Installation and Servicing Instructions. Alpha CD50S and 70S. Wall Mounted, Fan Assisted, Gas Fired, High Efficiency Condensing System Boilers

Similar documents
Alpha CD13R,18R and 24R

Installation and Servicing Instructions

Installation and Servicing Instructions. Alpha CD24C/32C

Installation and Servicing Instructions. Alpha CD25C/28C/35C

Installation and Servicing Instructions

Installation and Servicing Instructions. Alpha CD50

Installation and Servicing Instructions. Alpha CD25X/28X

Alpha InTec 26C, 30C, 34C and 24X, 28X

Alpha InTec 30C and 34C

Installation and Servicing Instructions. Alpha CB50

Alpha CombiMax 350 and 600

Installation and Servicing Instructions. Alpha 240/280. Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired Combination Boilers

Alpha FlowSmart 25 and 50

Installation and Servicing Instructions. Alpha FlowSmart

InTec² 20SE and 30SE

TEMPRA. Wall Mounted Fan Flue System boiler. Wall mounted fanned flue boiler INSTALLATION AND USE INSTRUCTIONS. Appr. nr. B A - CE 0063 AQ 2150

Installation and Servicing Instructions. E-Tec 28 and 33

User's Instructions. Alpha CD24C/32C. Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired, High Efficiency Condensing Combination Boilers

User's Instructions. Alpha CB50

Installation and Servicing Instructions. Alpha GasSaver GS-1

User's Instructions. Alpha CD25X/28X. Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired, High Efficiency Condensing Combination Boilers

Installation and Servicing Instructions. Alpha GasSaver GS-2

E-Tec Plus 28 and 33

With a power output ranging from 13kW to 24kW, they provide the flexible answer for the majority of traditional installation scenarios.

Compact. Installation & Servicing Instructions THESE INSTRUCTIONS TO BE RETAINED BY USER

Compact HE. High efficiency combi boiler. Installation & Servicing Instructions THESE INSTRUCTIONS TO BE RETAINED BY USER

Bosch Group. 15SBi / 24SBi. WALL MOUNTED BOILERS FOR CENTRAL HEATING and Indirect supply of domestic hot water

Performa System 12e, 18e, 24e & 28e

Mynute. Installation & Servicing Instructions. 28e THESE INSTRUCTIONS TO BE RETAINED BY USER

Installation and Servicing Instructions. Alpha SolarSmart 90

Bosch Group. 24CDi OF WALL MOUNTED COMBINATION BOILER FOR CENTRAL HEATING AND MAINS FED DOMESTIC HOT WATER INSTALLATION AND SERVICING INSTRUCTIONS

This is a Wall Mounted Powered Flue Condensing Combination Boiler Gas Fired Central Heating Unit.

Bosch Group. 24CDi RSF WALL MOUNTED COMBINATION BOILER FOR CENTRAL HEATING AND MAINS FED DOMESTIC HOT WATER INSTALLATION AND SERVICING INSTRUCTIONS

INSTALLATION AND SERVICING INSTRUCTIONS

Mynute 24m Installation & Servicing Instructions

kw Btu/h Metres Feet l/min. Gal/min C C

Highflow 400 ELECTRONIC BF FLOOR STANDING COMBINATION APPLIANCE FOR CENTRAL HEATING AND MAINS FED DOMESTIC HOT WATER

HALSTEAD Ace INSTALLATION & SERVICING INSTRUCTIONS FOR THE

INSTALLATION AND SERVICING INSTRUCTIONS

Bosch Group. 24i RSF WALL MOUNTED COMBINATION BOILER FOR CENTRAL HEATING AND MAINS FED DOMESTIC HOT WATER INSTALLATION AND SERVICING INSTRUCTIONS

SABRE. Installation & Servicing Instructions THESE INSTRUCTIONS TO BE RETAINED BY USER

Ace and Ace High. Installation and Servicing Instructions To be left with user adjacent to gas meter. Wall Mounted Gas Combination Boiler

Bosch Group. 35CDi WALL MOUNTED COMBINATION BOILER FOR CENTRAL HEATING AND MAINS FED DOMESTIC HOT WATER INSTALLATION AND SERVICING INSTRUCTIONS.

Bosch Group. 15SBi / 24SBi. WALL MOUNTED BOILERS FOR CENTRAL HEATING and Indirect supply of domestic hot water

Unvented Calorifier Range. Operating and Maintenance Manual. For Models & 500

Baxi Combi 80 Maxflue

MULTIPOINT FF Room Sealed Fan-Assisted Water Heater

CLUB HE 18 INSTALLATION AND SERVICING INSTRUCTIONS TO BE GIVEN TO THE USER SEALED SYSTEM CONDENSING BOILER. G.C. Appliance No Club HE 18

This is a Wall Mounted Powered Flue Condensing Combination Boiler Gas Fired Central Heating Unit.

24i RSF WALL MOUNTED COMBINATION BOILER FOR CENTRAL HEATING AND MAINS FED DOMESTIC HOT WATER INSTALLATION AND SERVICING INSTRUCTIONS

Light commercial products. High output boilers Cascade systems

ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL

CNTENTS. 1Introduction

Baxi Megaflo System HE IE Range. Installation & Servicing Instructions. Gas Fired Wall Mounted Condensing Boiler

CLUB HE 18 INSTALLATION AND SERVICING INSTRUCTIONS SEALED SYSTEM CONDENSING BOILER TO BE GIVEN TO THE USER Pin 87/BQ/44

Installation & Servicing Instructions

Finest. HALSTEAD Finest Finest Gold INSTALLATION & SERVICING INSTRUCTIONS FOR THE

VBX 18 & 30. Eden X Type INSTALLATION AND SERVICING INSTRUCTIONS OPEN VENT CONDENSING BOILER. SINGLE PAGES 20/9/10 09:58 Page 1

This is a Wall Mounted Powered Flue Condensing Combination Boiler Gas Fired Central Heating Unit.

MULTIPOINT BF Gas Fired Balanced Flue Water Heater

Compact 24 SE. Standard efficiency combi boiler. Users Instructions. Installation & Servicing Instructions. GC No

ESS. Installation & Servicing Instructions THESE INSTRUCTIONS TO BE RETAINED BY USER

Mikrofill Ethos Condensing combination boiler

Installation & Servicing Manual. for the Ultra range of wall mounted fan assisted balanced flue gas boilers

CONDENSING COMBINATION BOILER. Installation, Servicing and User Instructions

Installation & Servicing Instructions THESE INSTRUCTIONS TO BE RETAINED BY USER

FERROLI F30 INSTALLATION, SERVICING AND USER INSTRUCTIONS G.C. NO: Appr. nr. B99.06 A - CE 0461 BM /0-07/2001

Megaflo 2 System Compact GA Range. Installation & Servicing Instructions. Gas Fired Wall Mounted Condensing System Boiler

ecotec Instructions for installation and servicing Wall hung room sealed fan assisted condensing boiler For the installer

Suprima 30L - 100L. Installation & Service Instructions. About the Boiler

Osprey 2 CFL

Neta-tec Plus Combi GA Range. Installation & Servicing Instructions. Gas Fired Wall Mounted Condensing Combination Boiler

Wall hung combination boiler PROTHERM 23 BTVE

DOMINA 102 DGT INSTALLATION, SERVICING AND USER INSTRUCTIONS G.C. NO: Appr. nr. B99.06 A - CE 0461 AU /1-07/2001

24SiII / 28SiII WALL MOUNTED COMBINATION BOILERS FOR CENTRAL HEATING AND MAINS FED DOMESTIC HOT WATER

Duo-tec 2 Combi GA Range. Installation & Servicing Instructions. Gas Fired Wall Mounted Condensing Combination Boiler

