PART 4 ELECTRICAL STANDARDS

Similar documents
Port of Portland Conveying Equipment Guidelines

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

Chapter 1 General...9 Article 100 Definitions...11 Article 100 Questions Article 110 Requirements for Electrical Installations...

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems

Interfacing Fire Alarm, Sprinkler and Elevator Systems

CONTENTS AUTOMATIC TRANSFER SWITCHES

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION ISOLATED POWER SYSTEMS

TABLE OF CONTENTS CHAPTER 5 SPECIAL OCCUPANCIES CHAPTER 1 GENERAL RULES... 19

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase

Introduction Limited-Use / Limited-Application

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

9/7/2010. Chapter , The McGraw-Hill Companies, Inc. AND BONDING. 2010, The McGraw-Hill Companies, Inc.

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

Rules for Classification and Construction Additional Rules and Guidelines

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS

SECTION POWER SUPPLIES AND DISTRIBUTION

Functional Performance Test

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

Installation Guide for models:

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual

Installation Guide for models:

National Electrical Code

Fire Alarm System Fundamentals

Remote NAC Power Supply D7038

Chapter 1 General... 5

www. ElectricalPartManuals. com GADD MKIII Ground Fault Indication System Instruction Manual Ground Fault Protection

SECTION GENERATOR PARALLELING CONTROLS

Element D Services Electrical

Electrical Design Guidelines Table of Contents

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL

PSN-1000 & PSN 1000(E) Installation Manual

SECTION AUTOMATIC TRANSFER SWITCHES

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

Model 17A00 Expansion Enclosure

SECTION ELECTRIC TRACTION ELEVATORS PART 1 GENERAL 1.01 SUMMARY. A. Section Includes: Electric Traction Elevators.

CHAPTER 20 SERVICE EQUIPMENT

Step by Step Detailed Procedure Expected Result Observations Verify power off at all loads on emergency power. Verify all loads have power.

SECTION INTERIOR LIGHTING

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

www. ElectricalPartManuals. com GADP Ground Fault Indication System Instruction Manual Ground Fault Protection

Microgrid Fault Protection Based on Symmetrical and Differential Current Components

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

Electrical Safety Through Design. Mersen EP formerly Ferraz Shawmut

4100U City and Relay Cards Installation Instructions

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

SECTION SOLAR PHOTOVOLTAIC (PV) POWER GENERATION SYSTEM

SECTION (16460) - LOW-VOLTAGE TRANSFORMERS

PART GENERAL 1.01 SECTION INCLUDES

Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

NECA 169. Standard for Installing and Maintaining Arc-Fault Circuit Interrupters (AFCIs) and Ground-Fault Circuit Interrupters (GFCIs)

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

Reyrolle Protection Devices. 7PG26 DAD High Impedance Current Relay. Answers for energy

50M Integrated Single or Two-Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51

CAUTION WARNING. 50T Integrated Furnace Control INSTALLATION INSTRUCTIONS DESCRIPTION PRECAUTIONS

SECTION AUTOMATIC TRANSFER SWITCH

Molded Case Circuit Breakers, Bulletin 140G

CNA-Series - Large Industrial Heaters Tankless Water Heating Solutions

ELECTRICAL POWER SYSTEMS

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

Combination Type AFCI

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

C1N Series - Light Industrial Heaters Tankless Water Heating Solutions

SECTION CENTRAL BATTERY INVERTERS. A. This Section includes fast-transfer central battery inverters with the following features:

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- ELECTRICAL

tcm100, tcm101 Series Temperature Control Modules and PTS100, PTS100/3 Pipe Temperature Sensors Operations Manual

TECHNICAL DATA OBSOLETE

8. Multi-Family Residential Buildings

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description.

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 870 SERIES INDUSTRIAL CONTROL PANELS

PowerWave 2 Busway System

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description

NFPA Changes

FIRE ALARM: BY OTHERS, IF REQUIRED.

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

Cat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE

Page 1 of General

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018

FIRE ALARM: BY OTHERS, IF REQUIRED.

SERVICE BY QUALIFIED PERSONNEL ONLY

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS

Series. Access Power Controllers. Installation Guide

Operator: Save these instructions for future use!

