Energy Efficiency of Refrigeration Systems for High-Heat-Flux Microelectronics

Similar documents
Performance Analysis of a Miniature-Scale Vapor Compression System for Electronics Cooling: Bread Board Setup

Global Journal of Engineering Science and Research Management

Optimizaion of Electrostatically Actuated Miniature Compressors for Electronics Cooling

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

Chapter 11. Refrigeration Cycles. Study Guide in PowerPoint

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

PERFORMANCE ANALYSIS OF MULTIPURPOSE REFRIGERATION SYSTEM (MRS) ON FISHING VESSEL

FABRICATION SOLAR REFRIGERATION SYSTEM BY PELTIER EFFECT

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Impact of TXV and Compressor in the Stability of a High-End Computer Refrigeration System

A Design of Thermoelectric Cooler and Optimization

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

Refrigerator and Heat Pump Objectives

Dist Pune Maharastra, India 2,3 Prof. Ram Meghe Institute of Technology & Research, Badnera, Amravati , Maharashtra, India

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

Chapter 10. Refrigeration and Heat Pump Systems

Experimental and Numerical Study on the Performance of R410A Liquid Recirculation Cycles with and without Ejectors

Implementation of Microchannel Evaporator for High-Heat-Flux Refrigeration Cooling Applications

Review on Vapour Compression-Thermoelectric Hybrid Refrigeration system

TWO-PHASE MICRO-CHANNEL HEAT SINK FOR SPACE CRAFT THERMAL CONTROL

ADVANCES in NATURAL and APPLIED SCIENCES

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Thermal Performance of a Loop Thermosyphon

Week 9. Refrigeration Cycles I. GENESYS Laboratory

Shortcut Model for Predicting Refrigeration Cycle Performance

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

Flow Boiling of R245fa in a Microgap with Integrated Staggered Pin Fins

COMPACT HEAT EXCHANGERS FOR MOBILE CO 2 SYSTEMS

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

Experimental study of hybrid loop heat pipe using pump assistance for high heat flux system

International Journal Of Core Engineering & Management (IJCEM) Volume 2, Issue 9, December 2015

Experimental Investigation of a Miniature-Scale Refrigeration System for Electronics Cooling

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

Performance Analysis of Domestic Refrigeration System with Thermoelectric Module

Compact, Low Temperature Refrigeration of Microprocessors

Enhancement of COP using Nanoadditives in Domestic Refrigerator

International Journal of Research in Engineering and Innovation Vol-2, Issue-2 (2018),

Chapter 9. Refrigeration and Liquefaction

(Refer Slide Time: 00:00:40 min)

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Theoritical Analysis For Miniature Vapor Compression Cycle Performance Using Microchannel And Finned Tube Condenser

COMPARATIVE PERFORMANCE ANALYSIS OF EXPERIMENTAL FRIGORIFIC AIR CONDITIONING SYSTEM USING R-134A AND HFO-1234YF AS A REFRIGERANT

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

Vapour Compression-Absorption Cascade Refrigeration System- Thermodynamic Analysis

Modeling and Testing of an R-23/R-134a Mixed Refrigerant System for Low Temperature Refrigeration

Modelling the Performance of a Diffusion Absorption Refrigeration System

Chapter 11 REFRIGERATION CYCLES

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

CASE STUDIES OF THERMALLY DRIVEN HEAT PUMP ASSISTED DRYING. Minh Cuong Tran, Jamy Logie, Bruno Vanslambrouck, Martijn van den Broek

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

Thermodynamics: Homework A Set 7 Jennifer West (2004)

Experimental Analysis of Performance Characteristics of Mini Channel Heat Exchangers

Energy and Exergy Analysis of an Ejector-Absorption Refrigeration Cycle with Using NH3-H2O as the Working Fluids

An Experimental Study on Clothes Drying Using Waste Heat from Split Type Air Conditioner

Optimized Finned Heat Sinks for Natural Convection Cooling of Outdoor Electronics

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Theoretical and Experimental Analysis of the Superheating in Heat Pump Compressors. * Corresponding Author ABSTRACT 1.

