Installation and operation manual DPC200 - DIFFERENTIAL PRESSURE CONTROLLER. Low pressure with PI-control-mode

Similar documents
Operating manual GTL 369 GTL 369M GTL 389 GTL 389M. Temperature probe. Please keep the manual for future use.

ORIGA-SENSOFLEX Displacement Measuring System for Cylinder Series OSP-P

Beck. The differential pressure transmitter for air

Analog Room Pressure Monitor RPC Series

SCHMIDT LED Measured Value Display MD Instructions for Use

Pressure sensors. Ex ia I / IIC T6 acc. to ATEX. Features. Description. Measuring ranges. Applications

Gas cylinder scale Model GCS-1

S304 and S305 Dust Emission Monitors. User Manual. Distributor

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

I/A Series 716C 1/16 DIN Temperature Controller

WIO200 Water In Oil measuring instrument

Instruction Manual. Alarm Unit For Low Gas Level # Read manual before use! Observe all safety information! Keep manual for future use!

Modus Model DA General Eastern Low Differential Pressure Alarm Controller

F4 Process Controller Installation and Operation Guide

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products

Differential Pressure and Flow Meter. Media 5 Indicator 160 Ø PN 50

FA compressed air plants (refrigeration/adsorption driers) - granulate driers - medical gases - non-corrosive gases, e. g.

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER

Digital Display DS 52 in wall housing. Order no

02/11/2015

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

Datasheet PDCSY-MW-MD. Technical Overview. Features. Product warranty and total quality commitment. Heat Meter Integrator

DS 96/48 P. Digital indicator. Short manual 41/33-89 EN Rev. 00 DIM

02/11/2015

UDC100 Universal Digital Controller Specifications

Advance Optima Module Magnos 17

More Precision. indusensor // Linear inductive displacement sensors

Sensor unit MC2 with analog output for Freon gases and refrigerants

Oxygen (O2) Single-Point Gas Detection System

More Precision. indusensor Linear inductive displacement sensors

Software Version 2.01 LEVEL MONITOR MODEL 220

AM1 alarm module. RESOL AM1 alarm module * * Mounting Connection Function. Manual

Hygro and Hygrothermal Transducers (Capacitive) for Air Conditioning Applications

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual

Installation and Operating instructions for. C9900-U battery pack. Version: 2.0 Date:

Dry Block Heater Operating Manual

MF-PFA ver 3.x. Micaflex PFA ver 3. Pressure- and Flow transmitter with alarmfunction. Installation- & Operation manual [Dok. id: mi-303gb_180528]

AM54. Armored Variable Area Flowmeter Series AM54331/32 Series AM54371/72/73/74 Series AM54431/32 Series AM54471/72/73/74

Differential pressure sensors

More Precision. indusensor // Linear inductive displacement sensors

UDC 700 Universal Digital Controllers and Indicator Specifications

More Precision. indusensor // Linear inductive displacement sensors

Series Temperature Controller Instruction Sheet

Rosemount 3490 Series

Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications

Duct Sensors. Siemens Building Technologies HVAC Products. Symaro. for relative humitidy (high accuracy) and temperature

89BSD Digital Output

DSF xx10.xx xhv Ex-Atex Hall Effect Single Channel Speed Sensor

Inductive Conductivity Measurement. Simultaneous display of conductivity/ resistance/salinity and temperature; large measurement symbol.

M-Sens 2. Online-Moisture Meter for Solids. Operating Instructions. SWR engineering Messtechnik GmbH

AutomationDirect PM24. Microprocessor - Based Process/Temperature Limit Controller. Operator s Manual. Technical Support.

R1000 / R1040 / R1080

OVEN INDUSTRIES, INC.

Danfoss gas detection units

Two-Channel Gas Controller

M-Sens 2. Online moisture measurement for solids. Operating Instructions. SWR engineering Messtechnik GmbH PART OF THE ENVEA GROUP

DSF xx15.xx xhv Ex-Atex Ex-Atex Certified Two wire Hall Effect Speed Sensor

MEAS CAL ALARM WASH CONF APT4000 CC ENCLOSURE TYPE 2

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications

DDS-SSENSOR - INSTALLATION MANUAL. Installation Manual DDS-S SENSOR

SITRANS T. SITRANS T Explosion protected temperature sensor. General information. Marking of the degree of protection. Range of uses.

4100S. The operation and functions described in this manual are available from Software Version 4100S onwards.

