Economic Analysis Process Applied To The Worlds Largest Wind Tunnel. Arnold AFB. Arnold Engineering Development Center

Similar documents
Commercial Refrigeration

Evaporative-Cooled vs. Air-Cooled Chillers: Kirtland AFB Case Study

REFRIGERATED AIR DRYERS SCFM. CRPC Energy Saving Series

ORTEC INDUSTRIAL FLUID CHILLERS FC SERIES ( TONS) Compressed Air, Gas & Fluid Technologies. i e n d. l y. t a. R e. f r. i g e.

DEHUMIDIFICATION: Ice Arena Application & Product Guide. Design, construct and operate to control indoor humidity in ice rinks

Air Conditioning and process cooling Energy Components at a Glance

RECORD SUBMITTAL COVER SHEET

It:ill:~~~=~:~in~1 FIGURE 1 HOW AIR VOLUME IS RECOVERED BY AN ADAMS REHEAT SYSTEM

PACKAGED REFRIGERATION EQUIPMENT

Nirvana. Cycling Refrigerated Dryers

WO P NF L M 407c Spec Submittal

Case 13 Food Storage & Processing Center

WO P NF L M 407c Spec Submittal

ENGINEERING. Edition No. 13 October 2002

Nirvana Cycling Refrigerated Dryers

AHRI Certification Program Scopes - COOLING

TECHNICAL BULLETIN SELECTING A COMPRESSED AIR DRYER INTRODUCTION

2013 Guideline for Specifying the Thermal Performance of Cool Storage Equipment. AHRI Guideline T (I-P)

BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application

The Evaluation and Design of the Ventilation System within Mansfield Dam (Lake Travis)

Parilla Thermal Storage Project Case Study. May Page 1 of 11

Desiccant Drying DRYPOINT XC. efficient low dew point heatless desiccant drying. Truth in Compressed Air.

INSTANT CHILLER. Chester-Jensen Co., Inc. Unit Construction and Short Gas Flow

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

Daikin Blueprint: Delivering Hot Water with a Chiller

Natural Refrigerant Market Trends

MAXIMUM SERIES. Maximum Series portable chillers can be used on a variety of process applications that require 20 F to 70 F chilled water.

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

(2) 325 tpd York Chlorine Liquefier Systems

Refrigeration air dryer

ORTEC HIGH CAPACITY REFRIGERATED AIR/GAS DRYERS

Nitrogen Generation Systems Compressed Air Dryers

PRICE CHOPPER SARATOGA, NY. First cascade supermarket system in North America Installed and Started March of 2008

Chapter 10. Refrigeration and Heat Pump Systems

Frigi Tech International, Inc Prairie Wind Lane,. Houston, Texas T: F:

A New Dedicated Outdoor Air System with Exhaust Air heat recovery

OACS Outdoor Air-Cooled Central Chillers

HEAT OF COMPRESSION DESICCANT AIR DRYERS. DHC Series

Refrigeration Technology in Building Services Engineering

New standard in compressed air treatment, providing Energy Savings up to 99%

MACH N-407 Heat Pump Air-Cooled Chiller

Applying the Frick Low Charge Central System to a New Freezer/Cooler Facility

July 2012 was a significant date for the HVAC and Refrigeration industry as it saw the introduction of the Carbon Tax and the HFC Levy.

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

Subfreezing Dryers SF Dryer, -20 C (-4 F) PDP

Heat of Compression Desiccant Air Dryers. NRG-LES SERIES scfm ( nm 3 /h)

BOGE AIR. THE AIR TO WORK. Refrigerant Dryers RA Series

Green economy with natural refrigerants

Humidity Control Design Tips. R. Mark Nunnelly, PE, CxA, LEED AP President

Refrigeration Plant Information. We Speak Hockey 365

investment in R&D, the commitment to - name.

Why Secondary-Coolant Systems for Supermarket Refrigeration?