Alpha SolarSmart 100

Linea ONE. High efficiency combi boiler. Installation & Servicing Instructions THESE INSTRUCTIONS TO BE RETAINED BY USER

FERROLI F30 INSTALLATION, SERVICING AND USER INSTRUCTIONS G.C. NO: Appr. nr. B99.06 A - CE 0461 BM /0-12/2001

JANUS 3 CIRCULATOR WATER HEATER INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS G.C. No

USER GUIDE VOGUE COMBI GEN2 C26 C32 C40

Superior Mk.II. Installation, Servicing & User Instructions

Itho Solar System CombiSolar 150. Installation and service manual

Installation & Service Instructions Suprima HE Condensing Central Heating Boiler

GB24 & GB30. User Manual

WALL MOUNTED COMBINATION BOILERS FOR CENTRAL HEATING AND MAINS FED DOMESTIC HOT WATER INSTALLATION AND SERVICING INSTRUCTIONS

Installation & Service Instructions. Suprima 30-80

THELIA IN WARRANTY TECHNICAL HELPLINE THIS IS A CAT II2H3+ APPLIANCE

RD 628 WALL MOUNTED COMBINATION BOILERS FOR CENTRAL HEATING AND MAINS FED DOMESTIC HOT WATER INSTALLATION AND SERVICING INSTRUCTIONS

KEY TO COMPONENTS. 1. Heat exchanger 2. Pilot gas pipe 3. Gas injector nozzle 4. Measuring point

INSTRUCTIONS FOR INSTALLATION AND SERVICING ECOmax VUW 236 EH G.C. No

CBX 24, 32 & 38 SBX 30

Mikrofill Ethos Condensing combination boiler. Maintenance Instructions 24cc

GRANT. Euroflame Outdoor Condensing Oil Boilers. USER, INSTALLATION and SERVICING INSTRUCTIONS

LIST OF CONTENTS COMMISSIONING REPORT SERVICE LOG

HomeCare

Baxi Barcelona System

POWERFLOW Series. Unvented Electric Storage Water Heaters. Installation & Operating Instructions Manual

CARVER CASCADE 2 & CASCADE 2 GE CARAVAN WATER HEATER INSTALLATION INSTRUCTIONS LEAVE THESE INSTRUCTIONS WITH THE USER

FALCON II COPPER WALL-MOUNTED COMBINATION, GAS FIRED BOILER FOR CENTRAL HEATING INSTALLATION, SERVICING AND USER INSTRUCTIONS G.C.

Transcription:

Installation and Servicing Instructions Alpha CD5S and 7S Wall Mounted, Fan Assisted, Gas Fired, High Efficiency Condensing System Boilers For Technical help or for Service call... ALPHA HELPLINE Tel: 87 3964 Nepicar House, London Road, Wrotham Heath, Sevenoaks, Kent TN5 7RS 5 For use with Natural Gas or Propane Gas (LPG) Leave these instructions with the User

CONTENTS Introduction... 2 2 Technical data... 3 3 General boiler information... 8 4 Installation... 5 5 Commissioning... 9 6 Routine servicing... 24 7 Wiring diagram... 29 8 Fault finding... 3 9 Short parts list... 3 Benchmark Checklist... 32 Service record... 33 INTRODUCTION The Alpha CD5S and 7S are wall mounted high efficiency condensing, fan assisted system boilers. The burner is lit electronically and the heat output is controlled by a modulating fan and gas valve. These are system boilers providing heating only for sealed central heating systems. However, they may be used with an open central heating system if required - refer to Section 3.8. The boilers are supplied with type B23 flue configuration (open chamber and forced draught) but can be changed to type C (room sealed) by using a kit. The boilers are fitted with a pump, 4 bar pressure relief valve and pressure gauge fully assembled and tested. They are designed for use with a fully pumped, sealed and pressurised central heating system. If used with an open system refer to Section 3.8. The CD5S boiler is suitable for central heating loads of between and 53.8 kw (34 2 and 83 7 Btu/h). The CD7S boiler is suitable for central heating loads of between 8. and 72.8 kw (6 8 and 248 6 Btu/h). The boilers can be supplied for use with Natural gas or Propane Gas (LPG). Note: There are a number of additional controls and accessories available for use with the boilers to enable cascade and zone installations to be used. Further information is available from Alpha Therm Ltd. IMPORTANT It is the law that all gas appliances are installed by a competent person, ie CORGI registered personnel, in accordance with the following recommendations:- Current Gas Safety (Installation and Use) Regulations All current Building Regulations issued by the Department of the Environment, i.e. Approved Document L. Building Standards (Scotland) (Consolidation) Regulations issued by the Scottish Development Department UK Water Regulations/Byelaws (Scotland) Health & Safety Document No. 635 (The Electricity At Work Regulations 989) The installation should also be in accordance with the following British Standard Codes of Practice:- BS 544::2 Flues BS 5449:99 Forced circulation hot water systems BS 5546:2 Installation of hot water supplies for domestic purposes BS 67:997 Design, installation, testing and maintenance of services supplying water BS 6798:2 Installation of gas fired hot water boilers BS 689:998 Gas installation BS 7593:992 Code of Practice for treatment of water in heating systems BS 767:2 Requirements for electrical installations, IEE Wiring Regulations Reference should be made to DEFRA document 'Guide to condensing boiler installation assessment procedures for dwellings'. If installation is in a timber framed building, refer to the Institute of Gas Engineers document IGE/UP/7. This appliance meets the requirements of IPX5D, ie degree of protection against moisture. This appliance contains no asbestos and no substances have been used in the construction process that contravene the COSHH Regulations (Control of Substances Hazardous to Health). Failure to install this appliance correctly could lead to prosecution. It is in your own interest and that of safety to ensure that the law is complied with. Manufacturer's instructions must NOT be taken in anyway as over-riding statutory obligations. Notes:. Ensure that the Benchmark Checklist has been completed after the boiler has been installed and commissioned. 2. It is the law that all boiler installations are registered by the installer through the CORGI Gas Work Notification Scheme. 3. The boiler must only be used with the flue components supplied with the boiler. Propane Gas (LPG) - In addition to the regulations and requirements stated, the boiler must be installed in accordance with BS 5482: - The Installation of Propane Burning Appliances in Permanent Dwellings. 2 Alpha CD5S/7S - Contents/Introduction

