STUDY AND TEST MATERIAL FOR THE. FA2 and FA4 ASSESSMENTS. (Fire Alarm On-Site and Business Cert. Holder) June 14, 2017

Similar documents
ASCR2, ASCR4, ASC2, ASR2, ASD2

Assessment Overview. Updated March 29,

Fire Alarm System Fundamentals

2018 NICET Code Transition Changes

NFPA 72 Code Changes vs 2013

Fire Prevention Coffee Break Training. February 2017

Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018

Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment

Changes in NFPA

FIRE & LIFE SAFTEY STANDARD

1 Exam Prep Fire Alarm Signaling Systems Tabs and Highlights

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

FIRE ALARM SYSTEMS & 780 CMR. Dave LeBlanc, PE, FSFPE March 17, 2015

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III

TrueCom. Building Communications Systems 5115-Series , Area of Rescue Communications System. Description

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

SECTION FIRE ALARM SYSTEMS

NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities

Bold items are particular to the City of Euless

DERRY FIRE DEPARTMENT LISTED AGENT CERTIFICATION PROGRAM

COURSE SYLLABUS FIRE ALARM AND FIRE SUPPRESSION SYSTEMS CORRESPONDENCE COURSE

The 2013 National Fire Alarm and Signaling Code

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018

COMMISSION ORDER. IT IS FURTHER ORDERED that the Request for Bid and Notice to Bidders be displayed on the Franklin County website.

ABOUT THIS DOCUMENT AND THE DOCUMENT STRUCTURE WE USE

1.3 REFERENCE STANDARDS

Figure 1. Figure 2. See notes 1 and 2 below.

Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety

Simplex Panel Interface Guide

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:

The following information shall become and form part of the contract documents.

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

IQ PANEL USER GUIDE SMARTHOME.

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016

SECTION : FIRE ALARM & DETECTION SYSTEMS

TrueAlert Notification Appliances

University Design Standard Fire Alarm Systems

Fire Alarm, Water Flow Alarm & Signaling Systems

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

2019 COURSE CATALOG (rev )

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

Fire Alarm System Inspection and Testing Report

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

El Reno Fire Department Fire Alarm Plan Review Worksheet

INSPECTION AND TESTING FORM

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

PORTAL USER MANUAL. Mobeye WaterGuard-FS. Float sensor CM2300FS. SW version 5.n

AlertWave Smart Wireless Solutions for Today s Campus Whether you are a large university

Security System. User Guide for the LED Command Center

30.45 Electric Release PDRP-2001

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

Florida Building Code 2010

TrueAlert Multi-Candela Notification Appliances

Prefunctional Checklist

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system.

Full Service Central Station Fire Alarm Listing Evaluation

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

Ontech GSM 9040/50. Reference Manual English -1 -

Architectural and Engineering Specification for a. Flash / Flare

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Brighton Area Fire Authority

SECTION FIRE ALARM SYSTEMS

Operations Manual TS400. Test Station for G450/G460 Gas Detector

Entero Voice Alarm system.

Lake County / Multi-Department Storage Facility / Project / December 12, 2016 SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

DL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

SC-6 Six Supervised Control Module

CONDITIONS OF SERVICE - NBN SERVICES 1. ABOUT

MNEC NFPA 72 WHITE PAPER

Contents. Glossary

11:00 to 12:00 Secrets to achieving code-compliant strobe installations. Ralph Coco, Potter Canada Paul Jewett, Mircom Group of Companies

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

Security System. User s Guide for the Text Command Center

Notice... 1 Trademarks... 1 US Patent Numbers... 1 Technical Services Contact Information... 2 Document Conventions... 2 Warranty...

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Fire Prevention Coffee Break Training. February 2016

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1

DIVISION 28 ELECTRONIC SAFETY AND SECURITY


Unified Fire Authority - Fire Prevention Bureau

Fire Alarm Wiring. Circuit types, styles and limitations

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

Use this product according to this instruction manual. Please keep this instruction manual for future reference.

