TEC Controller Heat Pump Single Stage. Owner's Manual Building Technologies

Similar documents
BACnet Programmable TEC (PTEC) VAV Chilled Beam with Demand Control Ventilation (CO2) and Floating or Analog Output Owner s Manual

APOGEE Heat Pump Controller - Multi-Stage

TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application Application Note Building Technologies

TEC Controller Multiple Compressor Heat Pump with Reversing Valve & Mixed Air Control, Application Application Note

TEC Controller Heating & Cooling Heat Pump with Internal Reversing Valve & Mixed Air Control, Application 2072

TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application Application Note Building Technologies

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note

TEC Controller Unit Conditioner - Two-Pipe Fan Coil Cooling or Heating, Application Application Note Building Technologies

TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies

BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657

I/O ZONE 560/583 USERS GUIDE

SEQUENCE OF OPERATIONS

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

Verasys System Operation Overview Technical Bulletin

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN

TC-9102 Applications

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1

1.0 Digital Controller

Feature Summary. I. System

Pioneer Gold Controller Technical Guide. Pioneer Gold Controller Code: Version 1.1 Used with AAON WSHP WV Series Vertical and WH Series Horizontal

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include:

Reference Guide for Microprocessor Controller

*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide

MicroTech Self-Contained Air Conditioning System

Predator Controller Hardware Family

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Reciprocating Chiller

Table of Contents. W2W Open

Siemens Thermostats. RDY2000BN Thermostat

Reference Guide for Microprocessor Controller

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet

Tri-Stack Smart System

AD-1272 Advanced Thermal Dispersion Probe Airflow Measuring System

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT

Table of Contents. WSHP Open v3

OVEN INDUSTRIES, INC.

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47

Reference Guide for Microprocessor Controller

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

McQuay BACnet Solution: Microtech II Self-contained Unit Controller with Discharge Air Control (DAC)

MicroTech Unit Ventilator

Product Manual SZ1009

ZonexCommander. ZonexCommander(Plus) Installation and Applications Manual. Network All Your HVAC Equipment

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL

0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom

Introduction. What is the W2W Open controller?

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers


Digital Precise Air Control - DPAC

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

MicroTech Rooftop/RMC

UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units...

iworx Air Side Application Wiring Guide

Installation and Maintenance Manual IM

Product Data. Features/Benefits. 33CS Carrier Comfort System Variable Volume and Temperature (VVT )

Safety & Installation Instructions

CONTENTS. Installation Guide. VT7200 Series

Pioneer Gold Controller Technical Guide

I N STALL AT ION & O PERATIO N MANUAL TA 1/ TA 2 CONTROLLER. Redefine your comfort zone.

MB Therma-Fuser Standalone Motorized Disc VAV Diffuser

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide. SE8600 Series Room Controllers

Metasys Integrator TITUS Application

Introduction. What is the W2W Open controller?

MBS Therma-Fuser Standalone Motorized Swirl VAV Diffuser

BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

Document # R01

CM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B

L SERIES UNITS 505,191M. 4/2006 Supersedes 504,908M

BACnet MODBUS N2 LON Description Type Point Description Name # Object Type Register Type ID SNVT # Name SNVT Read Only

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana

ZonexCommander. ZonexCommander(Plus) Installation and Applications Manual. Network All Your HVAC Equipment

control sequences model QST / EST Series Table 47: QST / EST Analog Electronic Control Strategies Fan Powered Air Terminals

1.0 Digital Controller

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Networkable Fan Coil Controller Specification and Installation Instructions

VT8300 Series Installation Guide 24 Vac Low Voltage

Natural Ventilation Controller with 24vDC drive NVC-1204

C-TRAC3 COMMUNICATION MANUAL FOR. BACnet NOVEMBER 2010 TO JANUARY 2014 USA HEAD OFFICE AND FACTORY

HVAC Controls Upgrades: Requirement Details ( )

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability

THIS IS A DESIGN GUIDE NOT A SPECIFICATION. Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL

CP CP

P/N f. HomeWorks QS Palladiom Thermostat Configuration Guide

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR

Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT

B-40/B-41 Modulating Temperature Controller

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide

ROOM THERMOSTATS KNX BASIC DOCUMENTATION

ASHRAE JOURNAL ON REHEAT

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control

Operation manual. Rooftop Packaged Unit

Transcription:

TEC Controller Heat Pump Single Stage Owner's Manual 125-5073 Building Technologies

Table of Contents How To Use This Manual... 4 Chapter 1 Product Overview... 6 Hardware Inputs... 6 Hardware Outputs... 7 Ordering Notes... 7 Power Wiring... 7 Communication Wiring... 8 Controller LED Indicators... 8 Temperature Sensors... 9 Room Temperature Sensor... 9 Auxiliary or Mixed Air Temperature Sensor... 9 Actuators... 9 Relay Module... 9 Related Equipment... 10 Chapter 2 Applications... 11 Basic Operation... 11 Application 2070 Single Compressor Heat Pump with Reversing Valve... 11 Application 2071 Two Compressor Heat Pump with Reversing Valve and Mixed Air Control... 12 Application 2072 Heating and Cooling Heat Pump with Internal Reversing Valve and Mixed Air Control... 13 Application Heat Pump Slave Mode... 14 Using Auxiliary Points... 14 Using the Controller as a Point Extension Device... 14 Chapter 3 Point Database... 15 Chapter 4 Basic Service and Maintenance... 21 Basic Service Information... 21 Preventive Maintenance... 21 Safety Features... 22 Glossary... 23 Index... 27 3

