SECTION AIR DUCT ACCESSORIES

Similar documents
SECTION AIR OUTLETS AND INLETS

SECTION (15820) - AIR DUCT ACCESSORIES

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

AIR DUCT ACCESSORIES

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

15900 HVAC INSTRUMENTATION AND CONTROLS

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Louvers & Dampers April Product Guide Specification SECTION COMBINATION FIRE SMOKE DAMPERS

A. Section Common Motor Requirements for HVAC Equipment: Fan motors.

SECTION DUCTWORK

A. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

SECTION DUCTWORK

SECTION AIR HANDLING UNIT

SECTION AIR HANDLING UNITS WITH COILS. 1. Central Station Air Handling Units. 1. Section Basic Mechanical Requirements.

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters.

Submittal Data Performance Data Electrical Data

SECTION AIR COILS

SECTION HEATING BOILER FEEDWATER EQUIPMENT

Square Ceiling Diffusers : All extruded aluminum constructions. Opposed blade damper is adjustable from face of diffuser. Available in square and

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

SINGLE DUCT TERMINAL UNITS

SECTION DUCTWORK. A. Section Painting: Weld priming, weather resistant, paint or coating.

Chilled Water DOAS Fan Powered Terminal Units

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems.

SECTION HEATING BOILERS

Life Safety Dampers Selection and Application Manual

SECTION AIR COILS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

INSTRUMENTATION AND CONTROL DEVICES FOR HVAC

DACC Health Sciences Building Air Handler Assessment/Study

SECTION (15900) - INSTRUMENTATION AND CONTROL FOR HVAC

SECTION CENTRAL HVAC EQUIPMENT

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

SECTION (15767) - UNIT HEATERS

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section.

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise Modular Climate Changer Full Spec. Prepared by: Phone Number: Prepared for:

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials.

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

Stanford University Facilities Design Guidelines SECTION DECENTRALIZED UNITARY HVAC EQUIPMENT

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004)

City of Duluth Festival Center 04/25

FIRE & SMOKE DAMPERS. Meeting tomorrow's requirements for fire and smoke protection today.

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION AUTOMATIC VERTICAL CONVEYOR SYSTEM CLOSURE FIRE BARRIER

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup.

Tunnel Transit Dampers. Heavy Duty Tunnel Transit Life Safety

Recommended location under the current MasterFormat 2004 is Section Elevator Door Smoke Containment System.

SECTION (15833) - HVAC POWER VENTILATORS

SECTION FAN COIL UNITS

Recommended location under the current MasterFormat 2004 is Section Elevator Door Smoke Containment System.

SECTION ELEVATOR FIRE RATED SMOKE CONTAINMENT SYSTEM

VentZone Systems VentZone Zoned IAQ with Heat Recovery Kits

SECTION CUSTOM INDOOR CENTRAL-STATION AIR-HANDLING UNITS For large systems, 50,000 cfm or more.

SECTION CONVECTION HEATING AND COOLING UNITS

Recommended location under the current MasterFormat 2004 is Section Elevator Door Smoke Containment System.

A. Codes and Standards that are Standard at the University:

VentZone Systems VentZone Zoned IAQ with Energy Recovery Kits

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION EXHAUST FANS

A. This Section includes air-handling units with coils for indoor installations.

University of Delaware

SECTION DOMESTIC WATER PUMPS

UNIVERSITY OF ROCHESTER DESIGN STANDARDS NOVEMBER 1, 2013

SECTION Overhead Coiling Doors

HORIZONTAL FIRE TUBE BOILERS Piping (HVAC) Pumping Equipment (HVAC).

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters.

FAN TERMINAL UNITS Constant Volume (Series Flow), Standard Design

1.1 This section applies to air handling units for HVAC Systems.

Section (CSI ) I-Series Drum & Tube (04/23/10) Indirect-Fired Heating & Ventilating

UNIVERSITY OF ALASKA FAIRBANKS DIVISION 25- INTEGRATED AUTOMATION DESIGN STANDARDS SECTION INTEGRATED CONTROL OF FACILITY LAB FUME HOODS

Tunnel Transit Dampers Heavy Duty Tunnel Transit Life Safety

Contents INDEX. TDM Series Indirect Fired Heaters

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM

C. Manufactured double wall chimneys for fuel fired equipment. D. NFPA 54 - National Fuel Gas Code; National Fire Protection Association; 2009.

