TOTAL SYSTEM EFFICIENCY: CONDENSING BOILER SYSTEM MYTH BUSTING. David Grassl PE Mechanical Engineer Principal

Similar documents
TOTAL SYSTEM EFFICIENCY: AN INTRODUCTION TO CONDENSING BOILERS. David Grassl PE Mechanical Engineer Principal

TOTAL SYSTEM EFFICIENCY: CONTROL STRATEGIES & SYSTEM DISTRIBUTION. David Grassl PE Mechanical Engineer Principal

TOTAL SYSTEM EFFICIENCY: SYSTEM APPLICATIONS & DESIGNS. David Grassl PE Mechanical Engineer Principal

Best Practices for Condensing Boilers

MAXIMIZING HYDRONIC SYSTEM DESIGN PART III

CLEARFIRE HIGH-MASS CONDENSING FIRETUBE BOILER 500 TO 2,000 MBH

SAMPLE. added benefit of reduced operating costs during low demand periods, such as spring and fall.

Effects of Ultra-High Turndown in Hydronic Boilers By Sean Lobdell and Brian Huibregtse January 2014

HYDRONIC SOLUTIONS. More than just hydronic boilers, we offer the most efficient integrated hydronic solutions on the market.

The world s standard in efficiency. CBEX FIRETUBE

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

Removal of Non-condensable Gases and Air Is Critical In A Steam System

DISTRIBUTION SYSTEMS. Water Piping and Pumps

Panel Radiators. For Buderus Panel Radiator models: Applications Manual. - Model 21 - Model 22 - Towel Warmers

SmartLine Pressure Transmitters Modular, Accurate and Robust for the Lowest Cost of Ownership

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

CCLEARFIRE CONDENSING FIRETUBE BOILER DESIGNED FOR MAXIMUM HYDRONIC SYSTEM EFFICIENCY 500 TO 3,300 MBTU

Adding More Fan Power Can Be a Good Thing

Method to test HVAC equipment at part load conditions

A REASONABLE ALTERNATIVE TO CHILLED BEAMS Dan Int-Hout Chief Engineer

Helical Coil Heaters. Hot Oil Heaters Booster Heaters. CEI Enterprises

Air Conditioning Clinic

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

GT 120 >> >> >> << >> Sustainable Comfort. Longlasting comfort

Entrant: HJC Design Ltd. 192 Shoreham Street Sheffield, UK S1 4SQ Phone: Contact: Matthew Conley

PROFIRE -E SERIES BURNERS

Single Zone System. One duct system Used mostly in small buildings Forced air system All spaces controlled by a single thermostat Single air return

CHINOOK WARM AIR GAS FURNACE DESIGNED, ENGINEERED AND MANUFACTURED IN CANADA INCLUDING COMPONENTS MADE IN THE USA

Residential heating and domestic hot water. Customized heat transfer solutions

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

Flow Reversal in Primary/Secondary Systems by John Siegenthaler, P.E. April 17, 2007

Cclearfire HIGH EFFICIENCY, COMPACT CONDENSING BOILER 500-3,300 MBTU

MODEL M5M. High-Efficiency Packaged Watertube Boiler MMBTU

RSES Technical Institute Training Manual 3 72 hours, 72 NATE CEHs, 7.2 CEUs

By Thomas H. Durkin, P.E., Member ASHRAE, and James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE

Verasys System Operation Overview Technical Bulletin

SCHMIDT BRAZED PLATE HEAT EXCHANGERS. ...world leaders in heat transfer technology

COMcheck Software Version Review Mechanical Compliance Certificate

BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application

FLX FLEXTUBE. The Widest Range of Hydronic and Steam Watertube Boiler Systems 1,500 to 25,000 MBTU/HR (35-600HP)

VH Series B ENVIRO-STAC Vertical Hi-Rise Fan Coil Unit with Enhanced Humidity Control

ONQUEST. Featuring... Condensing Water Heater. Requires no tank linings or heat exchanger linings. Requires no anodes of any type. 10- year warranty.

