DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM

Similar documents
SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system.

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

Smoke Detector Activation of any smoke detector shall start the alarm verification mode.

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016

The following information shall become and form part of the contract documents.

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE

SECTION FIRE ALARM SYSTEMS

OKLAHOMA STATE UNIVERSITY

Fire Alarm System Fundamentals

SECTION FIRE ALARM SYSTEMS

SECTION : FIRE ALARM & DETECTION SYSTEMS

Environmental Health & Safety

Lake County / Multi-Department Storage Facility / Project / December 12, 2016 SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM

A. This Section covers fire alarm systems, including initiating devices, notification appliances, controls, and supervisory devices.

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5

SECTION COMMON WORK RESULTS FOR SAFETY AND SECURITY 1.1 RELATED SECTIONS

Addressable Fire Alarm Control Panel

SECTION FIRE DETECTION AND ALARM

SP40S-D. Kingfisher Company, inc. Features: Description:

SECTION ADDRESSABLE FIRE ALARM SYSTEM

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III

SECTION DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM

SECTION FIRE ALARM SYSTEM PART 1 GENERAL

CARD ACCESS CONTROL SYSTEM

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition

16721 FIRE ALARM AND DETECTION SYSTEMS

WINDOW & HVAC REPLACEMENT PEMBERTON TOWNSHIP BOE REGAN YOUNG ENGLAND BUTERA, PC PROJECT #5450E

Mircom FX /01/16

Functional Performance Test

LifeAlarm Fire Alarm Control Panels

1. The fire detection and alarm system (including the conduit) shall be a separate bid item and not part of the general electrical contract.

16721 FIRE ALARM AND DETECTION SYSTEMS

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS

Concerns: Affects: Dated: June 12, SECTION 1: GENERAL Scope Work Included... 3

SAFEPATH Mass Notification System (SPMNS)

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

C. All control equipment must have transient protection devices to comply with UL864 requirements.

University Design Standard Fire Alarm Systems

DIVISION 28 ELECTRONIC SAFETY AND SECURITY

PART IV DETAILED SPECIFICATION

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION FIRE ALARM SYSTEM (POINT GRAPHIC SYSTEM)

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Voice Annunicated Fire Alarm System Page 1 of 26

Fire alarm system specification for multiple tenant retail buildings

STATE OF NORTH CAROLINA

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

Autonomous control unit

DESIGN & CONSTRUCTION GUIDELINES

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

A. Provide addressable fire alarm system throughout the facility and supervise wet and preaction fire sprinkler system.

SECTION FIRE DETECTION AND ALARM

El Reno Fire Department Fire Alarm Plan Review Worksheet

Changes in NFPA

SECTION FIRE ALARM

FIRE ALARM AND DETECTION SYSTEMS

EIELSON AFB FIRE SYSTEMS STANDARDS 354 TH CIVIL ENGINEER SQUADRON ALARM MAINTENANCE SHOP

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

Mar H: SUPPLEMENTAL FIRE DETECTION AND ALARM (16720-H)

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

HARRIS COUNTY HOUSING AUTHORITY

Unified Fire Authority - Fire Prevention Bureau

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO

CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM. Bid # Addendum #1

E3 Series Broadband System

SECTION TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

E3 Series Broadband. Description. Features. Intelligent, Networked, Multi-Channel Fire Alarm Control and Emergency Voice Evacuation System

FIRE & LIFE SAFTEY STANDARD

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Changes to this Division since the last issuance are indicated with yellow highlighted text.

SECTION ADDRESSABLE FIRE ALARM SYSTEM

1. Buildings on the Pullman campus are monitored by a Simplex 4120 FDA Network or a Siemens XLS Network.

TrueAlarm Fire Alarm Systems

PEGAsys. Multi-Loop Intelligent Suppression Control System FEATURES DESCRIPTION. Effective: March 2007 K

Transcription:

