BS /1000V XLPE Insulation LSZH Sheath Cables

Similar documents
Photovoltaic Cables EN H1Z2Z2-K

600/1000V XLPE Insulated, LSZH Sheathed, Double steel tape Armoured Power Cables (3 Cores)

600/1000V XLPE Insulated, PVC Sheathed, Armoured Power Cables (Multicore)

600/1000V SR Insulated Flexibles Control Cables (2-4 Cores & Multicores)

FIRE RESISTANT CABLES FP300

Flame Retardant Overall Screened Instrumentation Cables (multicore)

Caledonian Fire resistant Coaxial Cables

Caledonian Flame Retardant Coaxial Cables

FIRE RESISTANT CABLES FP200 GOLD

Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design.

IEC ; EN ; DIN VDE ; CEI 20-37/2-1 ; BS * No Corrosive Gas Emission

AFUMEX LSX LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 PRODUCT DATASHEET & APPLICATIONS GUIDE KEY BENEFITS:

AFUMEX LSX BASEC APPROVED LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 PRODUCT DATASHEET & APPLICATIONS GUIDE KEY BENEFITS:

FIRE RESISTANT CABLES FP400

FIRE RESISTANT CABLES FP PLUS. New Generation. Now with enhanced Insudite TM insulation

Table of Contents. TELE-FONIKA KABLE SA (DMCC Branch). 4 TELE-FONIKA Kable Group 6 FLAME-X 950 SERIES 1 11 FLAME-X 950 SERIES 2

IEC ; EN ; DIN VDE ; CEI 20-37/2-1 ; BS * No Corrosive Gas Emission

High Performance LSZH Fire Resistant Cable

FIRE RESISTANT CABLES FP200 GOLD

Power Cables. Introduction 3 RV 4 RVMV 5 RVSV 6 RVFV 7. ELECWIRES 2 Page

All Prysmian FP400 cables are manufactured under an ISO 9001 Quality System certified by BASEC and LPCB.

Total Fire Solutions. Includes BS 8519 and the updated BS :

Catalogue Power Cables

FIRE PERFORMANCE CABLE

LSOH Flexible Cables

STANDARDS INSTALLATION. Certificate No 077m

ENHANCED FIRE PERFORMANCE CABLE

BS FP600 achieves the maximum 120 minute rating under the BS test conditions, which is required for fire fighting applications.

CONTENTS. Introduction Customer Service BS codes of practice BS Fire Performance Cable Selection Guide... 7

Fire Resistant Cables

Author Owner Issue Authority Name: Gordon MacKenzie Title: Senior Engineer Engineering Design and Standards

LV FIRE RESISTANT CABLES

Introduction.

Caledonian fire Resistant signal & Data cables

fire resistant cables

Multi-Core Fire Resistant Cable

Catalogue Telecommunication Cables INTRODUCCIÓN

Telecommunication Cables

Catalogue. Instrumentation & Control Cables

FIRE RESISTANT CABLES

PRODUCT CATALOGUE Norröna

INTRODUCTION. Our diverse range of world-class Specialty Insulated Wires and Cablesinclude: LV Cables -

GUARDIANTM QUALITY APPROVED CABLES. Cables Limited MADE IN IRELAND SINCE 1934 IDH CABLES LIMITED MECHANICALLY PROTECTED CABLES

FUMEGUARD TM QUALITY APPROVED CABLES. Cables Limited MADE IN IRELAND SINCE 1934 IDH CABLES LIMITED LOW SMOKE HALOGEN FREE CABLES

Tratos Railway Cables

Firetuf Cables ZERO HALOGEN, LOW SMOKE (0HLS ) CABLE

THE TRUE FIRE SURVIVAL CABLE

Firetuf Cables ZERO HALOGEN, LOW SMOKE (0HLS ) CABLE

Cable technology for highest safety requirements

Flexflame. Arctic Grade Cables for Extreme Conditions. Photo: Sakhalin Energy Investement Company Ltd.

Caledonian. FIREFLIX ire Resistant Coaxial Cables

The Quality Connection. BETAflam Fire Resistant Safety Cables

IEC UNE DESIGN. 1. Conductor. 2. Insulation. Cross-linked polyethylene (XLPE) 3. Outer sheath. Flexible PVC, black colour.

AFIREFENIX SZ1-K 0,6/1 kv PH120 (AS+)

LSOH Wiring Cables. LSOH Conduit Wire (HO7Z-R) Low Voltage (450/750 V) Cable Approvals. Key Applications. Conductor. Insulation. Core Identification

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

Compact Module. Category 6A FTP Cabling System 1.1

Flame Retardant EP/CPE POWER, CONTROL & INSTRUMENTATION CABLES

SAS Security and Alarm Safety Cables

Rolling Stock Cables.