2 TECHNICAL DATA 2. PERFORMANCE NATURAL GAS (CAT: I2H 2H - G2-2 mbar) Alpha CD5S Alpha CD7S Central Heating Heat Input (H s ) kw (Gross) Btu/h Heat Input (H i ) kw (Net) Btu/h Heat Output (H s condensing) kw (5 C/3 C) Btu/h Heat Output (H i non-condensing) kw (8 C/6 C) Btu/h Fan Speed rpm Gas Rate m³/h ft³/h MAX. 56.4 92 4 5.8 73 3 53.8 83 7 5. 7 6 5 8 5.37 89.6 MIN..5 39 25.4 35 5. 37 8. 34 2 28. 38.8 Central Heating Heat Input (H s ) kw (Gross) Btu/h Heat Input (H i ) kw (Net) Btu/h Heat Output (H s condensing) kw (5 C/3 C) Btu/h Heat Output (H i non-condensing) kw (8 C/6 C) Btu/h Fan Speed rpm Gas Rate m³/h ft³/h MAX. 77.5 264 3 69.8 238 2 72.8 248 6 67.9 23 7 5 24 7.4 26.2 MIN. 2.5 7 6 8.5 63 2 9.7 67 8. 6 8 4.96 69.2 PROPANE GAS (CAT I3P 3P - G3-37 mbar) Alpha CD5S Alpha CD7S Central Heating Heat Input (H s ) kw (Gross) Btu/h Heat Input (H i ) kw (Net) Btu/h Heat Output (H s condensing) kw (5 C/3 C) Btu/h Heat Output (H i non-condensing) kw (8 C/6 C) Btu/h Fan Speed rpm Gas Rate m³/h ft³/h MAX. 56.4 92 4 5.8 73 3 53.8 83 7 5. 7 6 5 2 2.5 75.9 MIN..5 39 25.4 35 5. 37 8. 34 2 25.44 5.5 Central Heating Heat Input (H s ) kw (Gross) Btu/h Heat Input (H i ) kw (Net) Btu/h Heat Output (H s condensing) kw (5 C/3 C) Btu/h Heat Output (H i non-condensing) kw (8 C/6 C) Btu/h Fan Speed rpm Gas Rate m³/h ft³/h MAX. 77.5 264 3 69.8 238 2 72.8 248 6 67.9 23 7 5 24 2.96 4.5 MIN. 2.5 7 6 8.5 63 2 9.7 67 8. 6 8 45.78 27.7 Note: The above appliances are fully modulating and are not range rated. 2.2 SYSTEM Central Heating (Sealed System) Max. Working System Pressure Min. System Pressure Max. System temperature Pressure Relief Valve Setting Flow Connection Return Connection Relief Valve Connection Recommended System Pressure (cold) CH Water Temp. (Approx. max.) 3.5 bar.5 bar 82 C 4 bar (58.8 PSI) ½" BSP ½" BSP ¾" BSP. bar 82 C (8 F) Alpha CD5S/7S - Technical Data 3

2.3 COMPONENTS 2.4 ELECTRICAL Burner Main Heat Exchanger Main Burner Injector CD5S NG CD7S NG CD5S LPG CD7S LPG Concentric Flue Outer Duct Concentric Flue Inner Duct Stainless steel Stainless steel 7.85 mm 3. mm 5.7 mm 7.8 mm 25 mm dia. 8 mm dia. Supply External Fuse Power Consumption Internal Fuse - Main Terminal PCB Fuse F PCB Fuse F3 Electrode Spark Gap Electrical Enclosure Degree of Moisture Protection 23/24 V ~ 5 Hz 3 A 8 W F2A T2A T4A 3 to 4 mm IPX5D Open Flue Single Flue Pipe 8 mm dia. 2.5 INSTALLATION 2.6 GENERAL Min. Clearances for Servicing Top 35 mm Case Dimensions Height 95 mm (from casing) Bottom Sides 25 mm mm Width Depth 6 mm 525 mm Flue Diameter Front Open Flue 45 mm 8 mm Gas Connection Water Content CD5S 28 mm 3.7 L Concentric Flue Flue Protruding Outside Open Flue 25 mm 8 mm CD7S 4. L Hole For Flue Assy. Concentric Flue Open Flue 8 mm mm dia. Lift Weight Concentric Flue CD5S 27 mm dia. 63 kg CD7S 68 kg 2.7 PERFORMANCE DATA Boiler model CD5S CD7S %CO 2 content (±.2%) Natural Gas (LPG) Propane Gas Min 9.25 9. CH Max 9.3 9.25 Min. 9.7 CH Max.6.5 Sedbuk rating Efficiency NOx class band A 5 A 5 4 Alpha CD5S/7S - Technical Data

2.8 FLUE LENGTHS - See also Section 3.4 Open flue - Maximum horizontal or vertical flue with single 8 mm dia. open flue is 3 metre 9 bend is equivalent to 2. m of flue length 45 bend is equivalent to.3 m of flue length Vertical terminal is equivalent to 3 m of flue length Concentric flue - Maximum horizontal flue is 4 metre, maximum vertical flue is 8 metre 9 bend is equivalent to.9 m of flue length 45 bend is equivalent to.4 m of flue length Vertical terminal is equivalent to 3.4 m of flue length Notes:. Ensure all flues slope downwards towards the boiler by a minimum of 25 to 3 mm per metre of flue. 2. It is recommended that horizontal and vertical flue assemblies should be supported approximately every.5 m with access provided to the joints. 2.9 AVAILABLE PUMP HEAD FOR CENTRAL HEATING 9 8 7 A = CD5S - Available head with pump at maximum speed B = CD5S - Available head with pump at speed two C = CD7S - Available head with pump at maximum speed D = CD7S - Available head with pump at speed two 6 TOTAL HEAD (M water) 5 4 3 D C 2 B A 2 4 6 8 2 46 8 222 24 26 28 3 32 FLOW RATE (litre/h) Fig. 2. ELECTRICAL CONNECTIONS Note: This Appliance Must Be Earthed External sensor (Optional) DHW temp sensor (Optional) Diverter valve motor (Optional) 23V ~ 5Hz Fused at 3A External Pump Max A (Optional) Zone manager (Optional) Room thermostat (Optional) 3 6 2 Summer switch (Optional) Analog input - Volt (Optional) L N N L 37 A 38 B LINK Fuse F2A X85 X86 L N Q P G J M O R H F E T S K V U Y Z 23/24 V ~ 5 Hz only Maximum 24 V connection only Note: Do not connect 23/24 V ~ 5 Hz Fig. 2 Alpha CD5S/7S - Technical Data 5

2. BOILER SCHEMATIC - CD5S 5 6 7 8 4 3 2 9 2 9 2 22 23 8 7 24 6 25 5 4 26 3 2 27 Flow Condensate discharge Gas Return Tundish 2 Pressure relief valve (4 bar) 3 Drain point 4 Primary pressure switch 5 Flow manifold 6 Condensate trap 7 Gas valve 8 Air inlet pipe 9 Fan Injector Flame sensing electrode 2 Combustion chamber cover 3 Heat exchanger 4 Flue overheat thermostat 5 Flue hood 6 Air inlet sampling point 7 Flue sampling point 8 Primary flow temperature sensor 9 Air vent - manual 2 Primary return temperature sensor 2 Overheat thermostat 22 Ignition electrodes 23 Burner 24 Venturi positive point (P) 25 Venturi 26 Automatic air vent 27 Pump Fig. 3 - CD5S 6 Alpha CD5S/7S - Technical Data

2.2 BOILER SCHEMATIC - CD7S 5 6 4 3 7 8 9 2 2 9 8 7 2 22 23 24 6 5 4 3 2 25 26 Flow Gas Condensate discharge Return Tundish 2 Pressure relief valve (4 bar) 3 Drain point 4 Primary pressure switch 5 Flow manifold 6 Gas valve 7 Fan 8 Injector 9 Air inlet pipe Ignition electrodes Combustion chamber cover 2 Hear exchanger 3 Flue overheat thermostat 4 Flue hood 5 Air inlet sampling point 6 Flue sampling point 7 Automatic air vent 8 Primary flow temperature sensor 9 Primary return temperature sensor 2 Overheat thermostat 2 Burner 22 Flame sensing electrode 23 Venturi 24 Venturi positive point (P) 25 Pump 26 Condensate trap Fig. 4 - CD7S Alpha CD5S/7S - Technical Data 7