DIVISION 26 ELECTRICAL SECTION 26 81 11 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install all equipment and accessories for a complete local, analog addressable, manually and automatically actuated, electrically operated, device annunciated, double supervised, non-coded 24 volt DC fire alarm system connected to Building Management network as described herein and as shown on the Plans. B. Furnish a network compliant (ANSI/ASHRAE Standard 135-1995), BACnet. Provide all necessary BACnet-compliant hardware and software to meet the system's functional specifications. Provide Protocol Implementation Conformance Statement (PICS) for every BACnet Device in the system, including unitary controllers. All Device hardware is to comply with BACnet. C. The fire alarm speakers will be used for mass notification during emergency situations and will also be used for non-emergency paging which will be accessed via the telephone system. System intelligibility testing will be required at completion of the project. 1.02 QUALITY ASSURANCE A. Fire alarm installation shall conform to the requirements of the NFPA 101, Life Safety Code, the Ohio Building Code, and Local Code and Building Authority requirements. B. All equipment shall be UL listed and labeled, and in accordance with applicable NEMA, ANSI Standards and Codes: 1. American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) ANSI/ASHRAE Standard 135-1995 BACnet 2. UL 916 Underwriters Laboratories Standard for Energy Management Equipment. Canada and the U.S. 3. National Electrical Code (NFPA 70) 4. FCC Part 15, Subpart J 5. EMC Directive 89/336/EEC C. All devices and installation shall be in accordance with the Americans with Disabilities Act. D. All BACnet device hardware shall be Listed Underwriters Laboratory for Open Energy Management Equipment (PAZX) under the UL Standard for Safety 916 in both the U.S. and Canada, with integral labels showing rating. All hardware shall be in compliance with FCC Part 15, Subpart J, Class A. The BACnet Device shall be tested by an objective third party for compliance to the BACnet Standard. E. All cabling for Signaling Line Circuit (SLC) and Notification Appliance Circuit (NAC) shall be Class A. Network cable shall be Style 7. 13-HC1-033 26 81 11-1

F. All vertical riser cable shall be a two (2) hour fire rated fire alarm cable and shall be listed in accordance with UL 2196. The vertical riser cable shall be installed in accordance with Electrical Circuit Protective System (FHIT), System No. 22. G. Emergency responder radio coverage shall be in compliance with 2012 Ohio Fire Code Section 510. 1.03 SUBMITTALS A. For Review: 1. Product data sheets of all components. 2. Riser/wiring diagrams and plans of entire system showing all devices, quantity, and size of wires, conduit sizes, zone schedule, sound levels, types of audible devices. 3. Power supply, amplifier and battery calculations indicating operating time and spare capacity for additional devices. 4. Voltage drop calculations for strobe circuits. B. To be included in Record and Information Manuals: 1. One (1) copy of each approval submittal 2. Certificate of Material Receipt 3. Certificate of System Completion C. Submit shop drawings to the appropriate Building Authority's office for review after approval by the Associate. These drawings shall include the following statement: 1.04 MANUFACTURER Korda/Nemeth Engineering, Inc., 1650 Watermark Drive, Columbus, Ohio 43215 as shown on the Construction Documents and as required by the OBC, designed the fire protective signaling system for this project. The [Insert Company Name] project drawings are provided with manufacturer's installation and wiring recommendations to assist in the installation. Korda/Nemeth Engineering, Inc., Job #. [Insert Designer Name] [Insert Company] [Insert City, State] NICET Level Fire Protection System Designer [Insert, Name] [Certification #, valid through ] A. Simplex-Grinnell 1.05 SYSTEM OPERATION A. Operation of any manual pull station or the actuation of any automatic device shall cause immediate and continuous operation of fire alarm signal and alarm indication at the control panel, remote annunciators and through the network connection to Building 701 until the actuated device is restored to normal and the control panel is manually reset. 26 81 11-2 13-HC1-033

