. Dust filters Fan Building means any structure used or intended for supporting or sheltering any use or occupancy.

4 Illustrated Commentary Combustible Dust Dust-Collecting Equipment 5.10.1.4.(1) Dust-collecting systems shall be made of noncombustible material. (2) Dust-collecting systems shall be of a design that will prevent sparks due to physical contact in the fan assembly. Dust-collecting systems must be made of noncombustible material and be designed to prevent sparks when foreign materials come in contact with the fan. Systems that convey combustible dust should be positioned so that the fan is situated on the clean air side of the collector. This allows the system to operate under suction and dust is collected before the air stream reaches the fan. This arrangement prevents combustible dust from passing through the fan where it could be ignited by a spark. As an alternative, where the fan is situated between the dust-producing equipment and the collector, the blades and spider of the fan and fan housing should be made of non-sparking material (Illustration A). Fan bearings and motor should be outside of casings unless the fan and motor are designed for use in dust type atmospheres (Illustration B). Illustration A Illustration B Gap between fan and casing Fan and motor mounted in a duct The entire fan unit has been designed for use in dust type atmospheres

Combustible Dust Illustrated Commentary 5 Dust-Collecting Equipment 5.10.1.5.(1) Except where specially designed and manufactured for internal use, dust-collectors shall (a) be located outside buildings, or (b) be equipped with exhaust stacks or ducts leading to the outside. This Article recognizes that the preferred location for dust collectors is outside. However it does permit dust collectors to be located within a building provided the dust collector has been designed for installation indoors. Fan Building Air flow Ducts Bag house Dust collector Cyclone Machinery Building means any structure used or intended for supporting or sheltering any use or occupancy.

6 Illustrated Commentary Combustible Dust Grounding 5.10.1.6. Electrically conducting paths of duct systems, dust-collectors and the machines they serve shall be grounded. To prevent a build-up of static electricity, equipment is grounded by running one or more wires between each component of the dust-collecting system and then grounding the wire to the earth. Fan Hopper Filter Copper wire is securely fastened to the equipment and then grounded to earth, for example by attaching it to a metallic water pipe or other object connected with earth.

Combustible Dust Illustrated Commentary 7 Explosion Venting 5.10.1.7. Except as provided in Article 5.10.1.11., manufacturing activities that produce, agitate, or convey combustible dusts shall be located only in buildings which have explosion venting to the outdoors. Except as provided in Article 5.10.1.11., buildings where combustible dusts are located must have explosion venting to the outdoors. There are a variety of explosion venting techniques. Explosion hatches or light lift off roof covering Explosion panels or light wall construction Hinged windows or flaps Combustible dust means dust and particles ignitable and liable to explode when mixed with air. Building means any structure used or intended for supporting or sheltering any use or occupancy.

8 Illustrated Commentary Combustible Dust Explosion Venting 5.10.1.8. Dust-collectors within buildings shall be designed with explosion venting to the exterior. Dust collectors within buildings must have explosion venting to the outdoors. Explosion vents should be located close to an outside wall and be vented through a short, straight duct directly outside. Wall Feed hopper Explosion relief Vent Grinder Cyclone collector Building means any structure used or intended for supporting or sheltering any use or occupancy.

Combustible Dust Illustrated Commentary 9 Interlocks 5.10.1.9. Equipment required to have a dust exhaust system shall not be capable of operating until the dust exhaust system is in operation. A system of interlocks should be provided to ensure that equipment requiring a dust-exhaust system will not start up until the exhaust system starts. For example, if the exhaust fan is not in operation, the dust producing equipment will not start. From power supply Dust exhaust system Dust producing machinery Switch 1 Switch 2 A simple illustration of an interlock where switch 1 must be engaged to operate the dust exhaust system before switch 2 can provide power to the dust producing machinery.

10 Illustrated Commentary Combustible Dust Air Velocity 5.10.1.10. Dust-collector systems shall be designed for an air velocity in the ducts of at least 1068 m/min. Dust-collecting systems must have an air velocity of at least 1068 m/min. The air velocity keeps the particles in suspension and moving within the ducts. Particles are suspended Air velocity at least 1068 m/min Build-up of dust particles Air velocity < 1068 m/min

Combustible Dust Illustrated Commentary 11 Vent Stacks 5.10.1.11.(1) Permanently open vent stacks may be used to ventilate storage containers where mechanical dust-collector systems are not practical, provided that the vent stacks (a) have a cross-sectional area not less than twice that of spouts discharging into the container, (b) are installed not more that 30 degrees from the vertical, (c) extend from the top of the container to a point not less than 1.2 m above the roof, and (d) are designed to prevent the entry of snow and rain. Weather protection hood Vent stack must be no more than 30 o from the vertical Not less than 1.2 m Roof of building

12 Illustrated Commentary Combustible Dust Separators 5.10.1.12. Magnetic and pneumatic separators shall be installed to prevent the entrance of foreign materials that may cause sparks in equipment such as shellers, crackers, crushers, grinding machines, pulverizers or similar machines that produce combustible dusts. Magnetic and pneumatic separators are required to be installed to collect ferrous metals that can cause sparks in equipment that produce combustible dust. In a magnetic separator, magnets attract and separate the metalic foreign objects from the desired materials. In a pneumatic separator the air current intake is adjusted to convey the desired material and reject heavier unwanted material. Magnetic separator Pneumatic separator Truck Grain chute Magnets collect ferrous metal objects Magnets Reject chute for undesired material Desired material Air intake Combustible dust means dust and particles ignitable and liable to explode when mixed with air.

Combustible Dust Illustrated Commentary 13 Grounding 5.10.1.13. Machinery and metal parts of the equipment in Article 5.10.1.12. and related conveying systems shall be electrically grounded. Similar to the requirements for grounding under Article 5.10.1.6., machines that produce combustible dust, conveying systems and their metal parts must be electrically grounded to prevent sparks from occurring due to static electricity. Conveyor Metal chute Copper cable grounding machinery Copper cable bonding machinery The machinery and metal parts can be grounded individually or bonded together and electrically grounded.

14 Illustrated Commentary Combustible Dust Ignition Sources Prohibited 5.10.1.14. Smoking, open flame and spark-producing equipment shall not be allowed in areas containing combustible dust producing operations. The purpose of this requirement is to ensure that sources of ignition are not in an area containing combustible dusts. Smoking, open flame and spark-producing equipment is not allowed in areas where combustible dust is produced. No-smoking signs should be posted in all operational areas. For welding and cutting operations, a hot work permit system should be in place. Electrical equipment and machinery must be of a type designed for use in areas containing combustible dust. No smoking signs Ignition sources Combustible dust means dust and particles ignitable and liable to explode when mixed with air.

Combustible Dust Questions and References 15 Q1 A1 What is meant by combustible dust? Combustible dust means dust and particles ignitable and liable to explode when mixed with air. Q2 Where should dust-collecting equipment be installed? A2 Refer to Ontario Fire Code 5.10.1.3. Q3 What features must dust-collecting systems have? A3 Refer to Ontario Fire Code 5.10.1.4.(1) and (2). Q4 What minimum air velocity is required for dust-collecting systems? A4 Refer to Ontario Fire Code 5.10.1.10. Q5 What is the purpose of magnetic and pneumatic separators? A5 Refer to Ontario Fire Code 5.10.1.12. Q6 What preventative measures must be taken with respect to ignition sources in areas containing combustible dust? A6 Refer to Ontario Fire Code 5.10.1.14.