INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS BG 2000-S (V13) RU PL DE IT ES NL EN 1 662Y0600 A

Similar documents
BG2000S PRE-MIX GAS BURNER

HeatMaster. Installation, operating and servicing instructions. HeatMaster 71 HeatMaster 101 HeatMaster 201 ENGLISH FRANCAIS NEDERLANDS ESPAÑOL

Installation, operating and servicing instructions

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

INSTALLATION AND MANINTENANCE INSTRUCTIONS

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

Installation, operating and maintenance instructions

A/23 MFFI - A/27 MFFI

Open Vented Condensing Boilers

Installation, Operating and Servicing Instructions

Q - Series Boiler. Troubleshooting Manual

Servicing Instructions Type C Boilers G.C.N: LEAVE THESE INSTRUCTIONS ADJACENT TO THE GAS METER

User Manual FLOWMAX-90. for model. Condensing water heater 85,000 BTU. Installation, operating, commissioning and maintenance instructions.

ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL

Prestige. Prestige Solo Prestige AquaSpeed Prestige Excellence Installation, Operating and Servicing Instructions

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A

Great Britain en. Installation, user and service manual. Control panel HMI Gas 310/610 ECO PRO

Servicing manual. Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C /2002 GB(EN) For trade use

Servicing manual. 600 Series - 11S / 19S / 24S / 24C. Wall-mounted condensing gas boiler. For trade use

This appliance must be installed and serviced by a competent person as stipulated by the

MAINTENANCE AND SERVICE GUIDE

SERVICE MANUAL RIVA COMPACT M90E.24S M90E.28S M90E.32S Wall hung, fan flue, room sealed gas boiler

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS. HeatMaster TC 664Y6800 A

Forced draught gas burner

Service manual RIVA ADVANCE HE M110.24SM/C M110.32SM/C Wall hung, fan flue, room sealed, high efficiency gas boiler

ProCon Streamline Gas Condensing Boiler. Installation and Operating Manual.

User Manual for model

Mikrofill Ethos Condensing combination boiler. Maintenance Instructions 24cc

HeatMaster 25 C. Installation, operating and maintenance. excellence in hot water 664Y4500 E

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS,

Light oil burners. One stage operation

Parts Available from

User Manual for model RK 18 RK 25 RK 34 CE 0694 RK 18_25_34 - RAD - ING - MAN.UT A - DIGITECH 2 - REGNO UNITO - EXTRAHEAT - CBD

NH DV NH DV

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND

User Manual RBS 24. for model CE series ENERGY. Wall mounted instantaneous combi boiler room sealed chamber

WHE 2.24 / WHE 2.24 FF

O. Gas boiler. Gaz 6000 W WBN H-E-N/L-S2400. Operating instructions for the end customer (2017/09) en

BENSON LINEAR RADIANT TUBE

CONVERSION TO PROPANE MANUAL M-Series Condensing Boiler. Wall-Mounted, Gas-Fired Boiler

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-SOLO-9/04

PowerVent. Installation manual (GB) English. Store this document in a safe place UK

Service Manual 3 Heater MPS & AUTO EMS Vol 1 of 2 Approved Issue 10 Printed 13/02/ :52:21 AM 1

Conversion Instructions Logano G234X. Gas boiler. Please read carefully before installing and servicing. Gas boiler

Oil burners Brûleurs fioul Stookoliebranders

Gas Instantaneous Water Heater

Service manual GARDA HE MK2. M96A.24SM/B Combi boiler M96A.28SM/B Combi boiler

User Manual for model

T UNI 7000 F. Operating instructions For the user (2006/05) AU/GB

Operating instructions

INSTALLATION AND OPERATION MANUAL

Synergy Grill User & Engineer Installation & Conversion Guide

VIESMANN. Installation and service instructions VITODENS 111-W. for contractors

Indirect gas-fired air heater

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS, for the User and the Installer. SMART Line. Smart ME A Y2000 B

Installation, operation and maintenance instructions. HRi Y1300-A

CAST IRON ATMOSPHERIC BOILERS

Light oil - kerosene burner

Service manual RIVA COMPACT HE M96.24SM/C M96.28SM/C M96.32SM/C M96.24SR/C2 M96.28SR/C