How To Use This Manual How To Use This Manual This manual is written for the owner and user of the Siemens TEC Heat Pump Controller Single Stage. It is designed to help you become familiar with the Siemens TEC and its applications. This section covers manual organization, manual conventions, symbols used in the manual, and other information that will help you use this manual. Manual Organization This manual contains the following chapters: Chapter 1 - Hardware, describes the hardware components and the accessories that are used with the TEC. Chapter 2 - Applications, describes the control applications available in the model of the TEC that includes a terminal block for wireable input/output connections. Chapter 3 - Point Database, defines the point database descriptors and includes address and applications. Chapter 4 Basic Service and Maintenance, describes basic corrective measures you can take should you encounter a problem when using the TEC. For issues not covered in this chapter, consult your local Siemens Industry representative. The Glossary describes the terms and acronyms used in this manual. The Index helps you locate information presented in this manual. Manual Conventions The following table lists conventions to help you use this manual in a quick and efficient manner. Convention Numbered Lists (1, 2, 3 ) indicate a procedure with sequential steps. Examples 1. Turn OFF power to the field panel. 2. Turn ON power to the field panel. 3. Contact the local Siemens Industry representative. Conditions that must be completed or met before beginning a task are designated with a. Intermediate results (what will happen following the execution of a step), are designated with a. Results, which inform the user that a task was completed successfully, are designated with a. Composer software is properly installed. A Valid license is available. 1. Select Start > Programs > Siemens > GMS > Composer. The Project Management window displays. 2. Open an existing project or create a new one. The project window displays. Actions that should be performed are specified in boldface font. Error and system messages are displayed in Courier New font. New terms appearing for the first time are italicized. Type F for Field panels. Click OK to save changes and close the dialog box. The message Report Definition successfully renamed displays in the status bar. The field panel continuously executes a userdefined set of instructions called the control program. 4

How To Use This Manual Convention Examples This symbol signifies Notes. Notes provide additional information or helpful hints. Cross references to other information are indicated with an arrow and the page number, enclosed in brackets: [ 92] Placeholders indicate text that can vary based on your selection. Placeholders are specified by italicized letters, and enclosed with brackets [ ]. For more information on creating flowcharts, see Flowcharts [ 92]. Type A C D H [username] [field panel #]. Manual Symbols The following table lists the safety symbols used in this manual to draw attention to important information. Symbol Meaning Description NOTICE CAUTION Equipment damage may occur if a procedure or instruction is not followed as specified. (For online documentation, the NOTICE displays in white with a blue background.) CAUTION Minor or moderate injury may occur if a procedure or instruction is not followed as specified. WARNING Personal injury or property damage may occur if a procedure or instruction is not followed as specified. DANGER Electric shock, death, or severe property damage may occur if a procedure or instruction is not followed as specified. Getting Help For more information about the Siemens TEC Heat Pump Controller Single Stage, contact your local Siemens Industry representative. Where to Send Comments Your feedback is important to us. If you have comments about this manual, please submit them to SBT_technical.editor.us.sbt@siemens.com 5

Chapter 1 Product Overview Hardware Inputs Chapter 1 Product Overview The Siemens TEC Heat Pump Controller Single Stage is used in single-stage heat pump applications. It provides Direct Digital Control (DDC) for three applications. The controller can operate as an independent, stand-alone, DDC room controller or it can be networked with a field panel. The controller provides all termination, input/output, system and local communication connections. The controller hardware consists of the controller with cover and mounting bracket (See Figure Siemens TEC Heat Pump Controller Single Stage). The following applications are covered: Slave Mode (Application ) Single Compressor Heat Pump with Reversing Valve (Application 2070) Two Compressor Heat Pump with Reversing Valve and Mixed Air Control (Application 2071) Heating and Cooling Heat Pump with Internal Reversing Valve and Mixed Air Control (Application 2072) Hardware Inputs Analog Room temperature sensor Application 2070 Application 2071 Application 2072 Room temperature setpoint dial (optional) Application 2070 Application 2071 Application 2072 Mixed air temperature sensor (optional) Application 2071 Application 2072 Aux temperature sensor Application 2070 Digital Night mode override (optional) Application 2070 Application 2071 Application 2072 Wall switch (optional) Application 2070 Application 2071 Application 2072 6

Chapter 1 Product Overview Hardware Outputs Hardware Outputs Analog None Digital Compressor Application 2070 Electric heat (optional) Application 2070 Reversing valve Application 2070 Application 2071 Damper actuator (floating control) (optional) Application 2070 Application 2071 Application 2072 Fan Application 2070 Application 2071 Application 2072 Compressor 1 Application 2071 Compressor 2 (optional); or stage 1 electric heat (optional) Application 2072 Stage 1 electric heat (optional) Application 2072 Stage 1 heating compressor Application 2072 Stage 1 cooling compressor Application 2072 Ordering Notes Siemens TEC Heat Pump Controller Single Stage 540-105N Power Wiring 7