SPECIFICATIONS: FIREGUARD CROSS CORRIDOR CC

Rosemex Products 96 VENTILATION CLIMATAIR COMPARTMENT AIR HANDLING UNITS

SECTION STEAM CONDENSATE PUMPS

Bypass Terminal Units. DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.) BYPASS TERMINAL UNITS

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Electric Duct Heaters. IDHB & IDHC Series

CONTENTS. B. System Design and Performance Requirements

Replacement of pneumatic actuators on Ruskin negator spring dampers with Belimo FSxx Series

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork.

University of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL

Advance Release September 2009

SECTION WATER-SOURCE UNITARY HEAT PUMPS

1. Items known commercially as finish hardware or builders hardware, required for swing, sliding, or folding doors.

Lombard Fire Department Bureau of Fire Prevention COMMERCIAL HOOD & DUCT SYSTEMS

SECTION AIR DOORS

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

ARCHITECTURAL SPECIFICATIONS

B. System Design and Performance Requirements

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

Transcription:

SECTION 23 33 00 AIR DUCT ACCESSORIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes back-draft dampers, combination fire-and-smoke dampers, duct access doors, fire dampers, smoke dampers, volume control dampers, flexible duct connections and duct test holes. 1.2 REFERENCES A. NFPA 90A (National fire Protection Association) Installation of Air Conditioning and Ventilating Systems B. NFPA 92A (national Fire Protection Association) Smoke Control Systems C. SMACNA (Sheet Metal Air conditioning Contractors National Association) HVAC Duct Construction Standards Metal and Flexible D. UL 33 (Underwriters Laboratories, Inc.) Heat Responsive Links for Fire-Protection Service E. UL 555 (Underwriters Laboratories, Inc.) Fire Dampers and Ceiling Dampers F. UL 555S (Underwriters Laboratories, Inc.) Leakage Rated Dampers for Use in Smoke Control Systems. 1.3 SUBMITTALS A. Section 01 33 00 Submittal Procedures: Submittal Procedures B. Shop Drawings: Indicate for shop fabricated assemblies including volume control dampers, duct access doors and duct test holes February 2018 Page 1 of 9 2018 FDG Section 23 33 00

C. Product Data: Submit data for shop fabricated assembles including volume control dampers, duct access doors, duct test holes and hardware used. Include electrical characteristics and connection requirements D. Manufacturer s Installation Instructions: Submit for Fire and Combination Smoke and Fire Dampers. E. Manufacturer s Certificate: Certify that products meet or exceed specified requirements. 1.4 CLOSEOUT SUBMITTALS A. Section 01 77 00 Closeout Procedures: Closeout procedures B. Project Record Documents: Record actual locations of access doors test holes, damper, controls and any other flow control device. Provide fire damper schedule sheet identifying but limited to: make, model, size and fire rating. Provide specific dedicated fire damper and fire smoke damper drawing sheet(s) identifying specific location and access panels (if applicable). Drawings shall be separate between fusible link fire dampers versus fire smoke dampers. C. Commissioning Report: Provide fire dampers commissioning and re-commissioning report. Report shall demonstrate that each damper is tested per NFPA80 and NFPA 105 which states that each damper shall be tested and inspected after the damper is installed, then one year after installation. The maintenance testing and inspection frequency shall then be every 4 years, except in hospitals, where the frequency shall be 6 years. Contractor shall be responsible for the commissioning testing at installation and after year one for re-commissioning, D. Operation and Maintenance Data: Submit for Combination Smoke and Fire Dampers. 1.5 QUALITY ASSURANCE A. Perform Work in accordance with applicable codes and laws as well as the Stanford University Facilities Design Guidelines and all Stanford University Contract documents. B. Maintain one copy of each document on site. February 2018 Page 2 of 9 2018 FDG Section 23 33 00

1.6 QUALIFICATIONS A. Manufacturer: Company specializing in manufacturing products specified in this section with minimum three years documented experience. 1.7 PRE-INSTALLATION MEETING A. Section 01330 Administrative Requirements: Pre-installation meeting B. Convene minimum one week prior to commencing work of this section. 1.8 DELIVERY, STORAGE AND HANDLING A. Store and protect equipment. B. Protect dampers from damage to operating linkages and blades. 1.9 FIELD MEASUREMENTS A. Verify field measurements prior to fabrication. 1.10 COORDINATION A. Coordinate work where appropriate with building control work. 1.11 WARRANTY A. Section 01 77 00 Closeout Procedures: Product warranties and product bonds B. Provide manufacturer warranty for duct accessories. 1.12 EXTRA MATERIALS A. Section 01 77 00 Closeout Procedures: Spare parts and maintenance products February 2018 Page 3 of 9 2018 FDG Section 23 33 00