GB24 & GB30. User Manual

Operating instructions

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

12.0 Servicing. Electrode Position Fig Annual Servicing Inspection (Cont) 4 ±0.5

VIESMANN. Operating instructions VITODENS 050-W. for the system user. With constant temperature or weather-compensated control unit

Operating instructions

GAS FIRED ATMOSPHERIC ELECTRONIC VERSION kw

Forced draught gas burner

INSTRUCTION MANUAL FOR OIL BURNER MODELS

INSTRUCTION MANUAL FOR OIL BURNER MODELS

LEIHDC70SC - LEIHDC70BB LEIHDC70BC. Instructions Manual.

MODENA 38C HE INSTRUCTIONS FOR USE, INSTALLATION AND MAINTENANCE MODENA 38 C HE GC N cod. 3541G612 Rev /2017

R e m e h a P Technical Information. Remeha P 300. Pressurized boiler. Heat output: kw

Light oil / kerosene burner

Service manual. Riva Plus HE. M296.28SR/C System boiler. Wall hung, fanflue, roomsealed, high efficiency gas boiler

SMART Line Smart E

Operating instructions

AUS. Format 34I-34E BF

TermEfekt USER S MANUAL AIR HEATER. Model PGA 14

Service booklet for the Engineer for Gas Condensing Boilers

INSTALLATION INSTRUCTIONS SAFETY INSTRUCTIONS USER INSTRUCTIONS PARAGON GAS SALAMANDER

HVG620 & HVG720 Gas Hob Manual for Installation, Use and Maintenance

Installation, operating and maintenance instructions

DOMESTIC HOT WATER Follow operational sequence

E1808, E1838, E1848 DEEP FAT FRYER INSTALLATION, SERVICING and USER INSTRUCTIONS

ENERGY TOP. Condensing boiler solutions

RL/1 SERIES. One Stage Light Oil Burners FIRING RATES LIGHT OIL RL 34/1 MZ kw

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-PRESTIGE Date revised: 11/10/08

Installation, Operating and Servicing Instructions

ProCon Boiler Controller Commissioning Quick Reference Guide

SIGMA. Wall Mounted Cast Iron, Gas Fired Boiler for Central Heating Fan Assisted, Room Sealed, Electronic Flame Ignition and Control

15 20 kw kw kw

NIKE Star 24 3 E. Instantaneous wall-hung with open chamber boilers. NIKE Star 24 3 E

VIESMANN. Installation and service instructions VITODENS 050-W. for contractors

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS,

Baxi Maxflow Combi WM

Gas burner automatic safety control MMI / 811.1

Figure 10 or Figure 6

TABLE OF CONTENTS TECHNICAL DOCUMENTATION 03. Technical Data

VIESMANN. Installation and service instructions VITODENS 050-W. for contractors

Transcription:

INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS G 2000-S 25-35 - 45-55 60-70 - 100 (V13) 1

Index WARNINGS GAS FLOW RATE DIMSIONS SETTINGS PARAMETERS SERVICING THE URNER 3 8 13 OPERATING DESCRIPTION - URNERS 4 G 2000-S 25 / 35 / 45 / 55 / 60 / 70 5 G 2000-S 100 6 FITTING THE URNER 5 7 FAN SETTING PROCEDURE URNER WIRINGS G 2000-S 25 / 35 / 45 / 55 / 60 / 70 10 G 2000-S 100 11 ELECTRODES ADJUSTEMT URNER COMPONTS 9 10 12 FAULT-FINDING PROCEDURES Fault table 14 Table of corrective 15 PROPANE CONVERSION 14 Assembling and dismantling the kit 16 Parameters of adjustment if you convert the burner 17 16 2

