Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Similar documents
Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

Study of R161 Refrigerant for Residential Airconditioning

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

R32 Compressor for Air conditioning and Refrigeration applications in China

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Performance of CO2 Cycles with a Two-Stage Compressor

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Performance Measurement of R32 Vapor Injection Heat Pump System

Design and Research of the Commercial Digital VRV Multi-Connected Units With Sub-Cooled Ice Storage System

Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat Pumps Application

Analysis of Oil Pumping in the Hermetic Reciprocating Compressor for Household Refrigerators

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Experimental Investigation of a New High Temperature Heat Pump Using Water as Refrigerant for Industrial Heat Recovery

Development of Performance Test Facility of Positive Displacement CO2 Refrigerant Compressor

Low GWP Refrigerants for Air Conditioning Applications

Purdue e-pubs. Purdue University

Sub-Critical Operation of the CO2 Expander/ Compressor

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Performance of an Improved Household Refrigerator/Freezer

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Thermal Modelling for the Motor in Semi-hermetic Screw Refrigeration Compressor under Part-load Conditions

EXPERIMENTAL STUDY ON R1234YF HEAT PUMP AT LOW AMBIENT TEMPERATURE AND COMPARISON WITH OTHER REFRIGERANTS

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

A study of high efficiency CO2 refrigerant VRF air conditioning system adopting multi-stage compression cycle

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Numerical Simulation of a New Cooling System for Commercial Aircrafts

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Performance Characteristics of a Refrigerator- Freezer with Parallel Evaporators using a Linear Compressor

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump

Effects of Oil on atranscritical Carbon Dioxide Air Conditioning Systems some experiences -

Effect of the Use Pattern on Performance of Heat Pump Water Heater

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

Dynamic Simulation of Liquid Chillers

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Mini Vapour Cycle System For High Density Electronic Cooling Applications

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Experimental Study of Two-phase Seperators for Vapor Compression Systems in Household Appliances

High Efficiency Heat Pump for Domestic Hot Water Generation

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Experimental Study on the Performance of Twisted Capillary Tube

Efficiency of Non-Azeotropic Refrigerant Cycle

Experimental Analysis of a Stirling Refrigerator Employing Jet-Impingement Heat Exchanger and Nanofluids

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Performance Characteristic and Optimization of a Simultaneous Heating and Cooling Multi Heat Pump

Energy Efficiency of Air-to-Air Mini Heat Pump

Quantification of Liquid Refrigerant Distribution in Parallel Flow Microchannel Heat Exchanger Using Infrared Thermography

Experimental Research and CFD Simulation on Microchannel Evaporator Header to Improve Heat Exchanger Efficiency

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

A Study on Compression Characteristic of Wet Vapor Refrigerant

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Performance Analysis of a Miniature-Scale Vapor Compression System for Electronics Cooling: Bread Board Setup

System Modeling of Gas Engine Driven Heat Pump

Figure 1: Schematic of internal heat exchanger vapor-injection cycle

Comparison Of Hermetic Scroll And Reciprocating Compressors Operating Under Varying Refrigerant Charge And Load

Volume 2, Issue 1 (2014) ISSN International Journal of Advance Research and Innovation

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Experimental Analysis Of Vapour Compression Refrigeration System With Superheating By Using R-134a, R-12, R-717 Refrigerant

Experimental and Numerical Study on the Performance of R410A Liquid Recirculation Cycles with and without Ejectors

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer Yongning He Xi'an Jiaotong University, China, People's Republic of, yongning.h2010@gmail.com Lei Jin Xi'an Jiaotong University, China, People's Republic of, king880106@stu.xjtu.edu.cn Feng Cao Xi'an Jiaotong University, China, People's Republic of, fcao@mail.xjtu.edu.cn Shengkun Chen Xi'an Jiaotong University, China, People's Republic of Follow this and additional works at: http://docs.lib.purdue.edu/iracc He, Yongning; Jin, Lei; Cao, Feng; and Chen, Shengkun, "Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer" (2014). International Refrigeration and Air Conditioning Conference. Paper 1491. http://docs.lib.purdue.edu/iracc/1491 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

