Thermodynamic study of R134a in Vapour Compression Refrigeration System in Summer Climate

Similar documents
NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Volume 4, Issue 1 (2016) ISSN International Journal of Advance Research and Innovation

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

Performance and exergy analysis of vapour compression refrigeration system using various alternative of R134a.

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

Part load performance analysis of vapour compression refrigeration system with hydrocarbon refrigerants

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT

η second law = Second law efficiency

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

International Journal of Multidisciplinary Research and Modern Education (IJMRME) ISSN (Online): (

Comparative Performance Analysis of Domestic Refrigerator using R12, R134a and R600a Refrigerants

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

Oyelami S., Bolaji B. O.

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

A Review of Hydroflorocarbons (HFC S) Refrigerants as an Alternative to R134a Refrigerant

Experimentation and Fabrication of Iceplant Using Ecofriendly Refrigerant

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

Assessment of LPG as a possible alternative to R-12 in domestic refrigerators

Department of MCE, Islamic University of Technology 2. Abstract

International Journal of Research in Engineering and Innovation Vol-2, Issue-2 (2018),

Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

Use of fourth generation ecofriendly refrigerants in two and three cascade refrigeration systems for reducing global warming and ozone depletion

Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS

Volume 2, Issue 4 (2014) ISSN International Journal of Advance Research and Innovation

A Comparison Between Refrigerants Used In Air Conditioning

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS

A Review Paper on Comparative Study of Household- Refrigerator with Alternative Low Global Warming Potential Refrigerants

Volume 6, Issue 3(2018) ISSN International Journal of Advance Research and Innovation

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

DEEPAK PALIWAL, S.P.S.RAJPUT

Volume 3, Issue 4 (2015) ISSN International Journal of Advance Research and Innovation

REPLACING HARMFUL CFC 12 BY ECO-FRIENDLY REFRIGERANT IN MILK CHILLER

Main Anthropogenic Sources of Greenhouse Gases Refrigerants

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

Design of LPG Refrigeration System

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

Australian Journal of Basic and Applied Sciences. Investigation of New Eco Friendly Refrigerant Mixture Alternative to R134a in Domestic Refrigerator

Effect of capillary diameter on the power consumption of VCRS using different refrigerants

CHAPTER 1 INTRODUCTION

Assessment of Alternatives to Refrigerant R134a in Automotive Air Conditioning System

A COMPARATIVE STUDY FOR RETROFITTING OF R-12 VAPOUR COMPRESSION REFRIGERATION SYSTEM BY ECO- FRIENDLY REFRIGERANTS R-134A, R-413A, R-423A

R134a Refrigerant in Vapour Compression Cycle: A Review Paper

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

IJESRT. (I2OR), Publication Impact Factor: (ISRA), Journal Impact Factor: 2.114

PERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India

Thermodynamics I. Refrigeration and Heat Pump Cycles

EXPERIMENTAL INVESTIGATION OF A REFRIGERATOR BY USING ALTERNATIVE ECO FRIENDLY REFRIGERANTS (R600A & HC MIXTURE)

ISSN Electronic International Interdisciplinary Research Journal (EIIRJ) Bi-monthly Reviewed Journal Mar- April 2015

Chapter 10. Refrigeration and Heat Pump Systems

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications:

Performance analysis of vapour compression refrigeration systems using eighteen ecofriendly and other CFC refrigerants

International Engineering Research Journal (IERJ) Special Issue Page , June 2016, ISSN

Volume 2, Issue 1 (2014) ISSN International Journal of Advance Research and Innovation

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Evaluation of Vapour Compression Refrigeration System Using Different Refrigerants

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

Performance improvement of vapour compression refrigeration systems

THEORETICAL INVESTIGATION OF THE PERFORMANCE OF SOME ENVIRONMENT-FRIENDLY REFRIGERANTS IN A SUB-COOLING HEAT EXCHANGER REFRIGERATION SYSTEM

Experimental performance evaluation of vapour compression refrigeration system without nano particles

Theoretical performance evaluation of R134a and its low GWP Hydrocarbon alternatives in Domestic Refrigerator

International Journal of Advance Engineering and Research Development

LPG Refrigerator. October 2017 IJIRT Volume 4 Issue 5 ISSN:

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

we will examine only the vapour compression systems transfers to the Carnot cycle can serve as the initial model of the ideal refrigeration cycle.