Chapter 1 Product Overview Communication Wiring Communication Wiring The controller connects to the field panel by means of a Floor Level Network (FLN) trunk. Communication wiring connects to the three screw terminals on the controller labeled + (positive), - (negative), and (reference). Controller LED Indicators NOTE: The TX and RX LEDs indicate communication over the FLN. To determine if the controller is powered up and working, verify that the Basic Sanity Test (BST) Light Emitting Diode (LED) is flashing ON/OFF once per second. The controller has nine Light Emitting Diode (LED ) indicators (see Figure Siemens BACnet VAV Controller). Controller LEDs. LED Type Label (if present)* LED Number Indication DO LED 1 - LED 6 1 6 Indicates the ON/OFF status of the DO associated with it. A glowing LED indicates that the DO is energized. Transmit TX 7 Indicates, when flashing, that the controller is transmitting information to the field panel. Receive RX 8 Indicates, when flashing, that the controller is receiving information from the field panel. BST Basic Sanity Test BST 9 Indicates, when flashing ON and OFF once per second, that the controller is functioning properly. * Some LED labels and numerals may be hidden by the controller cover. The TEC will automatically detect the MS/TP baud rate at start up and will communicate with other devices when configured as a master MS/TP device (address 8

Chapter 1 Product Overview Temperature Sensors 1 through 127). The TX LED will start flashing as it attempts to communicate with other devices. Temperature Sensors Temperature sensors used with the Siemens TEC Heat Pump Controller Single Stage include an electronic room temperature sensor or an optional auxiliary temperature sensor. Room Temperature Sensor The room temperature sensor connects to the controller by means of a cable terminated at both ends with a six-conductor RJ-11 plug-in connector. See the Ordering Notes section for the location of the room temperature sensor/human Machine lnterface (HMl) port. Auxiliary or Mixed Air Temperature Sensor The auxiliary or mixed air temperature sensor is a 100K ohm thermistor that connects to the controller at the screw terminals for Al 3. Actuators Actuators used with the Siemens TEC Heat Pump Controller Single Stage include an optional floating control (with or without spring return) damper motor. This actuator is powered through the controller to position an outside air damper. Relay Module The Equipment controller interposing relay module consists of four high voltage (240 Vac, 1.2A maximum) relay contacts mounted on a printed circuit board. A relay module must be used when one of the following conditions exists: The controlled load is high voltage AC (greater than 24 Vac). The controlled load is DC. The controlled load is powered from a transformer that is separate from the transformer used to power the controller. The VA of load exceeds 12 VA on a single DO. NOTE: See local codes (National Electrical Code Handbook) when mixing Class I and Class II wiring. 9

Chapter 1 Product Overview Related Equipment Related Equipment Damper Actuator (floating control) (optional) Mixed Air or Auxiliary Temperature Sensor (optional) Relay Module Room Temperature Sensor Contact your local Siemens Industry representative for product numbers and more information. 10

Chapter 2 Applications Basic Operation Chapter 2 Applications The Siemens TEC Heat Pump Controller Single Stage provides Direct Digital Control (DDC) technology for various compressor heat pump applications. Temperature control varies with the application. If present, mixed air temperature control a stage of electric heat can be provided. Basic Operation The Siemens TEC Heat Pump Controller Single Stage provides Direct Digital Control (DDC) technology for various compressor heat pump applications. Application 2070 Single Compressor Heat Pump with Reversing Valve In Application 2070, the controller controls a single stage compressor heat pump with a reversing valve. In addition to a compressor, this heat pump may also be equipped with electric heat for auxiliary heat and optional outdoor air damper can be provided for ventilation air. Application 2070 Control Diagram. 11

Chapter 2 Applications Application 2071 Two Compressor Heat Pump with Reversing Valve and Mixed Air Control Application 2071 Two Compressor Heat Pump with Reversing Valve and Mixed Air Control In Application 2071, the controller controls a two compressor heat pump with a reversing valve. In place of the second compressor, this heat pump may also be equipped with electric heat for auxiliary heat. Mixed air control for ventilation and free cooling is also available. Application 2071 Control Diagram. 12

Chapter 2 Applications Application 2072 Heating and Cooling Heat Pump with Internal Reversing Valve and Mixed Air Control Application 2072 Heating and Cooling Heat Pump with Internal Reversing Valve and Mixed Air Control In Application 2072, the controller controls a heating compressor for heating and a cooling compressor for cooling. The reversing valve is controlled internally by the heat pump. In addition to compressors, this heat pump may also be equipped with electric heat for auxiliary heat, mixed air control for free cooling, and ventilation air. This application also controls small air handling units with two position heating and cooling control. Application 2072 Control Diagram. 13