White paper Compressed air drying

Moisture can be very disruptive to a dust. Preventing moisture problems in your dust collector

PROJECT MANUAL GUIDE SPECIFICATIONS FOR: PFANNENBERG SERIES CC COMPACT PACKAGED CHILLERS PART 1 GENERAL

Energy saving refrigeration dryers SCFM. Purifying your compressed air, increasing your efficiency.

Dehumidification Strategies Application Note

Energy Efficiency Considerations in Refrigeration Systems

Humidity Control & Psychrometrics

Chiller Plant Design. Julian R. de Bullet President debullet Consulting

Temporary HVAC Equipment, Oil-Free Air Compression and Power Generation

Chilled Water system

AMERICAN EQUIPMENT SYSTEMS A Division Of Trevor-Martin Corporation th Terrace North Clearwater, Florida 33762

Q. Which hydrocarbons can be used as a refrigerant? The following hydrocarbons can be used as a refrigerant in cooling & heating applications:

DRYING YELLOW-POPLAR IN A SOLAR-DEHUMIDIFIER KILN WITH HEAT STORAGE AND HEAT RECOVERY SYSTEMS

Refrigerated Air Dryers

Thermodynamics I. Refrigeration and Heat Pump Cycles

Desiccant Air Dryers. Heatless, Heated and Heated Blower

SPRAY DRYING SYSTEMS INC.

Part IV: Flow Side Components Flow Diagram

Modelling of an Integrated Supermarket Refrigeration and Heating System Using Natural Refrigerants

AirCel. Heated Regenerative Desiccant Dryers. AEHD Externally Heated, HRE Blower Purge, and HRS-L Zero Purge Series

Refrigerants Type Expensive Coefficient of Performance Toxic

Refrigeration System Overview. ASTI 32 Hour Managing Ammonia Course September 27 30, 2016

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

FS 231: Final Exam (5-6-05) Part A (Closed Book): 60 points

Heat of Compression Desiccant Air Dryers. HOC SERIES scfm ( nm 3 /h)

Natural Refrigeration with Hydrocarbons Emerson s R290 Solutions

i-chiller 181 to 210 kw ic770 to ic780 ABOUT THE i-chiller RANGE RELIABILITY: ENERGY & PROCESS EFFICIENCY: EASE OF OPERATION & MAINTENANCE:

Wall Mounted Air Conditioners with Gas Heat Models AVGA

precision controlled industrial process chillers cooling capacity: ,255,668 BTU /hr ( tons) improved productivity & reduced costs

Combustion Safety Testing: What we learn from Standards and Research. Objectives. Objectives 2/24/2016

Desiccant Dehumidifier

Energy Saving Refrigerated Air Dryers SRC Cycling Dryers

Chillers and Refrigerants. Purpose of Today s Presentation. Agenda. GLHN Architects & Engineers, Inc. APPA Institute Session 322 EU

Homework Chapter2. Homework Chapter3

Use of transcritical CO 2 in industrial applications

KE2 EvaporatorEfficiency Theory of Operation

MAC N-407 Air-Cooled Chiller

DROP-IN EVALUATION OF REFRIGERANT 1234YF IN A RESIDENTIAL INTEGRAL HEAT PUMP WATER HEATER

Compressed Air System Products That Save Energy & Improve Operations. Dry, Clean Air for Sensitive Equipment. Refrigerated Air Dryers

Heat pump and energy recovery systems

Small Applications with Ammonia

MAC-120HE-03 Air-Cooled Chiller

Heat of Compression Desiccant Dryers: Clearing up the Confusion

: REFRIGERATION & AIR CONDITIONING COURSE CODE : 6023 COURSE CATEGORY : A PERIODS/ WEEK : 6 PERIODS/ SEMESTER : 90 CREDIT : 6 TIME SCHEDULE

YOUR BASIC REFRIGERAION SYSTEM SVASD MAY 26, 2011

INDUSTRIAL DEHUMIDIFICATION DRYING OF SOFTWOODS

Environmentally friendly refrigeration systems for industrial use

Transcription:

Arnold Engineering Development Center Researching, Developing, and Testing America s Aerospace Technology Arnold AFB Economic Analysis Process Applied To The Worlds Largest Wind Tunnel I n t e g r i t y - S e r v i c e - E x c e l l e n c e 1

Economic Analysis Process Applied To The Worlds Largest Wind Tunnel Presented by 1Lt Dan Wyman /FMP Robert Nelson /FMP MCR, LLC dana.wyman@arnold.af.mil robert.nelson@arnold.af.mil ISPA-SCEA 2007 Joint Conference June 12 15, 2007 2

Arnold Engineering Development Center () is the World s Largest Complex of Wind Tunnels and Simulation Facilities Located in Tullahoma, Tennessee Established in 1950 56 Interrelated Plant Systems and Test Facilities is a Major Range & Test Facility Base (MRTFB) Arnold Eglin Edwards is Undr USAF Management with Contractor Workforce 8% Government, 92% Contractor 2,978 Total Personnel 3

Aerial View 4

Detail View 1 5

Detail View 2 6

RC-1 Cooler 7

RC-1 Diagram 8

Some RC-1 Cooler Information 1,200 lb/second of ambient air brought in by compressors About the volume of a 2,100 sq ft house Exits at 300ºF. RC-1 cools and dries the air to simulate conditions at high altitude and prevent ice from forming Cools to -25ºF Humidity reduced up to 99.6% (over 3 gal/sec.) Downstream compressors suck out the air creating low pressure & low humidity high altitude conditions. Cold Dry Low Pressure Air Moving Really Fast 9

RC-1 Cooler Concern 1970s design Mechanical refrigeration Pressurized dehumidification cooler Time - worn out Could be a single-point-of-failure Environmental issues 24,000 lbs of Freon (R12) Ozone depletion 50,000 gallons of trichloroethylene (TCE) Affects the central nervous system Damage nerves, liver, kidneys, cause cancer 10

RC-1 Cooler Task Identify an approach to restore the RC-1 Cooler that: Meets current operational performance capabilities Eliminates single-point-of-failure Removes TCE as the brining agent Removes R12 as the refrigerant. 11

Economic Analysis Point 1 Those who are accomplishing the EA need and understanding of the technical attributes and features of the system for which the EA is being accomplished. 12

Options Considered Mechanical Drying Refrigerant System Upgrade with R12 & Dynalene HC40, new refrigeration system, new RC1 coils Refrigerant System Upgrade with Ammonia & Dynalene HC40, new refrigeration system, new RC1 coils) Four New Coolers (one cooler for each compressor) One New Cooler ( RC-1B parallel cooler) Desiccant Drying Desiccant Wheels (Parallel or Series) Liquid or Multi-bed Desiccants Others Cryogenic Dehumidification System (Liquid Air) Desiccant Wheels added to low-stage desiccant wheel Maintain Status Quo 13

Two Options Selected Further Study Mechanical Drying Refrigerant System Upgrade R12 to R507A TCE to Dynalene HC40 New industrial refrigeration system New RC1 coils) Desiccant Drying Desiccant Wheels (Parallel) 14

Mechanical Drying Moist, Ambient Air Cooling Coils Filled w/brine Dry, Cool, Conditioned Air Cooled Brine Returns to Coil Heated Brine Pumped to Refrigeration Unit Moisture Removed from Air Runs Off Refrigeration Unit Filled w/refrigerant 15

