Modular Active. Chilled. Beams

Similar documents
KLIMA Active Chilled Beams

Chilled Beams. Getting a Warmer Reception

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

IDL20e (2 way discharge) IDS60e (4 way discharge) Inffusers. UDI (vertical discharge) Frequently Asked Questions

Chilled beam technology overview John Woollett 1, Jonas Åkesson 2 Swegon AB 1,2

MECHANICAL SERVICES 101. Ian White

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

NOVEMBER 2012 THE EUROPEAN EXPERIENCE

Chilled beams. TRACE 700 incorporates two chilled beam strategies: passive and active.

Active Chilled Beams

APPLICATION GUIDE BEAMS

DADANCO Technical Paper

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

Inffusers. idl20 (2 WAY) ids60 (4 WAY)

Chilled Beam and Radiant Cooling Basics. Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle

Units for suspended ceilings Type DID632

NEW AR-L AR-C AND HIGH-CAPACITY LINEAR COOLING PANELS. Higher energy efficiency. Increased thermal comfort

Temperature Control and Zoning of UFAD Systems

Active Chilled Beams. Technical Data Bulkhead-Mounted Concealed Model With Horizontal Coil and Auxiliary Drain Pan

PRODUCTS TAO TAO PRODUCT: ADVANCING THE SCIENCE OF AIR DISTRIBUTION. temperature ambient optimizer. Redefine your comfort zone.

Don t Turn Active Beams Into Expensive Diffusers

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

Dehumidifying with Dedicated Outdoor Air

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning

b.) Technical Information:

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

Technical Development Program

Pharmaceutical Facility Design

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN

ENERGY EFFICIENCY WITH SUPERIOR INDOOR AIR QUALITY

Engineering Guide VAV Diffusers. Please refer to the Price Engineer s HVAC Handbook for more information on VAV Diffusers.

Rittling Induction Units Catalog

7. MECHANICAL SYSTEM DESIGN

Do All DOAS Configurations Provide the Same Benefits?

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE

Ventilation and Humidity Control in Army Barracks Using DOAS for Better Indoor Air Quality and Energy Conservation

Chilled Beams in Labs Eliminating Reheat & Saving Energy on a Budget

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

Adding More Fan Power Can Be a Good Thing

terminal units only provide sensible cooling, a separate dehumidification system is usually needed.

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

Active Chilled Beams. Technical Data Concealed Ceiling Mounted Model With Vertical Coil and Integral Drain Pan

Appendices. Included in this section are

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas

Air magic NTD500 Neutral Temperature Dehumidifier Air magic HRV500 Heat Recovery Ventilation. designed for radiant cooling systems.

Standards and Guidelines. Presented by: Aric Murray December 12, 2014

VH Series B ENVIRO-STAC Vertical Hi-Rise Fan Coil Unit with Enhanced Humidity Control

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM

Performance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment

Halton Rex 600 Basic R6B - Active chilled beam

SEMCO CHILLED BEAMS INDOOR AIR QUALITY AND ENERGY SAVINGS FANLESS FILTERLESS SPACE CONDITIONING

Chilled Beam/Induction Unit

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

CHAPTER IV AIR DISTRIBUTION AND BALANCE

Chapter 6 ALL-AIR HVAC SYSTEMS 6.1 CONTEXT

Air Conditioning Clinic

The swirl comfort unit is a compact air-conditioning unit providing swirl jet air supply.

DERV / ERV DEHUMIDIFICATION & ENERGY RECOVERY V E N T I L A T O R U N I T S I N N O V AT I O N W I T H S T Y L E

Technical Assignment 3 11/15/04. Executive Summary

Summary Comparison of Simulation Program Features

HVAC Optimization with Cold Air Distribution

Alpha Aire. Dedicated Outdoor Air System, VAV, Air-Source Heat Pump with Energy Recovery. Engineering Guide Effective February 2018

CTI Sponsored Educational Program

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

REPRODUCTION/DISTRIBUTION IS PROHIBITED. Energy-Savings Strategies for. Rooftop

High-Performance VAV Systems

WHAT - HOW - WHY - WHERE PROTERCEILING RADIANT CHILLED CEILINGS COMFORT - EFFICIENCY - SAVINGS - AESTHETICS

Product Data. Features/Benefits. 36CBAC,AE,AF,AH,AQ,AN, PB,PD,PS Series Active and Passive Chilled Beams. 11 to 190 cfm

DESCRIPTION OF TECHNOLOGY

PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION

HVAC 101. H V A C S y s t e m s

ENGINEERING. Edition No. 13 October 2002

Effects of Kitchen Ventilation on Residential Dwellings

Jim Aswegan Chief Engineer

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

Capt. Tim s s Duct Design Mythbusters. The bitterness of poor quality is remembered long after the sweetness of low price is forgotten!