Warnings WHO SHOULD READ THESE INSTRUCTIONS These instructions should be read by: - the design engineer/consultant - the user - the installer - the service engineer CERTIFICATION The products have received CE certification in accordance with the standards in force in various countries (European Directives 92/42/EEC "efficiency requirements", 2009/142/EC "gas appliances"). SYMOLS The following symbols are used in this manual: Essential instruction for the correct operation of the installation IMPORTANT NOTES RECOMMDATIONS Essential instruction for the safety of persons and the environment Electrocution hazard: use a qualified technician Carefully read this manual before installing and bringing the boiler into service. It is prohibited to modify the interior of the appliance in any way, without the manufacturer s prior written agreement. The product must be installed by a qualified engineer, in accordance with the applicable local standards and codes. Failure to follow the instructions describing test operations and procedures could result in personal injury or a risk of environmental pollution. In order to ensure the appliance operates safely and correctly, it is important to have it serviced by an approved contractor. If there is a problem please contact your contractor for advice. In spite of the strict quality standards that ACV applies to its appliances during production, inspection and transport, faults may occur. Please notify your approved contractor immediately of any faults. Defective parts can only be replaced with original factory parts. efore carrying out any work on the boiler, it is important to isolate the electrical supply to the unit. The user must not attempt to gain access to the components inside the boiler or the control panel. This appliance is not intended for use by persons with reduced physical, sensory or mental capacities, or lack of experience and knowledge (including children), unless they have been supervised or instructed concerning use of the appliance by a person responsible for their safety. If you smell gas : - Isolate the gas supply immediately. - Ventilate the room (Open the windows). - Do not use electrical appliances and do not operate switches. - Notify your gas supplier and/or your installer immediately. These instructions are an integral part of the equipment to which they relate and must be left for the user. The product is to be installed and serviced by qualified technicians, in accordance with current regulations. The manufacturer declines all liability for any damage caused as a result of incorrect installation or in the event of the use of appliances or accessories that are not specified by the manufacturer. The manufacturer reserves the right to change the technical characteristics and features of its products without prior notice. The availability of certain models as well as their accessories may vary according to markets. 3

Operating The G 2000-S burner is fitted with a gas valve venturi assembly, an electronic controller, a fan, a flame holder and lighting and ionisation electrodes. CONTROLLING THE AIR GAS MIXTURE As the fan sucks in air through the venturi, a drop in pressure (P1) is produced in the neck of the venturi. The gas valve regulator then reacts to maintain a pressure differential equal to the offset value between the pressure at the gas valve outlet (P2) and atmospheric pressure (P3): P2 P3 = offset If the air flow decreases, P1 increases; the same occurs for P2; P2 is then >P3; the regulator R is moved higher to make P2 offset = P3; pressure P4 falls and the valve C is turned down: the gas flow decreases. y careful adjustment of the offset, an air gas pressure ratio of 1 is obtained, regardless of the fan speed. The pressure differential between the venturi neck and the gas valve outlet then causes gas to be sucked through the venturi. The gas flow adjustment screw can be used to adjust the quantity of gas injected for a given air flow, which will set the % CO 2 in the flue gas. A given output can then be set simply by adjusting the speed of rotation of the fan and the % CO 2 to preset values. Functional diagram 1 7 2 C P4 P3 R 1. Air 2. Gas 3. Venturi 4. Fan 5. Offset adjustment screw 6. Gas flow a adjustement screw (CO 2 ) 7. Air - gas mixture 5 P1 3 4 P2 6 LIGHTING AND FLAME CONTROL The burner control unit performs the tasks of lighting the burner by producing a spark at the ignition electrode, and maintaining the flame when the gas valve is opened by measuring the ionisation current. The lighting sequence is shown in the diagram below: When the boiler thermostat detects a demand for heat, the fan starts; after 10 seconds of preliminary flushing, the gas valve is opened and simultaneously a spark is produced. If an ionisation current is detected in the first 5 seconds, combustion occurs normally until the end of the demand. If not, the gas valve is closed and the fan stopped, the burner being in safety mode. It must then be reset manually before lighting is attempted again. Sequence of starting G 2000-S 25 / 35 / 45 / 55 / 60 / 70 G 2000-S 100 Ionisation Spark Gas valve opens Fan 0 5 10 15 20 Sec. Pre-ignition Thermostat Ionisation Spark Gas valve opens Fan 0 5 10 15 20 Sec. Pre-ignition Thermostat 4