Refrigerant System Upgrade RC-1 LOW STAGE COOLER Water Glycol Dynalene HC40 R507A 152ft 80 to 900#/s W = 0.5 900 to 1200#/s W =1.8 1200 to 1540#/s W = 2.0 5TH STAGE RC15 Water HC40 TCE HC40 TCE Glycol WATER Water 42ft -24 F W=0.5 4TH STAGE RC14 0 F W=2 3RD STAGE RC13 38F W=12 2ND STAGE RC12 90 F W=79 1ST STAGE RC11 OUT WATER IN 25 to 50 psia 300 F W=114 gr 1100 #/S AIR FLOW WATER IN REHEAT HT EXCHANGER WATER OUT RC14 TCE PUMPS 400 HP 5000 GPM R507A RC14 REEFER RC13 TCE PUMPS 400 HJP 5000 GPM R507A RC13 REEFER RC12 GLY PUMPS 450 HP 5000 GPM RC12.1 REEFER RC12.2 REEFER REHEAT PUMPS 300 HP 1750 GPM 3 rd and 4 th Stages Dynalene HC40 replaces TCE R507A Refrigerant replaces R12 16

Refrigerant System Upgrade Life Cycle Cost Known maintenance costs System sustainment costs will mirror current costs 15-20% more pumping power required for Dynalene over TCE Risk that use of selected fluids (R507A refrigerant and Dynalene HC40 brine) will be restricted later 17

Desiccant Drying Post-Drying Coolers Moist, Ambient Process Air Desiccant Holder Dry, Warm, Conditioned Process Air Dry, Cool, Conditioned Process Air Desiccant Holder Hot, Regeneration Air Water Vapor vents to atmosphere Desiccant Holders Move in and out of Process Air 18

Desiccant Wheel Principal 19

Desiccant Wheels 20

Desiccant Wheel 21

Desiccant Drying Equipment Installation Electrical Switchgear Existing Compressor Tie-in Chillers Desiccant Wheels 22

Desiccant Drying Life Cycle Cost Desiccant Dryer Quad-Units Four 10 desiccant wheels per quad-unit Eight 8 Quad-Units required A total of 32 individual wheels No commercial installation of this magnitude exists. Commercial large dry-air --- up to 120 lbs/sec. This concept needs 1,200 lbs/sec.! 23

Desiccant Drying Life Cycle Cost Long life of desiccant wheels (10 15 years) O&M costs estimated based on power use and contractor maintenance cost data Uncertainty of natural gas costs 24

Economic Analysis Approach Construction Cost Operations Cost Maintenance Cost 25

Construction Cost Estimate Approach Engineers estimated labor & material cost for each item. Example of scope for one Work Package MECHANICAL UTILITIES - Work Package 1 Replace RC14 System Replace RC14 System Subtotal P&I new base for custom built RC14 chiller P&I new bases for new RC14 brine pumps Equipment - Replace RC14 System P&I new custom built RC14 chiller. (includes condensers, evaporators, compressors, vessels, & related chiller piping) Demo RC14 Coils within RC1 cooler (Coils K,L,M,N) Demo Existing RC14 brine pumps (14.1, 14.2, 14.3, 14.4) Demo existing RC14 brine expansion tank P&I new brine pumps for RC14 circuit P&I new RC14 brine expansion tank P&I new RC14 coils within RC1 cooler Coils Demo old RC14 chiller and remaining related RC14 equipment 26

Economic Analysis Point 2 The EA analyst will develop some of the supporting cost estimates. In these cases, an understanding of the system is necessary to develop a credible cost estimate for each EA cost area. If the estimate is provided the EA analyst must understand and concur with that cost estimate information. 27

Construction Cost Estimate Approach The construction cost estimates for both approaches were close to each other. The primary difference was that the Desiccant Wheel option construction costs are earlier than for the Mechanical Drying approach. 28

Operations Cost Estimate Approach Example of calculations based on power requirements. 29

Operations Cost Estimate Approach Mechanical Drying Electric power requirements are large for the refrigeration system. Desiccant Dryer Natural gas costs for the regeneration heater is the primary component. 30

Maintenance Cost Estimate Approach Mechanical Drying based on historical costs for the current system. Desiccant Wheel Dryers based on contractor rates for maintenance of this equipment. The Mx costs are lower than the Operations costs. 31