Swegon PACIFIC. Integrated chilled beam PACIFIC CHILLED BEAM KEY FIGURES

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc.

Rosemex Products 96 VENTILATION CLIMATAIR COMPARTMENT AIR HANDLING UNITS

Benefits Offered by Passive Dehumidification Wheel Speed Control

INSTALLATION & OPERATIONS MANUAL

HVAC: The Next. Variable-air-volume systems. Outside-the-box thinking suggests the integration of dedicated

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

A REASONABLE ALTERNATIVE TO CHILLED BEAMS Dan Int-Hout Chief Engineer

NON-REVERSING, 100% OUTSIDE AIR HEAT PUMP FOR HEATING AND COOLING

chilled beams Redefine your comfort zone.

SMART DUCT SYSTEM. Caution: Do not tamper with the unit or its controls. Call a qualified service technician.

Energy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE

Best Practices for Condensing Boilers

Halton Rex for Vario R6O - Variable air volume chilled beam

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH

Cooling and heating systems. Static cooling ceiling system SKS-5/3 for visible installation

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH

ASHRAE JOURNAL ON REHEAT

Dehumidification and ventilation for residential, industrial radiant systems and swimming pools

High Efficiency Heating and Cooling Systems for Community Colleges Kirk Mescher, PE, LEED AP Principal ICCCFO

Chilled Ceilings / Beams Working Principles & Applications

THERMAL ICE STORAGE: Application & Design Guide

Transcription:

Modular Active Chilled Beams

How Twa MAC Beams Work Primary air (100% outside air) is dehumidified to between 50-57 F dew point and is used to: control the latent requirements of the space, provide fresh air to the occupants, and pressurize the beam plenum. The primary air then passes through an array of formed nozzles along the length of the beam. The jets of air discharging from the nozzles cause room air (secondary air) to be drawn through the unit mounted coil via induction. The coil is serviced by chilled water which is maintained at 2-8 F above the dew point of the primary air. The localized recirculation of room air provides substantial sensible cooling to the space at exceptionally low acoustic signatures (NC18-NC26). As a result of the reduction in total fan power, and higher chilled water operating temperatures, the building HVAC operating cost can be reduced by as much as 50% compared to all-air systems. A 4 7/8" [125 mm] B G E D F C 23 3/4" [604 mm] A) 1 (25mm) standing duct collar for primary air. Duct run-out servicing unit is sized to limit air velocity 600 fpm. Balance of system duct work sized traditionally. B) Primary air plenum. (100% outside air) C) Secondary air. (room air) D) Unit mounted coil. (Two and/or four pipe available. Typical chilled water: 55-61 F, hot water: 85-115 F) E) Mixed air. (Induction ratio range = 3:1-6:1 depending on nozzle selection.) F) Discharge air (Typical Cooling: 63-66 F, Heating: 75-85 F). G) Adjustable mounting brackets. Unit quickly attaches to building structure via aircraft cable or threaded rod. 1 (Qty: 4) Due to the highly localized mixing within the beam, the temperature variations observed by the occupants are less than half of what would be expected with traditional air delivery systems. As a result, comfort levels are improved, and occupant complaints are minimized. Twa MAC Beams are available in three basic sizes which are designed to fit within a standard 2 wide T-bar ceiling grid, and can also be installed within a finished drywall ceiling (2 x4, 2 x6, 2 x8 ). Each module can be equipped with optional coil lengths, circuits, and induction nozzles, to suit the heating, ventilation, and air conditioning requirements of the space. 1 Seismic locations may require additional bracing. Providing high performance HVAC solutions for over 20 years