Comparative Exergy Analysis of Vapor Compression Refrigeration System Using Alternative Refrigerants

Volume 1, Issue 2 (2013) ISSN International Journal of Advance Research and Innovation

Experimental Investigation on R 290 and R 600a In a Vapor Compression Refrigeration

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

THERMODYNAMIC PERFORMANCE ANALYSIS OF R-600 AND R-600A AS REFRIGERANT

Refrigeration Cycles MOHAMMAD FAISAL HAIDER. Bangladesh University of Engineering and Technology

CH2351 Chemical Engineering Thermodynamics II Unit V Refrigeration. Dr. M. Subramanian

Performance of an Improved Household Refrigerator/Freezer

PERFORMANCE OF A VERY LOW TEMPERATURE REFRIGERATION SYSTEM OPERATING WITH NATURAL FLUIDS

Sarthak Thakar, 2 R.P.Prajapati 1

Keywords: Climate change; ozone depletion; Montreal protocol; eco-friendly refrigerant; hydrocarbon refrigerant; performance analysis.

PERFORMANCE OF REFRIGERATOR USING R-600A AS REFRIGERANT

ENERGY, EXERGY AND SUSTAINABILITY ANALYSIS OF TWO-STAGE VAPOUR COMPRESSION REFRIGERATION SYSTEM

STUDY AND PERFORMANCE ANALYSIS OF ECO-FRIENDLY REFRIGERANT FOR RETROFITTING R22 IN RESPECT TO BANGLADESH

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

Optimization of Capillary Tube Parameters in Vapour Compression System using Environmentally Friendly Refrigerant R1234yf

International Journal of Informative & Futuristic Research ISSN (Online):

Technology Application of Environmental Friendly Refrigeration (Green Refrigeration) on Cold Storage for Fishery Industry

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

JJMIE Jordan Journal of Mechanical and Industrial Engineering

Paper No. : 04 Paper Title : Unit Operations in Food processing Module 11 : Principles of Refrigeration

Experimental investigation on the performance of air conditioner using R32 Refrigerant

Transcription:

International Journal of Research in Engineering and Innovation (IJREI) Vol-1, Issue-2, (2017), 49-53 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com ISSN (Online): 2456-6934 Thermodynamic study of R134a in Vapour Compression Refrigeration System in Summer Climate Kaushalendra Kumar Dubey 1 R.S Mishra 2 Department of Mechanical Engineering, Delhi Technological University, Delhi-110042 Email id.: professor_rsmishra@yahoo.co.in, dubey.kaushalendra@gmail.com Abstract Thermodynamic analysis of an ideal vapour compression refrigeration system is done using refrigerants R134a.This Energy- Exergy analysis is carried out by developed mathematical model. Various parameters are numerically computed are first law efficiency in terms of coefficient of performance (COP) of the system both ideal case and actual experimental and exergetic efficiency and exergy destruction ratio have been computed. The eco-friendly R134a refrigerant gives lower COP than R22. Comparing with R22, R134a takes more compressor power and second law efficiency (exergetic efficiency) of VCRS is also lower than using R22. Due to higher GP and ODP of R22, R134a can be used for domestic / commercial and industrial applications. 2017 ijrei.com. All rights reserved Keywords: Hydrofluorocarbon refrigerants, ozone-friendly, performance characteristics, ODP, GP, 1. Introduction Refrigerant is a substance which is used as a working substance in refrigeration system to move heat from lower temperature to higher temperature to get cooling effect. Midgley discovered halogenated hydrocarbon refrigerants having favourable thermodynamic properties. But these halogenated hydrocarbon refrigerants attack the atmospheric stratosphere and destroy ozone layer. ith the discovery of ozone hole in stratosphere as stated by Molina and Rowland et al [1] and the Montreal protocols (Paul, et al [2]), the CFC and HCFC refrigerants are to be phased out due to their higher global worming potential (GP) and higher ozone depletion potential (ODP). For these reasons, recently ODP and GP plays a vital role in the development of new environment friendly alternative refrigerants other than CFC and HCFC refrigerants for their higher ODP and GP. So, develop countries stopped production of CFC and HCFC refrigerants and looking for alternative environment friendly refrigerants. So, HC and HFC refrigerants with zero ODP and low GP are considered for long term purpose. Although the ODP of some HFCs is zero, their GP related to the greenhouse investigated on domestic refrigerator using propane and iso-butane as a refrigerant mixture and found that mass effect is large. On the other hand, HC refrigerants have a flammability issue, which restricts the usage in existing systems. However this flammability issue can be avoided by blending HC refrigerants with HFC refrigerants. It is also found that an HC/HFC mixture makes a very good solution with mineral oil and contribution to global warming of HC/HFC mixture is very low due to very lowgp (about one third of HFC) and hence R134a is found to be most suitable alternative refrigerant for R12. Refrigerant R134a has very similar thermodynamic properties such as molecular weight, critical temperature, boiling as R12, with zero ODP and less GP as compared to CFC12 are shown in table 1 (Calm and Hourahan, et al [3]). This gave confidence to the researchers to consider R134a as a suitable replacement to R12 for short term basis. Hammad and Alsaad et al [4] investigated on domestic refrigerator using LPG (24.4% propane, 56.4% butane and 17.2 % iso-butane) as refrigerant. They concluded that this is the environment friendly refrigerant mixture and that can replace R12 in domestic refrigerator. Jung et al. (Jung, et al, 1996) fraction range of 0.2 to 0.6 of propane increase the COP up to 2.3% compared to R12. Mani and Selladurai (Mani and Corresponding author: Kaushalendra Kumar Dubey 1 Email Address: dubey.kaushalendra@gmail.com 49