3 GENERAL BOILER INFORMATION 3. GAS SUPPLY Natural Gas: The Alpha CD5S boiler requires a gas rate of 5.37 m³/h (89.6 ft³/h). The Alpha CD7S boiler requires a gas rate of 7.4 m³/h (26.2 ft³/h). Propane Gas (LPG): The Alpha CD5S boiler requires a gas rate of 3.94 kg/h (8.4 lb/h) or 7.6 litres/h of liquid gas. The Alpha CD7S boiler requires a gas rate of 5.42 kg/h (.6 lb/h) or.4 litres/h of liquid gas. The local Propane Gas supplier should be consulted, at the installation planning stage, in order to establish the availability of an adequate supply of gas. The meter and supply pipes must be capable of delivering this quantity of gas in addition to the demand from any other appliances. The boiler requires at least a 28 mm gas supply pipe and ensure the inlet supply pressure is at least 2 mbar for Natural Gas or 37 mbar for Propane Gas (LPG). The complete installation, including the meter, must be tested for gas tightness and purged as described in BS 689. 3.2 ELECTRICAL SUPPLY The boiler requires a 23/24 V ~ 5 Hz mains supply, fused at 3 A Note: The boiler must be earthed. There must only be one common isolator, providing complete electrical isolation, for the boiler and any external controls. This boiler has been fitted with a supply cable, however, if it is necessary to fit a cable use PVC insulated cable not less than.75 mm² (24 x.2 mm) to BS 65 Table 6. The boiler should be connected to a fused three pin plug and unswitched shuttered socket outlet (both complying with BS 363), or a fused double pole switch with a contact separation of at least 3 mm in both poles. Wiring external to the boiler must be in accordance with the current IEE Wiring Regulations (BS 767). 3.3 AIR SUPPLY Open flued (Type B23 flue) Alpha CD5S and CD7S boilers leave the factory with 'B23' type configuration (open chamber and forced draught - single flue pipe) and receive the air for combustion from openings in the rear of the boiler, therefore air supply for combustion and ventilation must be provided in accordance with BS544:2.. If the boiler is installed in a room - The room must have a permanent air vent either direct to the outside air or to an adjacent room which itself has a permanent air vent to the outside air. The minimum effective air vent(s) required is: Alpha CD5S: 22 cm² Alpha CD7S 35 cm² 2. If the boiler is installed in a cupboard or compartment - Permanent air vents are required in the cupboard or compartment, one at high level and one at low level, either direct to the outside air or to a room. Both the high and low level air vents must communicate with the same room or must be on the same wall to outside air. The minimum effective areas required are given in Table. Where the cupboard or compartment is ventilated to a room, the room itself must have an effective air vent direct to outside air of minimum effective area as given above in paragraph. Boiler model Vents to outside air CD5S 255 cm² 5 cm² 5 cm² 2 cm² CD7S 35 cm² 7 cm² 7 cm² 4 cm² High level Low level High level Low level Vents into a room Table Room sealed (Type C flue) If the boilers are converted to a 'C' type configuration (sealed chamber and forced draught - concentric flue pipe) as described in Section 3.4 only air for ventilation is required.. If the boiler is installed in a room - No air vents are required in the room in which the boiler is installed. 2. If the boiler is installed in a cupboard or compartment - Permanent air vents for ventilation are required in the cupboard or compartment, one at high level and one at low level, either direct to the outside air or to a room. Both the high and low level air vents must communicate with the same room or must be on the same wall to outside air. Both the high and low level vent must each have a free area as follows. The free area of each vent may be halved if the ventilation is provided directly from outside. Alpha CD5S: 5 cm² Alpha CD7S 7 cm² The minimum clearances for servicing must always be maintained. 8 Alpha CD5S/7S - General Boiler Information

3.4 FLUE SYSTEM The flue system must be installed in accordance with BS 544:. For horizontal flues ensure the flue assembly slopes downwards towards the boiler by a minimum of 25-3 mm per metre of flue. It is recommended that horizontal and vertical flue assemblies should be supported approximately every.5 m with access provided to the joints. Alpha CD5S and CD7S boilers leave the factory with 'B23' type flue configuration (open chamber and forced draught - single flue pipe). To change the configuration to 'C' type (sealed chamber and forced draught - concentric flue pipe), remove the 8 mm dia. adapter, the bracket and gasket from the top of the boiler and fit the concentric flue adaptor, see Section 4.5. Note:. Under no circumstances must the flue length (including allowances for extra bends) exceed the maximum flue lengths stated for each type of flue. 2. Failure to use the correct Alpha flue components with the boiler will invalidate the boilers CE approval, guarantee and may be unsafe. Seals for flue elements - If lubrication of components (already performed by the manufacturer) is not sufficient, remove the residual lubricant using a dry cloth, then to ease fitting apply a small amount of common or industrial talc to the seal. Ensure that the seals are correctly located in the elbows and extensions as shown in Fig. 5. Seal Seal Fig. 5 Flue components are available as follows:- Open flue - 8 mm dia. single pipe Horizontal terminal kit 8 mm dia. (includes m straight with terminal, one 9 bend and two collars) Vertical terminal kit 8 mm dia. Extension pipe m x 8 mm dia. 9 bend 8 mm dia. 45 bend 8 mm dia. Concentric flue - 8/25 mm dia. Horizontal terminal kit 8/25 mm dia. (includes m straight with terminal, one 9 bend, two collars and adaptor) Vertical terminal kit 8/25 mm dia. (includes adaptor) Extension kit m x 8/25 mm dia. 9 bend 8/25 mm dia. 45 bend 8/25 mm dia. Alpha CD5S/7S - General Boiler Information 9

3.4. Horizontal Flue Options L max L max Open flue: 8 mm dia. single pipe Lmax = 3 m 9 bend is equivalent to 2. m of flue length 45 bend is equivalent to.3 m of flue length Concentric flue: 8/25 mm dia. Lmax = 4 m 9 bend is equivalent to.9 m of flue length 45 bend is equivalent to.4 m of flue length L max Open flue: 8 mm dia. single pipe Lmax = 27.9 m Concentric flue: 8/25 mm dia. Lmax = 2. m L max Open flue: 8 mm dia. single pipe Lmax = 27.4 m Concentric flue: 8/25 mm dia. Lmax =.2 m Fig. 6 - Horizontal flues 3.4.2 Vertical Flue Options Not less than 3 mm Not less than 3 mm H Not less than 3 mm H Not less than 3 mm Open flue: 8 mm dia. single pipe Hmax = 3 m Concentric flue: 8/25 mm dia. Hmax = 8 m Open flue: 8 mm dia. single pipe Hmax = 27.4 m Concentric flue: 8/25 mm dia. Hmax = 5.2 m Fig. 7 - Vertical flues Alpha CD5S/7S - General Boiler Information

