Air System Sizing Summary for AHU/CU-1 Project Name: Wilton Manors Fire Station#16 06/26/2016 Prepared by: L.N.I.

Similar documents
Air System Sizing Summary for Lobby System Project Name: Existing Lobby 04/04/2005 Prepared by: psuae

MECHANICAL INFRASTRUCTURE ASSESSMENT FOR VICTOR VALLEY COLLEGE

COOLING LOAD CALCULATION SHEET

Company Acme HVAC Inc. Customer James Allen Preparer J White Address 3652 Shady LaneAnywhere, Earth Phone

90% Design Submittal Mechnical Equipment Calculations Parking Garage CDRL

MANUAL J/S Summary One summary sheet for each system

Technical Development Program

Fundamentals of Psychrometrics. By James L. Murphy, Colorado Building Environments Sales Engineer

ApacheHVAC User Guide Part F: Loads Analysis and Reporting Tools

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN

PhEn-602 Pharmaceutical Facility Design. Notes #7 J. Manfredi

Dehumidification: Energy Efficiency Comparisons

Building Systems: HVAC

Standards and Guidelines. Presented by: Aric Murray December 12, 2014

ELECTRICAL QUANTITY WEIGHT (LB)

7. MECHANICAL SYSTEM DESIGN

50HS018, 024, 030, 036, 042, 048 & 060 STANDARD-EFFICIENCY COMBINATION HEAT PUMP UNITS W/OPTIONAL ELECTRIC HEAT

SUBMITTAL DATA SHEET FEATURES. SPLIT-SYSTEM EVAPORATOR BLOWERS 7.5, 10, 15 & 20 TONS MODELS: NH-07 thru -20, 2-PIPE NJ-10 thru -20, 4-PIPE

303 Garibaldi Ave, Roseto, PA Phone: Fax: Web: License: PA007413

UNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM

The Ed Roberts Campus Berkeley, CA

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE

TDSHS Air Change Requirements and the Basics of Psychrometrics. Presented by: Aric Murray December 06, 2013

HVAC Myths and Realities Trane Engineers Newsletter Live Series

We are pleased to submit the following equipment for your approval on the above project:

DIRECT DRIVE BLOWER COILS

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

In Search of the Magic Box: A Review of Crossover Conditioning/Ventilation/ Dehumidification Devices on the US Market

C13-Series Engineering Guide

ENERGY COST AND FEATURE REPORT

SELF-CONTAINED VERTICAL AIR COOLED PACKAGE AIR-CONDITIONERS

Practical and Effective Approaches to Residential Ventilation for Production Builders

December 6, 2018 Optimizing Solutions through Superior Dehumidification Technology SM

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

Designing Energy Efficient Outdoor Air Systems

Air Conditioning Clinic

Appendices. Included in this section are

VertiCool Aurora Engineering Guide

UNIT 1 AIR CONDITIONING 1. Write the various psychometric processes? Explain any four processes with neat sketches?

ASHRAE WILL GIVE YOU THE WORLD. This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee

VERTICAL AHU ENGINEERING SPECIFICATIONS BULLETIN

Radiant Exchange in Stratified Environments: Considerations and Challenges for Hourly Energy Simulation of UFAD, DV, and Radiant Cooling Systems

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

SPLIT SYSTEMS SELECTION & OPTIMIZATION GUIDE

In Search of the Magic Box: A Review of Crossover Conditioning/Ventilation/Dehumidification Devices on the US Market

Mystery of Sustainable Heat Exchange Material Heat Recovery Ventilator(HRV)

ISERIES VERTICAL AHU ENGINEERING SPECIFICATIONS

A/C Cooling Load calculation and measurement

Submittal Data Performance Data Electrical Data

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

Evaluating Moisture Control of Variable Capacity Heat Pumps in Mechanically- Ventilated, Energy-Efficient Homes.