Chapter 2 Applications Application Heat Pump Slave Mode Application Heat Pump Slave Mode Using Auxiliary Points It is possible to have extra points available on a Siemens TEC Heat Pump Controller Single Stage in addition to the ones used by the current application that is running in the controller. If these extra points will be controlled by a field panel, they must be unbundled at the field panel. See Chapter 3 for point database information. Using the Controller as a Point Extension Device A controller in default state can also be used as a point extension device by unbundling spare I/O points at the field panel. If the controller is only used as a point extension device, with no control application in affect, then its application must be set to slave mode and the points must be unbundled at the field panel. All points must be controlled from the field panel in order to be used. Unbundling points at the field panel allows you to use these available points. 14

Chapter 3 Point Database Chapter 3 Point Database This chapter presents a description of the Siemens TEC Heat Pump Controller Single Stage database including point descriptors, point addresses, and a listing of applications in which each point is found. Descriptor Address 1 Application Description CTLR ADDRESS 01 2070, 2071, 2072, APPLICATION 02 2070, 2071, 2072, Identifies the controller on the LAN trunk. Identification number of the program running in the controller. Valid input: 2070, 2071, 2072, RETURN DELAY 03 2070, 2071, 2072 Amount of time, in minutes, the heat pump will remain off after a return from power failure. ROOM TEMP {04} 2070, 2071, 2072, Actual reading from the room temperature sensor. HEAT.COOL {05} 2070, 2071, 2072 Current mode of operation for applications that can be either a heating mode or a cooling mode. DAY CLG STPT 06 2070, 2071, 2072 Temperature setpoint in degrees that the controller maintains during day periods in cooling mode if a room temperature sensor setpoint dial is not present or is not used. See STPT DIAL. Valid entry range: 48 to 95 F (9 to 35 C) DAY HTG STPT 07 2070, 2071, 2072 Temperature setpoint in degrees that the controller maintains during day periods in heating mode if a room temperature sensor setpoint dial is not present or is not used. See STPT DIAL. Valid entry range: 48 to 95 F (9 to 35 C) NGT CLG STPT 08 2070, 2071, 2072 Temperature setpoint in degrees that the controller maintains during night periods in cooling mode. Valid entry range: 48 to 95 F (9 to 35 C) NGT HTG STPT 09 2070, 2071, 2072 Temperature setpoint in degrees that the controller maintains during night periods in heating mode. Valid entry range: 48 to 95 F (9 to 35 C) RM STPT MlN 11 2070, 2071, 2072 Minimum temperature setpoint in degrees that the controller can use from the setpoint dial. This overrides any temperature setpoint from the setpoint dial that falls below this minimum. Valid entry range: 48 to 95 F (9 to 35 C) RM STPT MAX 12 2070, 2071, 2072 Maximum temperature setpoint in degrees that the controller can use from the setpoint dial. This overrides any temperature setpoint from the setpoint dial that raises above this maximum. Valid entry range: 48 to 95 F (9 to 35 C) RM STPT DIAL 13 2070, 2071, 2072, Temperature setpoint in degrees from the room temperature sensor (not available on all temperature sensor models). This setpoint will be used for control in day mode (heating or cooling) when enabled by STPT DIAL (Point 14). Valid entry range: 48 to 95 F (9 to 35 C) STPT DIAL 14 2070, 2071, 2072 YES indicates that there is a room setpoint dial on the room temperature sensor and must be used as the temperature setpoint for control in day/occupied mode. NO indicates that the appropriate preset setpoint will be used as the temperature setpoint for control in day/occupied heating or cooling mode. 15

Chapter 3 Point Database Descriptor Address 1 Application Description Valid input: YES or NO AUX TEMP 15 2070, 2071, 2072, WALL SWITCH 18 2070, 2071, 2072, Dl OVRD SW 19 2070, 2071, 2072, OVRD TIME 20 2070, 2071, 2072, Actual reading from a 100K Ω thermistor connected to the controller's AI 3 input. When a thermistor is connected at Al 3, DI 3 is not available. See DI 3. The physical input can not be used for both analog and digital input at the same time. YES indicates that the controller is to monitor the status of a wall switch that is connected to Dl 2. NO indicates that the controller will not monitor the status of a wall switch, even if one is connected. Valid input: YES or NO Actual indication of the status of the override switch (not physically available on all temperature sensor models) at the room temperature sensor. ON indicates that the switch is being pressed. OFF indicates that the switch is released. Valid input: ON or OFF Amount of time, in hours, that the controller will operate in day/occupied mode when the override switch is pressed while the controller is in night/ unoccupied mode. NGT OVRD 21 2070, 2071, 2072 Indicates the mode that the controller is operating in with respect to the override switch. NIGHT indicates that the switch has not been pressed and the override timer is not active. DAY indicates that the switch has been pressed and the override timer is active. The controller then uses a day mode temperature setpoint. This point is only in effect when DAY.NGT indicates night mode. FREE CLG 23 2071, 2072 Point commanded by the field panel PPCL to enable or disable mixed air control (free cooling). DI 2 24 2070, 2071, 2072, DI 3 25 2070, 2071, 2072, DAY.NGT 29 2070, 2071, 2072, DO 1 41 2070, 2071, 2072, DO 2 {42} 2070, 2071, 2072, Actual status of a contact connected to the controller at Dl 2. ON indicates that the contact is closed; OFF indicates that the contact is open. If a wall switch is used, it is connected to DI 2. See WALL SWITCH. Actual status of a contact connected to the controller at Al 3/Dl 3. ON indicates that the contact is closed; OFF indicates that the contact is open. When a contact is connected at Dl 3, Al 3 is not available. See Point number 15. The physical input can not be used for both analog and digital input at the same time. Indicates the mode in which the controller is operating. Day temperature setpoints are used in day mode. Night temperature setpoints are used in night mode. This point is normally set by the field panel. Digital output 1 controls a 24 Vac load with an ON or OFF status. If Motor 1 is enabled, DO 1 is coupled with DO 2 to control an actuator. Digital output 2 controls a 24 Vac load with an ON or OFF status. lf Motor 1 is enabled, DO 2 is coupled with DO 1 to control an actuator. DO 3 {43} Digital output 3 controls a 24 Vac load with an ON or OFF status. lf Motor 2 is enabled, DO 3 is coupled with DO 4 to control an actuator. ELEC HEAT 43 2070, 2072 This output controls the contact for the first stage of electric heat and has a status of ON or OFF. EHEAT1.CMP2 43 2071 This output controls the contact for the first stage of electric 16

