Full and Partial Load Performances of RAC and CAC Heat Pump using R-32

Similar documents
Performance Measurement of R32 Vapor Injection Heat Pump System

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump

Study of R161 Refrigerant for Residential Airconditioning

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

Performance of CO2 Cycles with a Two-Stage Compressor

Control Method Of Circulating Refrigerant Amount For Heat Pump System

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

The Circulation Composition Characteristic of the Zeotropic Mixture R1234ze(E)/R32 in a Heat Pump Cycle

Impacts of room temperature on the performance of a portable propane air conditioner

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Optimization of Capillary Tube Parameters in Vapour Compression System using Environmentally Friendly Refrigerant R1234yf

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Low GWP Refrigerants for Air Conditioning and Chiller Applications

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Effects of Refrigerant-Lubricant Combinations on the Energy Efficiency of a Convertible Split-System Residential Air-Conditioner

Low GWP Refrigerants for Air Conditioning Applications

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

*Corresponding author;

TEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

ETI-Z Series Centrifugal Chiller Applied Low GWP Refrigerant to Contribute to the Prevention of Global Warming

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Oil Return Measurements In A Unitary Split System Air Conditioner Using Different Refrigerant Mixtures

EXPERIMENTAL STUDY ON R1234YF HEAT PUMP AT LOW AMBIENT TEMPERATURE AND COMPARISON WITH OTHER REFRIGERANTS

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

January 16 th, 2014 New York City

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner

Evaluation and Development of Air-conditioners using Low GWP Refrigerant

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Evaluation of HCFC Alternative Refrigerants

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

SIMULATION OF POTENTIAL REFRIGERANTS FOR RETROFIT REPLACEMENT

International Journal of Informative & Futuristic Research ISSN (Online):

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

DEEPAK PALIWAL, S.P.S.RAJPUT

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

Heat Transfer Analysis of Vapor Compression System Using Nano Cuo-R134a

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

Air-Cooled Heat Exchanger Performance for R410A

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT

Performance of a Transcritical CO 2 Heat Pump for Simultaneous Water Cooling and Heating

Experimental Analysis on Effect of Design Parameters on the Performance of Single Loop Pulsating Heat Pipe

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Purdue e-pubs. Purdue University

STUDY AND PERFORMANCE ANALYSIS OF ECO-FRIENDLY REFRIGERANT FOR RETROFITTING R22 IN RESPECT TO BANGLADESH

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Passive cooling of telecommunication outdoor cabinets for mobile base station

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

Low Global Warming Refrigerants For Commercial Refrigeration Systems

System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

An Experimental and Theoretical Study on System Performance of Refrigeration Cycle Using Alternative Refrigerants

Thermal Performance of a Loop Thermosyphon

Two Phase Flow Boiling Heat Transfer and Pressure Drop of Two New LGWP Developmental Refrigerants Alternative to R-410A

Developing Two-Phase Flow Distribution in Horizontal Headers With Downward Minichannel-Branches

R32 Compressor for Air conditioning and Refrigeration applications in China

Performance Testing of Unitary Split-System Heat Pump with an Energy Recovery Expansion Device

COMPACT HEAT EXCHANGERS FOR MOBILE CO 2 SYSTEMS

A/C Cooling Load calculation and measurement

FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

Transcription:

Paper O.1.2.4-1 - Full and Partial Load Performances of RAC and CAC Heat Pump using R-32 Sungjin In, Graduate student, Sungkyunkwan University, Suwon, Gyunggi-do, 440-746, Korea Keumnam Cho, Professor, School of Mechanical Engineering Sungkyunkwan University, Suwon, Gyunggi-do, 440-746, Korea Byounghan Lim, Principal research engineer, Samsung Electronics Co., Ltd, Suwon, 446-746, Korea Hana Kim, Research engineer, Samsung Electronics Co., Ltd, Suwon, 446-746, Korea Kyoungrock Kim, Senior research engineer, Samsung Electronics Co., Ltd, Suwon, 446-746, Korea Abstract:Refrigerant with high GWP such as R-410A for residential and commercial heat pump systemsmight bereplaced with alternative refrigerants with low GWP. R-32 with the GWP of 675 might be one of strong candidates. Present study investigated the performances of a residential and commercial heat pump system using R-32 and R-410A under full and partial load conditions.optimum refrigerant charge amounts for both RAC and CAC systems using R-32were less by 20~30% than those for R-410A system. EER of R-32 was higher by approximately 3.8%~9.9% for RAC system and 3.3%~13.3 for CAC system than those of R- 410A RAC and CAC system, respectively, when the capacities of the system using three different refrigerants were set the same.seerusing R-32 was larger by 6-15% than that using R-410A, while SCOP using R-32 was larger by 2-12% for the RAC system. SEER using R-32 was larger by 1-13% than that using R-410A, while SCOP using R-32 was larger by 1-4% for the CAC system. Key Words: Heat pump, R-32, Partial load, SEER, SCOP 1 INTRODUCTION Residential heat pump and air-conditioner (RAC) using R-410A has been investigated alternative refrigerant with low Global Warming Potential (GWP) since R-410A has high GWP of 2088. Alternative refrigerants with low GWP might be R-32 as pure refrigerant since it has the GWP of 675.R-32 shows lower total equivalent warning impact (TEWI) than R- 410A (Kagawa 2012). TEWI might be calculated with the total effect of direct emissions and indirect effect of energy used forspecified period of time. There are lots of literatures on the heat pump system using R-32. Performances of air-water heat pump system using R-410A with cooling capacity of 1.8~2.4kW and heating capacity of 1.6~2.4kW were compared with those using R-32(Koyama et al 2010). Heat pump using R- 32 showed optimal refrigerant charge less by 20% than that using R-410A. Heating and cooling performances using R-32 were larger by 8~11% than those using R-410A, while compressor discharge temperature of heat pump using R-32 was higher by 20~30 than that using R-410A. Performance of air-water heat pump system with the capacity of 4.5kW system by using R-410A and R-32 was also compared(huang et al 2011). Optimal refrigerant charge of the heat pump using R-32 was less by 35% than that using R-410A. Cooling and heating capacities of the heat pump using R-32 were larger by 2.5% and 14.5% than those using R-410A respectively, while compressor discharge temperature of the heat pump using R-32 was larger by 15 ~ 20 than that using R-410A. Drop-in test on the performance of a residential air conditioner using R-410A was performed by substituting with

Paper O.1.2.4-2 - R-32 (Zhuang et al 2011). Optimal refrigerant charge of the heat pump using R-32 was lower by 25% than that using R-410A. Cooling capacity of the system using R-32 was larger by 1.2% than that using R-410A, while heating capacity of the heat pump using R-32 was larger by 2.7% than that using R-410A. Compressor discharge temperature of the system using R- 32 was higher by 15~35 than that using R-410A. Heat pump using R-32 with cooling capacity of 4kW and heating capacity of 5kW was tested (Hara et al 2012). Optimal refrigerant charge of the heat pump using R-32 was lower by 25% than that using R-410A. Cooling capacity of the heat pump using R-32 was larger by 2% than that using R-410A, while heating capacity of the heat pump using R-32 was larger by 5% than that using R- 410A. Performance of the heat pump system with the cooling capacity of 17.6kW using R-32 was tested(barve et al 2012). Tests at high outdoor temperature of 43 as well as cooling and heating standard modes were performed. Power at cooling and heating standard modes by using R-32 were lower by 7%~9% than those by using R-410A, while compressor discharge temperature of the system using R-32 was higher by 20~30 than that using R- 410A. Capacities of R-32 system were generally larger by 2.5~11.5% than those of R-410A system, while refrigerant charge of R-32 system was ranged within 75~80% of the R-410A system. Discharge temperature of compressor of the R-32 system was larger by 20~25% than that of the R-410A system. Since R-32 system showed high discharge temperature of compressor, change of oil, increase of compressor discharge volume might be suggested to decrease the discharge temperature of the compressor. As literature on commercial air conditioning system(cac system), heat pump using R-32 with capacity 10.6kW was tested (Palmiter et al 2011). Performance of R-32 was higher by 3~4% under cooling mode, higher by 1~3% under heating mode than those of R-410A. Aircooled water chiller using R-32 with cooling capacity 10kW was tested (Schultz et al 2012). Cooling capacity of R-32 was higher by 2% than that of R-410A. Heat pump using R-32 with cooling capacity of 12.5kW and heating capacity of 13.3kW was also tested (Crawford et al 2012). Performance of R-32 system was higher by 1~2% than that of R-410A system. Most of literatures reported the data by drop-in test at full load condition. Partial load performances of the heat pump using low GWP refrigerants might be investigated. Present study aimed to investigate the partial load performance of the residential and commercial heat pump using R-32. 2 EXPERIMENTAL APPARATUS AND PROCEDURE Residential and commercial heat pump system with cooling capacity of 3.5kW and 10kW respectively were utilized for drop-in test. Figure 1 shows the schematic diagram of the experimental apparatusas an air-to-air heat pump system. Refrigerant flow loop was reversed by a 4-way valve under cooling and heating conditions. Refrigerant loop was consisted of an inverter type rotary compressor, a 4-way valve, a condenser, a solenoid expansion valve, a mass flow meter, and an evaporator. Mass flow meter was installed at the outlet of the condenser to measure the refrigerant mass flow rate under heating and cooling modes. Test was performed for R-410A, R-32. Table 1 shows thermo-physical properties of R-410A and R-32 at both 47 and 7. Table 2 shows the partial load test conditions under heating and cooling modes according to EN 14825. Cooling and heating capacities of the residential and commercial heat pump were measured by air enthalpy method applied for the indoor and outdoor units of psychrometric calorimeter. Opening level of electric expansion valve(eev) and inverter frequency of the rotary compressor was controlled to keep the same capacity for three different refrigerants. Fan speed of indoor unit was kept constant regardless of partial load test condition, while fan speed of outdoor unit was updated according to SEER and SCOP conditions. Compressor frequency was controlled to keep pre-determined capacity through the drop-in test.