Selladurai, 2008) experimented on vapour compression refrigeration system using new refrigerant mixture of propane and iso-butane for substitution of R12 and R134a. They found that this mixture had a refrigeration capacity 19.9% to 50.1 % higher than R12 and 28.6% to 87.2% higher than R134a and COP improved by 3.9% to 25.1% than R12 at lower evaporator temperature and 11.8% to 17.6% at higher temperature. Chen and Prasad (Chen and Prasad, 1999) theoretically analysed vapour compression refrigeration system using R134a and R12 as refrigerants and reported that the COP for R134a is slightly (3%) lower than the R12.Richardson and Butterworth (Richardson and Butterworth, 1995) experimentally investigated the performance of hydrocarbon refrigerants in a hermetic vapour compression refrigeration system and came to the conclusion that propane and propane/isobutene mixtures can be used in an unmodified R12 system and can achieved better COPs than R12 under the same operating conditions. They found that around 50% propane and 50% isobutene mixture not only just give the similar saturation characteristics but also gives a better COP when proportion of propane is increased. They also mentioned that hydrocarbon refrigerants have a flammability issue, they can be safely used in hermetic vapour compression refrigeration The aim of this study is to investigate the performance of vapour compression refrigeration systems using R12, R125, R134a, R143a and R152a as refrigerants based on energy and exergy concept. Various parameters like COP, refrigerating capacity, compressor work, cycle efficiency, exergy efficiency are computed and compared in this work. Figure 1 (a) A basic Vapor Compression refrigeration Cycle. (b) T-S diagram (c) its P-H diagram. [1] Vapor compression refrigeration cycle on p-h diagram. The p-h diagram is frequently used in the analysis of vapor compression refrigeration cycle and usually consists of the four processes. Process 1-2 is the compression. Process 2-3 is the Condensation. Process 3-4 is the expansion. Process 4-1 is the evaporation. T 1 and T 2 are the suction and discharge temperatures. P e and P c are the evaporating and condensing pressures. The different enthalpies involved in the cycle are, h 1: enthalpy of suction pipe or end of evaporation. h 2: end of suction pipe or end of compressor. h 3: inlet of throttling valve or end on heat exchanger. h 4: inlet of evaporation or end of expansion. 1.1 Thermal Analysis of Vapour Compression Refrigeration System Figure 1 shows the p-h diagram of a complete ideal vapour compression refrigeration system. Various calculations are done based on this system using different refrigerants. COP of vapour compression refrigeration system is a very important criterion for performance analysis. It represents the refrigeration effect per unit compressor work. COP VCRS = Refrigeration Effect/ Compressor ork= R E/ here R E is the refrigeration effect and is the compressor work. The refrigerating effect, RE can be expressed as R E= ṁ (h 1 h 4) The compressor work, can be expressed as = ṁ (h 2 h 1) here (h 2 h 1) is the difference of enthalpy which includes the effect of compressor efficiency and ṁis the mass flow rate of the refrigerants which can be expressed as 50