Chapter 3 Point Database Descriptor Address 1 Application Description heat or for compressor 2. If used for compressor 2, then CMP TOTL must be set to 2. DO 4 44 Digital output 4 controls a 24 Vac load with an ON or OFF status. lf Motor 2 is enabled, DO 3 is coupled with DO 4 to control an actuator. HTG CMP 1 44 2072 Digital output used to control the heating compressor 1. REV VALVE 44 2070, 2071 Digital output used to control the reversing valve. COOL and HEAT status is indicated for the 24 Vac valve or relay. The default configuration is energized for HEAT. The configuration may be reversed in DO DIR.REV. CLG CMP 1 45 2072 Digital output used to control cooling compressor 1. COMPRESSOR 45 2070 Digital output used to control the compressor. ON or OFF status is indicated for the 24 Vac relay. COMPRESSOR 1 45 2071 Digital output used to control compressor 1. ON or OFF status is indicated for the 24 Vac relay. DO 5 45 Digital output 5 controls a 24 Vac load with an ON or OFF status. If Motor 3 is enabled, DO 5 is coupled with DO 6 to control and actuator. DO 6 46 Digital output 6 controls a 24 Vac load with an ON or OFF status. If Motor 3 is enabled, DO 6 is coupled with DO 5 to control and actuator. FAN 46 2070, 2071, 2072 Digital output used to control the fan. ON indicates that the DO is energized; OFF indicates that the DO is de-energized. DMPR COMD 48 2070, 2071, 2072 Value to which the damper motor is commanded in percent of full travel. MTR1 COMD 48 Value to which the Motor 1 actuator is commanded in percent of full travel. DMPR POS 49 2070, 2071, 2072 Current position of the damper motor in percent of full travel. This value is calculated based on motor run time. MTR1 POS 49 Current position of the damper motor in percent of full travel. This value is calculated based on motor run time. See MTR1 TIMING. MTR TIMING 51 2070, 2071, 2072 The time, in seconds, required for the damper actuator to travel from full closed to the full open position. MTR1 TIMING 51 The time, in seconds, required for the Motor 1 actuator to travel from full closed to the full open position. MTR2 POS 53 The current position of the Motor 2 actuator in percent of full travel (for use as an auxiliary slave point). This value is calculated based on motor run time. See to MTR2 TIMING. MR2 TIMING 55 The time, in seconds, required for the Motor 2 actuator to travel from full closed to the full open position. DMPR ROT ANG 56 2070, 2071, 2072 Number of degrees the damper is free to travel. DPR1 ROT ANG 56 Number of degrees that damper 2 is free to travel. DPR2 ROT ANG 57 Number of degrees that damper 2 is free to travel. MTR SETUP 58 2070, 2071, 2072, Configuration setup code for Motors 1 and 2. This enables the motors individually and sets each motor to be either direct or reverse acting. NOTE: When a motor is enabled, its associated DOs are 17