Paper O.1.2.4-3 - Figure 1: Schematic diagram of the experimental apparatus Compressor displacement was adjusted due to comparably large latent heat of R-32. Compressor displacement was decreased by approximately 3~4% for R-32 RAC and CAC system in order to maintain the same capacity with R-410A system. Data were gathered every 2 seconds until it reached steady condition. Uncertainty of the measured data was estimated according to the uncertainty analysis (Moffat 1988). Detailed specifications of measuring instruments and uncertainties are shown in Table 3. Table 1: Thermo-physical properties of test refrigerants R-410A R-32 T ( ) 47 7 47 7 ρ f (kg/m 3 ) 928.9 1141.2 856.4 1030.6 ρ v (kg/m 3 ) 126.4 37.51 90.05 27.56 h fg (kj/kg) 146.6 217.3 218.4 304.0 C p,f (kj/kgk) 2.134 1.5590 2.338 1.786 C p,v (kj/kgk) 2.201 1.213 2.304 1.329 k f (mw/mk) 77.23 99.08 109.3 139.7 k v (mw/mk) 23.04 12.84 21.38 12.45 μ f (μpa.s) 86.01 148.2 86.72 139.2 μ v (μpa.s) 15.66 12.57 14.43 11.85 Pr 2.377 2.331 1.855 1.779 3 DATA REDUCTION Heat transfer rates of condenser and evaporator, Q c and Q e, were estimated by using equations (1) and (2) by putting measured mass flow rate ( of refrigerant and estimated enthalpy. Enthalpies of refrigerant were found by applying measured data of temperature

Paper O.1.2.4-4 - and pressure for Refprop (version 9.0) developed by the NIST. Air-side heat transfer rate ( was obtained by equation (3). Mass flow rate of air ( was obtained by using density of air and air flow rate, while enthalpies of air were obtained by using temperature of air and relative humidity at both inlet and outlet. Compressor power was obtained by using equation (4). EER was obtained by substituting heat transfer rate in equations (1) and (2) and compressor power in equation (4) into equation (5).,, (1),, (2),, (3),, (4) EER (5) Table 2: Test Conditions DB( ) WB( ) DB( ) WB( ) Cooing Heating SEER A (Std.) 35 24 SEER B 27 19 30 24 SEER C 25 24 SEER D 20 - Standard 7 6 SCOP T -10-11 SCOP A -7-8 20 15 SCOP B 2 1 SCOP C 7 6 SCOP D 12 11 4 RESULTS AND DISCUSSION Figure 2 showed RAC system performance according to refrigerant inventory under cooling and heating standard modes. R-410A showed the best EER at the refrigerant charge of 900g under heating mode and 1000g under cooling mode. Ratio of EER for R-32to the best EER for R-410A for the RAC systemshowed the best EER at the refrigerant charge of 800g under heating mode and 900g under cooling mode. Optimal charge of R-32 RAC system was less by approximately 20%~30% than that of R-410A RAC system. Figure 3 showed CAC system performance according to refrigerant inventory under cooling and heating standard modes. R-410A showed the best EER at the refrigerant charge of 3000g under heating mode and 3100g under cooling mode. Ratio of EER for R-32 to the best EER for R-410A for the RAC system showed the best EER at the refrigerant charge of 2100g

