Datasheet. Dry-pipe Vacuum Sprinkler System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

Similar documents
Datasheet. Vacuum Double-interlock Preaction System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

TotalPac 3 Firecyle III Deluge Remote controlled system

TotalPac 3 Wet pipe system c/w retard chamber

TotalPac 3 Double interlock Preaction, Electric/PneuLectric release Self-contained system

N2 BLAST Datasheet Preaction double interlock, Electric/Pneumatic c/w N 2 Blast Nitrogen generating system Self contained unit

TotalPac 3 Single interlock Firecyle III Preaction Self-contained system

N2 BLAST Datasheet SUREFIRE double interlock c/w N 2 Blast Nitrogen generating system Self contained unit

TotalPac 3 Deluge, Electric release Self-contained system

N2 BLAST Datasheet Preaction double interlock, Electric/Pneulectric c/w N 2 Blast Nitrogen generating system Self contained unit

TotalPac X Single interlock SUREFIRE system

FireFlex DUAL Double Interlock, Self-contained system

TotalPac 3 Single interlock Preaction, Electric release Self-contained system

TotalPac X Firecycle III Preaction Double interlock system

TotalPac 3 Non interlock Preaction, Electric release Self-Contained system

FireFlex 1230 Self-contained system

TOTALPAC2 Integrated Fire Protection System

Advanced Integrated Fire Protection Systems TOTALPAC 2. Owner's Operation and Maintenance Manual FIRECYCLE III. September 2009 FM-086G-0-5E

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC RELEASE

TECHNICAL DATA. 319a. January 27, 2012

TECHNICAL DATA 1. SYSTEM DESCRIPTION 2. SYSTEM OPERATION 3. INSTALLATION. Page 1 of 5

TECHNICAL DATA OBSOLETE

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEU-LECTRIC RELEASE

Not to be distributed outside of FM Approvals and its affiliates except by Customer APPROVAL REPORT

Specification/ Data Sheet

30.45 Electric Release PDRP-2001

Operation & Maintenance Manual

Worldwide Contacts.

Technical Data. Approvals The 1-1/2 in. to 8 in. (DN40 to DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

Technical Data. Approvals The 1-1/2 thru 8 inch (DN40 thru DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package. General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP1300. Worldwide Contacts

Technical Data. Working Pressure Range 20 to 250 psi (1,4 to 17,2 bar)

1935, Lionel-Bertrand Blvd. Boisbriand, Quebec, Canada J7H 1N8 Tel.: (450) Fax: (450) Toll Free: (866)

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

Instructions for Installation, Operation, Care and Maintenance

TECHNICAL DATA DELUGE SYSTEM CONTROLLED BY ELECTRIC RELEASE

TECHNICAL DATA OBSOLETE

Pre-Pack INTEGRATED PRE-ACTION SYSTEM

Deluge & Preac tion Systems

Instructions for. Care and Maintenance 10 psi (0,7 bar) Pneumatic Supervising Pressure. Single Interlock

Commercial and Light Industrial Fire Alarm Control Panel

OPEN SPRINKLER SYSTEM

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description.

Model QRS Electronic Accelerator (Quick Opening Device) For Dry Pipe or Preaction Systems General Description

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Deluge Fire Protection Package General Description

Electric Release Panel Wiring Tips

DOUBLE INTERLOCK, PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC RELEASE

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Preaction Fire Protection Package General Description

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays

VIZOR Electronic Dry Pipe Accelerator (EDPA) Quick-Opening Device for Dry Pipe Systems General Description

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH ELECTRIC RELEASE

TECHNICAL DATA. Factory Mutual Approval is pending for the system as a whole.

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH WET PILOT ACTUATION

AutoTest VSR (VSR-AT) (EU) Vane Type Waterflow Alarm Switch With Electronic Retard and Auto Test Feature

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

Release Control Fire Alarm Systems

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

EVO192 v3.0 Fire and Burglary What s New

FA-1000 SERIES. Microprocessor-Based Fire Alarm Control Panel. Installation and Operation Manual

Smoke Detector Activation of any smoke detector shall start the alarm verification mode.