B. Fire alarm control panel shall send a signal to the remote monitoring service organization via leased telephone lines to indicate alarm or trouble condition. Alarm signals shall also be sent to the mall system and the existing fire alarm system within the space shall also report troubles and alarms to the new fire alarm panel. C. The remote LCD annunciator panels shall audibly and visually annunciate both alarm and trouble as well as the location of the affected device. D. In the event of operating power failure, an open or grounded circuit in the system, a trouble signal and trouble LED shall be activated until the system is restored to normal. The trouble signal may be silenced by means of a switch mounted on the control panel. Upon restoration of the system, the trouble signal shall resound until the trouble silence switch is restored to the NORMAL position. E. The incoming power to the system shall be supervised so that any power failures must be audibly and visually indicated at the control panel. A green "power on" LED shall be displayed continuously while incoming power is present. The system batteries shall be supervised so that a low battery condition or disconnection of the battery shall be audibly and visually indicated at the control panel and the remote annunciator. F. Sprinkler waterflow and tamper switches shall be supervised for alarm and trouble conditions. Coordinate exact location with Division 21 Contractor in field. Provide monitor modules as needed to report status of flow and tamper switches. G. All air handling units and return air fans shall shut down when smoke is detected by return air duct mounted smoke detectors at the unit, unless unit is an integral part of a smoke control system. Shutdown shall be achieved by relay module signaled by the fire alarm panel. Exact location of smoke detectors shall be coordinated with Division 23 Contractor. H. The fire alarm system shall have a programmable relay module for each HVAC air handler. This relay shall close upon smoke detection by any smoke detector associated with that air handler in ductwork or at fan powered VAV terminal boxes. I. Each fan powered VAV HVAC terminal box or fan coil unit shall have a duct mounted smoke detector installed in the return air duct, with auxiliary relay modules. J. Area type spot smoke detectors shall be installed within the HVAC ductwork for each smoke damper and combination fire/smoke damper. Smoke detector shall have auxiliary relay module and remote alarm light. K. The fire alarm panel shall have on-off-auto switches to override automatic operation of the following pieces of equipment: 1. Supply air fans 2. Future emergency generator start 3. Future automatic transfer switch transfer between normal and emergency power for each ATS. L. Pre-action sprinkler systems shall be monitored for loss of supervisory air pressure. 13-HC1-033 26 81 11-3

PART 2 PRODUCTS 2.01 FIRE ALARM PANEL A. Fire Alarm Panel, 4100 ES, shall be an analog addressable type. Panel shall be modular with solid state, microprocessor based electronics, expandable, semi-flush mounted cabinet with glass window and locking door. Program shall be stored in non-volatile memory. Features shall include: 1. 80 character English readout dynamic LCD display 2. Battery supervision 3. Multiple operator access levels 4. 800 event historical logging 5. Zone selectable alarm verification 6. Individual circuit disable 7. Alarm, trouble, power on, and supervisory service LED indicators 8. Alarm, acknowledge, drill, lamp test, signal silence, and system reset buttons 9. Full Qwerty keyboard 10. Printer communication module 11. Remote station transmitter module for connection to 24 hour supervisory service 12. Synchronizing module for synchronized strobe visual devices 13. Optional wire or fiber network modules B. The system shall be provided with sufficient battery capacity to operate the entire system upon loss of normal 120 VAC power in a normal supervisory mode for a period of twentyfour (24) hours with five (5) minutes of alarm operation at the end of this period. The system shall automatically transfer to the standby batteries upon power failure. All battery charging and recharging operations shall be automatic with 100% recharge within twelve (12) hours. C. All external circuits requiring system operation power shall be 24 VDC and shall be individually protected at the control panel. D. The system shall have a strip printer mounted directly in the FACP enclosure. Alarms shall be printed in RED, other messages, such as trouble, shall be printed in black. This printer is to receive power from the system power supply and shall operate via the system battery backup if AC mains are lost. The printer shall be UL 864 listed. E. Digital voice communication audio system, shall provide one way microphone voice communication, and pre-recorded voice and alarm tones to selectable speaker circuits. Features shall include: 1. Dual channel audio 2. Selectable alarm-tones 3. Local panel speaker 4. Fire fighters' master telephone module with master phone and circuit selector switches 5. Digital audio technology F. Digital amplifiers for voice communication audio systems shall have 50 watts of spare capacity for additional audible devices. Provide one (1) backup redundant digital amplifier with automatic transfer in the main voice evacuation panel and in all remote audio transponder cabinets. 26 81 11-4 13-HC1-033