Chapter 3 Point Database Descriptor Address 1 Application Description enabled. DO DIR.REV 59 2070, 2071, 2072, Configuration setup code for DOs. Allows the DOs to be direct or reverse acting (enabled equals energized or disabled equals de-energized). CYCLE FAN 60 2070, 2071, 2072 YES indicates that the fan should cycle ON and OFF with the compressor during day mode. NO indicates that the fan should remain ON constantly in day mode. Valid input: YES or NO NOTE: In either case, the fan will cycle during night mode. FREE CLG ON 61 2071, 2072 Value, in percent, that the cooling loopout must exceed for free cooling to turn ON. FREE CLG OFF 62 2071, 2072 Value, in percent, that the cooling loopout must exceed for free cooling to turn OFF. CLG P GAIN 63 2070, 2071, 2072 Proportional gain value for the cooling temperature control loop. CLG I GAIN 64 2070, 2071, 2072 Integral gain value for the cooling temperature control loop. CLG D GAIN 66 2070, 2071, 2072 Derivative gain value for the cooling temperature control loop. CLG BIAS 66 2070, 2071, 2072 Biasing of the cooling temperature control loop. See CLGLOOPOUT. HTG P GAIN 67 2070, 2071, 2072 Proportional gain value for the heating temperature control loop. HTG I GAIN 68 2070, 2071, 2072 Integral gain value for the heating temperature control loop. HTG D GAIN 69 2070, 2071, 2072 Derivative gain value for the heating temperature control loop. HTG BIAS 70 2070, 2071, 2072 Biasing of the heating temperature control loop. See HTG LOOPOUT. MA P GAIN 71 2071, 2072 Proportional gain value for the mixed air control loop. MA I GAIN 72 2071, 2072 Integral gain value for the mixed air control loop. MA D GAIN 73 2071, 2072 Derivative gain value for the mixed air control loop. MA BIAS 74 2071, 2072 Biasing of the mixed air control loop. CMP TOTL 75 2071 Number of compressors used by the application. Valid values: 0, 1, 2 HTG CMP TOTL 75 2072 Number of heating compressors used by the application. Valid values: 0, 1 EHTG STG CNT 76 2071, 2072 Number of electric heating stages used by the application. Valid values: 0, 1 CLG CMP TOTL 77 2072 Number of cooling compressors used by the application. Valid values: 0, 1 CTL TEMP 78 2070, 2071, 2072 Temperature used as input for the temperature control loops. This value will be the same as the value in ROOM TEMP + RMTMP OFFSET unless it is overridden. CLG LOOPOUT 79 2070, 2071, 2072 Cooling temperature control loop output value in percent. HTG LOOPOUT 80 2070, 2071, 2072 Heating temperature control loop output value in percent. EHEAT 1 ON 81 2071 Value, in percent, that the heating loopout must exceed for the first stage of electric heat to turn ON. ELEC HEAT ON 81 2070, 2072 Value, in percent, that the heating Ioopout must exceed for the 18

Chapter 3 Point Database Descriptor Address 1 Application Description electric heat to turn ON. CMP ON 82 2070 Value, in percent, which the active temperature control loop output must exceed for the compressor to turn ON. Actual turn on is subject to the CMP1 MIN OFF time being expired. It is also the value, in percent, which HTG LOOPOUT must go below for the electric heat (ELEC HEAT) to turn OFF. CMP1 ON 82 2071 Value, in percent, that the active temperature control loop output must exceed for compressor 1 to turn ON. Actual turn on is subject to the CMP MlN OFF time being expired. lt is also the value, in percent, which HTG LOOPOUT must go below for the electric heat (ELEC HEAT 1) to turn OFF when only one compressor is used. HTG CMP1 ON 82 2072 Value, in percent, that the heating temperature control loop output must exceed for heating compressor 1 to turn ON. Actual turn on is subject to the HTG1 MlN OFF time being expired. CMP OFF 83 2070 Value, in percent, which the active temperature control loop output must go below for the compressor to turn OFF. Actual turn off is subject to the CMP1 MIN ON time being expired. CMP1 OFF 83 2071 Value, in percent, that the active temperature control loop output must go below for compressor 1 to turn OFF. Actual turn off is subject to the CMP1 MlN ON time being expired. HTG CMP1 OFF 83 2072 Value, in percent, that the heating temperature control loop output must go below for heating compressor 1 to turn OFF. Actual turn off is subject to the HTG1 MlN ON time being expired. RVAL SWITCH 84 2070, 2071 Value, in percent, that the active temperature control loop output must go above for the reversing valve to switch. Actual switchover is subject to the status of HEAT.COOL, RVAL SW TIME, and HTG LOOPOUT or CLG LOOPOUT. SWITCH LIMIT 85 2070, 2071, 2072 Active temperature control loop output must be less than this value to switch between cooling mode and heating mode. Actual switchover depends on SWITCH DBAND being exceeded and is subject to SWITCH TIME being expired. SWITCH TIME 86 2070, 2071, 2072 Time, in minutes, that must expire to switch between cooling mode and heating mode. Actual switchover depends on the active temperature control loop being below the value of SWITCH LIMIT and exceeding the value of SWITCH DBAND. CMP MIN OFF 87 2070 Minimum time, in minutes, which the compressor will remain OFF before turning ON. CMP1 MlN OFF 87 2071 Minimum time, in minutes, that compressor 1 will remain OFF before turning ON. HTG1 MlN OFF 87 2072 Minimum time, in minutes, that heating compressor 1 will remain OFF before turning ON. CMP MIN ON 88 2070 Minimum time, in minutes, which the compressor will remain ON before turning OFF. CMP1 MlN ON 88 2071 Minimum time, in minutes, that compressor 1 will remain ON before turning OFF. HTG1 MlN ON 88 2072 Minimum time, in minutes, that heating compressor 1 will remain ON before turning OFF. RVAL SW TIME 89 2070, 2071 Length of time the compressor must be OFF before the 19