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA

Power Flame Incorporated

DELUGE VALVE MODEL: SD-DVH2 TECHNICAL DATA TRIM DESCRIPTION DESCRIPTION VALVE OPERATION. 82 ASTM A 216 WBC.

Model DDX Deluge Valve

KT-100 Door Controller

MR-2602 Two Zone Fire Alarm Control Panel

FireNET Plus Wiring Instructions

Instruction Manual. CMP-12/24 Fire Alarm Control Panel. 12 Clintonville Road, Northford, CT DOCUMENT /11/96 REV: D1

Fire Control/Communicator

FEC400 Series. Installation Manual

FIRE DETECTION CONTROL PANEL OPERATING & MAINTENANCE MANUAL

good things in small packages

INTELLIGENT FIRE ALARM CONTROL PANEL

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

AL800ULADA. NAC Power Extender. Installation Guide

LifeAlarm Fire Alarm Control Panels

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

TOTAL SOLUTIONS. Liquid Level Control Product Guide. MATELEC AUSTRALIA innovative by design

VSR-M REPLACEMENT Waterflow Switch for Globe Sprinkler Model UMC Manifold

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

FireSeeker Fire Alarm Control Panel Model FS-250 Installation, Operation and Maintenance Manual

INSTALLATION & OPERATION GUIDE

CONVENTIONAL FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels MEA. Features. Description

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

PFC-3002T Fire Alarm Control Panel

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM

Discontinued Product

TECHNICAL DATA OBSOLETE

BERMAD Fire Protection

I-745. Series 745 FireLock Fire-Pac for FireLock NXT Valves WARNING INSTALLATION, MAINTENANCE, TESTING, AND WIRING MANUAL WARNING

Transcription:

FIREFLEX VACTEC description This FIREFLEX VACTEC integrated fire protection system consists of a vacuum system trim totally pre-assembled, prewired and factory tested. All electrical and mechanical components of the system are contained in one single unit. Dry-pipe vacuum sprinkler system uses closed vacuum sprinklers specified for vacuum use with vacuum sprinklers piping network. The only connections required for installation are the water supply inlet, water discharge outlet, main drain, the electrical alarm connections, as well as the AC power line(s). The discharge outlet is connected to a fixed vacuum sprinklers piping network. Water is the extinguishing agent. The integrated FLX-PC vacuum pressure controller allows the release control panel to receive all appropriates alarm and supervisory signals which supervise the vacuum pressure for appropriate discharge condition. It also controls the vacuum pump operation. The FIREFLEX VACTEC is fully tested at factory. The maximum water pressure is 175 psi WWP (1207 kpa). The system is available in the following diameters: 3" (80 mm) (100 mm) 6" (150 mm) 8" (200 mm) Features Trouble free design for safe and easy application Available in 4 sizes from 3" to 8" diameter Uses the Viking deluge valve Unit comes standard with its owned integrated releasing control panel Uses the FLX-PC pressure controller Compact, aesthetic and easy to move User-friendly standardized owner's manual with every unit Unique serial number on every unit Trim is fully assembled and tested at the factory All trims are galvanized steel, listed and approved for 175 psi (1207 kpa) service maximum Quick connections to water supply and drain on both sides, and vacuum sprinklers riser on top of unit, all available with grooved end or optional flanged fittings Shut-off valve at the outlet of the vacuum sprinklers riser for easier maintenance No open drain cup inside unit Sturdy 14 gauge steel cabinet, painted fire red with oven baked polyester powder on phosphate base Textured rust proof finish Neoprene gasket on all doors to eliminate vibrations Removable doors for ease of access Separate unlocked access hatch to emergency manual release Key-alike locks on all cabinet doors Manufactured under ISO-9001 quality control procedures FM-076D-0-137A 1 of 14