2454, Page 1 Experimental Research on Vapor Injection High Temperature Heat Pump with an Economizer Yongning He 1, Lei Jin 1, Feng Cao 1 *,Shengkun Chen 2 1 School of Energy and Power Engineering, Xi an Jiaotong University, Xi an, 710049, China Phone: 86-29-82663583, Fax: 86-29-82663583, E-mail: fcao@mail.xjtu.edu.cn 2 Fusheng (Shang Hai) Co., Ltd, Shanghai, 200000, China * Corresponding Author ABSTRACT Vapor injection technique is often used in cold regions to increase heat pump s heating capacity and decrease discharge temperature at low evaporation temperature. Injecting refrigerant vapor into port opened at specific position of compressor can increase mass flow rate of compressor and condenser. Vapor injection also changes pressure ratio of compression process and decreases discharge temperature. It s a feasible way to improve heating performance of heat pump at cold regions. High temperature heat pump (HTHP) can provide up to 90-120 water for industrial usage regions but there exists some problems on its usage. Total heating capacity decreases and discharge temperature increases with the raise of condensation temperature. Refrigerant temperature before expansion valve is high and may exceed working temperature range of common used electronic expansion valve (EEV). Vapor injection technique with an economizer was adopted to solve these problems. In this paper a new high temperature heat pump cycle was designed based on vapor injection and outlets water temperature of the prototype manufactured was reached to 90. Heating capacity, discharge temperature, compressor power consumption of the heat pump system at different amount of injected vapor was conducted by theoretical and experimental research. Adopting vapor injection could increase total heating capacity of a certain heat pump unit worked at high condensation temperature. But coefficient of performance (COP) decreased due to the increment of compressor power consumption caused by mass flow rate increment. Refrigerant temperature before expansion valve was well controlled by the usage of economizer in the experimental research. 1. INTRODUCTION Vapor injection technique is widely used in heat pumps working in cold regions. To heat room space or supply hot water for household usage at low ambition temperature, heat pump works at a lower evaporation temperature. Reduction of evaporation temperature increases pressure ratio of the heat pump and refrigerant specific volume in suction line. Increased pressure ratio decreases compressor volumetric efficiency reduction and also leads to higher discharge temperature. High discharge temperature weakens the function of lubricating oil in compressor and may cause potential damage to the compressor and running stability of heat pump. The decreased volumetric efficiency and increased refrigerant specific volume of suction line causes a sharp decrease mass flow rate of refrigerant and heating capacity. To keep a reasonable heating supplement and discharge temperature, vapor injection technique is often adopted. By injecting refrigerant into compressor through specific port on compressor, refrigerant mass flow rate of condenser is increased as well as the total heating capacity. Vapor injection changes the pressure distribution in compression chamber and makes the compression process similar to a two-stage compression. Discharge temperature is decreased with the change of pressure ratio and keeps at a safety level for long running of compressor. High temperature heat pump provides much higher temperature water for commercial and industrial heating. Evaporation and condensation temperature of HTHP is much higher than that of regular heat pump. For a specific