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

Modeling and Design of an Indirect Air Conditioning System Operating With Low GWP Zeotropic Mixtures

International Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014 ISSN

Performance Analysis of Solar Assisted Cascade Refrigeration System of Cold Storage System

GSJ: VOLUME 6, ISSUE 6, JUNE GSJ: Volume 6, Issue 6, June 2018, Online: ISSN

Performance analysis of a vapour compression-absorption cascaded refrigeration system with undersized evaporator and condenser

Optimization of Electrostatically Actuated Miniature Compressors for Electronics Cooling

Refrigeration Cycles MOHAMMAD FAISAL HAIDER. Bangladesh University of Engineering and Technology

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM

Performance of an Improved Household Refrigerator/Freezer

Volume 2, Issue 4 (2014) ISSN International Journal of Advance Research and Innovation

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

Design of Miniature Loop Heat Pipe

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

DESIGN AND ANLYSIS OF MODIFIED HYBRID SOLAR SYSTEM USING NANO FLUIDS

Chapter 11 REFRIGERATION CYCLES. Department of Mechanical Engineering

η second law = Second law efficiency

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

Fig.: macroscopic kinetic energy is an organized form of energy and is much more useful

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

EXPLORING POSSIBILITIES WITH THE DEVELOPMENT OF THE LOOP HEAT PIPE TECHNOLOGY. Roger R. Riehl

*Corresponding author;

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Chapter 11 REFRIGERATION CYCLES

Passive cooling of telecommunication outdoor cabinets for mobile base station

Transcription:

P. E. Phelan 1 e-mail: phelan@asu.edu Y. Gupta H. Tyagi 2 Assistant Professor R. S. Prasher 3 Department of Mechanical and Aerospace Engineering, Arizona State University, Tempe, AZ J. Catano G. Michna 4 Assistant Professor R. Zhou J. Wen 5 M. Jensen Y. Peles Energy Efficiency of Refrigeration Systems for High-Heat-Flux Microelectronics Increasingly, military and civilian applications of electronics require extremely high-heat fluxes on the order of 1000 W/cm 2. Thermal management solutions for these severe operating conditions are subject to a number of constraints, including energy consumption, controllability, and the volume or size of the package. Calculations indicate that the only possible approach to meeting this heat flux condition, while maintaining the chip temperature below 65 C, is to utilize refrigeration. Here, we report an initial thermodynamic optimization of the refrigeration system design. In order to hold the outlet quality of the fluid leaving the evaporator to less than approximately 20%, in order to avoid reaching critical heat flux, the refrigeration system design is dramatically different from typical configurations for household applications. In short, a simple vapor-compression cycle will require excessive energy consumption, largely because of the additional heat required to return the refrigerant to its vapor state before the compressor inlet. A better design is determined to be a two-loop cycle, in which the vapor-compression loop is coupled thermally to a pumped loop that directly cools the high-heat-flux chip. DOI: 10.1115/1.4003041 Department of Mechanical, Aerospace and Nuclear Engineering, Rensselaer Polytechnic University, Troy, NY 1 Introduction The removal of very high-heat fluxes, up to 1000 W/cm 2,is required by some military and commercial electronics applications. Simultaneously, usually the electronic device temperature must be maintained below some threshold value, such as 65 C. The combination of an extremely high-heat flux removal and low device temperatures necessitates the use of refrigeration to maintain satisfactory performance. Several groups have investigated refrigeration cooling of electronic systems. A number of studies have examined how miniature, often termed mesoscale, refrigeration systems may be utilized for microelectronics cooling see, e.g., Refs. 1 5. A general review of electronics cooling approaches was given in Ref. 6. Somewhat larger vapor-compression systems are already commercially available for desktop computers 7 and remain the object of study 8. These systems are essentially conventional vapor-compression refrigerators applied to electronics cooling for the purposes of maintaining low operating temperatures and generally do not involve the removal of extremely high-heat fluxes. 1 Corresponding author. 2 Present address: School of Mechanical Materials & Energy Engineering, Indian Institute of Technology Ropar, Rupnagar, 140001, Punjab, India. 3 Also at ARPA-E, Department of Energy, 1000 Independence Ave. SW, Washington, DC 20585. 4 Present address: South Dakota State University, Mechanical Engineering Department, Crothers Engineering Hall 254, Box 2219, Brookings, SD 57007 0294. 5 Also at Department of Electrical, Computer, and Systems Engineering, Rensselaer Polytechnic University. Manuscript received September 11, 2009; final manuscript received November 6, 2010; published online December 16, 2010. Assoc. Editor: Anthony M. Jacobi. In contrast, our focus here is on the design of macroscale vaporcompression refrigeration systems for high-heat-flux microelectronic systems. Such systems are of considerable interest in the literature see, e.g., Refs. 9,10, but these are still largely confined to conventional vapor-compression systems. Our present work shows that when considering the limitations on the evaporator exit quality imposed by critical heat flux CHF avoidance, the conventional vapor-compression cycle may not be the optimum choice. We compare a number of alternative system designs and show that the best choice with regard to energy efficiency is a two-loop system in which the electronic device is cooled by a pumped loop that is cascaded with a conventional vaporcompression loop. Note that this is in agreement with recent reports that described how a similar two-loop system was utilized for subcooled flow boiling experiments in microchannels 11,12. 2 Analysis In order to cool the electronic component chip, several types of refrigeration cycles are envisaged in this study. An evaporator is placed in thermal contact with the chip. This evaporator contains microchannels through which subcooled refrigerant flows. This way the heat from the chip is removed by boiling the refrigerant flowing through the evaporator. In each of these cycles, the refrigerant considered is R-134a. The following assumptions and constraints are adhered to for most calculations in this study. The refrigerant enters the evaporator as subcooled liquid 10 C less than the evaporator temperature, i.e., subcooled by 10 C. Two values of evaporator temperatures are considered: T evap =0 C and T evap =20 C. These inlet temperatures are based on the estimated value of temperature dif- Journal of Thermal Science and Engineering Applications SEPTEMBER 2010, Vol. 2 / 031004-1 Copyright 2010 by ASME

