SLATE. Burner Control Module INSTALLATION INSTRUCTIONS R8001B2001

Similar documents
SLATE. Sub-Base Module INSTALLATION INSTRUCTIONS R8001S9001

SLATE. Base Module INSTALLATION INSTRUCTIONS R8001A1001

SLATE. Rectification Ampli-Check Flame Amplifier INSTALLATION INSTRUCTIONS R8001V1031

SLATE. UV Ampli-Check Flame Amplifier INSTALLATION INSTRUCTIONS R8001S1071

7800 SERIES RM7888A Relay Module

RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES Relay Modules

7800 SERIES RM7888A Relay Module

7800 SERIES 22-Terminal Universal Subbase

RM7838A 7800 SERIES Relay Modules

7800 SERIES EC7823/RM7823 Relay Module

7800 SERIES EC7885A/RM7885A Relay Module

7800 SERIES S7830 Expanded Annunciator

INSTALLATION INSTRUCTIONS

YP7999A1000 ControLinks Fuel Air Ratio Control Panel

7800 SERIES RM7840E,G,L,M; EC7840L Relay Module

RM7897A,C 7800 SERIES Relay Modules

7800 SERIES EC7890A,B; RM7890A,B,C Relay Module

RM7895A,B,C,D/EC7895A,C; RM7896A,C,D 7800 SERIES

R7120M 7800 SERIES Relay Modules

7800 SERIES EC7895A,C; RM7895A,B,C,D and RM7896A,B,C,D Relay Modules

Q7800H Integrated Burner Control Subpanel

RM7890A1056, RM7890B SERIES

R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 Amplifiers for 7800 SERIES and R7140 Relay Modules

7800 SERIES: EC7895A,C; RM7895A,B,C,D; RM7896A,B,C,D RM7897A,C and RM7898A Relay Modules

RM7890D; RM7895E,F 7800 SERIES Relay Modules

7800 SERIES RM7840E,G,L,M Relay Module

R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 Amplifiers for 7800 SERIES and R7140 Relay Modules

RM7890; RM Vac 7800 SERIES Relay Modules

7800 Series RM7888A Relay Module

7800 SERIES S7800A2142 Keyboard Display Module

Cleaver-Brooks CB780/CB784 Operation and Maintenance Manual

APPLICATION SPECIFICATIONS INSTALLATION INSTRUCTIONS. The following assumptions apply when using the RM7840G,L, RM7800L, EC7840L:

7800 SERIES EC7810A, EC7820A Relay Module

Commercial/Industrial Combustion Control Level Three Announcement

ELECTRONIC FLAME SUPERVISION MULTI-BURNER

R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 Amplifiers for 7800 SERIES and R7140 Relay Modules

R7910A SOLA (Hydronic Control) and R7911 SOLA (Steam Control) Systems

YP7899C SERIES Burner Management Panel

7800 SERIES S7800A1167 Keyboard Display Module

Honeywell SLATE ICM Platform

7800 SERIES RM7824A Relay Module

T7079A,B Solid State Remote Temperature Controllers

R7910A SOLA (Hydronic Control) and R7911 SOLA (Steam Control) Systems

IS Series Pressure Sensing Switches

CR Series Command Relays

MBCE-110/230FR Flame Sensor Module

Instructions For A and Flame Simulators

LFL Series Burner Flame Safeguard Control

RA890G Protectorelay Primary Control

FIREYE M4RT1 FLAME SAFEGUARD CONTROLS DESCRIPTION

Sola Hydronic Control. An Eco-Friendly Solution.

R7910A SOLA HC (Hydronic Control) R7911 SOLA SC (Steam Control)

C554A Cadmium Sulfide Flame Detector

R7824, R7847, R7848, R7849, R7851,R7861, R7886 Amplifiers for 7800 SERIES Relay Modules

Solid Core and Split Core 0-5, 0-10 Vdc Output Current Sensors CTS-05,10; CTP-05,-10

MBCE-110/230FR Flame Sensor Module

MBCE-110/230UV Flame Sensor Module

Refer to Bulletin E-1101 for detailed information on the FLAME-MONITOR System.