System configuration Dry-pipe Vacuum Sprinkler System, Electric Release Systems hydraulic limitations The information contained herewith is for estimation and evaluation purposes only. Its use remains the responsibility of the designer. Designers should refer to the appropriate NFPA Standards and any other applicable codes for their final design. Also refer to FIREFLEX Systems Inc. appropriate user manuals and to manufacturer's data sheets for additional details. Systems limitations indicated below are nominal flow limitations. System size Usage Range Piping Equivalent Lengths w/o Shut-off Valve Piping Equivalent Lengths c/w Shut-off Valve Drain Flow @ 175 PSIG (1207 KPA) W.P. in mm GPM LPM ft m ft m GPM LPM 3 80 100-700 379-2650 55.1 16.8 66.7 20.33 762 2884 4 100 200-1400 757-5300 71.8 21.89 83.1 25.33 1597 6405 6 150 400-3500 1514-13249 109.15 33.28 122.3 37.28 1597 6405 8 200 750-5200 2839-19684 135 41.15 146.7 44.71 1597 6405 Sequence of operation Dry pipe system operation 1. Water supply pressure is trapped in the priming chamber of the deluge valve (A1). The pressure in the priming chamber holds the deluge valve clapper closed. 2. The vacuum is maintained under the system piping by the operation of an integrated vacuum pump. 3. The opening of an automatic vacuum sprinkler will remove the vacuum pressure from the piping network. A low vacuum signal will activate the solenoid valve (F1) and depressurize the priming chamber of the deluge valve. It will cause the deluge valve to open. The alarm pressure switch (C1) will activate. The water flow and supervisory signals will be present. The water will enter the system piping. The water will flow out of any open vacuum sprinklers. 4. The manual operation of the emergency release valve (B10) will depressurize the priming chamber of the deluge valve. This will cause the deluge valve to open. 5. The opening of the deluge valve will allow water to enter the system piping. The alarm pressure switch (C1) will activate. The water flow signal will be present. The water will flow out of any open vacuum sprinklers. 2 of 14 FM-076D-0-137A

Standard equipment Releasing control panel 120 VAC / 60 Hz, 165VA 240 VAC / 50 Hz, 185VA 12VDC / 18Ah batteries (factory installed) The releasing control panel integrated into the FIREFLEX VACTEC cabinet is Viking's Model VFR-400. This panel offers four Class B, programmable detection zones (optional Class A); two Class B supervisory zones and four Class B, programmable output circuits. Some of these circuits are required for the operation of the Vacuum Non-interlock Preaction System; the others are available to the customer. The releasing control panel is compatible with many types of fire alarm & supervisory devices such as linear heat detectors, spot-type heat and smoke detectors, water flow and release indicators, low and high air pressure switches, manual pull stations. The releasing control panel is provided with menu driven programming, including a specific program assigned at the factory for the appropriate configuration of the system. It includes an alphanumeric display with 2 lines of 16 characters describing all the system conditions, as well as a set of red and yellow LED lamps individually indicating each of the alarm, supervisory and trouble conditions of the system. Easy to operate control buttons are provided to activate and operate the system's various functions. Releasing circuit disconnect switch The releasing circuit disconnect switch is used to disable the releasing solenoid. When the key is set to DISABLE, the releasing solenoid will be disconnected from the releasing control panel s releasing circuit, causing a supervisory signal and preventing accidental discharge during maintenance or inspection. Deluge valve The Viking Model F-1 Deluge Valve is a quick-opening, differential diaphragm flood valve with one moving mechanism. The deluge valve is used to control water flow in vacuum sprinkler systems. The valve is held closed by system water pressure trapped in the priming chamber, keeping the outlet chamber and system piping dry. In fire conditions, when the releasing system operates, pressure is released from the priming chamber. The deluge valve clapper opens to allow water to flow into the system. FM-076Z-0-3A Water supply control valve The water inlet control valve is a supervised, indicating butterfly valve. Purpose of this valve is to manually shut-off the vacuum preaction system. NORMAL DISABLE FM-076Z-0-3A RELEASING CIRCUIT DISABLE SWITCH FM-076Z-0-2A FM-076D-0-137A 3 of 14