Shipboard & Offshore Cables

Copper LAN cable. This specification describes the general requirements for AMP NETCONNECT* copper LAN cable.

LSZH Zero Halogen Cables

Traction Cable Radox 3 GKW

OIL & GAS INDUSTRY OTHER INDUSTRIES

SOLAR CABLES. Electric cables for solar PV installations

Fire alarm cables. for highest safety requirements TRADITION INNOVATION PASSION

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

Double insulated, electron-beam cross-linked, halogen free photovoltaic wire sunlight resistant. Single conductor, flame retardant insulation.

BS EN :2004. Test On Electric And Optical Fibre Cables Under Fire Conditions. WF Report Number. Date: 14 th November 2008.

BS EN :2004. Test On Electric And Optical Fibre Cables Under Fire Conditions. WF Report Number. Date: 14 th November 2008.

PERFORMANCE POLYMER SOLUTIONS

Havells Fire Survival Cables

Firetuf OFC-UT-CST Fire resistant Armoured Central Tube Cable, variant in red

More than Just a Cable Supplier

CORFLEX. TYPE MC-HL & MV-105 or MC-HL OIL & GAS CABLES

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

PHOTOVOLTAIC CABLES. Photovoltaic Cable 2000V/1500V Photovoltaic Cable 2000V/1000V

PolyOne is a global polymer solutions provider with the ability to meet regulatory and product

SPECIAL ELECTRICAL AND OPTICAL CABLES

BS EN : Measurements Of Smoke Density Of Electric Cables. WF Report Number. Date: 17 th November Test Sponsor:

Sensor and transducer cables

DNVGL-CP-0399 Edition March 2016

Firetuf OFC-UT-CST Fire resistant Armoured Central Tube Cable, variant in red

CIR CRUSH & IMPACT RESISTANT ARCTIC GRADE OIL & GAS CABLES

CORFLEX TYPE MC-HL POWER, CONTROL & INSTRUMENTATION CABLES

CIR AG Power Cables. CIR AG Control Cable. CIR Type VFD Cable. CIR AG Ratings & Approvals. n UL Listed as Type TC-ER n UL Listed as TC-ER-HL (E123629)

TELECOM SOLUTIONS CABLE CATALOGUE INNOVATIVE FIBRE OPTIC CABLE SOLUTIONS


Industrial Fiber Optic Cables, LSZH Corrugated Armored Cable, Fibers

CIR CRUSH & IMPACT RESISTANT OIL & GAS CABLES

THE INNOVATIVE CABLE PRODUCER INSTRUMENTATION CABLES FOR THE INDUSTRY - AND PLANT CONSTRUCTION

WHAT MAKES PRYSMIAN CABLES DIFFERENT?

CABLES FOR ALARM AND SAFETY SYSTEMS

DNVGL-CP-0401 Edition February 2016

UNIKA Universal Cable Cable Specialist

Requirements for Electrical Installations

System Circuit integrity in the event of fire. Safety cables and systems from a pro. Cabling Solutions

Power Control Cable Iec

Firecel Safety Cables

Transcription:

BS 8573 600/1000V XLPE Insulation LSZH Sheath Cables Caledonian www.addison-cables.com

Company Profile Caledonian & Addison, branded under Caledoniea & Addimax, established in 1978, offers one of the most complete lines of fiber and copper cabling solutions with over hundreds of different cabling system products. Our superior products provide leading edge within every cable series and for every application. Among the national and international standards with which our cables could comply are: BS-British Standard; LPCB Fire Performance Standard. ISO Standard etc. Caledonian & Addison offers a comprehensive stock of cables and cabling products through its nationwide network of resellers and distributors. Caledonian & Addison has continually expanded its global presence in Europe and Asia. Caledonian & Addison produces a wide range of cables for communication. power and electronics in its primary plants in UK. Turkey. Malaysia. Italy and Spain. To stay in front, we continually keep expanding our manufacturing capabilities in more low cost region such as China, Malaysia etc. This low-cost manufacturing facilities enable us provide a flexible scalable global system that delivers superior operational performance and optimal results for our customers. Our extensive global network of manufacturing facilities gives us significant scale and the flexibility to fulfill our customer requirements. This global presence provides design and consultancy solutions that are combined with core cable manufacturing, logistic services and vertically integrated with our E commerce technologies, to optimize customer operations by lowering costs and reducing time to market. Caledonian & Addison has been respected for its high standards of quality, excellent service level, competitive pricing and a unique and innovative spirit. With our latest technologies, we are both inspired and well-positioned to meet the changing needs of our customers. We have the resources to diversify and to enhance our product lines and services. We understand the need for change and with our accurate planning. we are ready for the future and the promise of new marketing opportunities. Our tradition of growth through excellence is assured. Our Design Centers work closely with customers to constantly improve its standard range of products and technologies and to develop customized, country and industryspecific solutions. Caledonian & Addison has established an extensive network of design, manufacturing, and logistics facilities in the world s major markets to serve the growing outsourcing needs of both multinational and regional customers.