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

6 PIPING ARRANGEMENTS

Benefits Offered by Passive Dehumidification Wheel Speed Control

Tranquility Digital Quick Start Guide

Hoval SR-plus heating boilers Outputs from 350 to 4000kW Working pressures to 8 bar

Advanced Hydronic Control Solutions for Geothermal heat pumps

AC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT

CONTROLLED CHILLED BEAM PUMP MODULE

THERMAL ICE STORAGE: Application & Design Guide

Tranquility Digital Quick Start Guide

HU, HCF, HCR Unit Heaters Technical Guide

HCLEARFIRE. High-efficiency, modular steam boiler HP

A Primary Concern by John Siegenthaler, P.E. October 1, 2005

VAV FAN POWERED TERMINAL UNITS TABLE OF CONTENTS FAN POWERED TERMINAL UNITS. C-2 Excellence in Air Distribution MODEL KQFS MODEL KQFP MODEL QFC

SEQUENCE OF OPERATIONS

Applications and Piping Strategies for Condensing Boilers - Introduction

UNITES TERMINALES ET MINI CTA FIDJI

Mechanical Redesign, Proposal Elizabeth C. Krauss Mechanical Option September 18, 2013

Hot Water Temperature Maintenance Product Selection and Design Guide

The First Name in Kickspace Heaters

hydronics WHAT S WRONG WITH THIS SCHEMATIC?

KN-SERIES MASTER SPECIFICATION

NON-REVERSING, 100% OUTSIDE AIR HEAT PUMP FOR HEATING AND COOLING

TANKLESS WATER HEATER HEATING SOLUTIONS

Contact Information. Steven Potratz, P.E. WSU Facilities Services, Engineering Services Manager Phone

NOVEMBER 2012 THE EUROPEAN EXPERIENCE

Designing Energy Efficient Outdoor Air Systems

ASHRAE JOURNAL ON REHEAT

4. OVERVIEW OF MECHANICAL SYSTEM

Accomplish Maximum Green Results in Commercial Buildings #

HIGH performance exchanger

Applications of Thermodynamics: Heat Pumps and Refrigerators

PRODUCT SERIES. VPR Series VPRX Series VPRE Series VPRP Series VPRC Series

Product Presentation. TUIG Indirect Gas Heated Tunnel Oven

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

CHINOOK THE INDUSTRY S MOST COMPLETE LINE. WARM AIR GAS FURNACE DESIGNED, ENGINEERED, AND MANUFACTURED IN CANADA

User s Manual. THE iq Drive SYSTEM USER S INFORMATION IMPORTANT. Variable Speed Ultra-High SEER Split System IMPORTANT NOTE

Greenheck Coils. A Complete Line of Custom Coils to Meet Your Needs. 3/8, 1/2 and 5/8 inch OD Tubing

Manual and installation instructions. Function. Operating phase

VCLEARFIRE. High-Efficiency, Commercial Steam Boiler Horsepower

KN2/4 SERIES MASTER SPECIFICATION

clearfire Large capacity condensing boilers 4,000 to 12,000 MBTU/hr

Refrigerant Dryers DS Series

ASHRAE S DOAS WEBCAST: A DEEPER EXAMINATION OF THE ROLE OF HEAT PIPES

DADANCO Technical Paper

GETTING THE MOST OUT OF HYDRONIC HEATING SYSTEMS

American University Design Standards

Over/Undersizing in TRACE 700

HEAT EXCHANGER FORMULAS & EXAMPLE

Infi niti Tankless. Water Heater Series Featuring SRT (Scale Reduction Technology) Built to be the Best

Water Piping and Pumps

KE2 EvaporatorEfficiency Theory of Operation

ASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes

THE ALL NEW COMBI BOILER

Greenheck Coils A Complete Line of Custom Coils to Meet Your Needs. 3/8, 1/2 and 5/8 inch OD Tubing

5 YEAR ADVANCE PLUS WARRANTY. High efficiency condensing combi and system boilers

VIFB Coil Technical Guide

Transcription:

TOTAL SYSTEM EFFICIENCY: CONDENSING BOILER SYSTEM MYTH BUSTING David Grassl PE Mechanical Engineer Principal