Standard equipment (continued) Solenoid valve The high pressure solenoid valve is a two-way type with one inlet and one outlet. It is a pack less, internal pilot operated valve, suitable for use in releasing water pressure from the priming chamber of Viking deluge valve. The solenoid valve has floating diaphragm construction, which requires a minimum pressure drop across the valve to operate properly. Shut-off valve & sight glass The shut-off valve & sight glass are intended to be used for applications where testing of the system operation without filling the sprinkler piping network is desirable and where it is critical that all functions of the vacuum preaction system be tested under actual discharge conditions. Main Drain Valve (D3) Supervised Shut-off Valve (D4) Sight Glass Assembly (D5) Deluge Valve (A1) FM-076Z-0-3A IN OUT Point flash light here Supervised Water Supply Control Valve (D1) Alarm pressure switch The alarm pressure switch monitors the water flow within the vacuum sprinkler piping. Should the deluge valve clapper opens to allow water to flow into the sprinkler piping, the alarm pressure switch will activate, indicating a water flow signal. POTTER PS10-1A FM-061H-0-223A FM-076Z-0-3A FLX-PC vacuum pressure controller The FLX-PC vacuum pressure controller monitors the vacuum pressure inside the vacuum sprinklers piping network and control the vacuum pump to maintain the appropriate vacuum pressure. Alarm and supervisory signals are transmitted to the release control panel upon presettled vacuum pressure levels. An alphanumeric display shows the vacuum pressure status. A single-button control allows the user to view history and set some parameters. FM-061H-0-267A 4 of 14 FM-076D-0-137A

Optional equipment Semi-flange and full-flange inlet / outlet (optional) When required by the user, FIREFLEX VACTEC unit can be provided in a semi-flanged or full-flange configuration. The semi-flanged option provides flanged fittings only on the water inlet pipe (side needs to be specified at the time of order) and on the system riser outlet. The drain manifold is provided with a threaded end that also needs to have its side specified (left or right). The rest of the fittings are the same as usual with the main components being provided in the standard flanged/grooved configuration. The full-flanged option is the same as above but goes a step further with the main components being also provided with a flanged/flanged configuration. When provided, the face of the flanges will always be located 6 inches (150mm) from the outside face of the mounting base or cabinet surface. Flanged fitting outside cabinet (when provided) Flanged fitting outside cabinet (when provided) Threaded end Field Connection to Open Drain (specify side) Field Connection to Water Supply (specify side) FM-061H-0-225B FM-076D-0-137A 5 of 14

Vacuum supply Vacuum supply description Vacuum sprinkler system uses negative vacuum pressure to supervise the piping network. The vacuum supply is provided within the FIREFLEX VACTEC unit. The vacuum supply trim is factory assembled in the system cabinet, calibrated and pressure tested. The vacuum supply system trim includes a liquid ring vacuum pump (G1), all regulating devices to control flow of water and pump motor shut off electrical components. The vacuum pump power requirement is specified at 220/240VAC, 50/60Hz, 1.5 HP, 1 phase. The vacuum pump is able to establish the total required vacuum pressure in less than 30 minutes for system capacity up to 4000 gallons. All pressure settings are factory set and do not need further calibration unless malfunction. G8 G10 To Riser Trim To System Trim 1 5 2 G8 G7 G12 G15 G1 G11 G14 To Drain Trim 4 G5 G4 To Drain Trim 4 G2 G6 G13 To Water Supply Trim 3 G3 G8 FM-061H-0-218D Vacuum pump components: G1 Liquid ring vacuum pump G2 240 VAC N.C. solenoid valve G3 Pre-regulator G4 Fine-adjust regulator G5 0.125" restricted orifice G6 Float check valve G7 2-way check valve G8 Strainer G10 System drain valve (N.C.) G11 Reversed check valve G12 Vacuum breaker valve G13 Water ring cut-off valve (N.O.) G14 Pre-regulator gauge & valve G15 Fine-adjust regulator gauge & valve 6 of 14 FM-076D-0-137A