Table of Content»» Single Core 600/1000V XLPE Insulation, LSZH Sheath Cables to BS 8573...2»» Two-core 600/1000V XLPE Insulation, LSZH Sheath Cables to BS 8573...5»» Three-core 600/1000V XLPE Insulation, LSZH Sheath Cables to BS 8573...8»» Four-core 600/1000V XLPE Insulation, LSZH Sheath Cables to BS 8573...11 Five-core 600/1000V XLPE Insulation, LSZH Sheath»» Cables to BS 8573...14

BS 8573 XLPE Insulation, LSZH Sheath Cables Single Core 600/1000V XLPE Insulation, LSZH Sheath Cables to BS 8573 XLPE Insulation Copper LSZH Sheath application These XLPE insulated and LSZH sheathed cables are generally used for fi xed installation. Suitable for building wiring, especially in areas where smoke and fume emissions may cause a potential threat to life but not for burial in the ground, either directly or in ducts. STaNDaRD Basic design to BS 8573:2012 FIRE PERFORMaNCE Flame Retardance (Single Vertical Wire Test) BS EN 60332-1-2:2004 Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) BS EN 60332-3-24:2009 (cat. C) Halogen Free BS EN 50267-2-1 Minimum Smoke Emission BS EN 61034-2 Spark Test BS EN 62230 VOLTaGE RaTING 600/1000V CaBLE CONSTRUCTION : Annealed copper conductor, strand according to BS EN 60228 class 2. 2

Insulation: XLPE type GP8 according to BS 7655-1.3. HEPR type GP6 according to BS 7655-1.2, or crosslinked polyolefi n material type EI 5 according to BS EN 50363-5 can be offered as option. Inner Covering option: The laid up cores may be coverd by an optional extrued inner covering or separating tape. It shall be possible to separate the cores easily. Outer Sheath: Thermoplastic LSZH type LTS 4 according to BS 7655-6.1. Outer Sheath option: UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. COLOUR CODE Insulation Colour: Brown or blue Sheath Colour: Black, other colours can be offered upon request. Physical AND THERMAL PROPERTIES Maximum temperature range during operation (XLPE): 90 C Maximum short circuit temperature (5 Seconds): 250 C Minimum bending radius: Circular copper conductors(up to 25mm 2 ): 4 x Overall Diameter Circular copper conductors(above 25mm 2 ): 6 x Overall Diameter Shaped copper conductors: 8 x Overall Diameter CONSTRUCTION PARAMETERS No. of CoresxCross Section Class of Insulation Inner Covering Sheath No.xmm 2 mm mm mm 1x1.5 2 0.7 0.4 1.4 1x2.5 2 0.7 0.4 1.4 1x4.0 2 0.7 0.4 1.4 1x6.0 2 0.7 0.4 1.4 1x10 2 0.7 0.4 1.4 1x16 2 0.7 0.4 1.4 1x25 2 0.9 0.4 1.4 1x35 2 0.9 0.4 1.4 1x50 2 1.0 0.6 1.4 1x70 2 1.1 0.6 1.4 1x95 2 1.1 0.6 1.5 1x120 2 1.2 0.8 1.5 3

BS 8573 XLPE Insulation, LSZH Sheath Cables No. of CoresxCross Section Class of Insulation Inner Covering Sheath No.xmm 2 mm mm mm 1x150 2 1.4 0.8 1.6 1x185 2 1.6 0.8 1.6 1x240 2 1.7 1.0 1.7 1x300 2 1.8 1.0 1.8 1x400 2 2.0 1.2 1.9 1x500 2 2.2 1.2 2.0 1x630 2 2.4 1.4 2.2 1x800 2 2.6 1.6 2.3 1x1000 2 2.8 1.6 2.4 BS 8573 N Standard 4