2454, Page 2 HTHP for crude oil heating, its condensation temperature reaches up to 100 and total heating capacity reaches to 1700kW. This heat pump could recovery heat from 50-60 waste water by-produced with oil and heat the crude oil through a heat exchanger. For high temperature heat pump, heating capacity decreased and discharge temperature increased with the raise of condensation temperature. Refrigerant temperature at the outlet of condenser is high and exceeds the working temperature arrangement of commercial available electric expansion valve. To ensure working safety of common throttling valve, some measures are used to provide big sub-cooling for HTHP. Extra cooling water or water from evaporator is often used to get sub-cooling. Heo et al. (2010) compared four different refrigerant injection strategies to evaluate the heating performance of air source heat pump. Flash tank cycle and combined flash tank and sub-cooler cycle considered to be the better injection cycle for heating performance. Roh and Kim (2012) did a research on two different ways of refrigerant injection, injecting vapor refrigerant into compressor and accumulator selectively. The research showed that injecting refrigerant into compressor increased heating capacity obviously while injecting refrigerant into accumulator decreased discharge temperature effectively but increased heating capacity and COP slightly. Roh and Kim (2014) applied a vapor injection technique in a cascade heat pump system. The research results showed that two vapor injection cycles of low and high stage increased heating capacity and COP of each stage but the cascade system COP was decreased. In cascade heat pump, vapor injection s advantage of improving system COP was not effective. Some other research focused on using different refrigerants to evaluate the performance of heat pump using vapor injection. R410a, R32 and mixture of R22 and R600a were common used be researchers (Cao et al., 2009, Wang et al., 2009, Roh and Kim, 2011, Xu et al., 2013, Xu et al., 2013). Heat pumps with economizer, flash tank or vapor injector were common ways to complete vapor injection. The open literature focused on reaching biggest COP of heat pump or getting a reasonable heating capacity at different vapor injection pressure or ratio. Little research was done on the combination of HTHP and vapor injection technique for now. To solve the heating capacity decrement at high condensation temperature and also obtain bigger sub-cooling of refrigerant before throttling valve, high temperature heat pump cycle adopted an economizer was presented. Theoretical and experimental research was done to test vapor injection function in high temperature heat pump. 2. SYSTEM DESCRIPTIONS 1 3' Msuc Minj oil-cooler compressor condenser 4 evaporator Valve1 Msuc economizer 8 4 Valve2 6 5 Minj Mdis Figure 1: Schematic of HTHP system with economizer

2454, Page 3 Figure 2: The P-h diagram of HTHP system Figure 3: Picture of HTHP Combining the vapor injection technique and high temperature heat pump, a new heat pump cycle was built. The schematic of system is shown in Figure 1 and Pressure-enthalpy diagram of this heat pump system is presented in Figure 2. State point s number on P-h diagram corresponded with the number in Figure.1. Compressor, condenser and evaporator were set same as regular heat pump. An extra economizer was set behind the condenser to complete the vapor injection process. Refrigerant from the condenser flowed through the economizer and then be divided into two parts. One part flowed expansion valve 2 and then flowed back into economizer. Its pressure decreased as well as the temperature after throttling function. This part of refrigerant exchanged heat with refrigerant from the condenser outlet and then the evaporated refrigerant vapor was injected into compressor. The mass flow rate of this refrigerant was defined as M inj. The other part refrigerant flowed through valve1 and then evaporated in evaporator. Mass flow rate of this part refrigerant was defined as M suc. Total refrigerant flowed through condenser was M dis and its value was the sum of M inj and M suc. Figure 3 shows a picture of the tested HTHP.

2454, Page 4 3. THEORETICAL SIMULATIONS AND ANALYSES To evaluate the function of vapor injection technique when it was used in high temperature heat pump, a theoretical analysis was made. Theoretical analyses focused on the performance of high temperature heat pump at different vapor injection ratio. During theoretical research, injection pressure was assumed to be a contest value while the vapor injection area was variable. Followed research was all based on this assumption. Common used refrigerant for high temperature heat pump R134a, R124 and R245fa was involved in theoretical comparison. Considering applications of high temperature heat pump, theoretical heat pump cycle was set as followed: Evaporation temperature and condensation temperature was set to be 35 and 100 respectively. Indicated efficiency of compressor was 0.65 and the mass flow rate of suction line was set to be 1kg/s for an easier simulation and comparison. State point 4 at the outlet of condenser had a sub-cooling of 5. State point 5 at suction line had a super heat of 5. Temperature of state point 6 was set to be 55 for getting better cooling of refrigerant in the economizer. To maintain the safety running of compressor, refrigerant injected into compressor should be vapor. State point 8 had a super heat of 3. To simplify the theoretical analyses, some assumptions were made as followed. Economizer in the system was isothermal and heat exchanged only between the refrigerant in different flow channels. Steady state heat balance in economizer was calculated by equation (1) and (2). M inj *(h 8 -h 6 )=M dis *(h 4 -h 5 ) (1) M inj +M suc =M dis (2) Refrigerant pressure drop during flowing was ignored and the throttling process was isenthalpic. Compression process in compressor was isentropic and the compressor was adiabatic. Power consumption of the compressor was given in equation (3). W comp =M dis *(h 3 -h 2 )+M suc *(h 2 -h 1 ) (3) Refrigerant injected into the compression chamber under pressure difference and then mixed with that from suction line. Injection port was opened on specific position after calculation. Here used twin screw compressor, the pressure of state point 2 was 1.1 times than that of state point 1. The mixture process in compression chamber was simplified and the energy balance was given by equation (4). In this paper, vapor injection ratio was defined in equation (5). M inj *h 8 +Msuc*h 2 =M dis *h 2 (4) α=m inj /M suc (5) Heating capacity and COP of the HTHP was calculated by equation (6) and (7) in theoretical analyses. Q cond =M dis *(h 3 -h 4 ) (6) COP=Q cond /W comp (7) Heating capacity and power consumption of compressor at different vapor injection ratio was shown in Figure 4 and 5. Three refrigerants had the same tendency with the variation of vapor injection ratio. Heating capacity and power consumption increased with the vapor injection ratio. More vapor injection meant more refrigerant flowed through compressor and condenser. Increment of refrigerant mass flow increased the total heating capacity and also power consumption. The R134a heating capacity decrement at the beginning of vapor injection process was caused by the