G. Panels shall have spare capacity for twenty-five (25) additional initiating devices. H. Digital communicator shall be point programmable, dual phone line with twenty-four (24) hour automatic test and automatic overload protection reset. I. Fire alarm system shall contain a relay module for each air handler fan. Relay shall be programmed to open upon smoke detection by any smoke detector associated with that air handling system and shutdown unit. Refer to Division 23 Drawings. J. Future software and firmware updates shall be provided at no cost to the Owner for two (2) full years following project close-out. K. The fire control panel must have one RS-232 port dedicated for connection to the BACnet Portal. The port is to be set to lock out Acknowledge, Silence, and Reset commands. In addition, the RS-232 port will be programmed to the lowest priority level for any control commands from the Portal. This setting locks out any outside commands affecting the panels programmed fire alarm operation. L. The BACnet Gateway shall be a fully self contained unit mounted within the fire panel, comprising of the Gateway circuit board assembly, power supply and mounting plate.. 2.02 REMOTE ANNUNCIATOR A. Remote annunciator, to be located at the main entrance, is to have an 160-character LCD display with English language readout, tone alert horn, control switches for alarm silence, system reset, alarm acknowledge, and key switch. 2.03 SMOKE DETECTORS A. Area smoke detectors shall be analog smoke sensor type photoelectric devices that communicate smoke density values to the fire alarm control panel. Sensors shall have integral insect screens and RFI shielded electronics in a white plastic head and base. Detectors shall be addressable and have LED status indicating light and locking tamper resistant base. Detectors performing auxiliary control function such as elevator lobby, hoistway, and machine room detectors shall be programmed to control a relay module for this function. B. Duct mounted smoke detectors shall be analog addressable with sampling tube as required to span HVAC duct width. Addressable relay module shall be provided for equipment shutdown. Housing shall be gasketed and weatherproof with internal heating means for applications where detector is located in an unheated space or on roofs. Remote LED indicator stations shall have a red status LED. Duct smoke detector and area smoke detectors installed within return air HVAC ductwork shall have a test port installed upstream for aerosol smoke injection. Test port shall consist of pipe and elbow within ductwork upstream of detector, flexible hose with cap below ductwork at an accessible location. Product available from: Lifesafetytest.com. 13-HC1-033 26 81 11-5

2.04 HEAT DETECTORS A. Heat detectors shall be combination rate-of-rise and fixed temperature (135 degree Fahrenheit) sensing with RFI shielded electronics. Detector shall be addressable with LED status indicating light and locking tamper resistant base. 2.05 MANUAL PULL STATIONS A. Manual pull stations shall be red lexan semi-flush mounted push type double action with pull handle. Unit shall lock in the pulled position requiring a key to reset. Unit shall be individually addressable on the system. Status LED shall be visible through the front cover. B. Manual pull stations shall have clear lexan tamper resistant cover over top, with integral battery and horn. 2.06 AUDIBLE/VISUAL DEVICES A. Visual devices (strobes) shall be multi candela, 24 VDC, xenon flash unit, white semi-flush base assembly stating "FIRE," clear tamper resistant lexan lens. Candela settings shall be set per Paragraph 3.01 D. Contractor shall verify with the AHJ that white is an acceptable color in their jurisdiction. B. Combination audible/visual devices (horn/strobes) shall have multi candela 24 VDC xenon flash unit, clear tamper resistant lexan lens, 24 VDC, white semi-flush base assembly stating "FIRE," minimum 95 db (at 10 feet) electronic horn. Contractor shall verify with the AHJ that white is an acceptable color in their jurisdiction. C. Combination audible/visual devices (speaker strobes) shall have multi candela 24 VDC xenon flash unit, clear tamper resistant lexan lens, white semi-flush base assembly stating "FIRE," minimum 85 dba (at 10 feet at 2 watts) speaker with water sealed compression driver and taps at 1/8, 1/4, 1/2, 1, 2, and 4 watts. Contractor shall verify with the AHJ that white is an acceptable color in their jurisdiction. D. Audible/visual devices installed on the exterior of building or in high humidity areas shall be weatherproof and moisture proof. 2.07 WATERFLOW AND TAMPER SWITCHES A. Sprinkler water flow and supervisory tamper switches shall be provided by Division 21. Provide addressable input monitor module to monitor each water flow switch and supervise each tamper switch. 2.08 CONTROL DEVICES A. Addressable output control modules shall provide relays with isolated contacts for controlling mechanical equipment. 26 81 11-6 13-HC1-033