Chapter 3 Point Database Descriptor Address 1 Application Description reversing valve can switch modes. SWITCH DBAND 90 2070, 2071, 2072 Temperature range in degrees that is compared to the difference between CTL TEMP and CTL STPT. The difference must exceed this value for temperature control mode to change over. Changeover is also subject to the active temperature control loop output being below SWITCH LIMIT and SWITCH TIME being expired. NGT MA CTL 91 2071, 2072 YES indicates that mixed air control should occur during night mode. NO indicates that mixed air control will not occur during night mode. Valid input: YES or NO. CTL STPT 92 2070, 2071, 2072 Actual setpoint value being used as input for the active temperature control loop. MA STPT 93 2071, 2072 Setpoint of the mixed air control loop. CAL TIMER 96 2070, 2071, 2072, Time interval, in hours, between the calibration sequence. LOOP TIME 98 2070, 2071, 2072 Time, in seconds, between control loop calculations. ERROR STATUS 99 2070, 2071, 2072, Status code indicating any errors detected during controller power up. A status of 0 indicates there are no problems. 1) Points not listed are not used in this application. 2) Point numbers that appear in brackets { } may be unbundled at the field panel. 20

Chapter 4 Basic Service and Maintenance Basic Service Information Chapter 4 Basic Service and Maintenance This chapter describes basic service and maintenance measures you can take when using a TEC. You may want to contact your local Siemens Industry representative if a problem occurs or you have any questions about the controller. NOTE: When troubleshooting, record the problem and what actions were performed immediately before the problem occurred. Being able to describe the problem in detail is important should you need assistance from your local Siemens Industry representative. Basic Service Information Always remove power to the TEC when installing or replacing it. Since the controller does not have a power switch, the recommended method of removing power to a locally powered controller is to turn OFF the power to the 24 Vac transformer. The recommended method of removing power to a controller on a power cable (even to service a single controller) is to turn OFF the power at the transformer. NOTE: When removing power to a controller to perform maintenance or service, make sure that the person in charge of the facility is aware of this and that appropriate steps are taken to keep the building in control. Never remove the cover from the TEC. There are no serviceable parts inside. If a problem is found with this device, contact your local Siemens Industry representative for replacement. An anti-static wrist strap is recommended when installing or replacing controllers. Preventive Maintenance Most controller components are designed so that, under normal circumstances, they do not require preventive maintenance. Periodic inspections, voltage checks, and point checks are normally not required. The rugged design makes most preventive maintenance unnecessary. However, devices that are exposed to dusty or dirty environments may require periodic cleaning to function properly. 21

Chapter 4 Basic Service and Maintenance Safety Features Safety Features The controller board stores the controller's address, applications, and point values. In the event of a power failure or a reset, these values are retrieved from the controller's permanent memory and are used by the controller unless overridden by a field panel. If one of the following conditions occurs, the controller will activate safety features present in its fail-safe mode. Sensor failure. Loss of power. Upon controller power loss, communication with the controller is also lost. The controller will appear as failed (*F*) at the field panel. 22

Glossary Glossary This glossary contains the collected terms and acronyms that are used in Siemens BACnet PTEC and TEC Controllers. For definitions of point database descriptors, see Chapter 3 - Point Database, in this manual. airflow Rate at which a volume of air moves through a duct. Usually expressed in cubic feet per minute (cfm) or liters per second (lps). algorithm Mathematical formula and control logic that uses varying inputs to calculate an output value. AVS Air Velocity Sensor. An electronic device that converts differential pressure from a pitot tube or multi-point pickup to an analog rate of fluid flow (air velocity in fpm, m/s) to provide calculations of air volume rate (cfm, lps) in a duct. The air velocity sensor may be an external device or an internal component of a controller. centralized control Type of control offered by a controller that is connected by means of Field Level Network (FLN). cfm Cubic Feet per Minute. Chilled Beam A cooling device that provides a cooling system by taking care of both the sensible and latent heat gains of a room in a single package by a series of chilled water coils mounted near or in the ceiling. Coupled with a CV or VAV terminal ventilation system, a chilled beam induces air movement over the coil in the way that it discharges fresh air into the room. This allows for both fresh air and cooling to be taken care of at the same time. control loop An algorithm, such as PI or PID, that is used to control an output based on a setpoint and an input reading from a sensor. CO2 Carbon dioxide, a naturally occurring chemical compound composed of two oxygen atoms and a single carbon atom. Among other production sources, carbon dioxide is produced as the result of breathing of humans and animals and can therefore be an indirect indication of the concentration of humans in a zone. CV Constant air volume. Ventilation system that provides a fixed air volume supplied to and exhausted from the rooms served. The fixed volume may be different during occupied and unoccupied times 23