ṁ = RE/ (h 1 h 4) here (h 1 h 4 ) is the difference of enthalpy in the cycle. The exergetic efficiency, ɳ II is computed in terms of second law efficiency, which is a the ratio of COP of VCRS to the COP of Carnot cycle, then ɳ II= COP VCRS/ COP Carnot = T e R E T e Tc Te and COP Carnot= T c T e here T e is evaporator temperature and Tc is condenser temperature (The COP of Carnot refrigeration cycle is a function of evaporator and condenser temperatures only and is independent of the nature of the working substance. The Carnot COP sets an upper limit for refrigeration systems operating between two constant temperature thermal reservoirs (heat source and sink). From Carnot s theorems, for the same heat source and sink temperatures, no irreversible cycle can have COP higher than that of Carnot COP.) The cycle efficiency (also called as second law efficiency) is a good indication of the deviation of the standard VCRS cycle from Carnot cycle. Unlike Carnot COP, the cycle efficiency depends very much on the shape of T s diagram, which in turn depends on the nature of the working fluid. Exergy or availability of a system is the maximum obtainable work output from the system. So exergy loss is the very important criterion to evaluate the thermodynamic performance of the vapour compression refrigeration system. System performance improved if exergy loss is less. For that reason it is our aim to minimize the exergy loss to improve the system thermodynamically. The exergy can be expressed following Chen and Prasad (Chen and Prasad, 1999) as e = (h-h 0) (s-s 0) where kinetic and potential energy are excluded. The exergy loss can be calculated by calculating exergy loss in each component of the system. Exergy loss in compressor can be expressed as Δe w=(h 1-h 2)+T 0(s 2-s 1)+ Exergy loss in condenser can be expressed as Δe c= (h 2-h 3)+T 0(s 3-s 2) 1.2 Properties and Environmental Impacts of Selected Alternative The vapour compression refrigeration system operates on refrigerant R12 which is most important CFC refrigerant identified for phase out in the country by HFC refrigerant. The institute has been one of the few institutes selected for funding for research work under orld Bank project TEQIP. A research work was undertaken for finding the most suitable ozone-friendly Hydrofluorocarbon refrigerant for replacing ozone depleting refrigerant R12. Then most suitable refrigerant has been selected for replacing harmful refrigerant. Four non-ozone depleting HFC refrigerants (R125, R134a, R143a and R152a) were selected from methane and ethane derivatives and their performances in vapour compression refrigeration system were investigated. Properties and environmental impacts of selected zero ozone-depleting refrigerants used as substitutes in the refrigeration systems are listed in the Table (1a) to Table-1(c) [3-6] respectively. Table-1(a) : Some properties and environmental impacts of selected alternative refrigerants.[3][5][6] Chemical formula Molecular mass Freezing ( C) R12 CF 2CL2 121-157.5 R125 C 2 HF 5 120-102.99 R134a C 2H 2F 4 102-96.67 R143a C 2H 3F 4 84-111 Table-1(b) : Some properties and environmental impacts of selected alternative refrigerants.[3][5][6] Chemical formula Boiling (ºC) R12 CF2CL2-29.8 112 Critical ( C) R125 C2 HF5-48.1 66.18 R134a C2H2F4-26.1 101.06 R143a C2H3F4-47.2 72.89 R152a C2H4F2-24.0 113.26 Exergy loss in expansion valve can be expressed as Δe v= (h 3-h 4)+T 0(s 4-s 3) Exergy loss in evaporator can be expressed as Δe w= (h 4-h 1)(T 0/T r)+t 0(s 1-s 4) And the total exergy loss can be expressed as ΔE = ṁ(δe w +Δe c+δe v+δe w) Exergetic efficiency can be expressed as ɳ x= To RE 1 Tr 51