Two-core 600/1000V XLPE Insulation, LSZH Sheath Cables to BS 8573 LSZH Sheath Copper XLPE Insulation application These XLPE insulated and LSZH sheathed cables are generally used for fi xed installation. Suitable for building wiring, especially in areas where smoke and fume emissions may cause a potential threat to life but not for burial in the ground, either directly or in ducts. STaNDaRD Basic design to BS 8573:2012 FIRE PERFORMaNCE Flame Retardance (Single Vertical Wire Test) BS EN 60332-1-2:2004 Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) BS EN 60332-3-24:2009 (cat. C) Halogen Free BS EN 50267-2-1 Minimum Smoke Emission BS EN 61034-2 Spark Test BS EN 62230 VOLTaGE RaTING 600/1000V CaBLE CONSTRUCTION : Annealed copper conductor, strand according to BS EN 60228 class 2. Insulation: XLPE type GP8 according to BS 7655-1.3. HEPR type GP6 according to BS 7655-1.2, or crosslinked polyolefi n material type EI 5 according to BS EN 50363-5 can be offered as option. Inner Covering option: The laid up cores may be coverd by an optional extrued inner covering or 5

BS 8573 XLPE Insulation, LSZH Sheath Cables separating tape. It shall be possible to separate the cores easily. Outer Sheath: Thermoplastic LSZH type LTS 4 according to BS 7655-6.1. Outer Sheath option: UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. COLOUR CODE Insulation Colour: Brown and blue Sheath Colour: Black, other colours can be offered upon request. Physical AND THERMAL PROPERTIES Maximum temperature range during operation (XLPE): 90 C Maximum short circuit temperature (5 Seconds): 250 C Minimum bending radius: Circular copper conductors(up to 25mm 2 ): 4 x Overall Diameter Circular copper conductors(above 25mm 2 ): 6 x Overall Diameter Shaped copper conductors: 8 x Overall Diameter CONSTRUCTION PARAMETERS No. of CoresxCross Section Class of Insulation Inner Covering Sheath No.xmm 2 mm mm mm 2x1.5 2 0.7 0.4 1.8 2x2.5 2 0.7 0.4 1.8 2x4.0 2 0.7 0.4 1.8 2x6.0 2 0.7 0.4 1.8 2x10 2 0.7 0.6 1.8 2x16 2 0.7 0.6 1.8 2x25 2 0.9 0.8 1.8 2x35 2 0.9 0.8 1.8 2x50 2 1.0 1.0 1.8 2x70 2 1.1 1.0 1.8 2x95 2 1.1 1.2 1.9 2x120 2 1.2 1.2 2.0 2x25 2 0.9 0.6 1.8 2x35 2 0.9 0.6 1.8 2x50 2 1.0 0.8 1.8 6

No. of CoresxCross Section Class of Insulation Inner Covering Sheath No.xmm 2 mm mm mm 2x70 2 1.1 0.8 1.8 2x95 2 1.1 1.0 1.9 2x120 2 1.2 1.0 2.0 BS 8573 N Standard 7

BS 8573 XLPE Insulation, LSZH Sheath Cables Three-core 600/1000V XLPE Insulation, LSZH Sheath Cables to BS 8573 LSZH Sheath XLPE Insulation Copper application These XLPE insulated and LSZH sheathed cables are generally used for fi xed installation. Suitable for building wiring, especially in areas where smoke and fume emissions may cause a potential threat to life but not for burial in the ground, either directly or in ducts. STaNDaRD Basic design to BS 8573:2012 FIRE PERFORMaNCE Flame Retardance (Single Vertical Wire Test) BS EN 60332-1-2:2004 Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) BS EN 60332-3-24:2009 (cat. C) Halogen Free BS EN 50267-2-1 Minimum Smoke Emission BS EN 61034-2 Spark Test BS EN 62230 VOLTaGE RaTING 600/1000V CaBLE CONSTRUCTION : Annealed copper conductor, strand according to BS EN 60228 class 2. Insulation: XLPE type GP8 according to BS 7655-1.3. HEPR type GP6 according to BS 7655-1.2, or crosslinked polyolefi n material type EI 5 according to BS EN 50363-5 can be offered as option. 8

Inner Covering option: The laid up cores may be coverd by an optional extrued inner covering or separating tape. It shall be possible to separate the cores easily. Outer Sheath: Thermoplastic LSZH type LTS 4 according to BS 7655-6.1. Outer Sheath option: UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. COLOUR CODE Insulation Colour: Brown, black and grey, Sheath Colour: Black, other colours can be offered upon request. Physical AND THERMAL PROPERTIES Maximum temperature range during operation (XLPE): 90 C Maximum short circuit temperature (5 Seconds): 250 C Minimum bending radius: Circular copper conductors(up to 25mm 2 ): 4 x Overall Diameter Circular copper conductors(above 25mm 2 ): 6 x Overall Diameter Shaped copper conductors: 8 x Overall Diameter CONSTRUCTION PARAMETERS No. of CoresxCross Section Class of Insulation Inner Covering Sheath No.xmm 2 mm mm mm 3x1.5 2 0.7 0.4 1.8 3x2.5 2 0.7 0.4 1.8 3x4.0 2 0.7 0.4 1.8 3x6.0 2 0.7 0.4 1.8 3x10 2 0.7 0.6 1.8 3x16 2 0.7 0.6 1.8 3x25 2 0.9 0.8 1.8 3x35 2 0.9 0.8 1.8 3x50 2 1.0 1.0 1.8 3x70 2 1.1 1.2 1.9 3x95 2 1.1 1.2 2.0 3x120 2 1.2 1.2 2.1 3x25 2 0.9 0.6 1.8 9