Description - burners G 2000-S 25 / 35 / 45 / 55 / 60 / 70 1. urner 2. Ignition electrode 3. Gas valve 4. Venturi 5. urner chamber plate seal 6. urner chamber plate insulation 7. Ionisation electrode 8. Fan 9. urner chamber plate 10. Flame inspection window 11. urner plug 12. Potentiometer setting 13. Fan power plug 14. urner control 15. Gas supply G 2000-S 25 / 35 / 45 / 55 / 60 / 70 6 3 2 1 14 15 7 5 12 4 8 9 10 13 11 5

Description - burners G 2000-S 100 1. urner 2. Ignition electrode 3. Gas valve (2x) 4. Venturi (2x) 5. urner chamber plate seal 6. urner chamber plate insulation 7. Ionisation electrode 8. Fan G 2000-S 100 9. Flame inspection window 10. urner chamber plate 11. urner plug 12. Potentiometer setting 13. Fan power plug 14. urner control 15. Gas supply 16. Air box 6 4 2 1 3 16 7 5 15 12 8 9 10 13 14 11 6

Fitting the burner 1 2 3 4 5 6 7 8 Adjust the CO 2 (see page 8) 7

Gas flow rate Measure burner combustion using an electronic flue gas analyser. Adjust the % CO 2 to the value given in the setting parameter table by turning the gas flow adjustment screw (1, illustration R): anticlockwise for increased flow (rise in %CO 2), clockwise for decreased flow (tall in % CO 2). 2 Venturi & gas valve 1. Gas flow adjustement screw (CO 2 ). 2. Pressure offset measurement. 3. Upstream gas pressure measurement. 4. Offset adjusting screw cover (Never touch this screw!) 4 Warning! To respect the parameters of the offset adjustement mentioned again in the table above. Settings parameters urners G 2000-S / 25 G 2000-S / 35 G 2000-S / 45 G 2000-S / 55 oilers Delta Performance 25 Delta Pro 25 Delta Performance 35 Alfa Sprint S / SV HeatMaster 30 N Delta Performance 45 Delta Pro 45 Delta Performance 55 Delta Pro 55 Output kw Note: The offset value is set at the factory. The burner can only be fitted to one of the boilers in the table above. 1 3 G20 - G25 % CO 2 Rpm max. G31 % CO 2 Rpm max. 25,0 9,0 3400 11.0 / 11,2 3100 34,9 9,0 4150 11.0 / 11,2 3760 45,0 9,0 4400 11.0 / 11,2 4000 55,0 9,0 4100 11.0 / 11,2 3700 G 2000-S / 60 HeatMaster 60 N 69,9 9,0 4600 11.0 / 11,2 4170 G 2000-S / 70 HeatMaster 70 N 69,9 9,0 4600 11.0 / 11,2 4170 G 2000-S / 100 85 kw HeatMaster 100 N 85,0 9,0 4600 11.0 / 11,2 4170 G 2000-S / 100 107 kw HeatMaster 100 N 107,0 9,5 5900 11.0 / 11,2 5440 8

Fan setting procedure FAN ROTATION SPEED (Rpm) 1. Remove the green protective disk 2. Release the clips of the fan motor cover. 3. Remove the cover protection of the fan. 4. Adjust the speed of the fan using the settings in the table underneath rotate counter clockwise to reduce and clockwise to increase the fan speed once the fan is adjusted please remount the fan motor cover. 9

urner wiring G 2000-S 25 / 35 / 45 / 55 / 60 / 70 S3 T2 T1 N L1 4 1. Power supply plug 2. Fan supply 3. urner control supply 4. Internal connection 230 V ~ 50HZ L1 N T1 T2 S3 4 1. lue k. lack r. rown R. Red Y/Gr. Yellow / Green r k L1 PE N Y/Gr r R T1 T2 S3 4 k r R 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 3 Y / Gr r 3 2 1 2 If on the control panel the warning-light: urner lock-out continuously lights up as the burner runs, please check if on the boiler-connector the bridge between 12 and 15 (for jet-burners) is replaced by the bridge 15 and 16 (for G 2000-S) See also installation manual: "HeatMaster 30 N / 60 N / 70 N". k 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 9 10 11 12 13 14 15 4 8 16 10