There are many reasons why engineers have been led to believe that condensing boilers do not fit a design application. Most of these reasons are inaccurate as condensing boilers can be used in most applications where a standard, non-condensing boiler can be used. Some of these reasons may have been valid for older, non-condensing boiler systems, but for condensing boilers, many of these concerns have been eliminated. Also, within the condensing boiler segment, there are a variety of technologies available. Some condensing boilers require more maintenance than others, or have specific piping, pumping, and flow requirements. High mass firetube condensing boilers have been developed to overcome many of these obstacles, and can be piped in a variety of systems with success. Therefore, it is important to understand each boilers operating requirements, as well as total cost of ownership, when making a boiler selection. MYTH #1 WE NEED TO MAINTAIN 180 F HOT WATER SUPPLY FOR THE SYSTEM TO WORK Prior to condensing boilers, it was common for systems to be designed with high hot water supply temperatures in the range of 180 F to 200 F. One of the main purposes of the high hot water temperature was to satisfy the hot water return temperature back to the boilers since a higher hot water supply temperature results in a higher hot water return temperature delivered back to the boiler. In non-condensing boilers, the hot water return temperature is critical, as the water temperature must always be maintained above the condensing temperature of the flue gases to protect the heat exchanger. Like non-condensing boiler systems, in condensing boiler systems, a lower hot water supply temperature results in a lower hot water return temperature delivered back to the boiler. The difference with a condensing boiler is that hot water return temperature is the driving force behind condensing boiler efficiency. In condensing boilers, the goal is to generate as much condensation as possible because the heat exchanger is constructed of a corrosionresistant material such as stainless steel or aluminum specific to this application. In addition to the hot water return temperatures, coils can also be designed to satisfy the load based on varying hot water temperatures. Table 1 demonstrates this point by comparing a main heating coil, typically found in an air handling unit, selected to do the same duty for both 180 F and 140 F hot water supply temperatures with a respective temperature difference of 40 F to satisfy the total heating capacity required. In both cases, the coil provides the same output, in MBH, to the heat air with minor differences in coil characteristics. Table 1: Comparison of two (2) heating coils selected at 180 F and 140 F hot water supply temperatures with the same system ΔT. Heating Coil #1 Heating Coil #2 Airflow 6000 CFM 6000 CFM Coil Capacity 305 MBH 305 MBH Hot Water Supply 180 F 140 F Hot Water Return 140 F 100 F Flow Rate 15 GPM 15 GPM Air Pressure Drop 0.02 IN WG 0.03 IN WG Water Pressure Drop 2 FT HD 2 FT HD Rows 1 1 Take note of existing systems that were designed for 180 F hot water supply temperature. With an existing system, the designer is typically stuck with the existing coils sized per the original design. Despite this, a condensing boiler is still an option, but care must be taken to ensure the hot water supply temperature at any given time will meet the load conditions required. With all things being equal, lower hot water supply temperatures will require more 2