3.5 FLUE TERMINAL LOCATION - Fig. 8 Note: In certain weather conditions the terminal will emit a plume of steam. If possible avoid positioning the terminal where this may cause a nuisance, i.e. positions A, D, G, H, J or M. The flue terminal must be exposed to the external air and the position must allow the free passage of air across it at all times. A terminal must not be sited below 2. m where people have access to, such as public footpaths, access routes, patios etc. However, If the terminal is fitted less than 2. m above a surface where there is no public access, the terminal must be protected by a terminal guard. A suitable guard is available from Alpha Therm Ltd. Q N O P D G J Boundary HI Fig. 8 Terminal position Min. distance (mm) A Directly below an opening, air brick, windows, etc. 3 (See Note ) B Below gutters, soil pipes or drain pipes 75 (See Note 3) C Below eaves 2 (See Note 3) D Below balconies 2 (See Note 3) E From a vertical drain pipe or soil pipe 5 (See Note 3) F From an internal or external corner 3 (See Note 2) G Above ground, roof or balcony level 3 H From a surface or boundary facing the terminal 6 (See Note 4) I From a terminal facing the terminal 2 mm J Above an opening, air brick, window etc. 3 (See Note ) K Vertically from a terminal on the same wall 5 mm L Horizontally from a terminal on the same wall 3 mm M Horizontally from an opening, air brick, window etc. 3 mm (See Note ) N Minimum protrusion through a roof 3 mm O From a vertical obstruction 3 mm P From an openable window 6 mm Q From an adjacent vertical terminal 6 mm Note: A terminal must not be sited under a car port roof Notes:. In addition, the terminal should not be nearer than 5 mm to the framework of an opening into the buiding, i.e. a window surround or door surround. 2. This clearance may be reduced to 25 mm without effecting the performance of the boiler. However, to ensure the condensate plume does not affect adjacent surfaces a clearance of 3 mm is preferable. 3. These clearances may be reduced to 25 mm without effecting the performance of the boiler. However, to ensure the condensate plume does not affect adjacent surfaces the terminal can be extended beyond gutters, pipes, eaves, balconies etc. by upto 5 mm. If the flue is extended more than 5 mm outside, it should be boxed and insulated. 4. To reduce the possibility of nuisance to neighbouring buildings etc. it is recommended the terminal shouild not be less than 25 mm from car parking spaces, building boundary walls, fences etc. 3.6 BOILER LOCATION The boiler is not suitable for external installation unless it is installed within a purpose designed weatherproof building. The boiler must be installed on a flat vertical wall which is capable of supporting the weight of the boiler. The boiler can be fitted to or adjacent to a wall comprising of a combustible material without the need for a special thermal insulation barrier. If the boiler is to be fitted in a timber framed building, it should be fitted in accordance with the Institute of Gas Engineers 'Guide for Gas Installations in Timber Frame Housing', reference IGE/UP/7. The boiler may be installed in any room or internal space, although particular attention is drawn to the requirements of the current IEE Wiring (BS767) Regulations, and in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, with respect to the installation of the boiler in a room or internal space containing a bath or shower. Where a roomsealed boiler is installed in a room containing a bath or shower, it must not be possible for a person using the bath or shower to touch any electrical switch or boiler control utilising mains electricity. The boiler may be installed in a cupboard or compartment, provided it is correctly designed for that purpose, i.e. complies with the Building Regulations and the requirements of BS 6798. Alpha CD5S/7S - General Boiler Information

Propane Gas (LPG): Installation pipes, cylinders and pressure regulators should be fitted in accordance with BS 5482:. Bulk tank installation must comply with the requirements of the Home Office code of practice for the storage of liquefied petroleum gas at fixed installations. The boiler must not be installed in a room or internal space below ground level, e.g. in a basement or cellar, except where at least one side is open to ground level. 3.7 FROST PROTECTION The boiler is fitted with a frost thermostat that activates the pump and burner when the system water temperature in the boiler falls below 3 C. The electrical supply to the boiler must be left on for the thermostat to operate and the selector switch must be set to ON. 3.8 CENTRAL HEATING SYSTEM - Fig. 9 The boiler is designed for use in a sealed central heating system in accordance with the requirements of BS 5449 and BS 6798. The system should be designed to operate with flow temperatures of up to 82 C. When designing the system, the pump head, expansion vessel size, mean radiator temperature, etc. must all be taken into account. Refer to the pump performance graph for guidelines (see Fig. ). However, if the boiler is to be used with an open central heating system refer to Fig. 9 and use a barrier heat exchanger (i.e. separates the boiler primary circuit from the open heating circuit). This will also ensure the boiler heat exchanger is protected from an old/dirty system. Sealed system volume - An expansion vessel is not incorporated into the boiler. An expansion vessel must be fitted in the position shown in Fig. 9. To check correct operation of the expansion vessel the system pressure should not be more than 3.5 bar when the system is at maximum operating temperature (for further guidance refer to BS 774:), For example an 8 litre expansion vessel is suitable for a sealed system of 8 litres. The boiler is supplied with the following components built in:- Pressure relief valve - complying with BS 6759 and set to operate at 4 bar. The discharge pipe must be routed clear of the boiler and terminated in such a manner that it can be seen, but cannot cause injury to persons or property. Pressure gauge - To indicate the system pressure to be maintained. By-pass - The boiler has no built-in by-pass, therefore an automatic by-pass is required for the system. Make up vessel (sealed system only) Static head of system Boiler Automatic air vent Expansion vessel (sealed system only) Double check valve assy. (sealed system only) Filling point (sealed system only) Heating flow Heating return Flow Return Barrier heat exchanger used on open or old/dirty systems Heating flow Note: A drain tap should be installed at the lowest point of the heating circuit and beneath the appliance. Fig. 9 System drain tap Heating return Fit pump if Barrier heat exchanger used Installation on a low temperature heating system. The boiler can directly feed a low temperature system, varying the maximum delivery temperature of the boiler and setting a value of between 2 and 85 C. To vary the boiler maximum delivery temperature, modify the boiler maximum delivery temperature of parameter No. 4 as described in Section 5.8 and Table 6. In this mode it is advisable to include a safety limit thermostat set at 55 C in series with the boiler circulating pump. The thermostat must be positioned in the system flow pipe at more than 2 metres from the boiler. Return Flow Drain tap 2 Alpha CD5S/7S - General Boiler Information

3.9 FILLING THE SEALED CENTRAL HEATING SYSTEM - Figs., The system design pressure (cold) should be set to. bar. This pressure is equivalent to a static head (see Fig. 9) of.2 metres of water. Provision should be made to replace water lost from the system. This can be by manual or automatic means, as shown in Figs. and. The position for connecting an automatic make-up vessel is indicated in Fig. 9. A double check valve assembly must be used, as shown in Fig.. Filling of the system must be carried out in a manner approved by the local Water Undertaking. Where allowed, the system may be filled via a temporary connection as shown in Fig.. After filling, always disconnect the flexible hose of the filling loop. All fittings used in the system must be able to withstand pressures up to 4 bar. Drain taps (to BS 2879) must be used to allow the system to be completely drained. Heating circuit return Stop valve Hose unions Double check valve assembly Test cock Filling loop temporarily connected Stop valve Mains water supply Heating circuit return Double check valve assembly Test cock Overflow Stop valve Fig. Fig. Mains water supply Feed cistern to be located above highest point in the system 3. FLUSHING THE HEATING SYSTEM It is essential that the central heating system is thoroughly cleaned and flushed when fitting an Alpha CD5S or CD7S boiler. Failure to do so will invalidate the warranty. If this is difficult because the system is old/dirty refer to Section 3.8, Fig. 9 gives consideration to using a barrier heat exchanger. The primary condensing heat exchanger is constructed in stainless steel and therefore is compatible with most materials used in a heating system. If a cleaning agent and inhibitor are used, they must be applied in accordance with their manufacturers instructions. Only products from Fernox and Sentinel are acceptable for use with the Alpha CD5S or CD7S boilers. Further information can be obtained from Fernox (Tel: 79 95233) or Sentinel (Tel: 5 429563). The system should be flushed in accordance with BS 7593 and BS 5449. The following procedures are recommended:. Installing onto a new system:- a.fill the system, vent at high points, at pump and radiators. b.check for leaks. c. Rapidly drain the system. d.if required, chemically clean the system as instructed by the recommended cleaner manufacturer. Note: Ensure that the system is flushed to remove any remains of the cleaner. e.if chemical cleaner is not used to clean the system:- i) Refill the system. ii) Switch on the boiler and allow the system to heat up to the normal operating temperature. iii) Rapidly drain the system while the water is still hot. iv) Refill the system. f. As required, add the recommended inhibitor to the system as instructed by the inhibitor manufacturer. g.recheck for leaks. 2. Installing onto an existing system, clean the system before fitting the new boiler:- a.if the old boiler is still working:- i) Switch on the boiler and allow the system to heat up to the normal operating temperature. ii) Rapidly drain the system while the water is still hot. iii) Refill and chemically clean the system as instructed by the recommended cleaner manufacturer. iv) Ensure the system is flushed to remove any remains of the cleaner. v) Fit the new boiler. b.if the old boiler is not working:- i) Rapidly drain the system. ii) Remove the old boiler. iii) Flush the system through. iv) Fit the new boiler. v) Refill and chemically clean the system as instructed by the recommended cleaner manufacturer. vi) Ensure the system is flushed to remove any remains of the cleaner. c. As required, add the recommended inhibitor to the system as instructed by the inhibitor manufacturer. d.check for leaks. Alpha CD5S/7S - General Boiler Information 3