Net Present Value Chart RC1 LCC - Net Present Value Millions of Dollars 2007 2010 2013 2016 2019 2022 2025 Year 2028 2031 2034 2037 Mechanical Drying Desiccant Wheels 32

Economic Analysis Point 3 Be be able to explain the reasons for the EA cost differences between the alternatives. 33

Net Present Value Observation The construction costs were about the same except for the timing of the expenditures The maintenance costs were both relatively low The larger operations cost for the Mechanical Drying option causes it s NPV to become much larger over time Operations is the NPV cost driver. 34

Economic Analysis Point 4 The EA results are only one component of a decision making process. The decision process will assess and weigh several decision criteria. An assignment of the relative value for each decision criteria will help in developing and defending the final decision. 35

Overall Evaluation Criteria Function (21%) Simplicity, Training, Ease of Operations Reliability, Availability, and Maintainability Operations, Degradation, Maintenance Viability (12%) Capital, Operations and Maintenance Costs Supportability (10%) Maintenance Requirements, Logistics Support, Liability (15%) Safety, Hygiene, Impacts, Energy Conservation Acquisition Planning (10%) MILCON, R&M Funds Technical Risk (7%) Obsolescence, Mitigation, Contamination Schedule (5%) Duration of Repair, Ops & Mx Impacts 36

Evaluation Matrix 37

Economic Analysis Interim Results At this point, the Desiccant Wheel approach has the smaller Net Present Value However, also at this time (mid-march 2007) technical changes were required that will change the results. 38

Economic Analysis Point 5 Systems analysis and evaluations often are dynamic. Due to technical, programmatic, funding and other concerns or constraints the alternatives are redefined. 39

Technical Changes The set of alternatives was modified to three options: Option 1: Mechanical Drying (Previous Option) Option 2: Mechanical Drying (Previous Option) + High-Stage Desiccant Drying Option3: Desiccant Wheels (Previous Option) + Low Stage Mechanical Drying 40

Option 1: Mechanical Drying Same as the earlier Mechanical Drying Alternative No change in the Economic Analysis 41

Option 2: Option 1 + High-Stage Desiccant Drying Add High-Stage Desiccant Drying to the Mechanical Drying Alternative. Install 8 Desiccant Dryer Units upstream of the high stage compressors Pre cooling coils remove about 2/3 moisture Desiccant wheels remove remaining moisture Regeneration with natural gas burners 42

Option 2: Desiccant Dryer Unit 43

Option3: Desiccant Wheels + Low Stage Mechanical Drying RC1 LOW STAGE COOLER 5TH STAGE RC15 4TH STAGE RC14 3RD STAGE RC13 2ND STAGE RC12 1ST STAGE RC11 WATER OUT -24 F W=0.5 0 F W=2 38F W=12 90 F W=79 300 F W=114 gr 1100 #/S AIR FLOW WATER IN WATER IN REHEAT HT EXCHANGER WATER OUT RC14 TCE PUMPS 400 HP 5000 GPM RC14 REEFER RC13 TCE PUMPS 400 HJP 5000 GPM RC13 REEFER RC12 GLY PUMPS 450 HP 5000 GPM RC12.1 REEFER RC12.2 REEFER REHEAT PUMPS 300 HP 1750 GPM 44

Option3: Desiccant Wheels + Low Stage Mechanical Drying Add Low-Stage Mechanical Drying to the Desiccant Wheel Alternative Modify the existing RC1 cooler system Provide new cooler coils and refrigeration Replace the R12 and Trichloroethylene Replace secondary coolant & brine systems Replace centrifugal with screw type chillers 45

Economic Analysis Point 6 Due to the often dynamic nature of the alternative process the EA process will continue to be dynamic. 46

Economic Analysis Point 7 As of the submission date for this paper (April 9) the parameters associated with these changes are being defined by the members of the technical team. 47

Economic Analysis Point 8 The EA process will continue upon availability of that data. Updated information will be provided at the ISPA-SCEA 2007 Joint Conference June 12-15, 2007 48