Duct Temperature Sensors

86BSD Digital Output

itemp RTD TMT 187 itemp TC TMT 188 Temperature head transmitter

Model D12-IR. Digital Gas Transmitter...

Toroidal Conductivity Transmitters Series APT4000 Specifications

Process Alarm Module RTA 421

Room Temperature Sensors

User manual CTX 300 CO 2

Flame Monitor for Multiple Burner Furnaces D-LE 603 D-UG 660

Room Sensors. Building Technologies HVAC Products ... Symaro. for relative humidity (high accuracy) and temperature

Safety. DANGER Indicates potentially fatal situations. WARNING Indicates possible danger to life and limb.

USER S MANUAL INTERSYSTEM PRESSURE TRANDUCER TYPE PM-22

Control Thermostat / Thermal Reset Limit Thermostat Combination of electromechanical TR and TW

Electronic Temperature Controller 70304,

Intrinsically Safe Pressure Transmitters for installation in hazardous locations Models IS-20-S, IS-21-S, IS-20-F, IS-21-F WIKA Datasheet IS-20

OPTIBAR DP 7060 Supplementary Instructions

Regulated Ex-Heater HEX with internal controller, HEX with external controller II 3 G II 3 D

ONX908PIT-V1-S1-F1/B Modulating Digital Thermostat

Ex SOLENOID / ALARM DRIVER. PRepower 5203B. Table of contents. Applications Safety instructions Technical characteristics...

Thermocouples and Resistance Thermometers

Danfoss gas detection unit Type GD Heavy Duty

Snifter ATEX22 VERSION. User Manual. Distributor

3-way switching valve

Operating instructions

for relative humidity and temperature

LOW PRESSURE Intrinsically Safe Transducer AST44LP

SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS

7NG , 7NG

MEAS CAL ALARM WASH CONF APT4000 TC

Sensor module. Operating instructions. Sensor module, Type 17-51P2-... Document No P2-7D0001 Version: 17 May 2011/Rev. 0

TER Active Room Temperature Sensor (Controller),

Static differential pressure measuring instruments. Pascal-ST/Z. for low measurement ranges Pa oder Pa

Operating Manual MS220DA

Instruction Manual. Electronic gas and smoke detector GRM

HT-1300 Series. Temperature and Humidity Duct Sensor. Product Bulletin. Power Supply VDC / 24 VAC. Humidity Accuracy 2.5% RH from 10 to 95% RH

QFM21... Duct sensors. Symaro. for relative humidity and temperature

Room Temperature Controller

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15

Transcription:

Installation and operation manual DPC200 - DIFFERENTIAL PRESSURE CONTROLLER Low pressure with PI-control-mode

Manufacturer: Phone: Fax: E-Mail: Website: Issue: Doc.-no.: Arthur Grillo GmbH Am Sandbach 7 40878 Ratingen +49 21 02-47 10 22 +49 21 02-47 58 82 info@grillo-messgeraete.de www.grillo-messgeraete.de www.sensor-store.de 12/2015 DPC200_001_EBM_UK This documentation including all parts is protected by copyright. Any utilisation or modification other than permissible under the strict limitations of copyright law is prohibited and liable to prosecution without the approval of the Arthur Grillo GmbH. This applies in particular to duplications, translations, microfilming and storage and processing in electronic systems. 2

TABLE OF CONTENT Table of content 1 General safety instructions 1.1 Signal words for safety instructions 1.2 Used pictograms and symbols 1.3 General notes 2 Product description 2.1 Type plate 2.2 Intended use 2.3 Functional description 3 Installation 3.1 Dimensions 3.2 Wall mounting 4 Start up 4.1 Overview DPC200 4.2 Schematic view inside 4.3 Pressure connections 4.4 Electrical connection 4.5 Zero adjustment 5 Operation 5.1 Start menu 5.2 Menu structure 5.3 Measuring mode 5.4 Control mode 5.5 Adjustable parameters 5.6 Function alarm output 6 Maintenance 7 Warranty 8 Troubleshooting 9 Disposal 10 Specifications 10.1 CE-labelling 11 Ordering information 04 04 04 04 05 05 05 05 06 06 06 07 07 07 07 08 08 08 08 09 10 11 12 13 13 14 14 14 15 16 16 3