ference between the heater surface and the refrigerant, obtained from Ref. 13, for heat fluxes close to 1000 W/cm 2. For simplicity, the flow through the evaporator is assumed to undergo no pressure drop. This is done in order to simplify the calculations and to focus on the comparison between the various refrigeration cycles while maintaining similar operating conditions among them. Similarly, the refrigerant exiting from the evaporator is assumed to be limited to a quality of x=20%. This constraint on evaporator exit quality helps to avoid CHF conditions inside the evaporator. The chip is assumed to produce heat at 1 kw, which is transferred completely to the refrigerant flowing in the evaporator. The exit quality constraint of x=20% was chosen because of the great uncertainty surrounding the effect of exit quality on CHF. Wojtan et al. 14 observed CHF at x 40% in a single channel with flowing R-134a. Depending on the mass flux, Koşar and Peles 15 found CHF for R-123 to occur in silicon-based microchannels for exit qualities as low as 25%. On the other hand, a number of studies found that exit qualities could be much higher before CHF was initiated see the review in Ref. 16 and the references cited within, leading to the statement there is no general agreement on the trends in the CHF condition in micro/ minichannels so far 16. Furthermore, measurements on the flow boiling of R-134a in copper microchannels showed that the peak heat transfer coefficient occurred at a local quality of 20% 17. Therefore, we choose to limit the exit quality in the evaporator to only 20% until more information is available that would allow us to confidently operate at higher exit qualities. Standard steady-state equations are applied to compute the refrigerant mass flow rates and the required power inputs. In all cases, the evaporator heat load is Q evap=1 kw. All compressors and pumps are assumed to have isentropic efficiencies of 80%, i.e., for the compressors com =0.8 and for the pumps pump =0.8. The condenser temperature is set at T cond =40 C in all cases. The system coefficient of performance COP for each case is defined as Q evap COP = 1 Ṗ in where Ṗ in is the power input required to drive any compressors or pumps in the system plus any additional heating. All computations are carried out in Engineering Equation Solver EES. The detailed calculations for each case are given in Sec. 3. Fig. 1 Schematic diagram of a conventional vaporcompression refrigeration system cycle 1, with a second vapor-compression cycle cascaded to produce subcooled conditions at the evaporator inlet the refrigerant leaving the evaporator. The mass flow rate in the primary vapor-compression loop ṁ and in the cascaded loop ṁ sub are found from ṁ = Q evap h 2 h 1, ṁ sub = ṁ h 5 h 6 h b h a The compressor power inputs are computed from Ẇ com1 = ṁ h 4 h 3, Ẇ com2 = ṁ sub h c h b 3 Additional details can be found in standard thermodynamics textbooks, such as Ref. 18. The system in case 1 suffers from two serious drawbacks. The first is the heating power required in the heater following the evaporator to bring the refrigerant to the saturated vapor condition, starting from the evaporator exit quality of x=20%. For 2 3 Results and Discussion In this study, four types of R-134a refrigeration cycles are considered. These four cycles are referred to as cycle 1, cycle 2, cycle 3, and cycle 4. Cycle 1 is a conventional vapor-compression refrigeration cycle, cascaded with a second vapor-compression cycle in order to deliver subcooled refrigerant at the evaporator inlet. The cycle 1 schematic diagram is shown in Fig. 1, and a T-s temperature-entropy diagram for the same cycle is shown in Fig. 2. In this and in the following cycles, the integrated circuit chip transfers its heat to the evaporator and, as discussed above, the exit quality of the refrigerant leaving the evaporator is limited to x=0.20. In cycle 1, after leaving the evaporator, the refrigerant flows through an additional heater in order to bring the refrigerant to the saturated vapor condition so that it can enter the compressor. After exiting the compressor, the refrigerant passes through the condenser, which is maintained at a temperature T cond =40 C. The subcooler, located after the condenser, subcools the refrigerant 10 C below the evaporator temperature. As stated above, standard steady-state equations are applied to compute the refrigerant mass flow rates and the required power inputs, which for case 1 is the power required by both compressors and the additional heating required to completely vaporize Fig. 2 T-s temperature-entropy diagram for cycle 1 conventional vapor-compression cycle cascaded with a second vaporcompression cycle 031004-2 / Vol. 2, SEPTEMBER 2010 Transactions of the ASME