C6097A,B Pressure Switches

Power Supply Display Module PSDM. Installation and Operation Manual

C7007A, C7008A, C7009A Flame Rod Holder & Flame Rod Assemblies

MBUV-100D, MBUVS-100D MBIR-100D, MBFR-100D DIN RAIL MOUNT FLAMEWORX MODULES

BC-R10 Series. Burner Controllers

Eclipse Self-Check UV Scanner

R7140G,L,M Burner Control Modules

Model 17A00 Expansion Enclosure

L8005A,B; LS8005A,C,D Electronic Pool and Spa Controllers

PARAGON Commercial Refrigeration Controls

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

C7005A,B Gas Pilot and Flame Rod Assemblies

C7232A,B Sensor and Controller CARBON DIOXIDE SENSOR

50A Integrated Furnace Control

SAFETY CONTROL REQUIREMENTS FOR OVENS AND FURNACES

EUROBOX SERIES TYPES CM... SM... MM...

T7984 A,B,C Electronic Modulating Control Thermostats

Submittal. Date: September 04, Customer P.O. Number: Customer Project Number:

Solid Core and Split Core 4-20 ma Output Current Sensors CTS-20; CTP-20

SERIES VAC Microprocessor-Based Hot Surface Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION AGENCY CERTIFICATIONS

CAUTION WARNING. 50T Integrated Furnace Control INSTALLATION INSTRUCTIONS DESCRIPTION PRECAUTIONS

C7915A Infrared Flame Detector

FIREYE NXF4000 ADVANCED BURNER MANAGEMENT SYSTEM with INTERNAL FLAME SAFEGUARD

RA889A Switching Relay

LC3000 Level Controller Installation and Maintenance Instructions

50A Integrated Furnace Control

configurable safety and programmable logic SLATE Integrated Combustion Equipment Management The revolutionary integration of

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

Interrupted Ignition Series Oil Primary Control

Honeywell Primary Control Cross Reference

C7232A,B Sensor and Controller

Solid Core and Split Core Fixed Current Status Switches CSS-O,C; CSP-O,C -F (FIXED) SERIES

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

S9360, S9361, S9370, S9371 Integrated Boiler Controllers

Quickheat 30 weather compensated boiler control

Dual Input ph/orp Analyzer

SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

50M Integrated Single or Two-Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS

Dual Input ph/conductivity Analyzer

Operator: Save these instructions for future use!

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

Transcription:

SLATE Burner Control Module R8001B2001 INSTALLATION INSTRUCTIONS

Scan for more information

Application SLATE brings configurable safety and programmable logic together into one single platform. The platform can easily be customized for almost any requirement or application offering virtually limitless development opportunities with far less complexity. The R8001B2001 Burner Control module provides flame safeguard controls for a variety of applications within the SLATE system. It can be configured as a primary or programmer, semiautomatic or fully automatic. Features Provides 24 VDC or 24 to 240 VAC flame safeguard Valve proving Parameters and behaviors that allow emulation of 7800 and SOLA Series flame safeguards Dual fuels capability Configurable safety Safety relay Specifications Electrical Ratings: Voltage and Frequency: 24 VDC (± 15%), 24 VAC (± 15%), 50/60 Hz, 85-264 VAC, 50/60 Hz Maximum Total Connected Load: 2000 VA Fusing Total Connected Load: 15A Fast Blow, type SC or equivalent SLATE BURNER CONTROL MODULE 3 R8001B2001

Environmental Ratings Ambient Temperature: Operating: -20 F to +150 F (-29 C to +66 C). Shipping: -40 F to +150 F (-40 C to +66 C). Humidity: 95% continuous, noncondensing. Vibration: 0.5G environment Dimensions: See Fig. 1 Weight: 1 lb 1 oz (0.48 Kg) Approvals Underwriters Laboratories Inc. Listed, File: MP268 Factory Mutual IRI Acceptable Federal Communications Commission: Part 15, Class A Must be mounted inside a grounded metal enclosure. Mounting DIN Rail (See Fig. 2) Required Components R8001A1001 SLATE Base Controller R8001S9001 SLATE Sub-Base Module 4 32-00010 01

7-3/32 (181) 2-11/16 (68) Fig. 1. Dimensions in in. (mm). 4-19/32 (117) M35382 Principal Technical Features The R8001B2001 SLATE Burner Control module provides the SLATE combustion system with flame safeguard capability. SLATE BURNER CONTROL MODULE 5 R8001B2001

