(3) - Door Closers.qxp_(3) - Door Closers Art 14/02/2014 16:14 Page 2 F O C U S D O O R C L O S E R S KD.915 With cover Successfully Tested to EN 1154 4 8 5 1 1 3 2 Adjustable 2 to 5 by Spring Closer opening forces 0 0 to 30 0 under 30 Newtons; 30 0 to 60 0 under 22 1 /2 Newtons. Without cover CONFORMITY No: KD.915 - CE AD0116 Variable closing force Spring strength (EN) 2 to 5 Fire doors 3 to 5 Standard doors Width (mm) 850-1250 Weight (kg) 45-110 Body dimensions Length (mm) 236 Height (mm) 55 Projection (mm) 38 Arm Standard YES Parallel Optional Mechanism Rack & Pinion Power shoe arm bracket Optional Angle of opening 180º Power adjustable by spring YES Sweep speed adjustable YES Latching speed adjustable YES Hold open Arm Optional Back-check Adjustable at valve Optional Delayed action adjustable Optional Non-handed YES With cover Optional Application Regular (1) YES Parallel arm (66) Optional Transom (61) YES Finish Without cover SIL, GLD With cover SSS, PSS, PB,RAL COLOUR (arms to match) 4.3
CERTIFICATE OF APPROVAL No CF 5263 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Unit 1 Westgate Business Park, Ballymount, Dublin 24, Ireland Tel: 00 353 1 4567 421 Have been assessed against the requirements of the Technical Schedule(s) denoted below and are approved for use subject to the conditions appended hereto: CERTIFIED PRODUCT FOCUS RANGE KD6800, KD913, KD913V & KD915 Overhead Door Closers TECHNICAL SCHEDULE TS34 - The Contribution of Controlled Door Closing Devices and Accessories to Fire Resisting Doorsets Signed and sealed for and on behalf of CERTIFIRE Sir Ken Knight Chairman - Management Council Issued: 19 th August 2014 Page 1 of 6 Valid to: 20 th May 2019
CERTIFICATE No CF 5263 FOCUS RANGE DOOR CLOSERS - KD6800, KD913, KD913V & KD915 1. This approval relates to the use of KD6800, KD913, KD913V and KD915 closers which are overhead mounted door closing devices. 2. This certification is designed to demonstrate compliance of the product or system specifically with Approved Document B (England and Wales), Section D of the Technical Standards (Scotland), Technical Booklet E (N. Ireland). If compliance is required to other regulatory or guidance documents there may be additional considerations or conflict to 3. This approval relates to their use with the following door assemblies: - Latched and unlatched, intumescent sealed door assemblies consisting of timber faced and edged leaves with timber, cellulosic or mineral cores in timber frames having a fire resistance up to 120 minutes (CERTIFIRE Code - ITT) as indicated in approval matrix detailed later in this certificate. Latched and unlatched, door assemblies consisting of metal faced and edged leaves in metal frames, with or without intumescent sealing, and having a fire resistance up to 240* minutes (Codes MM & IMM) as indicated in the individual 4. The closers are approved on the basis of: i) Initial type testing to EN1154 and BS EN 1634-1: 2000 ii) An appraisal against TS34 iii) Certification of quality management system to ISO 9001: 2008. iv) Inspection and surveillance of factory production control v) On-going audit testing in accordance with EN 1154 requirements 5. This approval is applicable only to the specified closers used in the specific arm configuratio door assemblies of proven fire resistance (as defined in BS EN 1634-1 or BS 476: Part 22: 1987) and having power ratings appropriate to the leaf sizes subject to a minimum size 3 (as specified in BS EN 1154). 6. This approval does not cover models with a mechanical hold open facility. 7. The closers may only be fitted to previously tested door assemblies when fitted in the manner described in this certificate and when particular aspects of the door assembly are maintained. shown above do not apply to all models. Page 2 of 6 Signed Issued: 19 th August 2014 Valid to: 20 th May 2019