GENERAL SAFETY INSTRUCTIONS 1. General safety instructions 1.1 Signal words for safety instructions The safety instructions in this operation manual are designed to prevent hazards. They can be found in the operation manual before an operation / task / activity is described, which can entail a possible hazard. CAUTION Identification of a hazard with a low risk, which can lead to material damage or minor or moderate bodily injuries. NOTICE Signal word for important information regarding the product, which needs to be specifically pointed out. Hazard word Type of hazard Hazard source Hazard prevention 1.2 Used pictograms and symbols In this manual the following symbols are used: General hazard symbol (danger, warning, caution) General information 1.3 General notes NOTICE This manual contains information for installation and operation of the pressure controller and is exclusively for the operator and expert staff. The guidelines in this manual will help to avoid danger and downtime. 4

PRODUCT DESCRIPTION 2. Product description The differential pressure controller DPC200 measures low pressure of inert gases, particularly of air. 2.1 Type plate 1. Product name 2. Measuring range 3. Supply voltage 4. Signal output 5. Serial no. 6. Manufacturer pressure controller DPC200-EP500 measurement range: 500 Pa 2. supply voltage: signal output: 3. U S (1+ 2-) = 10... 30 Vdc / 24 Vac U out (3+ 4-) = 0... 10 V 4. 1. 5. part-no.: 2572 serial-no.: 15. 4700 IP54 Arthur Grillo GmbH Ratingen Made in Germany 6. 2.2 Intended use This device is primarily intended for use with air conditioning systems, room pressure control or filter control with ebm-papst continuously variable speed fans. It can be operated solely as a sensor (measuring mode) or closed loop controller for pressure / volumetric flow rate control. As analogue output the operator can use a signal from 0...10 V DC. Depending on the settings the signal has different meanings: 1. If the device is used as a pressure sensor, the output signal is proportional to the measured pressure. 2. As a volume flow sensor the device outputs a square root signal. 3. With closed loop pressure or volume flow the output signal stands for the control variable of the PI-control. 2.3 Functional description A soft silicone diaphragm is used as sensor. Under the influence of the differential pressure the diaphragm displaces a measuring spring until the spring force compensates for the pressure pushing on the diaphragm. A contactless differential transformer and suitable electronics convert this displacement into a continuously variable output voltage signal. The DPC200 provides two function options: 1. On the one hand it is used as a measuring device. In the measuring mode the differential pressure is shown on the display, and a proportional 0...10V DC output signal is provided. 2. Besides the measuring mode the DPC200 also can be operated in a control mode. Two setpoints can be adjusted in the device and can be selected with the potential free contact input. The PI-Algorithm matches the measured differential pressure with the setpoint and operates the control variable so that a constant pressure results. The control variable is given as a 0...10 V DC output signal. Instead of the quantity differential pressure also the quantity volume flow can be used for measuring and for control. 5

INSTALLATION 3. Installation The differential pressure controller DPC200 is designed for wall mounting. The mounting surface must be solid enough and vibration-free. The environment has to fulfil the ambient climatic conditions as given in the technical data. CAUTION Material damage Read the manual carefully before installation and operation Only experienced staff may connect the device and bring it into operation. NOTICE The device is position depended. The DPC200 must be mounted vertically. 3.1 Dimensions All dimensions in mm. 95 54 70 M16x1,5 3.2 Wall mounting 1. Hold the DPC200 against the wall. Mark the mounting holes. 2. Drill mounting holes for properly sized screws. 3. Put the screws through the housing mounting holes. 4. Tighten screws. 104 ø6 ø5 4,5 - + 6

START UP 4. Start up 4.1 Overview DPC200 1. Front cover 2. Cable gland 3. Pressure connection 1 4. Pressure connection 2 5. Cable gland 1. 2. 3. 4. 5. 4.2 Schematic view inside Button T1 Button T1 and T2 serve for the operation of the menu Button T2 4.3 Pressure connections Connect all pressure connections properly with plastic tubing (inner diameter 5 or 6mm). 7

OPERATION 4.4 Electrical connection DPC200 P 1 2 3 4 + 10...30 Vdc or 24 Vac (±15%) excitation - GND (return) + 0...10 Vdc output - GND (return) Alarm output: Open Collector 5 6 7 8 dry contact open: Setpoint 1 close: Setpoint 2 Alarm output high ohm: alarm off low ohm: alarm on maximum customer circuit 30 Vdc / 30 ma 1. Unscrew screws of the front cover. 2. Open front cover. 3. Use M16 cable glands for connecting wiring to terminals. 4.5 Zero adjustment The output signal offset can be zeroed from the outside with a small bar magnet. Do not use buttons T1 or T2. 5. Operation N S Adjustment: Remove the tubing from the pressure connections. Hold the bar magnet (N/S) as shown here to the zero point adjustment for a short period of time to activate an internal reed switch. The new zero point will be displayed and stored. 5.1 Start menu For operating the menu, unscrew the front cover to reach buttons T1 and T2. 8