urner wiring G 2000-S 100 S3 T2 T1 N L1 230 V ~ 50HZ 4 1. Power supply plug 2. Connector box 3. Earth connection 4. Ignition transformer 5. Ignition cable 6. Fan supply 7. Gas valve supply 3 4 r Y/Gr 5 r Y / Gr r r 1 3 2 1 6 r r L1 Y/Gr k N L1 PE N r V T1 V T2 k S3 4 T1 T2 S3 4 1 2 3 4 5 6 7 8 9 S1 A PE PE PE N N N C S2 Y/Gr Y/Gr Y/Gr If on the control panel the warning-light: urner lock-out continuously lights up as the burner runs, please check if on the boiler-connector the bridge between 12 and 15 (for jet-burners) is replaced by the bridge 15 and 16 (for G 2000-S) See also installation manual: "HeatMaster 100 N". Y/Gr r Y/Gr r. lue k. lack r. rown V. Violet Y/Gr. Yellow / Green 2 7 11

Electrodes adjustement 4-6 mm : G 2000-S / 35 HM 30 N 8-12 mm : G 2000-S / 25 / 45 / 55 / 60 / 70 / 100 3 +1 0 urner components Description Model reference Code S4965 A 2058- (G 2000-S / 25-35 - 45-55 - 60-70) 537D8185 urner control : Honeywell DKG 972-N-mod28 (G 2000-S / 100) 537D8189 RG 148 1200 3612 (G 2000-S / 25-35 - 45-55 - 60-70) 537D3008 Fan : MVL RG 148 1200 3633 (G 2000-S / 100) 537D3037 VK4115V2038U (G 2000-S / 25-35 - 45-55 - 60-70) 537D4073 Gas valve : Honeywell VK4115V1014 (G 2000-S / 100) 537D4009 VF-002 45900444-002 (G 2000-S / 25 / 35 HM 30 N ) 537D4034 Venturi : Honeywell VF-001 45900444-001 (G 2000-S / 45) 537D6038 VF-051 45900446-501 (G 2000-S / 55-60 - 70-100) 537D4028 Ø 63 mm L. 287 mm (G 2000-S / 35 HM 30 N) 537DZ004 Ø 63 mm L. 224,5 mm (G 2000-S / 25-35 - 45) + NIT 537DZ017 urner : Furigas Ø 63 mm L. 313,5 mm (G 2000-S / 55-60 - 70) + NIT 537DZ029 Ø 98 mm L. 372 mm (G 2000-S / 100) + NIT 537DZ019 12

Dimensions URNER A C A G 2000-S / 25 228 209 307 G 2000-S / 35 HM 30 N 290 228 248 G 2000-S / 45 228 209 307 G 2000-S / 55 317 209 307 G 2000-S / 60 317 228 248 C G 2000-S / 70 317 248 342 G 2000-S / 100 376 248 342 Servicing the burner 1. After removing the burner, check the condition of the ignition (A) and ionisation () electrodes, insulation (C) and burner chamber seal (D). Change them if necessary. 2. Check the condition of the flame holder (E). 3. Refit the burner and check that the burner lights. 4. Check the gas connection for leaks. 5. Ensure correct combustion. C A E G 2000-S D 13

Fault-finding procedures FAULT TALE Condensation in chimney : Smell of flue gas : Insufficient heating : urner switches to safety mode after lighting : Circulator : Not enough hot water : Circulator does not turn : urner does not light : Manual reset safety thermostat has actuated : Corrective measures Problems Reasons Chimney cold and/or not lined 1 oiler T set too low 2 Chimney blocked 3 ack draught in chimney 3 oiler room vents insufficient or nonexistent 4 oiler clogged 5 urner clogged 5 Room thermostat T set too low 6 Circulator blocked or faulty 7 oiler switch in Summer position or faulty 8 Not enough water in the system 9 Radiator valves closed 10 Air in the system not vented properly 9 Gas pressure insufficient 11 Gas pipe too small 11 oiler thermostat is faulty 12 Electrical system not earthed (properly) 13 The system fuses have blown 14 Air in the system and/or boiler not vented properly 9 Interval for large drawoff is too short 15 Drawoff flow rate is too high 15 Room thermostat not in demand or faulty 16 Summer/Winter switch faulty 17 On/Off switch faulty or not on 18 95 C limit thermostat has activated 12 Manual reset safety thermostat has activated 19 urner fan faulty 20 Lighting electrode faulty or badly adjusted 21 Ionisation electrode faulty or badly adjusted 21 urner connectors not plugged in properly 22 Gas valve does not open 23 oiler thermostat faulty 12 Air in top of boiler not vented properly 9 14