BS 8573 XLPE Insulation, LSZH Sheath Cables No. of CoresxCross Section Class of Insulation Inner Covering Sheath No.xmm 2 mm mm mm 3x35 2 0.9 0.8 1.8 3x50 2 1.0 0.8 1.8 3x70 2 1.1 1.0 1.9 3x95 2 1.1 1.2 2.0 3x120 2 1.2 1.2 2.1 BS 8573 N Standard 10

Four-core 600/1000V XLPE Insulation, LSZH Sheath Cables to BS 8573 LSZH Sheath XLPE Insulation Copper application These XLPE insulated and LSZH sheathed cables are generally used for fi xed installation. Suitable for building wiring, especially in areas where smoke and fume emissions may cause a potential threat to life but not for burial in the ground, either directly or in ducts. STaNDaRD Basic design to BS 8573:2012 FIRE PERFORMaNCE Flame Retardance (Single Vertical Wire Test) BS EN 60332-1-2:2004 Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) BS EN 60332-3-24:2009 (cat. C) Halogen Free BS EN 50267-2-1 Minimum Smoke Emission BS EN 61034-2 Spark Test BS EN 62230 VOLTaGE RaTING 600/1000V CaBLE CONSTRUCTION : Annealed copper conductor, strand according to BS EN 60228 class 2. Insulation: XLPE type GP8 according to BS 7655-1.3. HEPR type GP6 according to BS 7655-1.2, or 11

BS 8573 XLPE Insulation, LSZH Sheath Cables crosslinked polyolefi n material type EI 5 according to BS EN 50363-5 can be offered as option. Inner Covering option: The laid up cores may be coverd by an optional extrued inner covering or separating tape. It shall be possible to separate the cores easily. Outer Sheath: Thermoplastic LSZH type LTS 4 according to BS 7655-6.1. Outer Sheath option: UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. COLOUR CODE Insulation Colour: Blue, brown black and grey, Alternatively, green-and-yellow, brown, black, grey Sheath Colour: Black, other colours can be offered upon request. Physical AND THERMAL PROPERTIES Maximum temperature range during operation (XLPE): 90 C Maximum short circuit temperature (5 Seconds): 250 C Minimum bending radius: Circular copper conductors(up to 25mm 2 ): 4 x Overall Diameter Circular copper conductors(above 25mm 2 ): 6 x Overall Diameter Shaped copper conductors: 8 x Overall Diameter CONSTRUCTION PARAMETERS No. of CoresxCross Section Class of Insulation Inner Covering Sheath No.xmm 2 mm mm mm 4x1.5 2 0.7 0.4 1.8 4x2.5 2 0.7 0.4 1.8 4x4.0 2 0.7 0.4 1.8 4x6.0 2 0.7 0.6 1.8 4x10 2 0.7 0.6 1.8 4x16 2 0.7 0.6 1.8 4x25 2 0.9 0.8 1.8 4x35 2 0.9 1.0 1.8 4x50 2 1.0 1.0 1.8 4x70 2 1.1 1.2 2.0 4x95 2 1.1 1.2 2.1 12

No. of CoresxCross Section Class of Insulation Inner Covering Sheath No.xmm 2 mm mm mm 4x120 2 1.2 1.2 2.3 4x25 2 0.9 0.8 1.8 4x35 2 0.9 0.8 1.8 4x50 2 1.0 1.0 1.8 4x70 2 1.1 1.2 2.0 4x95 2 1.1 1.2 2.1 4x120 2 1.2 1.2 2.3 BS 8573 N Standard 13

BS 8573 XLPE Insulation, LSZH Sheath Cables Five-core 600/1000V XLPE Insulation, LSZH Sheath Cables to BS 8573 LSZH Sheath XLPE Insulation Copper application These XLPE insulated and LSZH sheathed cables are generally used for fi xed installation. Suitable for building wiring, especially in areas where smoke and fume emissions may cause a potential threat to life but not for burial in the ground, either directly or in ducts. STaNDaRD Basic design to BS 8573:2012 FIRE PERFORMaNCE Flame Retardance (Single Vertical Wire Test) BS EN 60332-1-2:2004 Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) BS EN 60332-3-24:2009 (cat. C) Halogen Free BS EN 50267-2-1 Minimum Smoke Emission BS EN 61034-2 Spark Test BS EN 62230 VOLTaGE RaTING 600/1000V CaBLE CONSTRUCTION : Annealed copper conductor, strand according to BS EN 60228 class 2. 14