2454, Page 5 parameter change of state point 3. Vapor injection decreased the discharge temperature and then decreased the enthalpy difference between the inlet and outlet refrigerant of condenser. Figure 4: Heating capacity variation versus vapor injection ratio Figure 5: Power consumption variation versus vapor injection ratio Figure 6: COP variation versus vapor injection ratio

2454, Page 6 Figure 7: Temperature variation of state point 5 versus vapor injection ratio Figure 8: Discharge temperature variation versus vapor injection ratio COP variation versus vapor injection ratio can be seen in Figure 6. Compared with heat pump without vapor injection, HTHP had a higher COP value. High temperature COP increased with the raise of vapor injection ratio. For R124, 12.3% COP increment was got when the vapor injection ratio reached to 10%. The COP increment with vapor injection ratio is caused by the increment usage of refrigerant sensible heat. Temperature changes with vapor injection ratio are shown in Figure 7. Value of sensible heat used for economizer was enthalpy difference between enthalpy of state point 4 and 5. With increment of vapor injection ratio, temperature of state point 5 was decreased and more sensible heat was reused and then returned to compressor. State point 5 temperature changed with the vapor injection ratio and its value at different vapor injection was shown in Figure 7. More vapor injection meant lower temperature of state point 5. Lower refrigerant temperature of state point 5 kept the running safety of the EEV. Discharge temperature variation versus vapor injection ratio is shown in Figure 8. Injecting vapor into compressor decreased the discharge temperature obviously at the beginning of vapor injection. Discharge temperature changed slightly with the variation vapor injection. The function of economizer on controlling compressor discharge temperature at high condensation temperature was proven to be reasonable.

2454, Page 7 4. EXPERIMENTAL RESULTS AND DISCUSSION To verify the performance of high temperature heat pump with economizer, an experimental research was done based on the theoretical analyses. After comparison of refrigerant R134a, R245fa and R124 at condensation of 100, R124 was chosen as the refrigerant for its thermal properties at the high condensation working condition. Compressor used here was a modified twin-screw compressor with a vapor injection port specially designed for R124. Condenser and evaporator were shell and tube and the maximum working pressure of condenser was 3.2Mpa. Oil cooler set to control the lubricating oil temperature in compressor and economizer were both plate heat exchangers. Valve 1 was an electronic expansion valve for controlling the mass flow rate of evaporator while valve 2 was a hand-operated valve for controlling the mass flow rate of refrigerant in economizer. For more vapor injection, port on compressor should be designed specially based on the structure of compressor. In testing period, inlet and outlet water temperature of condenser was 82 and 88. Inlet and outlet water temperature of evaporator was 46 and 43. To keep safety running of EEV, the economizer was working all the time and vapor injection ratio we recorded changed from 10% to 22.6% during the whole test. Figure 9: Power consumption and heating capacity of heat pump at different vapor injection ratio Figure 10: COP variations of heat pump at different vapor injection ratio