Glossary Demand Control Ventilation A control algorithm that provides for the control or reduction of outdoor air intake below design rates when the actual occupancy of spaces served by the system is at less than design occupancy. DCV Demand Control Ventilation. DDC Direct Digital Control. Direct digital control The automated control of a condition or process by a digital device (computer). DO Digital Output. Physical output point that sends a two-state signal (ON/OFF, OPEN/CLOSED, YES/NO). English units The foot-pound-second system of units for weights and measurements. equipment controller FLN device, such as a BACnet PTEC or ATEC, that provides individual room or mechanical equipment control or additional point capacity to a field panel. field panel A DDC control device containing a microprocessor for centralized control and monitoring of system components and equipment controllers. Floating Control The combination of a modulating controlled device with the use of a pair of two position outputs. The control signal will either activate one or the other outputs to drive the controlled device towards its open or closed position. When both outputs are off, the controlled device maintains its last position. Also referred to as tri-state control. FLN Field Level Network. Network consisting of equipment controllers, FLN end devices, fume hoods, etc. lps Liters per Second. loopout Output of the control loop expressed as a percentage. Heat pump An HVAC device used for both space heating and space cooling. When a heat pump is used for heating, it employs the same basic refrigeration-type cycle used by an air conditioner but in the opposite direction, releasing heat into the conditioned-space 24

Glossary rather than the surrounding environment. In this use, heat pumps generally draw heat from the cooler external air or from the ground. HMI Human Machine Interface. Terminal and its interface program that allows you to communicate with a field panel or equipment controller. Occupancy sensor A control device that detects presence of people in a space by using infrared or ultrasonic technology. Occupancy sensors are used to save energy by controlling lighting and temperature and, along with CO2 sensors, to provide control input of demand control ventilation (DCV) algorithms. override switch Button on a room temperature sensor that an occupant can press to change the status of a room from unoccupied to occupied (or from night to day) for a predetermined time. pressure dependent Variable Air Volume (VAV) room temperature control system in which the temperature drives a damper such that the air volume delivered to the space at any damper position is dependent on the duct static pressure. pressure independent Variable Air Volume (VAV) room temperature control system in which the temperature drives an airflow setpoint such that the air volume delivered to the space is independent of variations in the duct static pressure. PID Proportional, Integral, Derivative. RTS Room Temperature Sensor. setpoint Data point that stores a value such as a temperature setting. In contrast, points that monitor inputs, such as temperature, report actual values. SI units Systeme International d'unites. The international metric system. slave mode Default application that displays when power is first applied to an equipment controller. No control action is initiated in the slave mode. Input and output points in the slave application can be monitored or controlled by a field panel (or by PPCL in a BACnet PTEC controller). stand-alone control Type of control offered by a controller that is providing independent DDC control to a space. 25

Glossary Terminal Equipment Controller Siemens Industry, Inc. product family of equipment controllers (one is the Siemens TEC Heat Pump Controller Single Stage) that house the applications software used to control terminal units, such as heat pumps, VAV terminal boxes, fan coil units, unit ventilators, etc. UI Universal Input. Can be used as an AI or DI. An AI input is a point receiving a signal that represents a condition that has more than two states. A DI input is a physical input point that receives a two-state signal. unbundle Term used to describe the entering of a point that resides in a controller's database into the field panel's database so that it can be monitored and controlled from the field panel. VAV Variable air volume. Ventilation system that changes the amount of air supplied to and exhausted from the rooms served. 26

Index Index A actuators, 9 address descriptions, 15 algorithm, 23 application, slave mode point extension, 14 applications basic operation, 11 ordering notes, 7 auxiliary points, using, 14 B basic operation, 11 Basic Sanity Test (BST), 8 basic service information, 21 BST LED, 8 C centralized control, 23 Chilled Beam, 23 CO2, 23 control loop, 23 controller Heat Pump, 6 LEDs/LED indicators, 8 Terminal Equipment Controller, 6 CV, 23 D database(see point database), 15 DCV, 24 DDC, 24 Demand Control Ventilation, 24 Direct digital control, 6, 24 Direct Digital Control (DDC), 11 DO, 24 E English units, 24 equipment controller, 24, 26 F field panel, 6, 14 FLN, 24 Floating Control, 24 Floor Level Network (FLN), 8 H hardware LEDs, 8 relay module, 10 temperature sensors, 9 Heat Pump product overview, 6 related equipment, 10 L LED, 8 Light Emitting Diodes (LEDs), 8 BST, 8 RX and TX, 8 loopout, 24 M mounting bracket, 6 O override switch, 25, 25 P PID, 25 point database, 15 point addresses, 15 point descriptors, 15 point extension, 14 preventive maintenance, 21 R relay module, 10 Room Temperature Sensor, 15 RTS, 25 RX LED, 8 27

Index S safety features, 22 service information, basic, 21 setpoint, 25 SI units, 25 slave mode, 25 stand-alone, 6 stand-alone control, 25 static discharge, 21 T temperature sensor, 9 temperature sensors auxiliary temperature sensor, 9 room temperature sensor, 9 RTS, 9 troubleshooting basic service information, 21 TX LED, 8 U unbundle, 14, 26 units, English, 24 28

Issued by Siemens Industry, Inc. Building Technologies Division 1000 Deerfield Pkwy Buffalo Grove IL 60089 Tel. +1 847-215-1000 2014 Copyright Siemens Industry, Inc. Technical specifications and availability subject to change without notice. Document ID 125-5073 125-5073(AA) Edition