2.09 MAGNETIC DOOR HOLDERS SECTION 26 81 11 A. Magnetic door holders shall be 24 VDC electromagnetic, flush wall or floor mounted single door devices. Door holders shall be controlled by a programmable relay module. Upon building power loss, door holders will close (not on battery power). 2.10 REMOTE NOTIFICATION APPLIANCE CIRCUIT (NAC) POWER EXTENDER PANELS A. Remote Notification Appliance Circuit (NAC) power extender panels shall be wall mountable, with locking hinged door cabinet. The panels shall contain batteries, charging circuit, and power supply. B. The Notification Appliance Circuit panel shall be addressable or controlled by programmable control modules. Strobe sync circuitry shall be built into each panel. C. Each Notification Appliance Circuit panel shall have a minimum of 6 Amperes of notification circuit power and shall have a minimum of four (4) zones. 2.11 EMERGENCY RESPONDER RADIO COVERAGE A. Radio boosters shall be provided to assure adequate emergency responder radio coverage. PART 3 EXECUTION 3.01 APPLICATION A. Maximum spacing between multiple smoke detectors in an area shall be 30 feet. No walls shall be more than 15 feet from a smoke detector. Smoke detectors shall not be installed within three feet of a HVAC diffuser. Wall mounted smoke detectors shall be installed at 12 inches from ceiling. B. Programming shall be done by the manufacturer's authorized representative. Electrical Contractor shall include in the bid sufficient funds to cover three (3) visits of eight (8) hours duration each for programming changes to include re-burning of electronic hardware components, to be done at the completion of the project after life safety test C. Refer to the Fire Protection drawings for location and quantity of tamper and waterflow switches. D. Visual device types shall be as follows: Candela Level Corridors 15/75 Rooms < 400 SF 15/75 Sleeping rooms 177 All other spaces 110 13-HC1-033 26 81 11-7

E. Visual devices shall be provided in every common use room (hallways, lobbies, restrooms, meeting and conference rooms, cafeteria, copy rooms, employee break rooms, etc) throughout the buildings and shall be mounted at least 80 inches above the floor and a minimum of 6 inches below the ceiling and located as follows: (1) within 15 feet of end of corridor, and in general no more than 100 apart in corridors (2) per the following table: F. Audible notification shall provide a sound pressure level 15dBA above the ambient sound or 5dBA above the maximum sound level having a duration of at least 60 seconds, whichever is greater. G. Manual pull stations shall be located no more than 5 feet from each exit and additional boxes so that the travel distance to the nearest box does not exceed 200. 3.02 INSTALLATION A. Follow manufacturer's written instructions regarding mounting, wiring, and testing the fire alarm system. Installers shall be certified for fire alarm work by State Agencies. B. Conductors shall be twisted pair No. 14 AWG solid copper for annunciation circuits. Provide minimum #18 shielded twisted pair solid copper wiring for initiation circuits and riser loops. Provide #14 AWG solid copper shielded twisted pair for speakers and fireman's phones. Installation shall be in accordance with the manufacturer's wiring diagrams, recommendations, and in compliance with practices set forth by local, State and National fire codes. Color code and tag all wires at all junction points. Do not exceed 40% conduit fill capacity. All cables shall be UL listed for Fire Alarm Application. Fire alarm wiring shall be red. 26 81 11-8 13-HC1-033

C. Duct mounted smoke detectors and duct mounted area detectors shall be installed in return ducts as directed by the mechanical equipment supplier under the supervision of the Division 23 Contractor, in a location that is accessible. Provide wiring to mechanical control equipment as necessary to achieve equipment control upon smoke detection. Install remote indicator lights at 60 inches above finished floor on adjacent wall in utility spaces, or in ceiling below duct detectors. Install label on each station identifying application. D. All wiring shall be in conduit unless noted and independent of all other systems. Paint all junction boxes with red paint and label "Fire Alarm." E. Provide 3/4 inch conduit from digital communicator to telephone terminal board. Provide two analog phone line cables from telephone board. F. Install tamper switches on sprinkler system post indicating valves. Install addressable monitor modules inside of the building. G. Smoke detectors located on either side of smoke doors and smoke shutters shall be installed between 1 and 5 feet of the door and connected to release magnetic door holders. Motorized smoke shutters with electric release shall have control power run from shutter operator through relay module to electric release mechanism. H. Provide 120 volt branch circuits from LSP panels, for power to fire alarm control panel, equipment racks, remote control panels, power supplies, and sprinkler system air compressors. I. The return path for all Class A circuits shall be in a separate conduit with a separate route back to the panel. J. Install printer jack and wiring from main panel in a location to be determined in the field. K. The system shall be programmed by the manufacturer to operate as described in Paragraph 1.05 - System Operation. In addition, the following sensitivity shall be programmed for smoke detectors in the following areas: General Areas 2.5% Duct Mounted Smoke Detectors 1.0% Mechanical/Electrical/Telephone Rooms 1.0% Elevator Lobbies 3.7% L. Signaling device circuits shall be loaded to no more than 75% of capacity. M. Provide wiring from fire alarm panel for alarm monitoring and supervision of kitchen exhaust hood fire suppression systems. Provide any required programmable modules for interfacing with hood system. N. Speaker taps shall be initially set as follows during installation: 1. Speakers in small rooms (less than 500 SF) - 1/4 watt 2. Speakers in large rooms and corridors - 2 watts 3. Adjustment of tap settings as required shall be the responsibility of the contractor to the satisfaction of the Fire Inspector and Engineer. 13-HC1-033 26 81 11-9