TALE OF CORRECTIVE Corrective measures Fit lining in chimney 1 Set boiler T higher 2 Check and clean chimney 3 Comply with local regulations on boiler room ventilation 4 Clean burner and boiler 5 Set room thermostat to desired temperature 6 Clear or replace the circulator 7 Set switch to Winter position or replace switch 8 Fill and vent the system and boiler properly 9 Open radiator valves or adjust thermostatic valves 10 Check that pipes and meter are suitable for the system 11 Replace boiler thermostat 12 Ensure electrical system complies with the regulations 13 Change fuses and find out what caused the problem 14 Keep within the ratings stated by ACV 15 Set the thermostat to the desired temperature or replace 16 Replace Summer/Winter switch 17 Replace On/Off switch 18 This is not normal, find the cause 19 Replace fan 20 Replace electrode or adjust properly 21 Insert connectors properly 22 Replace gas valve ensuring setting parameters are correct 23 This table may be used after instruction received at ACV 15

Propane conversion ASSEMLING AND DISMANTLING THE KIT 1. Switch off the boiler and disconnect it from the mains. 2. Remove the combustion chamber door and the burner from the boiler. 3. Remove the relay (1 screw, fig. 1). 4. Remove the valve - venturi unit from the fan (2 Torx screws, see fig. 2). 5. Remove the venturi from the valve (3 Torx screws, fig. 3). 6. Fit the right diaphragm (see table on page 3) to the centre of the joint of the valve and the venturi (fig. 4). 7. Refit the burner proceeding in reverse assembly order. 8. Power on and start up the boiler. 9. Adjust the fan speed and the % of CO 2 using the pressure regulator (fig. 5, marked A) referring to the table (page 17). Use a torx screwdriver ref. TX 25-100. Adjust the % of CO 2 using a combustion device. 1 3 5 6 Never touch this screw! 2 4 16

PARAMETERS OF ADJUSTMT IF YOU CONVERT THE URNER Alfa Sprint S / SV 35 Delta Performance G35 HeatMaster 30 N Delta Performance G25 Delta Pro G25 Delta Performance G45 Delta Pro G45 Delta Performance G55 Delta Pro G55 HeatMaster 60 N / 70 N / 100 N G 2000-S 35 G 2000-S 25 G 2000-S 45 G 2000-S 55 G 2000-S 60 G 2000-S 70 G 2000-S 100 85 kw G 2000-S 100 107 kw Ø 52 Ø 52 Ø 60 Ø 68 Ø 68 urners G 2000-S / 25 G 2000-S / 35 G 2000-S / 45 G 2000-S / 55 oilers Delta Performance 25 Delta Pro 25 Delta Performance 35 Alfa Sprint S / SV HeatMaster 30 N Delta Performance 45 Delta Pro 45 Delta Performance 55 Delta Pro 45 Output kw G20 - G25 % CO 2 Rpm max. G31 % CO 2 Rpm max. 25,0 9,0 3400 11.0 / 11,2 3100 34,9 9,0 4150 11.0 / 11,2 3760 45,0 9,0 4400 11.0 / 11,2 4000 55,0 9,0 4100 11.0 / 11,2 3700 G 2000-S / 60 HeatMaster 60 N 69,9 9,0 4600 11.0 / 11,2 4170 G 2000-S / 70 HeatMaster 70 N 69,9 9,0 4600 11.0 / 11,2 4170 G 2000-S / 100 85 kw HeatMaster 100 N 85,0 9,0 4600 11.0 / 11,2 4170 G 2000-S / 100 107 kw HeatMaster 100 N 107,0 9,5 5900 11.0 / 11,2 5440 17

18

19

20