PART 2 - PRODUCTS 2.1 BACKDRAFT DAMPERS A. Product Description: Gravity Back-draft Dampers, size 18 x 18 inches or smaller, furnished with air moving equipment: Air moving equipment manufacturers standard construction. B. Multi-Blade-back-draft dampers: Parallel-action, gravity-balanced, Galvanized 16 gage thick steel. Blades, maximum 6 inch width, center pivoted, with felt or flexible vinyl sealed edges. Blades linked together in rattle-free manner with 90-degree stop, steel ball bearings and plated steel pivot pin. Provide dampers with adjustment device to permit setting for varying differential static pressure. 2.2 COMBINATION FIRE AND SMOKE DAMPERS A. Dampers are as manufactured by Ruskin Manufacturing, Greenheck, or approved equal. B. Fabricate and install in accordance with NFPA 90A, UL 555 and UL 555S. C. Multiple-Blade Dampers: Fabricate with 14 gage galvanized steel frame and blades. Provide oil-impregnated bronze or stainless steel sleeve bearings and plated steel axles, stainless steel jamb seals, 1/8 x 1/2 inch plated steel concealed linkage, stainless steel closure spring, blade stops and lock, and 1/2 inch actuator shaft. Actuators; UL listed and labeled spring return (pneumatic type suitable for operation on 0-20 psig instrument air or electric type suitable for 120 volts, single phase, 60 Hz. Provide end switches to indicate damper position. A green LED pilot light indicates damper fully open, a red LED pilot light indicates damper fully closed. A keyed switch for testing the damper shall be installed. Locate damper Actuator on exterior of duct and link to damper operating shaft or install directly on the shaft accessible for maintenance in either position. Actuators are as manufactured by Belimo for this service unless approved otherwise in writing by Stanford responsible Engineer. Fire smoke damper position indicator panel shall send position status to BMS for remote viewing. D. Normally Closed Smoke Responsive Fire Dampers: Curtain type, opening by gravity upon actuation of Electro-thermal link, flexible stainless steel blade edge seals to provide constant sealing pressure. February 2018 Page 4 of 9 2018 FDG Section 23 33 00

E. Normally Open Smoke Responsive Fire Dampers: Curtain type, closing upon actuations of Electro-thermal link, flexible stainless steel blade edge seals to provide constant sealing pressure, stainless steel springs with locking devices to ensure positive closure for units mounted horizontally. F. Thermal Link: Fusible link melting at 165 degrees F. 2.3 DUCT ACCESS DOORS A. Fabricate in accordance with SMACNA HVAC Duct Construction Standards Metal and Flexible and as indicated. B. Fabrication: Rigid and close fitting of galvanized steel with sealing gaskets and quick fastening locking devices. For insulated ductwork, install minimum 1-inch thick insulation with sheet metal cover. 1. Less than 12 inches square, secure with sash locks 2. Up to 18 inches square: Proved two hinges and two sash locks. 3. Up to 24 x 48 inches: Three hinges and two compression latches (with outside and inside handles). 4. Larger sizes: Provide an additional hinge. 5. Access panels with sheet metal screw fasteners are not acceptable. 2.4 FIRE DAMPERS A. Provide in accordance with NFPA 90A and UL 555 and manufacturer s condition of listing. Dampers shall be permanently marked for use in static or dynamic systems. B. Ceiling Dampers: Galvanized steel, 22 gage frame and 16 gage flap, two layers 0.125 inch ceramic fiber on top side, and one layer on bottom side for round flaps, with locking clip. C. Horizontal Dampers: Galvanized steel, 22-gage frame, stainless steel closure spring, and lightweight heat retardant non-asbestos fabric blanket. D. Curtain Type Dampers: Galvanized steel with interlocking blades. Provide stainless steel closure springs and latches for horizontal installations or closure under airflow February 2018 Page 5 of 9 2018 FDG Section 23 33 00