heat- transfer surface area to meet the same load. This point is demonstrated in Table 1 as the coil selected for 140 F hot water supply temperature has more fi ns compared to the coil selected for 180 F hot water supply temperature. With that being said, many coils are oversized to some extent because upgrades to buildings have improved their envelope characteristics and leakage rates over time, so less heat output typically is needed. This means there is potentially the ability to operate the building the majority of the year at the reduced water temperatures or at the very least, be able to operate with more aggressive hot water reset strategies while improving system effi ciency. MYTH #2 WE NEED TO MAINTAIN A 20 F SYSTEM ΔT Myth #2 is similar to myth #1 in that older systems typically maintain a low T in order to keep the hot water return temperature above condensing conditions. In condensing systems, temperature differentials of 30 F or higher can be designed to increase boiler effi ciency by lowering the hot water return temperature back to the boiler. Increasing the temperature differential between the supply and return water has the added benefi t of reducing the fl ow rate since the fl ow rate is related to the overall heat output of the coil. Therefore, the higher the T, the lower the fl ow rate, which results in smaller pumps, less horsepower required to move the fl uid, smaller piping, and other system benefi ts. MYTH #3 HOT WATER RESET DOESN T WORK Hot water reset involves resetting the hot water supply temperature based on outside air conditions. The theory behind resetting the hot water supply temperature is that as the outside air temperature increases from the design condition, the amount of heat required to satisfy the space load decreases. Similarly, as the space load decreases, it is also possible to heat the space with a hot water supply temperature less than the design condition, which uses less energy to heat the water to a lower set point. Hot water reset is a simple control strategy that has Condensing Boiler Reset Curve been used for many years on hot water systems with a lot of success. With condensing boilers, the hot water reset functionality based on outside air is generally builtin, making this a relatively low- or no-cost item to implement within the system. Reset strategies have also been used on supply air and chilled water systems for years, so designers, operators, and contractors are aware of the design intent and goal of resetting system temperatures. The one item that should be understood regarding hot water reset is that there are conditions where resetting the hot water supply temperature will require additional fl ow to satisfy the load. In this scenario, hot water reset is less effi cient as the additional pump energy required to move the fl uid costs more than the energy benefi ts received from resetting the water temperature, so this condition should be avoided. MYTH #4 VARIABLE-FLOW-PRIMARY SYSTEMS ARE MORE COMPLEX Hot water systems are generally known for using primary-secondary systems, which became the norm as noncondensing boilers cannot handle variable fl ow to maintain hot water return temperatures above condensing conditions. In primary-secondary systems, primary fl ow is maintained as a constant fl ow rate, which keeps the return water away from potentially creating a condensing opportunity for the fl ue gases. 3

As for the argument that variable-fl ow-primary systems are more complicated, there are many installations that demonstrate primary-secondary systems are just as complicated. For example, installations that have a check valve in the common pipe. The check valve typically is used as a post-design solution on a system that has diffi culty supplying hot water to the system where the primary-loop, or boiler-loop, fl ow rate is less than the secondary loop, or distribution loop. This condition creates mixing and provides a hot water temperature less than that created by the boilers. It eliminates free, bi-directional fl ow in the common piping, which is the main objective of a primarysecondary system. In actuality, variable-fl ow-primary systems are simpler than primary-secondary systems as variable-fl ow-primary systems only require one set of pumps to handle everything in the system. Also, there is no mixing due to two hydraulically separate pumping loops and less equipment is required, so there are fewer devices to control. In variable-fl ow-primary systems, there are three items that must be addressed for proper system operation. The fi rst item is a fl ow meter that can measure the water fl ow rate to the distribution system. In many designs, this is common practice for measurement and verifi cation or for owners who are interested in tracking the energy consumption, so it may already be part of the design. The second item is a minimum-fl ow bypass with a modulating two-way temperature control valve, which is the same control valve at all the heating coils in the system. These two items work in parallel with one another as the fl ow meter ensures minimum fl ow to the boilers and/or pumps is always maintained thus protecting the equipment. Many condensing boilers have very low- or no-minimum fl ow requirements, but verify this with the manufacturer as the lower the minimum fl ow, the less bypassing that will occur. Once the minimum fl ow is determined, the control logic for the minimum-fl ow bypass is to modulate the two-way control valve to meet the minimum fl ow rate of either the boiler or pump, which bypasses the system and returns to the boilers and pumps as shown in Figure 1. The minimum-fl ow bypass concept is commonly used in today s system designs and is very similar to three-way valves in constant volume systems that reduce fl ow rate through the coil when the space is at reduced capacity, thereby bypassing excess fl ow around the coil and maintaining a constant fl ow rate at the coil. The third item that is required in a variable-fl ow-primary system is another two-way temperature control valve at each boiler when there are multiple boilers operating in parallel. This control valve is a two-position isolation control valve that remains closed when the boiler is off and opens when the boiler is on. Like the hot water reset controls that are built in to most condensing boilers, this is also typically a function that the boiler controls can perform, if desired by the designer. The purpose of the control valve is to prevent fl ow through the boiler when the boiler is off, which results in bypassing and mixing with reduced hot water supply temperatures. Based on these three items as described, there are no additional components required for a variable-fl ow-primary system. Similarly, all of these items are typically used in a system in some form already, either for coil control or measuring system fl ow, which limits the need to understand new control algorithms or special sequences. Figure 1: Minimum-flow-bypass control logic in a variableprimary-flow system. VSD VSD FLOW METER FOR PUMP MINIMUM FLOW FM MINIMUM FLOW BYPASS FOR PUMPS COIL 1 COIL 2 COIL 3 4 BOILER ISOLATION VALVES M M M TWO WAY CONTROL VALVES