Insulation: XLPE type GP8 according to BS 7655-1.3. HEPR type GP6 according to BS 7655-1.2, or crosslinked polyolefi n material type EI 5 according to BS EN 50363-5 can be offered as option. Inner Covering option: The laid up cores may be coverd by an optional extrued inner covering or separating tape. It shall be possible to separate the cores easily. Outer Sheath: Thermoplastic LSZH type LTS 4 according to BS 7655-6.1. Outer Sheath option: UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. COLOUR CODE Insulation Colour: Green and yellow, blue, brown black, grey. Sheath Colour: Black, other colours can be offered upon request. Physical AND THERMAL PROPERTIES Maximum temperature range during operation (XLPE): 90 C Maximum short circuit temperature (5 Seconds): 250 C Minimum bending radius: Circular copper conductors(up to 25mm 2 ): 4 x Overall Diameter Circular copper conductors(above 25mm 2 ): 6 x Overall Diameter Shaped copper conductors: 8 x Overall Diameter CONSTRUCTION PARAMETERS No. of CoresxCross Section Class of Insulation Inner Covering Sheath No.xmm 2 mm mm mm 5x1.5 2 0.7 0.4 1.8 5x2.5 2 0.7 0.4 1.8 5x4.0 2 0.7 0.6 1.8 5x6.0 2 0.7 0.6 1.8 5x10 2 0.7 0.6 1.8 5x16 2 0.7 0.8 1.8 5x25 2 0.9 1.0 1.8 5x35 2 0.9 1.0 1.8 5x50 2 1.0 1.2 1.9 5x70 2 1.1 1.2 2.1 5x95 2 1.1 1.4 2.2 15

BS 8573 XLPE Insulation, LSZH Sheath Cables No. of CoresxCross Section Class of Insulation Inner Covering Sheath No.xmm 2 mm mm mm 5x120 2 1.2 1.4 2.4 BS 8573 N Standard 16

Technical Reference Resistance No. of CoresxCross Section Min. no. of wires in the conductor Max. resistance of conductor@20 C Circular Circular Compacted Shaped Annealed copper conductor mm 2 CU CU CU plain wires Metal-coated wires 1.5 7 6-12,1 12,2 2.5 7 6-7,41 7,56 4.0 7 6-4,61 4,70 6.0 7 6-3,08 3,11 10 7 6-1,83 1,84 16 7 6-1,15 1,16 25 7 6 6 0,727 0,734 35 7 6 6 0,524 0,529 50 19 6 6 0,387 0,391 70 19 12 12 0,268 0,270 95 19 15 15 0,193 0,195 120 37 18 18 0,153 0,154 150 37 18 18 0,124 0,126 185 37 30 30 0,0991 0,100 240 37 34 34 0,0754 0,0762 300 61 34 34 0,0601 0,0607 400 61 53 53 0,0470 0,0475 500 61 53 53 0,0366 0,0369 630 91 53 53 0,0283 0,0286 800 91 53-0,0221 0,0224 1000 91 53-0,0176 0,0177 17

BS 8573 XLPE Insulation, LSZH Sheath Cables Electrical Properties Operating Temperature : 90 C Ambient Temperature : 30 C Current-Carrying Capacities (Amp) Single-core 90 C thermosetting insulated unarmoured, with or without sheath Reference Method A Reference Reference Method (enclosed in Method B F (in free air or on a conduit in (enclosed in Reference Method perforated cable tray, thermally conduit on C (clipped direct) horizontal or vertical insulating wall a wall or in etc) etc) trunking etc) Touching crosssectional area 2 singlephase a.c. or d.c. 3 or 4 three -phase a.c. 2 singlephase a.c. or d.c 3 or 4 threephase a.c. 2 singlephase a.c. or d.c. flat and touching 3 or 4 threephase a.c. flat and touching or trefoil 2 singlephase a.c. or d.c. flat 3 threephase a.c. flat 3 threephase a.c. trefoil Reference Method G (in free air) Spaced by one cable diameter 2 singlephase a.c. or d.c. or 3 cables threephase a.c. flat Horizontal Vertical 1 2 3 4 5 6 7 8 9 10 11 12 mm 2 A A A A A A A A A A A 1.5 19 17 23 20 25 23 - - - - - 2.5 26 23 31 28 34 31 - - - - - 4.0 35 31 42 37 46 41 - - - - - 6.0 45 40 54 48 59 54 - - - - - 10 61 54 75 66 81 74 - - - - - 16 81 73 100 88 109 99 - - - - - 25 106 95 133 117 143 130 161 141 135 182 161 35 131 117 164 144 176 161 200 176 169 226 201 50 158 141 198 175 228 209 242 216 207 275 246 70 200 179 253 222 293 268 310 279 268 353 318 95 241 216 306 269 355 326 377 342 328 430 389 120 278 249 354 312 413 379 437 400 383 500 454 150 318 285 393 342 476 436 504 464 444 577 527 185 362 324 449 384 545 500 575 533 510 661 605 240 424 380 528 450 644 590 679 634 607 781 719 300 486 435 306 514 743 681 783 736 703 902 833 400 - - 383 584 868 793 940 868 823 1085 1008 500 - - 783 666 990 904 1083 998 946 1253 1169 630 - - 900 764 113 1033 1254 1151 1088 1454 1362 800 - - - - 1288 1179 1358 1275 1214 1581 1485 18