Table 1 Comparison among the four cycles considered for the refrigeration system design T evap =0 C, T cond =40 C, 10 C of subcooling Cycle No. and description Net electric power consumption kw System COP Advantages/ disadvantages 1: Cascaded vapor-compression 4.08 0.245 High power consumption Difficult to control Potential for heat recovery from condensers and/or compressors 2: Vapor compression with economizer 2.41 0.415 Moderate power consumption Difficult to control Relatively simple design Potential for heat recovery from condenser and/or compressor 3: Pumped loop with thermoelectric cooler 5.53 0.181 Highest power consumption Large number of thermoelectric modules required Simplest design Easy to control 4: Pumped loop with vapor-compression two-loop 0.43 2.35 Lowest power consumption Easy to control Compressor loop is commercial off-the-shelf COTS Relatively simple design T evap =0 C, the additional heat added is Q add=3.00 kw, compared with compressor power inputs of Ẇ com1 =0.610 kw and Ẇ com1 =0.469 kw, leading to COP=Q evap/ Ẇ com1 +Ẇ com2 +Q add =0.245. Second, there are inherent difficulties to control the system to adjust to varying evaporator heat loads. The compressor speed can be varied, but care must be taken to ensure that 100% vapor enters the compressor. On the other hand, an opportunity exists for heat recovery from either compressor, or even from the condensers, in order to reduce the additional heat requirement. Implementing such a heat recovery scheme, though, would add complexity that might detract from the gains in energy efficiency. A summary of the calculated power input and COP, plus a listing of apparent advantages and disadvantages, is provided in Table 1 for each of the four cycles. In order to address the challenges that arose in cycle 1, some changes were made to the refrigeration cycle, and as a result cycle 2 was envisioned. Figure 3 shows the schematic of cycle 2, where an economizer is introduced, as well as a second expansion valve that enables subcooled conditions at the evaporator inlet. The economizer is a heat exchanger between the high-temperature liquid exiting the condenser and the liquid/vapor mixture leaving the evaporator. It reduces the additional heat required to Q add =1.51 kw T evap =0 C, as shown in the T-s diagram in Fig. 4. The system COP is consequently raised to COP=Q evap/ Ẇ com +Q add =0.415. Importantly, the complexity of the system is reduced since now there is only a single refrigerant compressor, but it is still difficult to control the system to adjust to rapidly varying evaporator heat loads. Another concept was introduced to address the cooling of the refrigerant, this time by incorporating a thermoelectric cooler Peltier device instead of a conventional vapor-compression cycle. The schematic diagram of cycle 3 is given in Fig. 5, and the accompanying T-s diagram is given in Fig. 6. Now, the relatively power-hungry compressor is replaced with a pump that consumes much less power, but the low efficiency of the thermoelectric cooler also has to be taken into account. The COP of a thermoelectric cooler, COP tec, is given by 1 Q 1 tec 2 COP tec = = ZT 2 c T h T c Ẇ ZT tec c T h where Q tec=ṁ h 3 h 4 is the heat load on the thermoelectric cooler, Ẇ tec is the power input to the thermoelectric cooler, Z is the thermoelectric figure of merit, T c is the cold temperature experienced by the thermoelectric cooler, and T h is the hot temperature to which the thermoelectric cooler rejects heat. For bismuth telluride Bi 2 Te 3, Z 300 K 1 19, giving Z 1/300 =0.0033 K 1. The corresponding system COP is COP 4 Fig. 3 Schematic diagram of a vapor-compression refrigeration system with economizer cycle 2 Journal of Thermal Science and Engineering Applications SEPTEMBER 2010, Vol. 2 / 031004-3