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

Rocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO

CARD ACCESS CONTROL SYSTEM

Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS

TrueAlert Non-Addressable, Multi-Candela Notification Appliances Installation Instructions

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

Frequently Asked Questions

Australian/New Zealand Standard

Substation Monitoring System

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

Transcription:

STUDY AND TEST MATERIAL FOR THE FA2 and FA4 ASSESSMENTS (Fire Alarm On-Site and Business Cert. Holder) June 14, 2017 This document contains sample questions to help participants study for the FA2 and FA4 assessments. If you intend to take this booklet into the test, make sure it is bound in a binder or stapled. You will not be allowed to take any material into the test center if it is not bound. (IMPORTANT: Material provided is not intended to endorse, represent quality, recommend a particular product, or single out any product. Material may be used to provide standardized content for test questions to ensure that participants know how to use data sheets and manufacturer materials to establish listing and installation limitations of these types of products. There is no implied or other relationship between CSA and the manufacturers or suppliers of information used. CSA is not liable for accuracy or content of material contained within these documents. Material in this booklet is for testing purposes only and is not to be used for installation of these systems / components. Check with suppliers for current and specific information to be used in actual design and installation conditions.) Copyright 2017 CSA; June 2017 Page 1 of 7

About the Assessments: Assessment Abbreviation: FA2 Number of Questions: 77 Amount of Time for Test: 120 Minutes Assessment Abbreviation: FA4 Number of Questions: 100 Amount of Time for Test: 180 Exam format: Open book (bring your own books); calculators will be available, writing tablet or paper will be provided for calculations. Any books or exam documents brought into exam must be bound as no loose papers are allowed. Tabbed pages must use permanent tabs. We strongly recommend using handbooks (when available) such as the NFPA 72 handbook. These provide more detailed information to help understand the intent of code requirements with additional commentary, pictures, figures, etc. NFPA handbooks include all code language. IBC handbooks do NOT contain all the code language so if purchasing IBC Handbook you also need the IBC code. Passing Score: 80% Cell Phones: Do not bring cell phones, pagers, or radios into the test center. Codes / Materials Used for Exam and Editions: 2013 or 2016 NFPA 72 (you can use either edition) 2008-2014 NFPA 70 (NEC) These editions have been verified for same exam content There will be a few questions related to Occupational Safety and Health Act related to Lock-out Tag-out, fall protection, hard hats, and other safety gear. FA4 Assessment includes 2012 / 2015 International Building Code (either edition of Building Code will work) {The IFC will not provide all necessary information} FA4 Assessment may include questions related to NFPA 20 for Fire Pump Monitoring General Assessment Information: About the Questions: Questions are randomly selected from respective topics within a larger database. Answer choices are randomly mixed. Exam Format: Questions are computer based and will be delivered one at a time. You will have the opportunity to go back and review all questions. You can also check a box within each question which will flag it for later review. During the review, checked questions will be marked for easier identification. See the document on Screen Shots under the Test Info link on our web site. Time Clock: Most assessments will have a count-down timer displayed on the screen. It may appear as if this timer is fluctuating between questions (gaining time on one question and loosing time on the next question). This is normal. The software has a specific function which ensures your time is protected if there is a loss of the Internet connection. It is very difficult to explain the logic behind the clock. However, we can assure you that you are getting all of your time. Do not steadily watch the clock, but rather use it as a general guide. Long pauses between questions will result in the biggest time jump as the computers verify that you are still testing and did not loose the Internet connection. Copyright 2017 CSA; June 2017 Page 2 of 7