MYTH #5 REVERSE RETURN HELPS BALANCING Piping distribution systems that deliver water to the system heating coils are designed using one of two strategies, either direct return or reverse return. Direct-return systems operate on the principle that the fi rst coil in the distribution path closest to the boiler plant will also be the fi rst coil to return the water to the boiler plant. Because of this, the piping distribution and corresponding pressure drop for this coil is typically much less than the last coil on the distribution network. As a result, if the fl ow rate to the coil is not properly balanced to have a pressure drop that effectively matches the other coil circuits, a large percentage of the system fl ow will take the path of least resistance, overfl owing the closer coils and starving the coils at the end of the piping circuit. Reverse return is a concept that evolved to solve the problem with direct-return systems. In a reverse-return confi guration, the fi rst coil to receive water from the central plant is designed to be the last coil to return water to the central plant. In theory, this equalizes the distance the water is pumped when distributed in the piping network and attempts to create a relatively equal pressure drop for each coil circuit. Figure 2 shows an example of directreturn compared to a reverse-return system for the distribution system. Figure 2: Direct-return compared to a reverse-return piping configuration. TO SYSTEM TO SYSTEM FROM SYSTEM DIRECT RETURN SYSTEM FROM SYSTEM REVERSE RETURN SYSTEM The reverse-return piping confi guration suggests that balancing can be signifi cantly reduced or eliminated. Unfortunately, this does not work as well in theory as each coil circuit has varying pipe sizes with different fl ow rates and dissimilar water pressure drops at each coil. For a typical system consisting of multiple air-handling unit coils with high fl ow rates and large pipe sizes mixed with VAV box reheat coils and terminal unit heating coils with smaller pipe sizes, each circuit will be completely different so balancing will still be required. Therefore, reverse return doesn t solve the issue it is designed to correct. Another disadvantage of a reverse-return piping system is that it takes the designer twice as long to design since both loops are different and must be sized based on the fl ow in the pipe at any given point in the system. One negative that is commonly cited for both systems is their limited expansion. Depending on the method of pipe sizing recommended by the designer, these systems can have no or very little capacity for expansion. The truth is the sizing of pipes dictates the expansion capacity, not the fact that a direct- or reverse-return piping confi guration is used. An additional argument that is typically made about reverse return is that there are conditions where reverse return is no more diffi cult to do from a piping layout. For example, as shown in Figure 3, a building has a piping shaft in the middle of the building and piping can be routed in a reverse return around the fl oor. This confi guration would be the only potentially recommended condition to use reverse return on the distribution piping as no additional piping is required. Despite this, it still takes twice the time to size all the piping. The piping circuits will not be equivalent since all the coils and fl ow rates are not the same, and only the fl oor will be 5

reverse return unless a third riser pipe is used in the shaft to create a complete reverse return system, which increases fi rst cost. Regardless of the method used, it is important to note that balancing will always be required to some extent. One time where reverse return could potentially pay off is when the equipment, fl ow rates, and pipe sizes are exactly the same, like in a boiler plant where there are multiple, similar-sized units. However, under this condition, the piping typically is much larger than in the distribution system, and the relative relationship of this equipment is so close that the equivalent length between individual devices is negligible. So, reverse return still doesn t provide the value and would only be recommended if it can be done without adding pipe length or additional design time. MYTH #6 HOT WATER SUPPLY TEMPERATURE IS IMPORTANT FOR EFFICIENCY IN CONDENSING BOILERS Figure 3: Reverse-return piping configuration on a floor where reverse return is relatively simple to design compared to direct return. Hot water supply temperature is part of the equation in defi ning heating coil sizing, but it is not the defi ning point of determining a boiler s effi ciency. As referenced previously, boiler effi ciency is dictated by the hot water return temperature since the amount of condensation that occurs in the heat exchanger depends on the temperature of the water compared to the fl ue gas temperature. Hot water supply temperature will almost always be above the condensing point of the fl ue gases, whereas the return water is the fl uid that comes in fi rst contact with the fl ue gases, cooling them to below the fl ue gas dew point, causing condensing and recovery of the latent heat from the moisture in the fl ue gas, which creates the effi ciency gains as shown in Figure 4. Furthermore, Figure 5 proves that hot water supply temperatures do not dictate effi ciency, as hot water supply temperatures are nowhere to be seen on the effi ciency chart as hot water return temperatures determine effi ciency based on boiler fi ring rates, demonstrating the lower the return water temperature, the higher the effi ciency that can be realized by the system Figure 4: The hot water return temperature to a condensing boiler dictates boiler efficiency as the water is the first contact point with the flue gases and more condensation occurs with lower water temperatures. HOT WATER SUPPLY HOT FLUE GASES COLD WATER RETURN COOL FLUE GASES CONDENSATE DRAIN AT REAR 6