Fig. 4 T-s temperature-entropy diagram for cycle 2 conventional vapor-compression cycle with an economizer heat exchanger =Q evap/ Ẇ tec +Ẇ pump =0.181, where T h =T cond =40 C and T c = 15 C. This value of COP is the lowest of the four systems considered because of the large power requirement of the thermoelectric cooler Ẇ tec =5.41 kw compared with a pump input power of only Ẇ pump =0.124 kw. Without a compressor, there is no need to add heat to completely vaporize the refrigerant at the evaporator exit, but this is more than offset by Ẇ tec. Still, this system may be attractive for some applications because of its simplicity. Furthermore, it can easily be controlled by varying the pump speed, an advantage also enjoyed by the fourth and final refrigeration system examined, case 4. Finally, after analyzing the previous three cycles, one last type of cycle was envisaged. This cycle, referred to as cycle 4, utilizes a two-loop approach and is shown in Fig. 7. The corresponding T-s diagram for this cycle is shown in Fig. 8. A conventional vapor-compression cycle the compressor loop is cascaded with a pump loop that directly cools the electronic chip. Similar to case 3 with the thermoelectric cooler, no additional heating of the refrigerant is required. As a result, this type of cycle consumes the lowest power of the four cycles 0.425 kw, including the Fig. 6 T-s temperature-entropy diagram for cycle 3 pumped loop with thermoelectric cooler compressor Ẇ com =0.375 kw and the pump Ẇ pump =0.050 kw, and is clearly the best among the four cycles from an energy point of view. Other advantages, in addition to dramatically reduced power consumption, are also inherent in the two-loop system cycle 4 Fig. 7 Schematic diagram of a two-loop system cycle 4 Fig. 5 Schematic diagram of a pumped-loop system cooled by a thermoelectric cooler cycle 3 Fig. 8 T-s temperature-entropy diagram for cycle 4 two-loop system 031004-4 / Vol. 2, SEPTEMBER 2010 Transactions of the ASME