OPERATION 5.2 Menu structure 9

OPERATION 5.3 Measuring mode Display ΔP Measurement 200 Pa menu unit metric operating mode control mode parameter diff. pressure Action Start menu: Press button T1 approx. two seconds Press button T1 to switch between: metric <=> imperial Press button T1 to switch between: measuring mode <=> control mode Press button T1 to switch between: diff. pressure <=> volume flow limit switch 150 Pa back and confirm If selected parameter = diff. pressure Press button T1 to leave the menu Press button T2 to stay in the menu fan k-factor k = 70 limit switch 300 m³/h back and confirm If selected parameter = volume flow than follows the additional input for the k-factor Press button T1 to leave the menu Press button T2 to stay in the menu 10

OPERATION 5.4 Control mode Display ΔP Measurement 200 Pa menu unit metric operating mode control mode parameter diff. pressure Action Start menu: Press button T1 approx. two seconds Press button T1 to switch between: metric <=> imperial Press button T1 to switch between: measuring mode <=> control mode Press button T1 to switch between: diff. pressure <=> volume flow setpoint 1 50 Pa setpoint 2 250 Pa output voltage U = 10,0 V DC P - parameter 50 l - parameter 3,15 controlling mode positive / heating back and confirm If selected parameter = diff. pressure resp. after the input of the k-factor follows: Press button T1 to switch between: positive / heating <=> negative / cooling Press button T2 to go to the next menu Press button T1 to leave the menu Press button T2 to stay in the menu 11

OPERATION fan k-factor k = 70 If selected parameter = volume flow than follows the additional input for the k-factor 5.5 Adjustable parameters Parameter Selection or parameter range Default setting Unit Metric or imperial metric Operating mode: Parameter Measuring mode or control mode Differential pressure ΔP [Pa or InH2O] Volume flow V [m 3 /h or cfm] Volume flow calculation up to 65,500 m 3 /h (38,514 cfm) K-factor: In measuring or control mode K = 70 Limit values: Nominal values (setpoints): Output voltage: Volume flow calculation according to: V = k Δp with: V = Volume flow in m 3 /h or cfm k = flow factor, adjustment range: 1...1000 measuring range up to 4000 Pa Δp = differential pressure in Pa or InH20 Maximum volume flow (V max ) Measuring range: 50 Pa, k=1000 Measuring range: 500 Pa, k=1000 Measuring range: 1000 Pa, k=1000 Measuring range: 2000 Pa, k=1000 Measuring range: 4000 Pa, k=1000 V max = 7,071 m 3 /h; (4,157 cfm) V max = 22,360 m 3 /h; (13,147 cfm) V max = 31,622 m 3 /h; (18,593 cfm) V max = 44,721 m 3 /h; (26,295 cfm) V max = 63,245 m 3 /h; (37,188 cfm) Differential pressure from 0 % up to 100 % of measuring range. Volume flow from 5 % up to 100 % of measuring range, k-factor is considered. Differential pressure from 0 % up to 100 % of measuring range. Volume flow from 5 % up to 100 % of measuring range, k-factor is considered. measuring mode differential pressure ΔP [Pa] OFF Set 1: 75 % Set 2: 25 % 0 10 V DC U out = 10 V DC P-gain: 0...1000 P = 50 I-gain: 0 100 I = 3.15 positive/(heating): Control deviation = set value actual value Control characteristic: The output increases when set value > actual value. negative/(cooling): Control deviation = actual value set value positive / heating The output increases when actual value > set value 12

OPERATION 5.6 Function alarm output The DPC200 has an open collector alarm output; depending on the operating mode the function is different. At the alarm event a contact between terminal no. 7 and no. 8 gets low-resistive and can be loaded with a maximum of 30 V DC/ 30 ma. When the alarm is switched off the contact will be high-resistive. During alarm state in the control mode / measuring mode an exclamation point is displayed (2nd line / 16th character). Control mode: In order to recognize the limits of control, the alarm output in the control mode refers to the set maximum output voltage (MaxU out ). MaxU out can be set in the menu item output voltage. In the default setting the value is set to 10 V DC. Alarm ON: Output voltage for 12 seconds constantly greater than: 0.95 MaxU out Alarm OFF: Output voltage for 12 seconds constantly less than: 0.9 MaxU out Measuring mode: For limit value monitoring a limit value can be entered. This value is set in the menu item limit switch. The previously set parameters are taken into account (unit, parameter, k-factor and the measuring range). In the default setting the limits are not active. Display 2nd line: OFF Alarm ON: Measurement for 12 seconds constantly greater than 1.0 limit value Alarm OFF: Measurement for 12 seconds constantly less than 0.95 limit value 13