Details & field wiring diagrams Main hydraulic components FIELD CONNECTION TO VACUUM SPRINKLERS PIPING NETWORK D4 G18 C1 D3 B10 A1 G20 B5 B11 G10 G1 B7 B12 B1 B6 D1 FIELD CONNECTION TO OPEN DRAIN (on both sides) FIELD CONNECTION TO WATER SUPPLY (on both sides) FIREFLEX VACTEC System Base (shown without enclosure) FM-061H-0-254A FM-076D-0-137A 7 of 14

Trim Diagram FIELD CONNECTION TO VACUUM SPRINKLERS PIPING NETWORK D4 G12 G8 CONTRACTOR'S HYDROSTATIC TEST PORT (system side) C2 C1 G6 B9 D3 A1 G18 1 2 Towards Vacuum Supply System Trim F1 B4 B10 D5 B8 B7 B5 B6 D1 4 5 3 Towards Vacuum Supply System Trim B13 B11 B12 G20 B4 B3 B2 CONTRACTOR'S HYDROSTATIC TEST PORT (water supply side) FIELD CONNECTION TO OPEN DRAIN (on both sides) B1 FIELD CONNECTION TO WATER SUPPLY (on both sides) FIREFLEX VACTEC System Base (shown without enclosure) FM-061H-0-247A Trim Components: A1 Deluge valve B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12 B13 Priming valve (N.O.) Strainer 1/16" Restricted orifice Spring loaded check valve Alarm test valve (N.C.) Flow test valve (N.C.) Alarm line drain valve (N.C.) 1/8" Restricted orifice PORV (pressure operated relief valve) Manual emergency release valve (N.C.) Priming pressure water gauge & valve (N.O.) Water supply pressure gauge & valve (N.O.) Clapper check valve C1 C2 D1 D3 D4 D5 F1 Alarm pressure switch (PS10-1A) ¾"-NPT (20mm) Connection to water motor gong (strainer supplied by contractor) Water supply control valve (N.O.) Main drain valve (N.C.) Shut-off- valve (N.O.) Sight glass assembly 24VDC N.C. Solenoid valve G6 Vacuum pump drain float check G8 Vacuum pump network strainer G12 Vacuum breaker valve G18 FLX-PC Vacuum pressure controller G20 Vacuum pump control pressure switch (PS40-1A) 8 of 14 FM-076D-0-137A

N L AC IN CONNECTOR NON-POWER LIMITED SUPERVISED 5 SW5 24VDC RS485 NON-RESETTABLE RUN PROGRAM GENERAL ALARM OUTPUT 1 RED OUTPUT LED STEADY: ABORT ZONE 1 ZONE 2 ZONE 3 ZONE 4 AC POWER POWER TBL SYSTEM TBL SUPV TBL GROUND FAULT VIEWING ANGLE S OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 SUP1 / ABORT SUPERVISORY 2 COMMON ALARM ALARM SILENCE STEADY: DISCHARGED FLASHING: PRE- DISCHARGE SET WATER FLOW RELEASE SUPERVISORY BELL CIRCUIT BELL OUTPUT 2 OUTPUT 3 OUTPUT 4 SELECT FUNCTION MODE PROGRAM AUX POWER 24VDC RESETTABLE SUP 1 SUP 2 SUPERVISORY LOW AIR RUN MODE SCROLL-UP BUZZER SILENCE SCROLL-DOWN BUZZER SILENCE SIGNAL SILENCE SYSTEM RESET VALVE TAMPER TROUBLE COM NO NC ZONE 1 HEAT / SMOKE DETECTORS ALARM ZONE 2 HEAT / SMOKE DETECTORS COM NO NC COM ZONE 3 WATER FLOW SUPV SWITCH NO COM ZONE 4 MANUAL STATION WTRFLW NO Dry-pipe Vacuum Sprinkler System, Electric Release Control Panel and Vacuum Pump Control Layout JUNCTIONS BOX (behind control panel) VACUUM PUMP ISOLATING SWITCH (G16) TB201 TB1 VFR-400 TB101 ELECTRICAL CONTACTOR (G17) (c/w trip reset) UNLATCH TO ROTATE THE CONTROL PANEL CONTROL PANEL (shown with door open) RELEASING CIRCUIT BATT TB102 TB103 UNLATCH TO OPEN THE RIGHT DOOR (or rotate the control panel) SYSTEM NORMAL SYSTEM DISABLED DISABLE SWITCH VACUUM PUMP CONTROL BOX (behind right door) RELEASING CIRCUIT DISCONNECT SWITCH 12VDC BATTERY SET FM-061H-0-220B Junctions Box Layout TBB Terminals TBA & TBC Terminals TBB TBA TBC Junction Box with cover removed (behind Control Panel) Optional ARM-44 Relay Module Location Factory wired flexible conduits to Control Panel and system devices FM-061H-0-221B FM-076D-0-137A 9 of 14