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH

ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering


MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH

Best Practices for Applied Rooftop ` Systems, Applications and. Jerry Cohen President Jacco & Assoc. Installation

Commercial load calculator instructions (all measurements are imperial)

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

Time-Based Scheduling of Residential Ventilation

Adding More Fan Power Can Be a Good Thing

Pharmaceutical Facility Design

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

Technical Report #3 Mechanical Systems Existing Conditions Evaluation

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

Humidity Control Design Tips. R. Mark Nunnelly, PE, CxA, LEED AP President

DCC Series. Submittal Data Form. 7½- to 12½-Ton Three-Phase Packaged Air Conditioners

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

DCC Series. Submittal Data Form. 7½- to 12½-Ton Three-Phase Packaged Air Conditioners Up to 11.3 EER

August 15, 2013 Page 1 of 19

Residential HVAC System Design

Controlling Indoor Humidity in High Performance Homes. Danny Gough, Energy Solutions, LP

DCC Series. Submittal Data Form 15- & 20-TON, THREE-PHASE PACKAGED AIR CONDITIONERS UP TO 11 EER

Product Data. Features/Benefits. 50HS Single-Package Heat Pump Units 50 Hz

BENEFITS. Daikin North America LLC, 5151 San Felipe, Suite 500, Houston, TX, 77056


Split System Heat Pumps

Chilled beam technology overview John Woollett 1, Jonas Åkesson 2 Swegon AB 1,2

DCG Commercial. Submittal Data Form

SUBMITTAL. Project. CLU Swenson Center. Date 01/07/2010. Mechanical Contractor. West Coast Air Conditioning. Mechanical Engineer

Dehumidifying with Dedicated Outdoor Air

Multi-Path RTU-TYPE 2

DCC Commercial. Submittal Data Form. 7½ - 12½ Ton Packaged Air Conditioners Up to 11.3 EER Cooling Capacity: 88, ,000 BTU/h

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

COMcheck Software Version Interior Lighting Compliance Certificate

Andrea Borowski The Pennsylvania State University University Park, PA November 11, 2002 Consultant: Dr. Bahnfleth Technical Assignment M-3

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

GreenPac & GreenPac HGR Heat Pumps & Air Conditioners Models AVP

Richard Hiles ClimateMaster

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

EnergyPlus Testing with Global Energy Balance Test

Report No CRT-414

SR SERIES WATER SOURCE HEAT PUMP SYSTEM SELECTION AND OPTIMIZATION GUIDE

Building Science Principles for Managing Moisture in Tight Buildings

ASHRAE Standard 62 Ventilation Report Technical Assignment #1. Calvert Memorial Hospital Prince Frederick, MD

VariCool VAV Engineering Guide

TAG: RTU-2B 3B 4B 5B 6B 7B 1E MODEL: QTY. (7) 48TCED14A3A5-0B0A0 PACKAGED GAS/ELECTRIC ROOF TOP UNITS

DCG Series. Submittal Data Form. 7½- to 12½-Ton Three-Phase Packaged Air Conditioners

Working With DHPS and Other Variable Capacity Heat Pumps. October 05, 2017

IDL20e (2 way discharge) IDS60e (4 way discharge) Inffusers. UDI (vertical discharge) Frequently Asked Questions

Transcription:

Air System Sizing Summary for AHU/CU-1 AHU/CU-1 Floor Area 1678.0 ft² Central Cooling Coil Total coil load 4.8 Tons Total coil load 57.8 MBH Sensible coil load 41.8 MBH Coil CFM at Jul 1500 1909 CFM Max block CFM 1909 CFM Sum of peak zone CFM 1909 CFM Sensible heat ratio 0.723 ft²/ton 348.3 BTU/(hr-ft²) 34.5 Water flow @ 10.0 F rise Load occurs at Jul 1500 OA DB / WB 91.0 / 77.0 F Entering DB / WB 78.6 / 67.1 F Leaving DB / WB 58.3 / 57.3 F Coil ADP 56.1 F Bypass Factor 0.100 Resulting RH 55 % Design supply temp. 58.0 F Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 F Central Heating Coil Max coil load 14.1 MBH Coil CFM at Jan 0700 1909 CFM Max coil CFM 1909 CFM Water flow @ 20.0 F drop Load occurs at Jan 0700 BTU/(hr-ft²) 8.4 Ent. DB / Lvg DB 57.9 / 64.8 F Supply Fan Actual max CFM 1909 CFM Standard CFM 1908 CFM Actual max CFM/ft² 1.14 CFM/ft² Fan motor BHP 0.26 BHP Fan motor kw 0.21 kw Fan static 0.50 in wg Outdoor Ventilation Air Data Design airflow CFM 305 CFM CFM/ft² 0.18 CFM/ft² CFM/person 5.75 CFM/person Hourly Analysis Program v4.80 Page 1 of 6