Table-1(c): Some environmental properties of selected alternative refrigerants [3][5][6. Ozone Depletion Potential (ODP) Global arming Potential (GP) R12 1 8100 R125 0 2800 R134a 0 1300 R143a 0 3800 R152a 0 140 ɳ IItheoritical = (COP Actual / COP ideal cycle) = 0.2083 Exergy loss in each component of the system Exergy loss in compressor Δe w= (h 1-h 2) +T 0 (s 2-s 1) + Δe w=133.5768 KJ/KG Exergy loss in condenser Δe c= (h 2-h 3)+T 0(s 3-s 2) Δe c= 18.1078 KJ/KG Exergy loss in expansion valve Δe v= (h 3-h 4)+T 0(s 4-s 3) Δe v=-7.0274kj/kg 2. Results and Discussions Experiment was conducted in the laboratory for obtaining thermal performance using eco-friendly R134a, refrigerant. The following data have been recorded. Atmospheric pressure: 1 bar Atmospheric temperature: T 0 =30 C =303 K Condenser pressure: 135psi Evaporator pressure: 8psi Compressor delivery temperature: 61.9 C Compressor suction temperature: -12.7 C Ref. leaving condenser temperature: 29.6 C Evaporator inlet temperature:-16.7 C Mass flow rate: 5 kg/min Evaporator volts: V e/v = 196 Evaporator AMPS: I e/n =2.24 Motor volts: V m/v =198 Motor amps I m/a =2.892 Motor compressor speed: 2800rpm The Enthalpy and Entropy have been computed on above state temperature data as shown in the table-2. Table-2 Enthalpy and Entropy of various components of VCRS States Outlet of evaporator-1 Compressor outlet-2 Condenser outlet-3 Evaporator Inlet-4 Tempe rature in 0 C Enthalpy in KJ/Kg Entropy in KJ/Kg-K -12.7 391 1.7355 61.9 427 1.7011 29.6 240 1.1437-16.7 178.6 0.9179 Coefficient of performance COP ideal cycle = (h 1-h 4)/((h 2-h 1)/0.8) = 4.719 (Assuming 80% volumetric efficiency of compressor) COP Actual =Q e/power =V I/Power= V I/(Motor volts Motor amps Cos ) =0.983 Exergy loss in evaporator Δe w= (h 4-h 1)(T 0/T 2)+T 0(s 1-s 4) Δe w=-3.3565kj/kg And the total exergy loss ΔE = ṁ(δe w + Δe c+ Δe v+ Δe w) ΔE = 706.5035 KJ/KG Exergectic Efficiency (ɳ x) ɳ x= To RE 1 T 2 ɳ_ II_exp=0.1791= 17.91% 3. Conclusion The experimental work presented in this paper on vapour compression refrigeration system, the following conclusions were made. 1. The eco-friendly R134a refrigerant gives lower COP than R22. 2. Comparing with R22, R134a takes more compressor power. 3. Second law efficiency (Exergetic efficiency of VCRS is also lower than using R22. 4. Due to higher GP and ODP of R22, R134a can be used for domestic / commercial and industrial applications. Acknowledgement Authors) thanks to my respected teachera Prof (Dr.) Vijay Gupta, Vice-Chancellor, Sharda University, Greater Noida and Prof. N K Bansal, Ex-VC of MVDU katra for guidance. References [1] M.J.Molina, FS.Rowland, (1974) Stratospheric sink for chlorofluoromethane: chlorine atom catalyzed destruction of ozone, Nature, 249,810 812. 52

[2] S.Paul, A.Sarkar, B.K.Mandal, (2013) Environmental impacts of halogenated refrigerants and their alternatives: recent developments, International Journal of Emerging Technology and Advanced Engineering, 3: Special Issue 3: ICERTSD 2013:400-409. [3] J.M.Calm, G.C.Hourahan, (2001) Refrigerant data summery, Engineering Systems, 18,74 88. [4] M.A.Hammad, M.A.Alsaad, (1999) The use of hydrocarbon mixtures as refrigerants in domestic refrigerators, Applied Thermal Engineering, 19,1181 1189. [5] Bhatti, M.S. (1999). A historical look of chlorofluorocarbonrefrigerants. ASHRAE Transactions, part 1, 1999.pp.1186-1206 [6] Cavallini A, orking fluids for mechanical refrigeration. International Journal of Refrigeration 19 (1996) 485-496. [7] McMullan JT, Refrigeration and the environment issues and strategies for the future, International Journal of Refrigeration 25 (2002) 89-99. 53