Paper O.1.2.4-5 - under heating mode and 2100g under cooling mode. Optimal charge of R-32 CAC system was also less by approximately 20%~30% than that of R-410A CAC system. Table 3:Specification of measuring instrument Instrument Measurement Uncertainty refrigerant side thermocouple (T-type) T r ( ) -200 ~ 300 ± 0.15 pressure gauge P r (Bar) 0~35 ±0.04% mass flow meter r (kg/min) 0 ~ 5 ± 0.1% dew point meter T a ( ) -10 60 ± 0.2 air side hygrometer Φ a (%) 5~98 ± 0.8% air flow meter E a (m 3 /min) 5.5~60 ± 2% (a) Cooling standard mode (b) Heating standard mode Figure 2: RAC system performance according to refrigerant inventory under cooling and heating standard modes Reduction of refrigerant charge of R-32 was due to the difference of thermo-physical properties of R-410A and R-32. Latent heat and specific volume of R-32 were higher by 43% and 40% than those of R-410A, respectively. Figures 4, 5, 6 and 7showed comparison of, EER, G and compressor discharge temperature for RAC and CAC systems under cooling and heating standard modes by setting equalized capacity for R-410A and R-32.

Paper O.1.2.4-6 - (a) Cooling standard mode (b) Heating standard mode Figure 3: CAC system performance according to refrigerant inventory under cooling and heating standard modes EER of R-32 RAC system was higher by approximately 3.8~9.9% than that of R-410A RAC system.eer of R-32 CAC system was higher by approximately 3.3%~13.3 than that of R- 410A CAC system. Since compressor input powers for R-32 RAC and CAC systems were decreased to keep the same capacity with R-410A RAC and CAC systems, its EER was increased. Compressor discharge temperatures of R-32RAC and CAC systems were higher than those of R-410A RAC and CAC systems, because of different compressor suction specific volume and specific heat ratio. They went up to 82.7 and 81.5 for RAC system, 84.2 and 73.6 for CAC system under cooling and heating standard modes, respectively. Figure 4:, EER, G and T d for RAC system under cooling standard mode Table 4 and 5 showed partial-load performancesof RAC and CAC systemsaccording to EN14825. Partial load cooling and heating performances except D condition of R-32 RAC system were higher by 6~15% and 2~12% than those of R-410A RAC system, respectively. Partial load cooling and heating performances except D condition of R-32 CAC system were higher by 1~13% and 1~4% than those of R-410A CAC system, respectively.

Paper O.1.2.4-7 - Figure 5:, EER, G and T d for RAC system under heating standard mode Figure 6:, EER, G and T d for CAC system under cooling standard mode Figure 7:, EER, G and T d for CAC system under heating standard mode

Paper O.1.2.4-8 - Partial load performances of R-32 system were higher than those of R-410A system. It was due to the high latent heat of R-32. High latent heat caused high capacity. When capacities of R-32 RAC and CAC systems were similar than those of R-410A RAC and CAC systems, input power of R-32 RAC and CAC systems were decreased by 11%, and thus EER was higher than R-410A RAC and CAC systems. Table 4: Partial load performances of RAC system according to EN14825 R-32 / R-410A SEER Condition (Cooling) EER A 100% 115% B 100% 106% C 100% 108% D 100% 111% R-32 / R-410A SCOP Condition (Heating) EER T 96% 102% A 98.5% 105% B 100% 105% C 99% 112% D 123% 131% Table 5: Partial load performances of CAC system according to EN14825 R-32 / R-410A SEER Condition EER (Cooling) A 101.2% 113.3% B 100.7% 104.8% C 100.5% 101.7% D 96.9% 100.3% SCOP Condition (Heating) R-32 / R-410A EER T 99% 99.3% A 101.1% 98.1% B 102.4% 103.7% C 101.3% 100.9% D 96.6% 104.5%