Zone Sizing Summary for AHU/CU-1 AHU/CU-1 Floor Area 1678.0 ft² Zone Maximum Maximum Zone Cooling Design Minimum Heating Floor Sensible Airflow Airflow Time of Load Area Zone Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft² Zone 1 33.7 1909 1909 Jun 1500 7.7 1678.0 1.14 Zone Terminal No Zone Terminal required for this system. Space Loads and Airflows Cooling Time Air Heating Floor Zone Name / Sensible of Flow Load Area Space Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft² Zone 1 Bedroom area(e) 1 5.7 Jul 1500 311 0.9 499.0 0.62 Kitchen(E) 1 4.8 Jul 1400 262 1.2 190.0 1.38 Meeting Rm(E) 1 23.4 Jun 1600 1277 5.6 989.0 1.29 Hourly Analysis Program v4.80 Page 2 of 6

Air System Design Load Summary for AHU/CU-1 DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 91.0 F / 77.0 F HEATING OA DB / WB 46.0 F / 38.6 F Sensible Latent Sensible Latent ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr) Window & Skylight Solar Loads 102 ft² 2973-102 ft² - - Wall Transmission 254 ft² 981-254 ft² 1135 - Roof Transmission 1678 ft² 6679-1678 ft² 2986 - Window Transmission 102 ft² 1580-102 ft² 2717 - Skylight Transmission 0 ft² 0-0 ft² 0 - Door Loads 48 ft² 1074-48 ft² 816 - Floor Transmission 1290 ft² 0-1290 ft² 0 - Partitions 679 ft² 1245-679 ft² 0 - Ceiling 0 ft² 0-0 ft² 0 - Overhead Lighting 2349 W 7292-0 0 - Task Lighting 0 W 0-0 0 - Electric Equipment 0 W 0-0 0 - People 53 10302 6700 0 0 0 Infiltration - 0 0-0 0 Miscellaneous - 1525 240-0 0 Safety Factor 0% / 0% 0 0 0% 0 0 >> Total Zone Loads - 33652 6940-7654 0 Zone Conditioning - 36264 6940-6945 0 Plenum Wall Load 0% 0-0 0 - Plenum Roof Load 0% 0-0 0 - Plenum Lighting Load 0% 0-0 0 - Return Fan Load 1909 CFM 0-1909 CFM 0 - Ventilation Load 305 CFM 4850 9048 305 CFM 7783 0 Supply Fan Load 1909 CFM 708-1909 CFM -708 - Space Fan Coil Fans - 0 - - 0 - Duct Heat Gain / Loss 0% 0-0% 0 - >> Total System Loads - 41822 15988-14021 0 Central Cooling Coil - 41822 15990-0 0 Central Heating Coil - 0 - - 14021 - >> Total Conditioning - 41822 15990-14021 0 Key: Positive values are clg loads Positive values are htg loads Negative values are htg loads Negative values are clg loads Hourly Analysis Program v4.80 Page 3 of 6