compared with the others. The compressor loop can be a commercially available off-the-shelf system, making it low cost and highly reliable. In the pump loop, the choice of refrigerant is no longer tied to the compressor design. Rather, one is free to select any refrigerant with desirable properties, such as high critical heat flux. Furthermore, the range of operating pressures in the pump loop can be made much larger than for vapor-compression cycles since the pressure rise is accomplished via an inexpensive pump rather than by an energy-intensive compressor. Finally, it appears easier to control the pump loop to operate under transient conditions compared with controlling a vapor-compression loop. The pump speed and expansion valve opening can both be rapidly varied to produce different evaporator conditions without compromising the integrity of the system or damaging any components. We will explore the controllability and other aspects, such as optimum refrigerant choice, of the cycle 4 system in future work. For example, the expansion valve in the pump loop is not essential and can possibly be removed to simplify the system. For high-heat flux electronics cooling, the two-loop system cycle 4 performs better than the conventional vapor-compression system cycle 1 or the other two systems investigated. However, it is recognized that, above some evaporator exit quality, the power consumption reduction enjoyed by the two-loop case 4 system becomes insignificant. Thus, there has to be a critical evaporator exit quality where the use of a conventional vaporcompression system may be a better choice. Figure 9 shows a comparison of the COP for the conventional vapor-compression system case 1 and the two-loop configuration case 4 for various exit qualities. Two values of evaporator temperature are considered: T evap =0 C which has been used in all previous calculations and T evap =20 C. It is seen that the two-loop system is more efficient than the conventional system up to an exit quality of x 0.9 for T evap =0 C and up to x 0.8 for T evap =20 C. Thus, for very high evaporator exit qualities, the two-loop system case 4 loses its energy efficiency advantages relative to a conventional vapor-compression system, but it still offers an advantage in being easier to control for varying evaporator heat loads. 4 Conclusions Four different types of refrigeration systems were evaluated for their potential to cool a high-heat-flux electronic component. The primary metric for comparison was the power consumption of the various cycles, as represented by the system COP. Each cycle was required to deliver subcooled R-134a to an evaporator and had to reject heat at 40 C. Results show that a two-loop system, in which a conventional vapor-compression loop is coupled thermally to a pumped loop that directly cools the high-heat-flux chip, consumes much less energy than a conventional vaporcompression system. The simple vapor-compression cycle requires excessive energy consumption, largely because of the additional heat required to return the refrigerant to its vapor state before the compressor inlet. Acknowledgment This work is supported by the Office of Naval Research as a MURI award Prime Award No. N00014-07-1-0723. Fig. 9 Comparison of the single-loop case 1 and two-loop case 4 configurations based on COP for two different evaporator temperatures T cond =40 C Nomenclature Q heat flow, kw h specific enthalpy, kj/kg ṁ mass flow rate, kg/s Ṗ in total power input, kw s specific entropy, kj kg 1 K 1 T temperature, C Ẇ power input for compressors or pumps, kw x quality, % isentropic efficiency for compressors or pumps Subscripts 1, 2,,8 state points A, B,,D state points a, b,,d state points add additional heat required com compressor cond condenser evap evaporator pump pump tec thermoelectric References 1 Phelan, P. E., Chiriac, V. A., and Lee, T.