Wiring diagram TBB 1 2 3 4 5 6 WIRING OF INPUT POWER SOURCE 120VAC, 60Hz LINE NEUTRAL GROUND GROUND NEUTRAL LINE 220VAC, 60Hz 240VAC, 50Hz CONTROL PANEL 100VA MAX (120VAC) 170VA MAX (220/240VAC) VACUUM PUMP 220VAC 50/60Hz 1.5HP Refer to Local Electrical Codes for wiring size. OPTIONAL WIRING IN CLASS A / STYLE D MANUAL RELEASE ZONE 4 LEGEND MANUAL RELEASE BELL OR HORN DRY CONTACT END OF LINE RESISTOR Branch circuit for vacuum pump shall not be the same as the release control panel power source. WIRING IN CLASS B / STYLE B DO NOT USE 5.1K EOLR DO NOT USE 5.1K EOLR MANUAL RELEASE ZONE 4 5.1K EOLR WIRING IN CLASS B / STYLE Y 5.1K EOLR 5.1K EOLR 5.1K EOLR NOTES: Class A / Style D requires CA2Z modules. End-of-line devices are not required for Class A / Style D wiring. TBA 9 10 11 12 13 14 1 2 3 4 5 6 7 8 15 16 SILENCEABLE ALARM OUTPUT 1 17 18 19 20 21 22 23 24 25 26 27 28 29 30 NON-SILENCEABLE WATERFLOW OUTPUT 2 SILENCEABLE SUPERVISORY OUTPUT 4 C TROUBLE NO NC C ALARM NO NC TBA C SUPERVISORY NO C 9 WATER FLOW NO 10 24VDC RESETTABLE 120 TBC 1 2 3 4 5 11 12 24VDC NON RESETTABLE RS485 SHIELD CONTACTS RATED 3A, 30VDC RESISTIVE NOTES: - Control panel AC power source is supervised and non-power limited. - All devices are shown in their normal supervisory state. - Use dry contacts with power limited circuits only. FM-061H-0-252A Power Limited (supervised) Initiating Device Circuits Zone 4 (manual release): Class B or optional Class A Max. loop resistance: 100 ohms End of line: 5.1K ohms, 1/4W Leave ELR (provided) on all unused circuits. Refer to Device Compatibility in the VFR-400 Releasing control panel Manual. Auxiliary Power 24Vdc Regulated Source Total current available: 0.2A Resettable for 4 wires smoke detectors Power Limited (supervised) Notification Appliance Circuits Output Circuit 1, 2 and 4: Maximum operating voltage: 27Vdc (ripple: 0.3Vdc) Maximum usable current per circuit: 1.0A Total current available (all circuits): 2.5A Polarity is reversed in supervisory condition. Leave ELR (provided) on all unused circuits. Refer to Device Compatibility in the VFR-400 Releasing control panel Manual. WARNING Releasing control panel shall be supplied by a dedicated circuit breaker, as per NFPA 70, Section 760 and Canadian Electrical Code, Section 32. 10 of 14 FM-076D-0-137A