MYTH #7 CONDENSING BOILERS ARE MORE DIFFICULT TO SERVICE AND REQUIRE MORE FREQUENT SERVICE Condensing boilers do not require any more service or maintenance compared to a standard boiler and heat exchanger. A condensing boiler consists of a stainless steel or aluminum heat exchanger that provides more resistance to changing water temperatures as compared to a standard, non-condensing boiler, where the operating temperatures, especially the return water temperature, are extremely important. In theory, although it is not recommended, less care could be provided to a condensing boiler due to its overall robustness. Due to its construction, a condensing boiler will last Figure 5: Boiler efficiency as a function of hot water return temperature. longer than a non-condensing boiler. If proper water chemistry and maintenance is performed, some condensing boilers are built to last longer than a non-condensing boiler. NEUTRALIZATION TANK NEUTRALIZATION MEDIA Figure 6: Example of a condensate neutralization media. One area that does require more attention in a condensing boiler is the condensate drain. It needs to be checked to ensure the neutralization kit is in working order. The neutralization kit is an acid neutralizer that increases the ph of the condensate to a neutral condition prior to discharge to the drain. The neutralization media is located within a bag that should be checked regularly to ensure there is enough media to fully neutralize the condensate. When the media has expired, replacement is necessary and involves discarding the old media and replacing it with new media, a task that can be completed in less than fi ve minutes. Condensate neutralizers can be purchased from the boiler manufacturer, and it is important to ensure there is enough neutralizer based on the boiler capacity, which dictates the amount of condensate produced. There are most likely more myths that exist for condensing boiler systems, but as explained, condensing boilers are not more diffi cult to design, install, or service compared to non-condensing boilers. In fact, the opposite is true for high-mass condensing boilers, which are generally more robust and require less attention. Systems can be designed for virtually any hot water temperature and T provided a coil can be sized to provide the appropriate output at acceptable air- and water-pressure drops to maintain system effi ciency. Similarly, hot water reset drives down hot water return temperatures, which is the main driver in system effi ciency as more fl ue gases are allowed to condense with lower hot water return temperatures. Finally, variable-fl ow-primary systems with direct return should be considered the new paradigm since their system design is more straightforward and shortens design time. 7

Providing energy-efficient, environmentally friendly boiler room solutions Cleaver-Brooks is one of only a few boiler room solution providers in the world to operate a dedicated research and development facility. Having pioneered several industry-leading technologies, we remain just as committed today to introducing technology and products that enable a more energy-efficient and environmentally friendly generation of steam and hot water. We distribute our products through the Cleaver-Brooks Representatives Association, or CBRA, an alliance of independently owned and operated companies that provide boiler room products and service. CBRA companies can be counted on to provide Cleaver-Brooks products and parts, engineering support, customer training, technical service and system maintenance. To find a CBRA representative near you, please visit cleaverbrooks.com/reps. Boiler system icons are copyrights of Cleaver-Brooks, Inc. Packaged Boiler Systems 221 Law Street Thomasville, GA 31792 USA 800-250-5883 info@cleaverbrooks.com cleaverbrooks.com Printed in the USA 2017 Cleaver-Brooks, Inc CB-XXXX 1/17