crosssectional area Reference Method A (enclosed in conduit in thermally insulating wall etc) 2 singlephase a.c. or d.c. 3 or 4 three -phase a.c. Reference Method B (enclosed in conduit on a wall or in trunking etc) 2 singlephase a.c. or d.c 3 or 4 threephase a.c. Reference Method C (clipped direct) 2 singlephase a.c. or d.c. flat and touching 3 or 4 threephase a.c. flat and touching or trefoil Reference Method F (in free air or on a perforated cable tray, horizontal or vertical etc) Touching 2 singlephase a.c. or d.c. flat 3 threephase a.c. flat 3 threephase a.c. trefoil Reference Method G (in free air) Spaced by one cable diameter 2 singlephase a.c. or d.c. or 3 cables threephase a.c. flat Horizontal Vertical 1 2 3 4 5 6 7 8 9 10 11 12 mm 2 A A A A A A A A A A A 1000 - - - - 1443 1323 1520 1436 1349 1775 1671 Multicore 90 C thermosetting insulated and thermoplastic sheathed unarmoured crosssectional area Reference Method A (enclosed in conduit in Reference Method B thermally insulating wall (enclosed in conduit on etc) a wall or in trunking etc) 1 two-core cable, singlephase a.c. or d.c. 1 three- or four-core cable, three -phase a.c. 1 two-core cable, singlephase a.c. or d.c. 1 three- or four-core cable, three -phase a.c. Reference Method C (clipped direct) 1 two-core cable, singlephase a.c. or d.c. 1 three- or four-core cable, three -phase a.c. Reference Method E (free air or on a perforated cable tray etc. horizontal or vertical) 1 two-core cable, singlephase a.c. or d.c. 1 three- or four-core cable, three -phase a.c. 1 2 3 4 5 6 7 8 9 mm 2 A A A A A A A A 1.5 18.5 16.5 22 19.5 24 22 26 23 2.5 25 22 30 26 33 30 36 32 4.0 33 30 40 35 45 40 49 42 6.0 42 38 51 44 58 52 63 54 10 57 51 69 60 80 71 86 75 16 76 68 91 80 107 96 115 100 25 99 89 119 105 138 119 149 127 35 121 109 146 128 171 147 185 158 50 145 130 175 154 209 179 225 192 70 183 164 221 194 269 229 289 246 95 220 197 265 233 328 278 352 298 120 253 227 305 268 382 322 410 346 19