LED Array There are four LEDs on the front of the burner control module that provide quick identification of system status and problems. This status is broadcast to other modules on the platform bus in case they are affected by the inoperable module(s). See Table 1 for descriptions. LED Color Description Power No light System does not have power Green System has power CPU Fault Flame Red Green Red No light Yellow No light Table 1. LED Descriptions. LED Displays No valid configuration Running Fault No fault Flame is detected No flame is detected The SLATE system modules have three-character LED displays used for indicating the module number of the SLATE system. They also have three-position LED colors to indicate terminal states as shown in Table 2. Color Green Red No light Description Terminal is ON or is Normal Fault Terminal is OFF or Not in use Table 2. Terminal LED Meanings. 6 32-00010 01

Select and Reset Buttons The SLATE Burner Control have Select and Reset buttons located on the front of the module and beneath the segment display. The Reset button is used to clear a lockout and reset the module. The Select button is used to scroll through the segment display information. There are also 22 LEDs for each of the burner control module terminals. Installation WARNING Fire or Explosion Hazard Can cause severe injury, death, or property damage. Verification of safety requirements must be performed each time a control is installed on a burner to prevent possible hazardous burner operation. When Installing This Product 1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. 2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application. 3. After installation is complete, check out the product operation as provided in these instructions. 4. The SLATE module must be mounted in an electrical enclosure with adequate clearance for servicing, installation and removal of modules. WARNING Electrical Shock Hazard. Can cause severe injury, death or equipment damage. SLATE BURNER CONTROL MODULE 7 R8001B2001

1. Disconnect the power supply before beginning installation to prevent electrical shock and equipment damage. More than one power supply disconnect can be involved. M35383 Fig. 2. Installing the Burner Control Module on the Sub-Base Module. 2. Wiring must comply with all applicable codes, ordinances and regulations. 3. Wiring must comply with NEC Class 1 (Line Voltage) wiring. 4. The R8001B2001 should not interfere with the proper safety operation of the controls, limits and interlocks it is monitoring. After installation, check each control, limit and interlock to ensure that it is operating properly. DO NOT PLACE JUMPER WIRES ACROSS THE INSTALLATION CONTROLS, LIMITS AND INTERLOCKS. 8 32-00010 01

IMPORTANT 1. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with these instructions, may cause interference for radio communications. It has been tested and found to comply with the limits of a Class A computing device of part 15 of FCC rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area may cause interference; in which case, the user, at their own expense, may be required to take whatever measures are required to correct this interference. 2. This digital apparatus does not exceed the Class A limits for radio noise, set out in the Radio Interfeence Regulations of the Canadian Department of Communications. 3. Cable shield must be terminated to ground at both ends. If shielded cable is NOT used, use three-wire twisted cable. Wiring WARNING Fire or Explosion Hazard Can cause severe injury, death, or property damage. Disconnect the power supply from the main disconnect before beginning installation to prevent electrical shock and equipment damage. More than one disconnect can be required. Terminal Description Rating 1 Unused (reserved for --- future use) 2 Unused (reserved for --- future use) 3 Unused --- 4 K1 Relay Dry Contacts (Burner / Fan Motor) 9.8 FLA, 58.8 LRA @ 120VAC, 4A (0.5 PF), 20A inrush @ 240VAC SLATE BURNER CONTROL MODULE 9 R8001B2001

Terminal Description Rating 5 K1 Relay Dry (see above) Contacts 6 Pilot Valve Hold (PVH) 7 Manual Open Switch (MOS) 8 Purge Position Proven (PPP) 9 Main Valve 2 (MV2) 120VAC (see Table 2), 4A (0.5 PF), 20A inrush @ 240VAC, 2A cont, 10A inrush @ 24VDC 10 Lightoff Position Proven (LPP) 11 Main Valve 1 (MV1) 120VAC (see Table 2), 4A (0.5 PF), 20A inrush @ 240VAC, 2A cont, 10A inrush @ 24VDC 12 Limit and Control Input (LCI) / Fuel (F) 2 13 Limit and Control Input (LCI) / Fuel (F) 1 14 Pre-Ignition Interlocks (PII) 15 Pilot Valve (PV) 120VAC (see Table 2), 4A (0.5 PF), 20A inrush @ 240VAC, 1A cont, 5A inrush @ 24VDC 16 Interrupted Air Switch (IAS) 17 Ignition (IGN) 120VAC (see Table 2), 4A (0.2 PF) @ 240VAC, 1A cont, 5A inrush @ 24VDC 18 Valve Proving Switch (VPS) 10 32-00010 01