Cabinet The FIREFLEX VACTEC unit cabinet is made of sturdy 14 gauge steel, it is available in two (2) sizes: 46" x 25" x 77" (1170mm x 640mm x 1960mm) for 3", or 6" system 5 x 31" x 81" (1370mm x 790mm x 2060mm) for 8" system All external and internal surfaces are rust proof coated, inside and outside, with fire red, oven baked polyester powder on phosphate base. Cabinet is provided with two doors, both provided with a neoprene gasket to absorb vibrations. The cabinet unit is pre-assembled, pre-wired, and factory tested under ISO-9001 specifications. Each cabinet door is provided with hinges that can be disassembled on site to remove the door assemblies for servicing. Gauges to indicate water supply pressure, priming water pressure and vacuum pressure are all visible through clear Lexan windows. The release control panel of the FIREFLEX VACTEC system is installed inside the cabinet at the factory. The field wiring electrical junction boxes is integrated with the cabinet for connection of applicable detection system, auxiliary contacts and signaling devices. All inputs & outputs are factory wired to a terminal strip (TBA) for contractor's field wiring. Figure 1 - Floor anchoring template Figure 2 - knockouts details 8½" 3" Figure 3 - Required clearance B min. 2½" 3¾" FIREFLEX-VACT EC UNIT High voltage Top of Cabinet Low voltage 2½" Typ. TYPICAL MECHANICAL ROOM A min. FM-061H-0-68B-12 A C 5" B min. B TOP VIEW C min. ¾" 6 HOLES FM-061H-0-229B 1" Unit size A 3" 6" 8" 48" 1220mm FRONT 48" 1220mm 48" 1220mm FM-061H-0-128A 56" 1422mm Unit size A B C 3" 6" 8" 70" 1780mm 12" 305mm 2 610mm 70" 1780mm 12" 305mm 2 610mm 70" 1780mm 12" 305mm 2 610mm 78" 1980mm 12" 305mm 2 610mm B 15" 380mm 15" 380mm 15" 380mm 21" 530mm C 25" 635mm 25" 635mm 25" 635mm 29" 735mm FM-076D-0-137A 11 of 14

Figure 4 - Cabinet dimensions D E P TBA, TBB & TBC Q TBB TBA & TBC VACUUM PUMP CONTROL BOX ØB CONTROL PANEL SPRINKLER RISER SCH.40 GROOVED OUTLET CONTROL PANEL SPRINKLER RISER SCH.40 GROOVED OUTLET F R J L N DRAIN - SCH.40 GROOVED OUTLET N ØC ØA M WATER INLET SCH.40 GROOVED OUTLET M K H G S FM-061H-0-228B Unit size 3" 6" 8" A B C D E F G H J K L M N P Q R S 100mm 100mm 6" 150mm 8" 200mm 3" 75mm 100mm 6" 150mm 8" 200mm 2" 50mm 2" 50mm 2" 50mm 2" 50mm 46" 1170mm 46" 1170mm 46" 1170mm 5 1370mm 25" 635mm 25" 635mm 25" 635mm 31" 785mm 77" 1955mm 77" 1955mm 77" 1955mm 81" 2055mm 100mm 100mm 100mm 100mm 10" 255mm 10" 255mm 11" 280mm 12" 305mm 11½" 290mm 11½" 290mm 11½" 290mm 13¼" 335mm 13¾" 350mm 13¾ 350mm 13¾" 350mm 17½" 445mm 3¾" 950mm 3¾" 950mm 3¾" 950mm 3¾" 95mm 2½" 65mm 2½" 65mm 2½" 65mm 3¾" 95mm 2½" 65mm 2½" 65mm 2½" 65mm 3¾" 95mm 22¼" 565mm 22¼" 565mm 21¼" 540mm 27" 685mm 11½" 290mm 11½" 290mm 11½" 290mm 13¼" 335mm 57¾" 1465mm 62½" 1590mm 64½" 1640mm 75½" 1920mm 50" 1270mm 50" 1270mm 50" 1270mm 58" 1270mm Dimensions are nominal and may vary by ¼ (5mm) 12 of 14 FM-076D-0-137A

This page is left blank intentionally. FM-076D-0-137A 13 of 14