In a sea of available HVAC equipment options, Twa Panel Systems, Inc. with their experienced staff and agents can help guide you with your selection to one of the most efficient applied HVAC systems available today. Twa s Modular Active Chilled Beams (MAC Beams), were originally developed in Europe, and have helped to minimize building operating costs for more than a decade. In many cases, Twa MAC Beams allow building designers to use minimal ventilation air (100% outside air) to satisfy the total cooling requirements of the space. With Twa MAC Beams you can potentially Cut building operating costs by up to 50% Double the COP of the cooling plant Eliminate or reduce comfort complaints Minimize operating control costs Capture credits towards LEED certification for both Energy & Innovation Construction Details Optional Bomb-Bay doors for easy coil access and cleaning Attractive powder coat finish on exposed surfaces Room air enters through perforated access panel Various nozzles and coil lengths available to suit the space requirements. 1 Flange for duct connection. Opening sized to limit primary air velocity to 600 fpm Durable sheet metal construction Adjustable mounting brackets (Qty: 4) 1/2 copper piping connections, suitable for Sweat, Push-on or PEX terminations. Airtight plenum box (galvanized steel) Coils available for cool only, or heat/cool applications.

Twa Modular Active Chilled Beams Comfort, Operation & Energy Savings Installation/Controls Twa MAC Beams use only 100% fresh outside air. Absenteeism, and lost time is reduced as a result of a more comfortable environment. Using dedicated outside air systems allow for smaller MUA footprints and provide more affordable air-side energy recovery. The chilled water servicing the coil within the MAC Beam is maintained at 2-8 F above the dew point of the primary air, as a result, no condensate forms on the unit mounted coil. Acoustic signatures of MAC Beams are barely perceptible. In the case of a unit operating at 1 w.c., all nozzle sizes will yield no more than NC26. Lower duct static pressures, yield lower sound pressure levels. Twa MAC Beams can produce one ton of refrigeration with as little as 99 cfm. This ensures that the least amount of air is processed by the HVAC system, which in turn, optimizes fan energy usage. MAC Beams offer all the advantages of fan coils, yet require no: condensate drainage filters electrical service maintenance and provide comfort at up to half the operating cost. Buildings equipped with mixed-mode ventilation generally require dew point sensors installed on the chilled water supply lines, which help to prevent the formation of condensate on the unit mounted coil. MAC Beams can easily provide 110 Btuh/ft 2 of total cooling. Challenging sensible heat gains are no longer an additional fan burden. In typical HVAC applications, Twa MAC Beams require no more than 99-225 cfm/ton of cooling. A high induction ratio within the beam provides excellent room air mixing. Room air temperature variations are reduced, ventilation effectiveness is increased, and a comfortable air movement within the space is enjoyed by the occupants. Higher chilled water temperatures (55-61 F), and lower hot water temperatures (85-115 F) dramatically improve equipment efficiencies and potentially double the COP of the chiller plant compared to conventional operating temperatures. 2 The low overall requirement for system air fan horsepower allows for low velocity downstream ducting. As a result, frictional duct losses can be made negligible by slightly over-sizing only the duct work servicing the beams. ( 600 fpm for beam run-outs.) Chilled and hot water RESET allow the building automation system to optimize the comfort and energy costs of HVAC systems equipped with Twa MAC Beams. The approach between room and chilled water temperatures dictate the Beam s ability to absorb heat. The cooler the room, the less heat can be absorbed by the coil, and vice-versa. As such the Beam s capacity is selfregulating. The effect is linear. Mixing of primary and secondary air within the beams, produce warmer discharge air temperatures allowing flexible beam placement. High induction ratios of 3:1-6:1 ensure the least amount of ventilation air is used to cool/heat the occupied space; minimizing operating costs. Water-side economization is maintained with closed circuit fluid coolers, dry coolers or cooling towers. Where appropriate, mixed-mode ventilation also adds the possibility of additional energy savings. Geothermal and water-to-water heat pumps allow for the efficient management of heating/cooling loads within the building envelope. Two-position control valves can be used to manage the MAC Beam s capacity. Approximately 65-75% of the cooling effect is provided by the chilled water coil. The primary air continues to provide ventilation with no water flow to the coil, and the dehumidification effect remains. Two-position control valves are the most common and least costly control technique. By using Variable Air Volume (VAV) to reduce primary air to the beam, proportional capacity control, and additional fan savings are achieved. 2 Assuming the chiller plant has been decoupled from the MUA ventilation load.