O. Panel shall be programmed to use slow "whoop" tone for annunciation before verbal message on voice system. P. Audible device (speaker) circuits shall be separately run to each of the following areas and selectivity controllable from the voice control panel: 1. Future Elevator Lobbies 2. Main Corridors 3. Exit Stairways 4. General Areas on a Floor 5. Rooms exceeding 1000 square feet area Q. Provide relays and wiring connection from the fire alarm system to all security system controllers to cause stairway door locks, exterior doors, and other egress doors to be released. R. Provide conduit and wire connection to main building management system control panel from fire alarm panel relays for remote monitoring of general alarm and trouble. S. Provide relays as required to connect fire alarm system to auxiliary systems as specified in other sections and noted on Drawings. T. Smoke and heat detector bases shall have an adhesive tape label with the programmed address visible from floor when head is removed. U. Provide an area type smoke detector within HVAC ductwork for each HVAC smoke damper shown on the HVAC plans. Detector shall be located within 5 feet of damper at access door location. Provide two (2) smoke detectors for ducts between 36 inches and 72 inches wide. Provide three (3) smoke detectors for ducts greater than 72 inches. Provide a system relay adjacent to smoke damper for signal damper to close. V. Area smoke detectors shall be located a minimum of 36 inches away from HVAC air supply diffusers or return air grills. 3.03 TESTING A. Each zone in the fire alarm control panel and remote annunciator and each device shall be individually tested as installed in the building under the supervision of an authorized manufacturer's representative. Contractor shall include in his/her bid, time for testing after normal work hours. B. The complete fire alarm system shall be tested by the Contractor as required by the Fire Marshal inspecting authority in the presence of the Owner's representative. Contractor shall make all modifications as required by the Fire Marshal. Contractor shall include in bid a second fire alarm system test of modifications mode. C. Operate system for a minimum of seven (7) consecutive days with no trouble conditions before claiming contract completion. D. Complete and submit the required NFPA 72 test and inspection forms. 26 81 11-10 13-HC1-033

3.04 SPARE PARTS A. Provide spare parts as follows: 1. Area Smoke Detectors 2 2. Duct Smoke Detectors 2 3. Heat Detectors 4 4. Manual Pull Stations 2 5. Audio Visual Devices 4 6. Magnetic Door Holders 2 B. Electrical Contractor shall include in his/her bid, an allowance for furnishing and installing (with average length of conduit and wire), the following, at completion of project as directed by the Architect. If not all used, remaining labor and material shall be credited to Owner: 1. Area Smoke Detectors 4 2. Duct Smoke Detectors 2 3. Heat Detectors 4 4. Manual Pull Stations 2 5. Audio Visual Devices 8 6. Magnetic Door Holders 4 7. Re-Programming Time 24 hours C. Furnish ten (10) keys to open panels, pull stations and annunciators. D. Obtain a signed copy of the Certificate of Material Receipt from Section 26 00 99, "Requirements for Contract Completion." 3.05 EQUIPMENT DEMONSTRATION A. After all system operational tests have been completed, schedule an instruction period with the Owner. Instruction to be provided by manufacturer's authorized field technician. B. The instruction is to include the following: 1. Location of all components of the system and explanation of their function 2. Demonstration of equipment 3. Maintenance and repair procedures 4. Programming procedures 5. Review of documents in Record and Information Manuals C. All participants shall sign the Certificate of System Completion from Section 26 00 99, "Requirements for Contract Completion." 3.06 SMOKE DETECTOR SENSITIVITY TEST A. All area and duct mounted smoke detectors shall have a sensitivity test conducted at the time of completion and during the eleventh month after date of contract completion. Sensitivity test shall be conducted by the manufacturer's representative. Clean all detectors that are out of their listed sensitivity range. Provide written documentation of test results. END OF SECTION 13-HC1-033 26 81 11-11