3. DISPOSAL OF CONDENSATE Provision must be made for the safe disposal of condensate produced by the flue gases of the Alpha CD5S or CD7S boilers and reference should be made to BS 6798: 2 for the requirements on the disposal of condensate. The boilers incorporate a condensate trap which has a seal of 75 mm, therefore no additional trap is required. The condensate should ideally be discharged internally into an internal waste pipe (washing machine/sink waste) or soil pipe to avoid the possible risk of freezing. The pipework must be in 22 mm pipe. External pipe runs should be avoided, but if it is necessary, the pipework should be at least 32 mm and protected from the risk of freezing with a waterproof insulation and the length should be kept to a maximum of 3 m. Termination should be into an external gulley or soakaway as shown in Figs. 2 and 3. Note: All pipework must have a continuous fall (see Figs. 2 and 3) from the boiler and must be of an acid resistant material such as plastic waste pipe. (copper or steel is not suitable). It should be noted that the connection of a condensate pipe to a drain may be subject to local building control requirements. Plastic pipe Use waterproof pipework insulation in very exposed positions Ensure pipe is adequately supported Open end of pipe diverted into gully below grid but above water level Minimum gradient 2½ Fig. 2 - External gully 22mm termination from boiler Cement mortar sealing 5 mm min. O 2½ fall Ground level (either/or) mm plastic tube 25mm 3mm Bottom of tube sealed Soakaway depth 4mm filled with limestone chippings Two rows of 3 x 2mm holes at 25mm centres, 5mm from the bottom of the tube. Holes to face away from house. Fig. 3 - External soakaway 4 Alpha CD5S/7S - General Boiler Information

MINIMUM TOP CLEARANCE 35 mm MINIMUM SIDE CLEARANCE mm BOILER MOUNTING HOOK FIXING HOLE TOP OF CASING WITH COVER BOTTOM OF CASING HEATING FLOW (/2" BSP) SAFETY VALVE (3/4" BSP) GAS (28 mm) MINIMUM BOTTOM CLEARANCE 25 mm WITHOUT HYDRAULIC OPTIONAL KIT FOR USE WITH ALPHA CD5-7S BOILER MOUNTING HOOK FIXING HOLE MINIMUM SIDE CLEARANCE mm HEATING RETURN (/2" BSP) 4 INSTALLATION 4. UNPACKING. The basic boiler is supplied in a single box, containing the following:- Cased boiler supplied with water connections and washers Mounting hooks and wall plugs Tundish for pressure relief valve outlet Condensate discharge pipe Gas service cock and 28 mm connection tail Literature pack and Wall template Other parts of the flue system are supplied in seperate packs as ordered. 2. Unpack boiler and remove the loose items. 4.2 DIMENSIONS and CONNECTIONS- Fig. 4 3 3 8 Dia. 232 95 95 Alpha CD7S A 7 25 Heating flow B 5 Pressure relief valve discharge C Gas A Heating return B 7 3 495 6 B C 22 285 525 Fig. 4 4.3 PREPARE THE WALL - Fig. 5. Decide upon the position of the boiler taking into account the clearances required for servicing (refer to Section 2.5) and the flue terminal position. 2. Tape the template to the wall (ensure it is level and the right way up) and mark the position of the two holes for the boiler mounting hooks. 3. Drill the fixing holes (2 mm dia.) to accept the No.2 plugs supplied. Screw the boiler mounting hooks fully into the plugs. 4. Cut suitable holes in the wall/roof mm dia for open flue 8 mm dia. pipe or 27 mm dia. for concentric flue. Use the centre line positions given on the flue template. 5. Lift the boiler and locate it on the mounting hooks. Note: When handling or lifting always use safe techniques - keep your back straight, bend your knees, don't twist - move your feet, avoid bending forwards and sideways and keep the load as close to your body as possible. Where possible transport the boiler using a sack truck or other suitable trolley. Always grip the boiler firmly, and before lifting feel where the weight is concentrated to establish the centre of gravity, repositioning yourself as necessary. Centre line for horizontal concentric flue 7 mm Centre line for horizontal open flue Centre line for vertical flues Alpha Fig. 5 2 mm Alpha CD5S/7S - Installation 5

4.4 CONNECT THE PIPEWORK - Fig. 4. Thoroughly flush out all the water pipework. Refer to Section 3.. 2. Connect the system flow and return pipework to the boiler using suitable isolating valves. Note: Do not forget that the pressure relief valve discharge pipe must be routed clear of the boiler to a drain in such a manner that it may be seen, but cannot cause injury to persons or property. 3. Connect the 22 mm condensate trap drain pipe to the condensate discharge pipe using the clip supplied. Ensure that the condensate discharge pipe is as required in Section 3.. Pour at least.5 litre of water into the flue duct, as shown in Fig. 6, and check the condensate discharge pipe for soundness 4. Ensure that all the valves are closed and do not turn on the water or gas supplies at this stage. Fig. 6 4.5 'B23' TYPE SINGLE PIPE 8 mm FLUE KITS Vertical kit - see Fig. 7 and 8, and refer to Section 3.4. Fig. 7 shows the vertical flue kit parts. To assemble the kit to the boiler - Slide the flue pipe down through the roof seal and place the seal over the flue duct. Push the flue duct into the flue socket on top of the boiler up to the stop. Ensure the seal is pushed in position against the ceiling. The maximum vertical length (without bends) for flue pipe is 3 metres (see Fig. 7 and 8) To install extensions or other flue components, proceed as follows: fit the male end of the pipe or elbow up to the stop on the female socket (with lip seals) of the previously installed component, this will ensure a secure fit and seal of the joints. Ensure all joints have the seal located correctly and the tape supplied is applied around each joint to ensure the flue ducts cannot be pulled apart. It is recommended that the flue should be supported approximately every.5 m with access provided to the joints. Vertical terminal 43 mm minimum Flue pipe Maximum length 3 m Seal Seal Fig. 7 Fig. 8 Horizontal through the wall kit - see Fig. 9 and 2, and refer to Section 3.4. Fig. 9 shows the horizontal through the wall kit parts. To assemble the kit to the boiler - Fit the male end of the flue elbow into central flue outlet on the top of the boiler to the stop. Place the outer seal over the flue duct and slide it throught the wall from the outside. Place the inner seal over the flue duct then insert the duct into the elbow up to the stop. Slide the seals along the duct to seal it to the inside and outside of the wall. To install extensions or other flue components, proceed as follows: fit the male end (smooth) of the pipe or elbow up to the stop on the female socket (with lip seals) of the previously installed component, this will ensure a secure fit and seal of the joints. Extensions for flue kit - The maximum vertical/horizontal straight length (without flue bend) is 3 metres (refer to Section 3.4). Note: To prevent condensate lying in the flue pipe, slope the pipe towards the boilers with a minimum slope of 2.5-3 (25-3 mm per metre). When installing the extensions, a wall/ceiling mounted clamp must be installed every.5 metres. 6 Alpha CD5S/7S - Installation