-Y. T., 2002, Current and Future Miniature Refrigeration Cooling Technologies for High-Power Microelectronics, IEEE Trans. Compon., Hybrids, Manuf. Technol., 25, pp. 356 365. 2 Phelan, P. E., Swanson, J., Chiriac, F., and Chiriac, V. A., 2004, Designing a Mesoscale Vapor Compression Refrigerator for Cooling High-Power Microelectronics, ITHERM, Las Vegas, NV, Jun. 1 4, pp. 218 223. 3 Mongia, R., Masahiro, K., DiStefano, E., Barry, J., Chen, W., Izenson, M., Possamai, F., Zimmermann, A., and Mochizuki, M., 2006, Small Scale Refrigeration System for Electronics Cooling Within a Notebook Computer, ITHERM, San Diego, CA, May 30 Jun. 2, pp. 751 758. 4 Trutassanawin, S., Groll, E. A., Garimella, S. V., and Cremaschi, L., 2006, Experimental Investigation of a Miniature-Scale Refrigeration Systems for Electronics Cooling, IEEE Trans. Compon. Packag. Technol., 29, pp. 678 687. 5 Chiriac, V., and Chiriac, F., 2008, An Overview and Comparison of Various Refrigeration Methods for Microelectronics Cooling, ITHERM, May 28 31, Orlando, FL, pp. 618 625. 6 Chu, R. C., Simons, R. E., Ellsworth, M. J., Schmidt, R. R., and Cozzolino, V., 2004, Review of Cooling Technologies for Computer Products, IEEE Trans. Device Mater. Reliab., 4, pp. 568 585. 7 Peeples, J. W., 2001, Vapor Compression Cooling for High Performance Applications, Electronics Cooling, 7, pp. 16 24. 8 Nnanna, A. G. A., 2006, Application of Refrigeration System in Electronics Cooling, Appl. Therm. Eng., 26, pp. 18 27. 9 Lee, J., and Mudawar, I., 2006, Implementation of Microchannel Evaporator for High-Heat-Flux Refrigeration Cooling Applications, ASME J. Electron. Packag., 128, pp. 30 37. 10 Lee, J., and Mudawar, I., 2009, Low-Temperature Two-Phase Micro-Channel Cooling for High-Heat-Flux Thermal Management of Defense Electronics, IEEE Trans. Compon. Packag. Technol., 32, pp. 453 465. 11 Lee, J., and Mudawar, I., 2008, Fluid Flow and Heat Transfer Characteristics of Low Temperature Two-Phase Micro-Channel Heat Sinks Part 1. Experimental Methods and Flow Visualization Results, Int. J. Heat Mass Transfer, 51, pp. 4315 4326. 12 Lee, J., and Mudawar, I., 2008, Fluid Flow and Heat Transfer Characteristics of Low Temperature Two-Phase Micro-Channel Heat Sinks Part 2. Subcooled Boiling Heat Transfer and Pressure Drop, Int. J. Heat Mass Transfer, 51, pp. 4327 4341. 13 Mudawar, I., and Bowers, M. B., 1999, Ultra-High Critical Heat Flux CHF Subcooled Water Flow Boiling I: CHF Data and Parametric Effects for Small Diameter Tubes, Int. J. Heat Mass Transfer, 42, pp. 1405 1428. 14 Wojtan, L., Revellin, R., and Thome, J. R., 2006, Investigation of Saturated Critical Heat Flux in a Single, Uniformly Heated Microchannel, Exp. Therm. Fluid Sci., 30, pp. 765 774. 15 Koşar, A., and Peles, Y., 2007, Critical Heat Flux of R-123 in Silicon-Based Microchannels, ASME J. Heat Transfer, 129, pp. 844 851. 16 Roday, A. P., and Jensen, M. K., 2009, A Review of the Critical Heat Flux Journal of Thermal Science and Engineering Applications SEPTEMBER 2010, Vol. 2 / 031004-5

Condition in Mini- and Microchannels, J. Mech. Sci. Technol., 23, pp. 2529 2547. 17 Bertsch, S. S., Groll, E. A., and Garimella, S. V., 2008, Refrigerant Flow Boiling Heat Transfer in Parallel Microchannels as a Function of Local Vapor Quality, Int. J. Heat Mass Transfer, 51, pp. 4775 4787. 18 Çengel, Y. A., and Boles, M. A., 2008, Thermodynamics: An Engineering Approach, 6th ed., McGraw-Hill, Boston, MA, pp. 623 660. 19 Riffat, S. B., and Ma, X., 2004, Improving the Coefficient of Performance of Thermoelectric Cooling Systems: A Review, Int. J. Energy Res., 28, pp. 753 768. 031004-6 / Vol. 2, SEPTEMBER 2010 Transactions of the ASME