2454, Page 8 Performance of heat pump at different vapor injection ratio is shown in Figure 9 and 10. Heating capacity of heat pump and power consumption both increased with the increments of vapor injection. When the vapor injection ratio changed from 10% to 22.6%, heating capacity and power consumption increased 4.4% and 9.5%, respectively. This tendency agreed the theoretical analyses well and vapor injection did increase the heating capacity. COP increased at the beginning of vapor injection and the decreased with the increment of vapor injection. The biggest COP occurred when the vapor injection ratio was 13%. Here existed a difference between the experimental and theoretical conclusion. This might be caused by the model accuracy of compressor consumption during theoretical analyses. Figure 11: Discharge temperature and temperature of state point 5 variations versus vapor injection ratio Discharge temperature and temperature before the electronic expansion valve is presented in Figure 11. Discharge temperature rose with the increment of vapor injection. Vapor injection changed from 10%-22.6% while discharge temperature increased only 3. Increment on discharge temperature of vapor injection was small and the discharge temperature maintained at a safety value. Bigger vapor injection did not raise the discharge temperature obviously would not cause damage to the compressor. Refrigerant temperature before the electronic expansion valve (temperature of state point 5) decreased with the ratio of vapor injection. More vapor injection meant a larger enthalpy difference between state point 4 and 5. The refrigerant sensible heat was reused by the economizer to evaporate the injected refrigerant. The lower temperature of state point 5 maintained the stability of electronic expansion valve. The usage of economizer made a great subcooling of refrigerant and kept the running of electronic expansion valve. 5. CONCLUSIONS Adopting vapor injection technique in high temperature heat pump with an economizer was conducted on by theoretical and experimental research. The following conclusion was obtained. High temperature heat pump could adopt vapor injection technique to increase its heating capacity at higher condensation temperature. The injected vapor increased mass flow rate of condenser and then raised total heating capacity. Adopting vapor injection could increase total heating capacity of a certain heat pump unit worked at high condensation. Power consumption of compressor increased with the vapor injection ratio. Function of vapor injection on COP was slight and also influenced by the characters of refrigerant.

2454, Page 9 Discharge temperature did not decrease with the increment of vapor injection but increased only 3 when the vapor injection ratio reached to 22.6%.The use of economizer decreased the refrigerant temperature before electronic expansion valve. This was especially important for the stable working of electronic expansion valve. For high temperature heat pump, an economizer could provide enough sub-cooling of refrigerant and replace other cooling strategy for high temperature heat pump. NOMENCLATURE α vapor injection ratio COP coefficient of performance h enthalpy (kjkg -1 ) M mass flow rate (kgs -1 ) Q heating capacity (kw) W power consumption (kw) Subscript cond condenser comp compressor dis discharge inj injection suc suction REFERENCES Cao. F, Wang. K, Wang. S, Xing. Z, Shu. P, 2009, Investigation of the heat pump water heater using economizer vapor injection system and mixture of R22/R600a, Int. J. Refrig., vol. 32, no. 32: p. 509-514. Heo, J., Jeong, M., Baek,C., Kim, Y., 2011, Comparison of the heating performance of air-source heat pumps using various types of refrigerant injection, Int. J. Refrig., vol. 34, no. 2: p. 444-453. Roh, C., Kim, M.,2012, Comparison of the heating performance of an inverter-driven heat pump system using R410A vapor-injection into accumulator and compressor, Int. J. Refrig., vol. 35, no. 2: p. 434-444. Roh,C., Kim,M.,2014, Effect of vapor- injection technique on the performance of a cascade heat pump water heater, Int. J. Refrig., vol. 38, p. 168-177. Roh. C, Kim. M, 2011, Effects of intermediate pressure on the heating performance of a heat pump system using R410A vapor-injection technique, Int. J. Refrig., vol. 34, no. 8: p. 1911-1921. Wang. X, Hwang. Y, Radermacher. R, 2009, Two-stage heat pump system with vapor-injected scroll compressor using R410A as a refrigerant, Int. J. Refrig., vol. 352, no. 6: p. 1442-1451. Xu. S, Ma. G, Liu. Q, Liu. Z, 2013,Experiment study of an enhanced vapor injection refrigeration/heat pump system using R32, Int. J. Ts., vol. 68, p. 103-109. Xu. X, Hwang. Y, Radermacher. R, 2013, Performance comparison of R410A and R32 in vapor injection cycles, Int. J. Refrig., vol. 33, no. 3: p. 892-903.