Air System Sizing Summary for AHU/CU-2 AHU/CU-2 Floor Area 1270.0 ft² Central Cooling Coil Total coil load 3.7 Tons Total coil load 44.4 MBH Sensible coil load 35.3 MBH Coil CFM at Jun 1500 1586 CFM Max block CFM 1586 CFM Sum of peak zone CFM 1586 CFM Sensible heat ratio 0.795 ft²/ton 343.2 BTU/(hr-ft²) 35.0 Water flow @ 10.0 F rise Load occurs at Jun 1500 OA DB / WB 90.0 / 77.0 F Entering DB / WB 77.9 / 65.4 F Leaving DB / WB 57.3 / 56.1 F Coil ADP 55.0 F Bypass Factor 0.100 Resulting RH 50 % Design supply temp. 58.0 F Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 F Central Heating Coil Max coil load 16.5 MBH Coil CFM at Jan 0700 1586 CFM Max coil CFM 1586 CFM Water flow @ 20.0 F drop Load occurs at Jan 0700 BTU/(hr-ft²) 13.0 Ent. DB / Lvg DB 56.9 / 66.6 F Supply Fan Actual max CFM 1586 CFM Standard CFM 1585 CFM Actual max CFM/ft² 1.25 CFM/ft² Fan motor BHP 0.22 BHP Fan motor kw 0.17 kw Fan static 0.50 in wg Outdoor Ventilation Air Data Design airflow CFM 200 CFM CFM/ft² 0.16 CFM/ft² CFM/person 15.38 CFM/person Hourly Analysis Program v4.80 Page 4 of 6

Zone Sizing Summary for AHU/CU-2 AHU/CU-2 Floor Area 1270.0 ft² Zone Maximum Maximum Zone Cooling Design Minimum Heating Floor Sensible Airflow Airflow Time of Load Area Zone Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft² Zone 1 26.4 1586 1586 Oct 1400 8.4 1270.0 1.25 Zone Terminal No Zone Terminal required for this system. Space Loads and Airflows Cooling Time Air Heating Floor Zone Name / Sensible of Flow Load Area Space Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft² Zone 1 Hallway/Rest(E) 1 4.6 Jul 1500 253 0.8 466.0 0.54 Offices(DIE/SEC/Chef) 1 10.1 Jul 1400 552 3.1 391.0 1.41 Reception(E) 1 9.5 Nov 1400 518 2.8 218.0 2.38 Storage Rm(E) 1 1.9 Nov 1500 104 0.8 84.0 1.24 Watch(E) 1 2.9 Nov 1500 159 0.9 111.0 1.43 Hourly Analysis Program v4.80 Page 5 of 6

Air System Design Load Summary for AHU/CU-2 DESIGN COOLING DESIGN HEATING COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 90.0 F / 77.0 F HEATING OA DB / WB 46.0 F / 38.6 F Sensible Latent Sensible Latent ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr) Window & Skylight Solar Loads 119 ft² 4247-119 ft² - - Wall Transmission 558 ft² 2300-558 ft² 2493 - Roof Transmission 1316 ft² 5174-1316 ft² 2342 - Window Transmission 119 ft² 1712-119 ft² 3170 - Skylight Transmission 0 ft² 0-0 ft² 0 - Door Loads 24 ft² 484-24 ft² 408 - Floor Transmission 960 ft² 0-960 ft² 0 - Partitions 195 ft² 437-195 ft² 0 - Ceiling 0 ft² 0-0 ft² 0 - Overhead Lighting 1728 W 5363-0 0 - Task Lighting 0 W 0-0 0 - Electric Equipment 502 W 1644-0 0 - People 13 2590 2070 0 0 0 Infiltration - 0 0-0 0 Miscellaneous - 0 0-0 0 Safety Factor 0% / 0% 0 0 0% 0 0 >> Total Zone Loads - 23951 2070-8413 0 Zone Conditioning - 25885 2070-8420 0 Plenum Wall Load 0% 0-0 0 - Plenum Roof Load 0% 0-0 0 - Plenum Lighting Load 0% 0-0 0 - Return Fan Load 1586 CFM 0-1586 CFM 0 - Ventilation Load 200 CFM 2996 7042 200 CFM 5184 0 Supply Fan Load 1586 CFM 588-1586 CFM -588 - Space Fan Coil Fans - 0 - - 0 - Duct Heat Gain / Loss 0% 0-0% 0 - >> Total System Loads - 29469 9112-13016 0 Central Cooling Coil - 35298 9112-0 0 Central Heating Coil - -5829 - - 13016 - >> Total Conditioning - 29469 9112-13016 0 Key: Positive values are clg loads Positive values are htg loads Negative values are htg loads Negative values are clg loads Hourly Analysis Program v4.80 Page 6 of 6