Paper O.1.2.4-9 - 4 CONCLUSIONS The present study might be summarized as follows. (1) Optimal charge of R-32 RAC and CAC systems was less by approximately 20%~30%than that of R-410A RAC and CAC systems. (2) EER of R-32 was higher by approximately 3.8%~9.9% for RAC system and 3.3%~13.3for CAC system than those of R-410A RAC and CAC system, respectively, when the capacities of the system using three different refrigerants were set the same. (3) Discharge temperatures of R-32 were higher by the maximum of 8.8 forrac systems, 9.1 for CAC system than those of R-410A RAC and CAC system, respectively. (4) SEERusing R-32 was larger by 6-15% than that using R-410A, while SCOP using R- 32was larger by 2-12% for the RAC system. SEER using R-32 was larger by 1-13% than that using R-410A, while SCOP using R-32 was larger by 1-4% for the CAC system.. ACKNOWLEDGEMENT This work was supported by the SFARC at Sungkyunkwan University sponsored by Samsung Electronics Co. Ltd. NOMENCLATURE C p Specific heat (kj/kg-k) G Mass flux (kg/m s) h Enthalpy (kj/kg) k Thermal conductivity (mw/mk) m& Mass flow rate (kg/s) P Pressure (Pa) Pr Prantl number Q Heat transfer rate (W) T Temperature ( ) W Power(W) Greek symbols μ Viscosity (μpa.s) ρ Density (kg/m 3 ) Subscripts A Air c Condenser com Compressor d Discharge e Evaporator f Liquid in Inlet out Outlet r Refrigerant v Vapor

Paper O.1.2.4-10 - REFERENCES Barve, A., Cremaschi, L., 2012, "Drop-In Performance of Low-GWP Refrigerants in a Heat Pump System for Residential Application", Int. Refrigeration and Air Conditioning Conference at Purdue, paper no. 2197: P. 1-10. Crawford T., Uselton D., 2012, "System Drop-in Test of Refrigerant R-32 in Split System Heat Pump", AHRI, #4, pp.1-17. Hara, H., Oono, M., Iwata, I., 2012, "Experimental study of low GWP refrigerants for room air-conditioners", Int. Symposium on Next-generation Air Conditioning and Refrigeration Technology, paper no. NS 26: P. 1-9. Fujitaka, A., Shimizu, T., Sato, S., Kawabe, Y., 2010, "Application of low global warming potential refrigerants for room air conditioner", Int. Symposium on Next-generation Air Conditioning and Refrigeration Technology, paper no. NS 25P: p. 1-8. Kagawa, N., 2012, "Future aspect of refrigerants : considering thermo-physical properties and cycle performance", Int. Journal of Air-conditioning and Refrigeration, paper no. 1230002: p. 1-9. Koyama, S., Takada, N., Matsuo, Y., Yoshitake, D., Fukuda, S., 2012,, "Possibility to introduce HFO-1234ze(E) and its mixture with HFC-32 as low-gwp alternatives for heat pump/refrigeration systems", Int. Symposium on Next-generation Air Conditioning and Refrigeration Technology, paper no. NS 09: p. 1-10. Moffat, R, J., 1988, "Describing the uncertainties in experimental results", Experimental Thermal and Fluid Science, vol. 1, p. 3~17 Okazaki, T., Maeyama, H., Saito, M., Yamamoto, T., 2010. "Performance and reliability evaluation of a room air conditioner with low GWP refrigerant", Int. Symposium on Nextgeneration Air Conditioning and Refrigeration Technology, paper no. NS 27: p. 1-7. Palmiter L., Kim J,H,. Larson B., Francisco W.P., Groll A.E, Braun E.J., 2011, "Measured effect of airflow and refrigerant charge on the seasonal performance of an air-source heat pump using R-410A", Energy and buildings, Vol.43, pp.1802-1810 Schultz K., Kujak S., 2012, "System Drop-in test of R-410A alternative fluids (ARM-32a, ARM-70a,DR-5, HPR1D, L-41a, L-41b, and R-32)in a 5-RT Air-Cooled Water Chiller", AHRI, #1, pp.1-13 Huang, Y., Yin, Q., Yu, J., Wang, J., 2011, "Comparative experimental researches of air-towater heat pump with R32 and R410A for household", Int. Congress of Refrigeration, paper No. ID255: p. 1-5. Zhuang, R., Tu, X., Liang, X., 2011, "Study of R32 refrigerant for residential air conditioning applications", Int. Congress of Refrigeration, paper No. ID 259: p. 1-8.