Flue elbow Flue pipe Inner seal Outer seal 7 mm mm 8 mm Fig. 9 Note: Ensure the flue slopes downwards towards the boiler by a minimum of 25 to 3 mm per metre (2.5-3 ) Fig. 2 4.6 'C' TYPE CONCENTRIC FLUE KITS Convert the boiler from the factory supplied 'B23' type configuration to 'C' type, i.e. room sealed concentric flue by removing the 8 mm dia. adaptor and four screws securing the fixing plate and gasket from the top of the boiler. Horizontal through the wall concentric flue kit - see Fig. 2 and 22. Fig. 2 shows the flue kit parts that need to be fitted to the boiler to ensure the room sealed concentric flue can be used. To assemble the kit to the boiler - Fit the adapter into the central flue outlet on the top of the boiler up to the stop. Slide the square gasket over the adapter up to the groove, then fix it to the cover by means of the previously removed fixing plate and four screws. Fit the male end of the flue elbow up to the stop on the adapter. Place the outer seal over the concentric flue pipe and slide it throught the wall from the outside. Place the inner seal over the concentric flue pipe then insert the pipe into the elbow up to the stop. Slide the seals along the duct to seal it to the inside and outside of the wall. To install extensions or other flue components, proceed as follows: fit the male end (smooth) of the concentric pipe or concentric elbow up to the stop on the female socket (with lip seals) of the previously installed component, this will ensure a secure fit and seal of the joints. Extensions for horizontal kit - The horizontal kit can be extended up to a maximum horizontal distance of 4 metres (Fig. 22), including the flue terminal and excluding the flue bend on the boiler (refer to Section 3.4). Note: To prevent condensate lying in the flue pipe, slope the pipe towards the boilers with a minimum slope of 3 (25-3 mm per metre). When installing the extensions, a wall/ceiling mounted clamp must be installed every.5 metres. Flue elbow Fixing plate Inner seal Outer seal Square gasket Adapter Concentric flue pipe Fig. 2 Maximum 4 mm 36 mm 382 mm 8 mm Inner seal 2 mm Outer seal Note: Ensure the flue slopes downwards towards the boiler by a minimum of 25 to 3 mm per metre (2.5-3 ) Fig. 22 Alpha CD5S/7S - Installation 7

4.7 CONNECT THE MAINS SUPPLY - Fig. 2. Remove the four screws securing the plastic top cover so that it can be lifted slightly at the front edge. 2. Remove the two fixing screws (one each side at the bottom) securing the case front panel (refer to Fig. 25). Pull the bottom of the panel outwards while pushing up at the same time and remove the panel then remove the two screws securing the control panel and lower the panel to gain access to the terminal block. Refer to Technical Data, Section 2. for connection details. 3. Note: This boiler has been fitted with a mains supply cable. However, if it is necessary to fit an alternative supply cable, ensure the cable clamp that has been fitted is removed and connect as follows:- Pass the mains supply cable through the cable clamp and connect as follows:- Brown to L, Blue to N and Green/Yellow to. Ensure correct polarity. Note: Ensure that the length of the earth wire is such that if the supply cable is pulled out of its clamp the live and neutral wires become taut before the earth wire. Do not switch on the electrical supply at this stage. 4. If any external control, i.e. room thermostat etc. is to be fitted, refer to Fig. 2. Note: All external control connections are less than 24 volts. Do not connect 23/24 volts to any of the terminals G to Z on the X86 terminal block or to the X84 terminal block. 5. Ensure that there is sufficient free cable to allow the control panel to be raised and lowered then tighten the cable clamp screws. 6. Leave the control panel open until commissioning procedures have been completed. 7. Carry out electrical system checks - Short circuit, Polarity, Earth continuity and Resistance to earth with a suitable multimeter. 8 Alpha CD5S/7S - Installation

5 COMMISSIONING When commissioning the boiler, ensure the Benchmark Checklist is completed. 5. FILL THE SYSTEM. The boiler is fitted with an automatic air vent positioned as shown in Fig. 3, ensure that the vent is always open. The CD5S also has a manual air vent (see Fig. 3) 2. Open the central heating flow and return valves. 3. Open the fill point valve on the filling loop until water is heard to flow. 4. To remove the air - Vent each radiator in turn, starting with the lowest in the system. 5. It is important that the pump is properly vented to avoid it running dry and damaging its bearings. Unscrew and remove the cap from the centre of the pump. Using a suitable screwdriver rotate the exposed spindle about half a turn, then replace the cap. 6. Check the operation of the pressure relief valve (see Fig. 3 or 4) by turning the head anti-clockwise until it clicks. The click is the valve lifting off its seat allowing water to escape from the system - check that this is actually happening. 7. Continue to fill the system until the pressure gauge indicates. bar. Close the fill point valve and check the system for water soundness, rectifying where necessary. Disconnect the filling loop from the mains supply. If the system has been over pressurised water may be released from the system by manually operating the drain point (see Fig. 3 or 4) until the system design pressure is obtained. The system design pressure (cold) should be between.75 and.25 bar. Refer to Sections 3.9 and 3.. Filling and Flushing the system. 5.2 TEST FOR GAS TIGHTNESS AND PURGE THE SUPPLY. With the boiler gas service cock closed. Pressure test the gas supply and inlet pipework connection to the boiler gas service cock for tightness in accordance with BS 689. 2. Loosen the gas inlet pressure test point screw on the gas valve (see Fig. 23). Ensure the gas supply is on and open the boiler service cock to purge in accordance with BS 689. 3. Retighten the test point screw and test for gas tightness. Close the boiler gas service cock. P3 Outlet gas pressure test point Outlet flow regulator Off-set adjusment screw P Inlet gas pressure test point 5.3 BOILER CONTROLS - Fig. 24 On/Off switch Display panel Fig. 23 Pressure gauge ON RESET MODE STEP STORE + - Alpha 5.4 INITIAL LIGHTING - Refer to Fig. 24 Fig. 24. Ensure that the gas and electrical supplies to the boiler are off and that the heating flow and return valves are open. 2. Turn on the gas and electrical supplies to the boiler. 3. Ensure any external controls are calling for heat. 4. Set the On/Off switch to ON. The boiler will now run in the central heating mode. The pump will start, the fan will start and the main gas valve solenoid will open allowing the main burner to light. Alpha CD5S/7S - Commissioning 9

5.5 BOILER DISPLAY PANEL AND FUNCTION MODES The boiler display panel (see Fig. 24, is composed of a 4-character display and 6 keys. By using these keys it is possible to adjust the boiler as it would be by using traditional selector switches and knobs. Table 2 gives the function of each key. RESET MODE STEP STORE + - Manual reset for possible boiler block Display menu selection key Selection of parameter to be displayed or edited Data and storage confirmation key Increase set value Decrease set value When the boiler is operating, the 4-figure display indicates the mode code (by means of the first 2 figures on the left) and the boiler flow temperature (by means of the other two figures on the right). For example if these values are shown on the display it means that the boiler is operating in heating mode with a flow temperature of 6 C. 3 6 The boiler function modes are given in Table 3: Table 2 Mode code 2 3 4 5 6 7 8 9 (flashing) A Mode description Stand - by, no operation demand Pre-ventilation Burner ignition Burner lit (system heating) Burner lit (domestic hot water) Fan check Burner off, requested temperature reached Pump over-run in system heating mode Pump over-run in domestic hot water mode Burner off for one of the reasons given in Table 8 3 - way valve check Table 3 5.6 BOILER FUNCTIONING PARAMETERS - Refer to Fig. 22 PARAMETER Mode - Press the MODE key once to enter Parameter mode. In this mode the preset operational values can be changed. The first two figures indicate the parameter number, the last two give the setting value. To change the boiler settings proceed as follows:. Press the MODE key once to enter parameter mode, using the STEP key select the parameter to be changed. 2. Change the value using the + or - keys, press the STORE key to store the new value. 3. Press MODE to make the new value effective. Parameters that can be modified are given in Table 4 Parameter Description Lower limit value Upper limit value Factory set New value Domestic hot water setting value * 2 C = disabled 7 C 2 Domestic hot water functioning mode = enabled 2 = disabled + continuous pump 3 = enabled + continuous pump = disabled 3 Heating function mode = enabled 2 = disabled + continuous pump 3 = enabled + continuous pump 4 Max. heating flow temperature 2 C 85 C * Only active with hot water function enabled when external accessories are fitted. 2 C 85 C Table 4 2 Alpha CD5S/7S - Commissioning