Important Candidate Information PRINTING SCORE REPORTS Candidates are not able to print reports at PSI centers. This is a computer restriction at PSI centers. Reports are not automatically emailed. However, while at the exam center Score Reports can be Sent to the email used to register your exam. At the bottom of window Click on Send. There is no confirmation, but it will be sent to the email shown at the top of the Score Report. From your home or office you can log into your Dashboard and print a copy. Go to www.csaexams.com and find links to Dashboard under the Test Info or Contractor Info pages. You will need your CA number and password. In the History tab click on the words Passed or Failed under the Outcome column for the exam you want to view. Then either Print to your printer, or Send to email in system. Taking Materials into Exams CSA exams are open book. You must provide your own code books and required exam materials. Check the study guide to verify what editions the exams are based on. All material must be bound (no loose papers). Other than sample questions and materials within a CSA study guide, do not take other study questions into the exam. Page tabs must be of permanent type. Do not mark in any materials during an exam. Phones, radios, pagers are not allowed in exam rooms, please leave these in your vehicles. ID is required. How to Schedule Your First Exam / Assessment To start the process, you must Request an Assessment from www.csaexams.com. Within 1 3 days you should receive an email from PSI with a link to their website along with your user name and password. Using this link log into PSI, make your payment and schedule your exam. If you do not get the email from PSI in 3 days, reply to your CSA Request email so we can look into it. Please check your spam / junk folders for emails from PSI. Make sure you are paying for the correct exam as there are no refunds. Rescheduling an Exam To reschedule an exam you must log back into the PSI system where you scheduled the exam, or using links at www.csaexams.com under Contractor Info. Changes should be made 3 days before your scheduled exam. (You can try up to 48 hours before start time depending on time zones.) If the system will not give you the option to Cancel/Reschedule than you must show up or firefight your fees. There are no refunds. If You Fail an Exam If you fail an exam, you must Request a new Assessment from www.csaexams.com. Then, when you get the email from PSI you can go to PSI website and make new full payment and schedule the exam. Photographs Your photograph will be taken when you register at the proctoring center. This is to verify who took the exam. This photo will also be used on your ID card. Although not required, you may want to wear a company shirt/logo. Pictures are cropped to best fit ID card, so there is no guarantee the logo will show. If you are worried about the quality or background, ask the proctor if the picture is good enough to be used on your ID card. When you Pass an Exam ID cards and certificates will generally be mailed out within three weeks. They will be mailed to the address provided when requesting the assessment. If the address has changed, please email CSA with new address. If You Need a New ID Card To change the company name, change your last name, or if you have lost your card, go to www.csaexams.com and select Replacement ID link. Exams are good for 3 years. Then a new exam is required. Please be respectful of others taking exams by minimizing noise and interruptions. If you have any exam or computer problems please see the proctor so they can assist. If necessary, the proctor can log a report for further investigation. Then notify CSA so we can look into the problem. Please report cheating to the proctor or CSA. Copyright 2017 CSA; June 2017 Page 3 of 7

The following questions are related to the FA2 and FA4 Assessments. Additional questions that are specific to only the FA4 assessment are later in this document. 1. Which wire size is largest in diameter? a) 12 AWG b) 18 AWG c) 14 AWG d) 24 AWG 2. Which wire size has the least resistance in Ohms? a) 12 AWG b) 18 AWG c) 14 AWG d) 24 AWG 3. Ohms law is defined by what equation? a) a2+ b2= c2 b) V=IR c) l x w = a d) r + i = v 4. A fire alarm circuit has five strobes with current values of 0.125A, 0.095A, 0.209A, 0.209A, 0.209A. What is the total current of these devices? Answer: 0.125A + 0.095A + 0.209A + 0.209A + 0.209A = 0.847A Now, let s use this information and calculate voltage drop for the circuit. Using the information above, and a wire resistance of 3.07 ohm per 1,000 feet (0.00307 ohms per foot). The total distance between the panel to the last device is 500 ft. What is the voltage drop on the circuit? We need to know and apply Ohms Law: V=IR, in our case V is Vdrop or the Voltage drop. I is Current, R is Resistance. Answer: First you must account for the wire resistance in the pair of wires (out to last device on black wire and back on red wire). Thus, the total distance of wire is 1,000 ft. Using ohms law you calculate the following: V = 0.847A x (1,000 x 0.00307ohm/ft). This results in a voltage drop of 2.60 volts. The standard format that NFPA 70 and manufacturers provide for wire resistance is ohms per 1,000 feet. If a question is provided with this format you will need to convert this to a resistance/foot. Example: Resistance is 3.07 ohms per 1,000 ft is converted by 3.07 ohms / 1000 ft = 0.00307 ohms/ft Copyright 2017 CSA; June 2017 Page 4 of 7