INCREDIBLE AIR SIDE EFFICIENCY Twa MAC Beams generally require only: 99-225 CFM/Ton of cooling. 3 Duct Static Working Pressures As a result of efficient nozzle design, Twa MAC Beams optimize air turnover within the space, and require less primary air. Also known as induction diffusers, Twa MAC Beams can create a higher induction effect and consequently a greater total capacity with duct static pressures in the range of (0.5-1 w.c.); without generating excessive noise (NC18 - NC26). Some manufacturers prefer lower operating static pressures, because their nozzle design requires too much primary air and their beams generate too much noise to justify their use at higher pressures. However, the superior capacity benefit of a higher induction ratio is lost at these lower duct static pressures. Twa MAC Beams can operate with as little as 0.3 w.c. and can yield up to a 6:1 induction ratio. This allows the ventilation system to provide the least amount of outside air processing for the highest secondary cooling/heating capacity. Although fan energy is increased slightly, the increase in beam capacity generally offsets the effect. Secondary Capacity (W) 1 176 226 276 326 376 426 476 526 576 626 676 250 0.9 Plenum Pressure (in. W.C.) 0.8 0.7 0.6 0.5 0.4 200 150 100 Plenum Pressure (Pa) 0.3 0.2 50 600 800 1000 1200 1400 1600 1800 2000 2200 2400 Secondary Capacity (Btuh) B-Nozzle C-Nozzle A-Nozzle D-Nozzle Secondary Cooling Capacity of a 2 x4 Twa MAC Beam at 18 F approach. 3 In typical office HVAC applications, including building envelope humidity control.