Terminal Description Rating 19 Lockout Interlocks (ILK) 20 Vref+ 24VDC (0.1mA), 24VAC (0.1mA), 85-264VAC (0.2mA) 21 Unused --- 22 Vref- (see Vref+ above) Note: only one voltage can be used per module (same at all terminals). Table 3. Terminal Ratings. Combination Pilot Valve Ignition MV1 & MV2 1 C no load E 2 B no load E 3 E A E 4 D A E 5 D A D Load Table Key A 4.5 A Ignition B C D E 4.5 A plus 50 VA Pilot Duty 180 VA Ign plus motor valves with: 660 VA inrush, 360 VA open, 250 VA hold 2 A Pilot Duty 65 VA Pilot Duty plus motor valves with: 3850 VA inrush, 700 VA open, 250 VA hold Table 4. Combinations for PV, IGN, MV1 & MV2 Terminals. SLATE BURNER CONTROL MODULE 11 R8001B2001

Application Recommended Wire Size Recommended Part Numbers Line voltage terminals 14, 16 or 18 AWG copper conductor, 600 volt insulation, moisture-resistant wire. TTW60C, THW75C, THHN90C Communication Lines Other terminals 22 AWG two-wire twisted pair with ground, or fivewire. 18 AWG wire insulated for voltages and temperatures for given application. Table 5. Recommended Wire Sizes and Part Numbers. Belden 8723 shielded cable or equivalent. TTW60C, THW75C, THHN90C Recommended Grounding Practices Use an Earth ground or a signal ground as described below. Earth ground (Base, Rectification Flame Amp Module, other modules optional) 1. Use to provide a connection between the base and the control panel of the equipment. Earth ground must be capable of conducting enough current to blow the breaker in the event of an internal short circuit. 2. Use wide straps or brackets to provide minimum length, maximum surface area ground conductors. If a leadwire is required, use 14 AWG copper wire. 3. Make sure that mechanically tightened joints along the ground path are free of nonconductive coatings and protected against corrosion on mating surfaces. Signal ground Note the 18V system ground is not electrically connected to earth ground. Follow local codes and appliance recommendations to determine if this should be connected to earth ground. 12 32-00010 01

Recommended wire routing of leadwires Do not run high voltage ignition transformer wires in the same conduit with the flame detector or data lines. Do not route flame detector or data lines in conduit with line voltage circuits. Enclose flame detector leadwires without armor cable in metal cable or conduit. Follow directions in flame detector instructions. Be sure loads do not exceed the terminal ratings. Refer to the labels or terminal ratings in Table 3. The SLATE system must be mounted in an electrical enclosure. When mounting in an electrical enclosure, provide adequate clearance for servicing, installation and removal of SLATE modules. Maximum wire length: The maximum leadwire length is 300 feet to terminal inputs (Control, Running/Lockout Interlock) For remote reset leadwires, maximum length to remote pushbutton is 1000 feet. For Remote Bus data lines, maximum cable length depends on the number of modules connected, the noise conditions and the cable used. The maximum of all interconnecting wires is 4000 feet. SLATE BURNER CONTROL MODULE 13 R8001B2001

BURNER CONTROL MODULE 6 RELAYS 15 OPTO-INPUTS 1 2 3 UNUSED 4 5 BLR, HSI OR WIRE SHEET 6 PVH 7 M05 8 PPP 9 MV2 10 LPP 11 MV1 12 LCI FUEL2 13 LCI FUEL1 14 PII 15 PV 16 IAS 17 IGN SAFETY RELAY 18 VPS 19 ILK 20 REMOTE BUS IS ON SUBBASE BIAS 21 22 VREF M35387 Fig. 3. Wiring diagram for Burner Control Module. 14 32-00010 01

SLATE BURNER CONTROL MODULE 15 R8001B2001

32-00010-01 For more information on the R8001B2001 and the entire SLATE system please refer to the SLATE User Guide located on our website at http://www.combustion.honeywell.com/slate Automation and Control Solutions Honeywell International Inc. U.S. Registered Trademark. 1985 Douglas Drive North 2015 Honeywell International Inc. Golden Valley, MN 55422 32-00010 01 M.S. 05-15 customer.honeywell.com Printed in U.S.A.