WARRANTY & SUPPORT 6. Maintenance The DPC200 contains no wearing or consumable parts. Servicing is not required. On request, Arthur Grillo GmbH offers an annual calibration with factory certificate. For information, please contact: 7. Warranty Warranty and liability claims for personal and property damage are excluded if they are caused by one or more of the following reasons: Improper use of the device. Improper installation, commissioning, operation and maintenance of the device. Unauthorized modifications to the device beyond the intended use. Disasters due to external influences and force majeure. 8. Troubleshooting 9. Disposal Arthur Grillo GmbH Phone: +49 21 02-47 10 22 Am Sandbach 7 Fax: +49 21 02-47 58 82 40878 Ratingen E-Mail: info@grillo-messgeraete.de Description Activity Display does not show anything Check electrical connection Measurement stays zero Function test with a slight pressure increase in measuring mode for differential pressure Measuring error Perform zeroing as described in chapter 4.5. Error remains Contact manufacturer Dispose of parts so as not to endanger human health or the environment. Follow the laws in the country of use for disposing of electronic components and devices during disposal. 14

SPECIFICATIONS 10. Specifications Measuring medium: Measuring principle: Lowest span: Highest span: Overpressure protection: Static pressure: Pressure connections: Enclosure: Electrical connections: Supply voltage: Current consumption: Output: Alarm output: Display: Mode: Controlling algorithm: Setpoints: Protection class: Ambient temperature: Storage temperature: Weight: Mounting: Interference / emission: Influences / limits: Air or inert gases Silicon diaphragm with spring and differential transformer 0...50 Pa 0...4000 Pa 0.2 bar max. 0.2 bar tubing 5 mm ø or 6 mm ø UL 94 HB; Case polyamid, cover ABS cable inlet M16x1.5, screw terminal Electronic protection against reversed polarization 10...30 Vdc; 24 Vac (±15%) approx. 10 ma @ 10 Vdc, ca. 12 ma @ 24 Vdc 0...10 V (I max = 0.5 ma @ 10 Vdc, I max = 2 ma @ 20 Vdc) Open Collector, max. 30 V / 30 ma LCD-Display, 2 x16 characters Measuring mode or controlling mode PI 2 setpoints adjustable within software, Setpoints are selectable with floating contact input IP 54 according EN 60529-10...50 C -25...60 C approx. 250 g vertical, position dependence by turning of 90 : approx. 25 Pa according EN 61000-6-2, EN 61000-6-3, CE mark Zero error: ± 0.75 % Sum of linearity and hysteresis (depends on measuring range): ± 0.5 %... ± 1 % Temperature drift, zero point: ± 0.3 % / 10 K Temperature drift, span: ± 0.2 % / 10 K 15

CE-LABELLING & ORDERING INFORMATION 10.1 CE-labelling As an electric device the DPC200 falls within the scope of the directive 2004/108/EG (EMV-directive). In the scope of the EMV-directive the following norms were applied: DIN EN 61000-6-2:2006-03 Berichtigung 1:2011-06 DIN EN 61000-6-3:2011-09 Electromagnetic compatibility (EMC) - Part 6-2: Generic standards - Immunity for industrial environments Electromagnetic compatibility (EMC) - Part 6-3: Generic standards - Emission standard for residential, commercial and light industrial environments You can order the Declaration of Conformity at: Arthur Grillo GmbH Am Sandbach 7 40878 Ratingen Phone: +49 21 02-47 10 22 Fax: +49 21 02-47 58 82 E-Mail: info@grillo-messgeraete.de 11. Ordering information Article Differential pressure controller DPC200 Measurement range: 0...50 Pa Differential pressure controller DPC200 Measurement range: 0...500 Pa Differential pressure controller DPC200 Measurement range: 0...1000 Pa Differential pressure controller DPC200 Measurement range: 0...2000 Pa Differential pressure controller DPC200 Measurement range: 0...4000 Pa Mounting set M-DS with screws, bleeders and 2m plastic tube (4 x 1,5 mm) Item no. 2570 2572 2574 2576 2578 25110 16