CERTIFICATE No CF 5263 FOCUS RANGE DOOR CLOSERS - KD6800, KD913, KD913V & KD915 8. The closers shall only be fitted using the fixings supplied by the closer manufacturer. 9. The doorset, including door frame and associated building hardware, should be either CERTIFIRE approved for the relevant application and classification or the doorset, including door frame and associated building hardware, should have achieved at least the required period of fire resistance when tested, or subsequently assessed to EN 1634-1. In either case regard should be paid to the maximum door mass permitted for use with the closer (see classifications). 10. The doorset shall be installed in accordance with BS 8214: 2008 where applicable. 11. The approval relates to on-going production. Product and/or its immediate packaging is he product name or number, the CERTIFIRE name or name and mark, together with the CERTIFIRE certificate number and application where appropriate. 12. The following tables show acceptable doorsets types and fire resistance periods: Matrix of acceptable doorsets for KD915 Approved Door Type Class IMM MM TT ITT ITM ITC FD20 FD30 FD60 FD120 FD240 E 20 EI 20 E 30 EI 30 E 60 EI 60 E 90 EI 90 E 120 EI 120 E 240 EI 240 The KD915 is approved for use in projecting arm (Figure 1) and parallel arm (Figure 6) applications. Page 3 of 6 Signed Issued: 19 th August 2014 Valid to: 20 th May 2019
CERTIFICATE No CF 5263 FOCUS RANGE DOOR CLOSERS - KD6800, KD913, KD913V & KD915 Matrix of acceptable doorsets for KD913 & KD913V Approved Door Type Class IMM MM TT ITT ITM ITC FD20 FD30 FD60 FD120 FD240 E 20 EI 20 E 30 EI 30 E 60 EI 60 E 90 EI 90 E 120 EI 120 E 240 EI 240 The KD913 and KD913V models are approved for use in projecting arm (Figure 1) and parallel arm (Figure 6) applications. Page 4 of 6 Signed Issued: 19 th August 2014 Valid to: 20 th May 2019
CERTIFICATE No CF 5263 FOCUS RANGE DOOR CLOSERS - KD6800, KD913, KD913V & KD915 Matrix of acceptable doorsets for KD6800 Approved Door Type Class IMM MM TT ITT ITM ITC FD20 FD30 FD60 FD120 FD240 E 20 EI 20 E 30 EI 30 E 60 EI 60 E 90 EI 90 E 120 EI 120 E 240 EI 240 The KD6800 is approved for use in projecting arm (Figure 1) and parallel arm (Figure 6) applications. Key: - approved - not approved See CERTIFIRE Technical Schedules for designation of doorset types i.e. ITM etc. The closers can only be used in single-acting configuration. Page 5 of 6 Signed Issued: 19 th August 2014 Valid to: 20 th May 2019
CERTIFICATE No CF 5263 FOCUS RANGE DOOR CLOSERS - KD6800, KD913, KD913V & KD915 Scope of Approval: All ITT applications apply to unglazed doorsets and glazed doorsets incorporating an uninsulated glass panel size of less than 20% of the leaf area. The closer application is as referenced in the Classification code section below in accordance with EN 1154. Classification codes - The approval provides the following classifications: KD915 in projecting arm configuration (Figure 1) 4 8 5 3 KD915 in parallel arm configuration (Figure 6) 3 8 5 3 1 1 3 1 1 3 KD913 and KD913V in projecting arm configuration (Figure 1) 4 8 4 3 1 1 3 KD913 and KD913V in parallel arm configuration (Figure 6) 4 8 4 1 1 3 KD6800 in projecting arm (Figure 1) and parallel arm (Figure 6) configurations Further Information 4 8 3 1 1 3 Further information regarding the details contained in this data sheet may be obtained from KCC Architectural (Tel: 00 353 1 4567 421). Further information regarding the CERTIFIRE certification and other approved products can be obtained from CERTIFIRE (Tel: 01925 646777). Page 6 of 6 Signed Issued: 19 th August 2014 Valid to: 20 th May 2019
DOP003: KD915 Construction Products Regulation 2011 DECLARATION OF PERFORMANCE DOP003 1. Unique identification code of the product-type: Controlled door closing device 2. Type, batch or serial number or any other element allowing identification of the construction product as required under Article 11(4) of the CPR: KD915 3. Intended use or uses of the construction product, in accordance with the applicable harmonised technical specification, as foreseen by the manufacturer: For use on fire and smoke compartmentation doors, when fitted in accordance with the manufacturer's fitting instructions. 4. Name, registered trade name or registered trade mark and contact address of the manufacturer as required under Article 11(5): KCC Architectural, Unit 1, Westgate Business Park, Ballymount, Dublin 24, Ireland Tel: +353 (0)1 456 7421 Web: www.kccarchitectural.com 5. 5. Where applicable, name and contact address of the authorised representative whose mandate covers the tasks specified in Article 12(2): N/A 6. System or systems of assessment and verification of constancy of performance of the construction product as set out in CPR, Annex V: System 1 7. In case of the declaration of performance concerning a construction product covered by a harmonised standard. EN 1154: 1996: A1: 2002 Notified product certification body No. 1121 performed the type testing and issued test reports. 8. European Technical Assessment: N/A 1