If you were asked to find the end-of-line voltage you would apply the starting voltage - voltage drop = end-of-line voltage. Such as 24-2.6 = 21.4 volts at end-of-line. You may find additional information about calculating voltage drops on the internet, or through on-line CSA training modules that discuss electronic principles. 5. Given a wire resistance value of R = 4.89 Ohms/1000ft from NEC Chapter 9, Table 8 and excluding temperature (16 AWG wire). Class B circuit The circuit was designed with a conduit length between panel and last device of 800 feet (red wire out to device). Circuit has 8-110 cd strobes at 200ma each (I = 1.6 amp) [8 x 200ma = 1600ma or 1.6A]. Nominal panel voltage of 24 vdc What is the voltage drop in this circuit using lump-sum approach? 0.46 volts 12.5 volts (correct) 14.2 volts 1.96 volts 6. Which term defines a mandatory requirement of the code? a) should b) must c) AHJ d) shall 7. What section of the 2013 edition of NFPA 72 applies to Power Supplies for protected premises systems? a) 1.2 b) 10.6 c) 12.1 d) 26.2.3 8. Several documents are required to be provided to an owner. Out of those listed, which form (document) is required to be completed and delivered to the owner upon completion of a mass notification system? a) Flush Test b) Invoice c) Maintenance contract d) Record of Completion 9. Visual notification appliances are required in all exam rooms within a doctor s office. 10. Notification zones shall be consistent with the emergency response or evacuation plan for the protected premises. Copyright 2017 CSA; June 2017 Page 5 of 7

11. In accordance with NFPA 72, elevators are not allowed to be used for emergency egress during a fire. 12. Detection devices used for door hold-open release service is not required to be monitored for integrity if within 5 of the door. The following are some additional topics that will be tested over. This is not all inclusive, but we want to make sure you have studied this material. Limitations to the number of addressable devices that can be impacted by a single fault. Strobe spacing and candela of the strobes for wall and ceiling mount. Power supplies, batteries, duration of secondary supply. Audibility levels including ambient, public mode, private mode. Pathway survivability Classes. Impacts of doubling the distance, and doubling the wattage of speakers and horns. Wire types, ratings, limitations. NEC sections including 110, 300, 760, and others. Detector spacing such as heat, smoke, duct detectors, flow switches, pull stations, room temperature sensors, etc. Mass notification, risk assessments, intelligibility, message priority, etc. Measuring velocity / pressure readings on duct detectors, how and what equipment Frequency of inspection, testing, and maintenance for various components ADA requirements for strobes in common use / public use areas The following questions represent questions that may be found on the FA4 Assessment in addition to the types of questions included in the FA2 Assessment. 13. You have a motel with 160 guest rooms. In accordance with the IBC, how many sleeping units are required to have visible alarms? a) 4 b) 7 c) 9 d) 14 14. You are replacing a fire alarm system and control panel in a Business occupancy that has an older audible alarm system with no visual notification. In accordance with the IBC, you would need to bring the system up to code since you are installing a new system. Copyright 2017 CSA; June 2017 Page 6 of 7

15. In accordance with NFPA 72, you are not allowed to use an emergency voice evacuation system for non-emergency messages such as paging. In addition to the above questions, there will be voltage drop calculation questions that are slightly more difficult than those used in the FA2 exam. Questions from Chapter 10 of the IBC related to access controlled egress, delayed egress, related to interconnection to the fire alarm system and impacting egress of occupants. This is in addition to numerous questions from Section 907. Copyright 2017 CSA; June 2017 Page 7 of 7