conditions. Configure with blades out of air stream except for 1.0 inch pressure class ducts up to 12 inches in height. E. Multiple Blade Dampers: 14 gage galvanized steel frame and blades, oil-impregnated bronze or stainless steel sleeve bearings and plated steel axles, 1/8 x1/2 inch plated steel concealed linkage, stainless steel closure spring, blade stops and lock. F. Fusible links: UL 33, separate at 160 degree F with adjustable link straps for combination fire/balancing dampers. 2.5 SMOKE DAMPERS A. Fabricate in accordance with NFPA 90A and UL 555S and as indicated. B. Dampers: UL Class 1 curtain or multiple blade type fire damper, normally open or closed automatically operated by pneumatic or electric actuator depending on design and application. C. Thermal Link: Fusible link melting at 165 degree F. 2.6 VOLUME CONTROL DAMPERS A. Fabricate in accordance with SMACNA HVAC Duct Construction Standards Metal and Flexible and as indicated. B. Multi-Blade Damper: Fabricate of opposed blade pattern with maximum blade sizes 8 x 72 inches. Assemble center and edge crimped blades in prime coated or galvanized frame channel with suitable hardware. C. End Bearings: Except in round ductwork 12 inches and smaller, provide end bearings. On multiple blade dampers, provide oil impregnated nylon or sintered bronze, or stainless steel bearings. Provide closed end bearings on all ducts having a pressure classification over 2 inches wg. D. Quadrants: 1. Provide locking, indicating quadrant regulators on single and multi-blade dampers, indicate position by marking at end of shaft. February 2018 Page 6 of 9 2018 FDG Section 23 33 00

2. On insulated ducts mount quadrant regulators on standoff mounting brackets bases or adapters. 3. Where rod lengths exceed 39 inches provide regulator at both ends. 2.7 FLEXIBLE DUCT CONNECTIONS A. Fabricate in accordance with SMACNA HVAC Duct Construction Standards Metal and Flexible and as indicated. B. Connector: Fabric crimped into metal edging strip. 1. Fabric: UL listed fire-retardant neoprene coated woven glass fiber fabric conforming to NFPA 90A, minimum density 30 oz per sq yd. 2. Net Fabric Width: Approximately 2 inches wide. 3. Metal: 3 inches wide, 24 gage galvanized steel. C. Leaded Vinyl Sheet: Minimum 0.55 inch thick, 0.87 lbs per sq ft, 10 db attenuation in 10 to 10,000 Hz range. 2.8 VARIABLE AIR VOLUME (VAV) BOXES. A. Use Titus, Metal Aire or approved equal. Each assembly shall be pressure independent. It will provide air flow regulation with +50 fpm, regardless of duct pressure fluctuation, through its entire rated cfm range. Each assembly shall reset to any air flow between zero and the maximum cfm without changing orifices or any other parts. CFM limitations will not be accepted. At 2000 fpm inlet velocity the differential static pressure for any size shall not exceed 0.15 w.g. for the basic assembly or 0.45 w.g. with the sound attenuator added. For control of VAV boxes refer to Controls section of the FDG. 2.9 DUCT TEST HOLES A. Temporary Test Holes: Cut or drill in ducts as required. Cap with neat patches, neoprene plugs, threaded plugs, or threaded or twist on metal caps. B. Permanent Test Holes: Factory fabricated air tight flanged fittings with screw cap. Provide extended neck fittings to clear insulation. February 2018 Page 7 of 9 2018 FDG Section 23 33 00

PART 3 - EXECUTION 3.1 EXAMINATION A. Verify rated walls are ready for fire damper installation B. Verify installed ductwork and equipment is ready for accessories. 3.2 INSTALLATION A. Install in accordance with NFPA 90A and follow SMACNA HVAC Duct Construction Standards Metal and Flexible. B. Install work in accordance with applicable codes and laws as well as the Stanford University Facilities Design Guidelines and all Stanford University Contract documents. C. Provide back-draft dampers on exhaust fans or exhaust ducts nearest to outside and where indicated. Do not install on fume exhaust fans. D. Provide duct access doors for inspection and cleaning before and after filters, coils, fans, automatic dampers, at fire dampers combination fire and smoke dampers and elsewhere as indicated. Provide for cleaning kitchen exhaust ductwork in accordance with NFPA 96. Provide minimum 8 x 8 inch size for hand access, 24 x 24 inch size for shoulder access and as indicated. Review locations prior to fabrication. E. Provide duct test holes where indicated and required for testing and balancing purposes. F. Provide fire dampers, combination fire and smoke dampers or smoke dampers as required by design and application at locations indicated on contract drawings. Install with required perimeter mounting angles, sleeves, breakaway duct connections, corrosion resistant springs, bearings, bushings and hinges. G. Install smoke dampers and combination smoke and fire dampers in accordance with NFPA 92A. February 2018 Page 8 of 9 2018 FDG Section 23 33 00

3.3 DEMONSTRATION AND TESTING Stanford University Facilities Design Guidelines A. Demonstrate re-setting of fire dampers to Owner s representative. END OF SECTION February 2018 Page 9 of 9 2018 FDG Section 23 33 00