DOP003: KD915 9. Declared Performance Figure 1 Essential characteristic Self closing Performance Harmonised technical specification 5.2.1 General Application Door-mounted pull side (Fig.1) EN1154:1996:A1:2002 5.2.2 Durability 500,000 test cycles 5.2.3 Closing moment Pass size 2-5 5.2.4 Opening moment Pass size 2-5 5.2.5 Efficiency; More than 50% size 2 More than 55% size 3 More than 60% size 4 More than 65% size 5 5.2.6 Closing time Pass- After 5K and 500K test cycles, the closing time from an opening angle of90 was capable of adjustment to 3 s or less, and 20 s or more- After 500K test cycles, the closing time set at 5K test cycles did not increase by more than 100%, or decrease by more than 30%. 5.2.7 Angles of operation Grade 4, 180 5.2.8 Overload performance Pass - The closer withstood the closing overload tests 5.2.9 Temperature -15 C to +40 C dependence 5.2.10 Fluid leakage Pass - There was no leakage of fluid from the closer 5.2.11 Damage Pass - There was no damage to the door closing device that would adversely affect its performance to the standard 5.2.12 Latch control Pass - Effective over max. range of 15º from closed position, and adjustable 5.2.13 Backcheck Pass - Arrested door before 90 open position 5.2.14 Delayed closing NPD 5.2.15 Adjustable closing force Pass - Complies with performance requirements of Clause 5 at both min. and max. power settings claimed 5.2.16 Zero position NPD (Double action only) 5.2.18 Fire / smoke doors Grade 1: Suitable for use on fire/smoke door assemblies 5.2.2 Durability Grade 8 500,000 test cycles 5.2.17.1 Corrosion Grade 3 : 96 hrs 5.2.17.2 Corrosion Pass - After the salt spray test, the closing moment of the door closer was not less than 80% of that measured prior to the test. Dangerous Substances Annex ZA3 The materials in the product do not contain or release any dangerous substances in excess of the maximum levels specified in existing European material standards or any national regulations. 2
DOP003: KD915 10. Declared Performance Figure 6 Essential characteristic Self closing Performance Harmonised technical specification 5.2.1 General Application Door-mounted push side (Fig.6) EN1154:1996:A1:2002 5.2.2 Durability 500,000 test cycles 5.2.3 Closing moment Pass size 2-5 5.2.4 Opening moment Pass size 2-5 5.2.5 Efficiency; More than 50% size 2 More than 55% size 3 More than 60% size 4 More than 65% size 5 5.2.6 Closing time Pass- After 5K and 500K test cycles, the closing time from an opening angle of90 was capable of adjustment to 3 s or less, and 20 s or more- After 500K test cycles, the closing time set at 5K test cycles did not increase by more than 100%, or decrease by more than 30%. 5.2.7 Angles of operation Grade 3, 105 5.2.8 Overload performance Pass - The closer withstood the closing overload tests 5.2.9 Temperature -15 C to +40 C dependence 5.2.10 Fluid leakage Pass - There was no leakage of fluid from the closer 5.2.11 Damage Pass - There was no damage to the door closing device that would adversely affect its performance to the standard 5.2.12 Latch control No Latch control in this conguration 5.2.13 Backcheck No backcheck in this configuration 5.2.14 Delayed closing NPD 5.2.15 Adjustable closing NPD force 5.2.16 Zero position NPD (Double action only) 5.2.18 Fire / smoke doors Grade 1: Suitable for use on fire/smoke door assemblies 5.2.2 Durability Grade 8 500,000 test cycles 5.2.17.1 Corrosion Grade 3 : 96 hrs 5.2.17.2 Corrosion Pass - After the salt spray test, the closing moment of the door closer was not less than 80% of that measured prior to the test. Dangerous Substances Annex ZA3 The materials in the product do not contain or release any dangerous substances in excess of the maximum levels specified in existing European material standards or any national regulations. 11. The performance of the product identified in points 1 and 2 is in conformity with the declared performance in point 9. 3
DOP003: KD915 This declaration of performance is issued under the sole responsibility of the manufacturer identified in point 4. Signed for and on behalf of the manufacturer by: Chris Kilpatrick Managing Director Date of issue: 1 st July 2013 KCC Architectural, Unit 1, Westgate Business Park, Ballymount, Dublin 24 Ireland 4