Parameter : Parameter 2: Parameter 3: Allows domestic hot water temperature to be set if controlled with NTC probe. Allows domestic hot water production to be activated or cut out. With factory settings domestic hot water production is cut out. Allows system heating function (Summer) to be cut out, or enabled (Winter). With factory settings system heating is on. Parameter 4: Allows heating flow temperature to be set. If the external temperature probe is connected to the boiler, the electronics automatically determine the ideal system water temperature. This parameter represents the maximum temperature that the system delivery water can reach. INFO Mode - Press the MODE key twice to enter INFO mode. In this mode the instantaneous operational values can be displayed and checked, but without making changes. The first two figures indicate the step number; the last two give the setting value. For example if these values are shown on the display it means that the boiler is operating in heating mode with a return temperature of 4 C. 2 4 Step 2 3 4 6 7, 8, 9 E Visulisation Flow temperature Return temperature Not active (Domestic temp., if domestic circuit probe is present) Not active (External temp., if probe is installed) Flow temperature set point Temperature gradients (cannot be modified) Flame current value Value Value in C Value in C 7 (value in C) -37 (value in C) Value in C C/S µa Table 5 5.7 BOILER FUNCTIONING PARAMETERS Tables 6 and 7 gives the boiler adjustment parameters with factory settings. To modify the parameters reserved for the Installer, it is necessary to enter an access code, which can be supplied on request. To enter the code:. Press the MODE and STEP keys at the same time for 2 seconds; the display will show the wording CODE and subsequently a random number on the last two digits. 2. Change the value by operating the + or - keys until reaching the correct code. 3. Press the STORE key to confirm. Possible settings for the Installer and User (without entering an access code) Parameter 2 3 4 Description Domestic hot water set point value Domestic hot water functioning mode Central heating functioning mode Max, central heating flow temperature Lower limit value 2 C = disabled = enabled 2 = disabled + continuous pump 3 = enabled + continuous pump = disabled = enabled 2 = disabled + continuous pump 3 = enabled + continuous pump 2 C Upper limit value 7 C 85 C Factory set 2 C 85 C New value Table 6 Alpha CD5S/7S - Installation 2

Settings accessible by the Installer only Parameter 2 3 4 5 6 7 8 9 2 2 22 23 24 25 26 27 28 29 3 3 32 33 34 35 36 37 38 39 4 4 42 43 44 45 46 47 48 Description Minimum heating flow temperature Lower external temperature limit Upper external temperature limit Antifreeze temperature External probe reading correction Max. secondary heating circuit temperature Min. secondary heating circuit temperature Secondary heating circuit temp hysteresis Min. tempearature set point value Booster time Flow temp compensation with ambient temp Temp increase rel to DHW set point Max fan rpm in heating mode (x) Max fan rpm in heating mode (units) Max fan rpm in DHW mode (x) Max fan rpm in DHW mode (units) Min fan rpm in heating mode (x) Min fan rpm in heating mode (units) Fan rpm during ignition (x) Fan rpm during stabilisation period (x) Stabilisation period Heating mode ramp up Pump overrun at end of heating cycle Pump overrun at end of DHW cycle Hysteresis modulation with heating ON Hysteresis modulation with heating OFF Hysteresis modulation with DHW ON Hysteresis modulation with DHW OFF Hysteresis measurement with DHW ON Hysteresis measurement with DHW OFF Heating mode timer DHW timer DHW heating mode transition timer Max time with DHW prioritised Cascade address Control type for heating installation Type of DHW installation Manual fan speed PWM signal level for pump Lower limit value 5 C -3 C 5 C -3 C -5 C Not active Not active Not active = Off C = no booster minute C 5 5 2 2 2 = minute seconds C C -5 C C C -5 C = phase with burner on 3 = phase with burner off s min Not active = ambient temp stat = external probe 2 = - V power 3 = - V temperature = instantaneous with probe = instantaneous no probe 2 = Boiler with probe 3 = Boiler without probe = Off % Upper limit value 6 C C 25 C C 5 C 6 C 3 minutes 8 C 3 C 6 99 38 99 6 99 27 38 9 5 99 minutes 3 seconds 2 C C 3 C 3 C 3 C 3 C 3 seconds 3 seconds 2 min % 4 Factory set New value 2 C -5 C 2 C C C C C C 5 C CD5S=52 CD7S=53 38 CD5S=3 CD7S=5 23 CD5S=6 CD7S=7 6 2 3 6 C 5 C C 5 C 5 C C 8 min 2 - Not active Table 7 22 Alpha CD5S/7S - Installation

Parameter 49 5 5 52 53 54 55 56 57 Description PWM signal level for pump PWM signal level for pump PWM hysteresis PWM pump high/low level Low/Off and pump cycle Min rpm for pressure switch (x) Min temp for boiler maintain function Ramp up for HTG or HTG + DHW function Pre-ignition time Lower limit value 5 C 6 x = Off x = On x = Normal heating pump cycle x = Normal DHW pump cycle 5 C (heating only) Not active Upper limit value 5 5 C 255 7 8 C (HTG + DHW) Factory set New value Not active Not active Not active Not active 5 C Table 7 - continued 5.8 FINAL COMMISSIONING. Allow the heating system to heat up, then balance the system to achieve the necessary temperature difference across the heating flow and return pipes at the boiler and check the system volume and pressure. (Refer to Technical Data, Section 2.2). 2. Turn off the boiler. 4. Thoroughly flush out the water pipework (refer to Section 3.). 5. Re-pressurise the system as described in Section 5.. 5.9 FINAL ASSEMBLY. Raise and secure the control panel, replace the front cover and secure in position with the screws removed and secure the plastic top cover in position using the screws previously removed. 2. If the boiler is to be left in service with the User, set any external controls to the User's requirements. 3. If the boiler is not to be handed over immediately, close the boiler gas service cock and switch off the electrical supply. 4. If there is any possibility of the boiler being left during frost conditions, then the boiler and system should be drained. It is recommended that a label is attached to the boiler drawing attention to the fact that the system has been drained. 5. Complete the details of the installation in the Benchmark Checklist on page 32. 5. USER INFORMATION The User must be advised (and demonstrate if necessary) of the following important points:-. How to light and turn off the boiler and how to operate any external system controls. 2. The importance of annual servicing of the boiler to ensure safe and efficient operation. 3. That any servicing or replacement of parts must only be carried out by CORGI registered personnel. 4. Ensure that the boiler controls are set to the User's requirements. 5. Tell the User about the sealed system pressure. 6. Tell the User that if the electrical supply is on and the boiler has not operated for 24 hours for heating or hot water, the pump will automatically operate for 5 minutes. 7. Explain to the User that an internal frost thermostat is fitted in the boiler, and that the electrical supply to the boiler must be left on for the thermostat to operate, i.e. the On/Off switch must be set to ON. 8. Explain to the User that in certain weather conditions the terminal will emit a plume of steam, i.e. water vapour. This is safe and quite normal. 9. Show the User the position of the pressure relief valve and condensate discharge pipes.. Hand the User's instructions to the User.. Ensure the Benchmark Checklist on page 32 has been completed after the boiler has been installed and commissioned. Note: It is a requirement that the installation is registered by the installer through the CORGI Gas Work Notification Scheme. 2. Leave these Installation and Servicing instructions with the User for use on future calls. Alpha CD5S/7S - Commissioning 23