Twa MAC Beam Quick Select (Cooling Only) Beam Coil Length 2 4 5 6 7 8 Air P (APD) w.c. Nozzle Type cfm / Total Capacity (Q T ) = Btuh A B C D 0.3 5.8 / 548 6.6 / 521 10.6 / 771 14.4 / 831 0.4 6.8 / 680 7.7 / 663 12.3 / 922 16.6 / 991 0.5 7.5/ 785 8.6 / 771 13.7 / 1034 18.5 / 1119 0.6 8.3 / 863 9.4 / 855 15.0 / 1128 20.3 / 1221 0.7 8.9 / 936 10.1 / 928 16.2 / 1214 21.9 / 1315 0.8 9.5 / 997 10.8 / 988 17.3 / 1293 23.4 / 1401 0.9 10.1 / 1054 11.5 / 1045 18.4 / 1367 24.9 / 1482 1.0 10.7 / 1107 12.1 / 1098 19.4 / 1426 26.2 / 1548 0.3 14.2 / 1354 16.6 / 1358 25.6 / 1850 36.2 / 2099 0.4 16.4 / 1653 19.1 / 1664 29.6 / 2152 41.8 / 2440 0.5 18.3 / 1866 21.4 / 1902 33.0 / 2406 46.7 / 2727 0.6 20.1 / 2047 23.4 / 2087 36.2 / 2617 51.2 / 2969 0.7 21.7 / 2199 25.3 / 2242 39.1 / 2811 55.3 / 3190 0.8 23.2 / 2338 27.0 / 2385 41.8 / 2989 59.1 / 3394 0.9 24.6 / 2467 28.7 / 2517 44.3 / 3132 62.7 / 3561 1.0 25.9 / 2588 30.2 / 2642 46.7 / 3286 66.1 / 3738 0.3 18.4 / 1728 21.1 / 1676 32.5 / 2289 46.8 / 2678 0.4 21.1 / 2103 24.3 / 2085 37.5 / 2686 54.1 / 3105 0.5 23.7 / 2368 27.2 / 2359 41.9 / 2998 60.4 / 3464 0.6 26.0 / 2593 29.8 / 2585 45.9 / 3256 66.2 / 3766 0.7 28.1 / 2781 32.2 / 2795 49.6 / 3493 71.5 / 4042 0.8 30.0 / 2953 34.4 / 2969 53.0 / 3709 76.4 / 4295 0.9 31.8 / 3112 36.5 / 3131 56.2 / 3884 81.1 / 4504 1.0 33.5 / 3261 38.4 / 3283 59.3 / 4071 85.5 / 4723 0.3 22.5 / 2092 25.8 / 2031 40.0 / 2777 58.0 / 3274 0.4 26.0 / 2537 29.8 / 2518 46.2 / 3250 67.0 / 3788 0.5 29.1 / 2851 33.3 / 2843 51.6 / 3619 74.9 / 4219 0.6 31.9 / 3116 36.5 / 3109 56.5 / 3926 82.1 / 4580 0.7 34.4 / 3337 39.4 / 3357 61.0 / 4205 88.7 / 4910 0.8 36.8 / 3539 42.1 / 3562 65.2 / 4460 94.8 / 5211 0.9 39.0 / 3726 44.7 / 3752 69.2 / 4667 100.5 / 5461 1.0 41.1 / 3900 47.1 / 3930 72.9 / 4887 106.0 / 5721 0.3 26.7 / 2508 30.5 / 2427 47.4 / 3369 68.0 / 3879 0.4 30.9 / 3045 35.3 / 3013 54.8 / 3902 78.6 / 4490 0.5 34.5 / 3424 39.4 / 3404 61.2 / 4348 87.8 / 5003 0.6 37.8 / 3745 43.2 / 3753 67.1 / 4718 96.2 / 5434 0.7 40.8 / 4012 46.6 / 4023 72.4 / 5055 103.9 / 5827 0.8 43.6 / 4256 49.8 / 4271 77.5 / 5364 111.1 / 6187 0.9 46.3 / 4482 52.9 / 4500 82.2 / 5613 117.8 / 6484 1.0 48.8 / 4693 55.7 / 4714 86.6 / 5879 124.2 / 6796 0.3 30.5 / 2871 34.8 / 2776 54.9 / 3911 78.6 / 4495 0.4 35.2 / 3488 40.2 / 3407 63.4 / 4532 90.8 / 5205 0.5 39.3 / 3925 44.9 / 3899 70.9 / 5052 101.5 / 5802 0.6 43.1 / 4294 49.2 / 4268 77.6 / 5483 111.2 / 6303 0.7 46.5 / 4602 53.2 / 4612 83.9 / 5876 120.1 / 6761 0.8 49.8 / 4883 56.8 / 4897 89.7 / 6236 128.4 / 7180 0.9 52.8 / 5144 60.3 / 5161 95.1 / 6527 136.2 / 7526 1.0 55.6 / 5387 63.5 / 5408 100.3 / 6837 143.6 / 7888 MACB Size Nom. Coil Length H 2 O GPM WPD ft. w.c. 2 x 4 2 0.60 2.50 4 1.00 1.60 2 x 6 5 1.00 1.90 6 1.00 2.20 2 x 8 7 1.25 4.00 8 1.50 6.50 Procedure: 1. Choose a working static pressure from column: APD P w.c. 2. Nozzles A and B provide more total cooling with less primary air (i.e. higher induction ratios). Nozzles C and D are generally used to address higher ventilation requirements. 3. Each value within a nozzle column represents a ventilation rate in cfm, followed by a total cooling capacity: Q T, in Btuh. Example: coil length = 4, APD = 0.6 w.c. This beam with an A nozzle would require 20.1 cfm, and produce a total cooling capability of Q T = 2047 Btuh. 4. Choose the quantity of coils required to satisfy the cooling and ventilation needs of the space. Coil lengths can be mixed however, each zone would share the same static pressure. 5. Shorter coils can be mounted in longer modules. 6. The latent cooling, or dehumidification capability of the beam (Q L ), can be calculated by equation 2.0, below. 7. The total sensible cooling capacity can be determined by subtracting Q L from Q T. 8. The equipment has been rated with water as the working fluid, at sea level altitude. 9. Typical acoustic impact = NC18 @ 0.5 w.c., NC26 @ 1 w.c. 10. Heating is also available with four-pipe MAC Beams. 11. Q PA = Sensible cooling effect provided via primary air. 12. Q S = Secondary sensible cooling effect provided via unit mounted coil. EQ 1.0 Q PA = 1.08 * cfm * (T Room -T PA ) EQ 2.0 Q L = 0.68 * cfm * (Gr Beam - Gr ) OC EQ 3.0 Q S = Q T - Q PA Table Parameters: Room design dry bulb temperature (T Room ) = 75 F Room design relative humidity = 50% Primary air temperature (T PA ) = 54 F Primary air dew point (T PADP ) = 52 F MAC Beam chilled water supply temp (EWT) = 58 F Assume typical office space requires (cfm/person) = 20 Beam s coil condensate threshold, grain ratio (Gr BEAM ) = 72.15 MUA off-coil grain ratio (Gr OC ) = 57.80 For more information on how MAC Beams can help to lower your building operating costs, please contact: USA Canada Radiant Advantage LLC Twa Panel Systems, Inc. 10253 Brentwood Circle 1201 4th St. Highlands Ranch, CO, 80126 Nisku, Alberta, Canada, T9E 7L3 Phone: (413) 262-2989 Phone: (780) 955-8757 Fax: (303) 777-8531 Fax: (780) 955-8696 email: mike@twapanels.ca email: darren@twapanels.ca www.twapanels.ca