BS 8573 XLPE Insulation, LSZH Sheath Cables Voltage Drop (Per Amp Per Meter) Single-core 90 C thermosetting insulated unarmoured, with or without sheath Cross Section Area 2 cables d.c. Ref. Methods A and B (enclosed in conduit or trunking) 1 2 3 2 single-phase a.c. 3 or 4 three-phase a.c. Ref. Methods C, F&G(clipped direct, on trays or in free air) Cables touching 4 Cables spaced*5 Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall) Ref. Methods C, F&G (clipped direct, on trays or in free air) Cables touching, Trefoil Cables touching, Flat Cables spaced*, Flat 6 7 8 9 mm 2 mv/a/m mv/a/m mv/a/m mv/a/m mv/a/m mv/a/m mv/a/m mv/a/m 1.0 46 46 46 46 40 40 40 40 1.5 31 31 31 31 27 27 27 27 2.5 19 19 19 19 16 16 16 16 4.0 12 12 12 12 10 10 10 10 6.0 7.9 7.9 7.9 7.9 6.8 6.8 6.8 6.8 10 4.7 4.7 4.7 4.7 4.0 4.0 4.0 4.0 16 2.9 2.9 2.9 2.9 2.5 2.5 2.5 2.5 r x z r x z r x z r x z r x z r x z r x z 25 1.85 1.85 0.31 1.90 1.85 0.190 1.85 1.85 0.28 1.85 1.60 0.27 1.65 1.60 0.165 1.60 1.60 0.190 1.60 1.60 0.27 1.65 35 1.35 1.35 0.29 1.35 1.35 0.180 1.35 1.35 0.27 1.35 1.15 0.25 1.15 1.15 0.155 1.15 1.15 0.180 1.15 1.15 0.26 1.20 50 0.99 1.00 0.29 1.05 0.99 0.180 1.00 0.99 0.27 1.00 0.87 0.25 0.90 0.86 0.155 0.87 0.86 0.180 0.87 0.86 0.26 0.89 70 0.68 0.70 0.28 0.75 0.68 0.175 0.71 0.68 0.26 0.73 0.60 0.24 0.65 0.59 0.150 0.61 0.59 0.175 0.62 0.59 0.25 0.65 95 0.49 0.51 0.27 0.58 0.49 0.170 0.52 0.49 0.26 0.56 0.44 0.23 0.50 0.43 0.145 0.50 0.43 0.170 0.45 0.43 0.25 0.49 120 0.39 0.41 0.26 0.48 0.39 0.165 0.43 0.39 0.25 0.47 0.35 0.23 0.42 0.34 0.140 0.37 0.34 0.165 0.38 0.34 0.24 0.42 150 032 0.33 0.26 0.43 0.32 0.165 0.36 0.32 0.25 0.41 0.29 0.23 0.37 0.28 0.140 0.31 0.28 0.165 0.32 0.28 0.24 0.37 185 0.25 0.27 0.26 0.37 0.26 0.165 0.30 0.25 0.25 0.36 0.23 0.23 0.32 0.22 0.140 0.26 0.22 0.165 0.28 0.22 0.24 0.33 240 0.190 0.21 0.26 0.33 0.20 0.160 0.25 0.195 0.25 0.31 0.185 0.22 0.29 0.170 0.140 0.22 0.170 0.165 0.24 0.170 0.24 0.29 300 0.155 0.175 0.25 0.31 0.160 0.160 0.22 0.155 0.25 0.29 0.150 0.22 0.27 0.140 0.140 0.195 0.135 0.160 0.21 0.135 0.24 0.27 400 0.120 0.140 0.25 0.29 0.130 0.155 0.20 0.125 0.24 0.27 0.125 0.22 0.25 0.110 0.135 0.175 0.110 0.1600.195 0.110 0.24 0.26 500 0.093 0.120 0.25 0.28 0.105 0.155 0.185 0.098 0.24 0.26 0.100 0.22 0.24 0.090 0.135 0.160 0.088 0.1600.180 0.085 0.24 0.25 630 0.072 0.100 0.25 0.27 0.086 0.155 0.175 0.078 0.24 0.25 0.088 0.21 0.23 0.074 0.135 0.150 0.071 0.1600.170 0.068 0.23 0.24 800 0.056-0.072 0.150 0.170 0.064 0.24 0.25-0.062 0.130 0.145 0.059 0.1550.165 0.055 0.23 0.24 1000 0.045-0.063 0.150 0.165 0.054 0.24 0.24-0.055 0.130 0.140 0.050 0.1550.165 0.047 0.23 0.24 Note: *Spacings larger than one cable diameter will result in a large voltage drop. r = conductor resistance at operating temperature x = reactance z = impedance 20

Multicore 90 C thermosetting insulated and thermoplastic sheathed unarmoured Cross Section Area Two-core cable d.c. Two-core cable, single-phase a.c. Three- or four-core cable, three-phase a.c. 1 2 3 Cables touching 4 mm 2 mv/a/m mv/a/m mv/a/m 1.5 31 31 27 2.5 19 19 16 4 12 12 10 6 7.9 7.9 6.8 10 4.7 4.7 4.0 16 2.9 2.9 2.5 r x z r x z 25 1.85 1.85 0.160 1.90 1.60 0.140 1.65 35 1.35 1.35 0.155 1.35 1.15 0.135 1.15 50 0.98 0.99 0.155 1.00 0.86 0.135 0.87 70 0.67 0.67 0.150 0.69 0.59 0.130 0.60 95 0.49 0.50 0.150 0.52 0.43 0.130 0.45 120 0.39 0.40 0.145 0.42 0.34 0.130 0.37 Note: *Spacings larger than one cable diameter will result in a large voltage drop. r = conductor resistance at operating temperature x = reactance z = impedance 21

Address: Marchants Industrial Centre, Mill Lane, Laughton, Lewes, East Sussex, BN8 6AJ, UK Tel: 44(0) 207 4195087 Fax: 44(0) 207 8319489 E-mail:sales@caledonian-cables.co.uk