Guide Specification Model CTG Automatic Transfer Switch

Transcription:

PART 4 ELECTRICAL STANDARDS

1.0 INTRODUCTION AND SCOPE: These standards reflect the general requirements and recommendations of elevator contractors, with respect to the power distribution system to achieve acceptable elevator performance. Additional requirements will be found on the Power Supply Confirmation Data Form. 1.1 Design Responsibility and System Boundary Point: The requirements and recommendations of these standards represent design and installation responsibility for the contractor(s) who design and install the building or site electrical distribution system. Because of design requirements and electrical contractor(s) responsibility for coordination with other building loads, it is necessary to define and agree upon the boundaries of responsibility between electrical contractor, and elevator installer. The defined boundary of responsibility for the elevator installer is at the mainline input power terminals to the elevator equipment. The electrical contractor is responsible for all electrical power system design up to the elevator equipment, including the appropriate location of the point of common coupling for other building loads that might be influenced by harmonic distortion. See AC Line Distortion Tutorial in NEII 1, Part 4 for recommendations on point of common coupling. 2.0 VOLTAGE: Nominal System Voltage. 208, 240, 480, 600-3 Phase, 3 live phases plus a ground, Main Elevator Feeders. 125-1 Phase (See 11.0, Additional Power). 3.0 VOLTAGE VARIATION: The actual continuous service voltage supplied to the elevator equipment (measured at per car Mainline Disconnecting Means) should be at the nominal system voltage. Under all load conditions short duration voltage variations must be limited to the maximum and minimum values found on the appropriate Power Supply Confirmation Data Form, inclusive of voltage drop. Continuous operation of equipment at or near the maximum or minimum values may result in reduction of equipment life. 4.0 VOLTAGE BALANCE: Maximum deviation from the average voltage, divided by the average voltage times 100. Phase to Phase 5% Phase to Neutral 5% 5.0 NOMINAL FREQUENCY: Confirmed at site. 60 Hz 50 Hz 6.0 FREQUENCY TOLERANCE: ± 2% with a maximum Slew Rate (the rate of change of frequency with respect to time) of 5 Hz/s. For static DC control 1 Hz/s maximum (continuous) 3.5 Hz/s maximum (10 cycles maximum transient). 7.0 HARMONIC DISTORTION: Solid-state power converters used in elevator control panels generate line current harmonics and line voltage distortion. See AC Line Distortion Tutorial in NEII-1, Part 4. Equipment that is sensitive to these distortions should be properly isolated from the elevator feeders. 8.0 CONDUCTORS: Ampacity of conductors is determined by the electrical contractor per NFPA 70 and/or local code requirements, based on information provided on the Power Supply Confirmation Data Form. 9.0 CONDUCTOR BRACING: Recommend conductor bracing to avoid unwanted noise being emitted from raceway. 10.0 MAIN LINE DISCONNECTING MEANS: Size and locate the fused Main Line Disconnect switch or circuit breaker in accordance with NFPA 70. Fuses are to be current limiting class RK1 or equivalent. Circuit breakers are to have current limiting characteristics equivalent to RK1 fuses. 11.0 ADDITIONAL POWER: Requirements for additional supplies will vary with the type of equipment. These are typically single phase, 125 Vac (nominal) 15A or 20A circuits. The additional supplies are used for: 11.1 Machinery Spaces, Machine Rooms, Control Spaces and Control Rooms: Lighting per ASME A17.1/CSA B44, Section 2.7 and 125 V duplex receptacle. 11.2 Secondary Level Rooms: Lighting per ASME A17.1/CSA B44, Section 2.7 and 125 V duplex receptacle. Page 4-2 30-Oct-13

11.3 Elevator Pit: Adequate illumination with switch near entrance and 125 V duplex receptacle (ASME A17.1/CSA B44, Section 2.2.5). 11.4 Car: Separate 125 V feed with disconnecting means in machinery space, machine room, control space or control room to each elevator. The car lighting branch circuit is not required to be provided with ground-fault circuit-interrupter (GFCI) protection for personnel. 11.5 Other: Elevator contractor should identify any other additional circuits or requirements for their equipment (e.g. intercom systems, console panels, car receptacles, etc.). 11.6 Receptacles: 125 V receptacles must be provided with ground fault circuit interrupter protection, where required by NFPA 70, Article 620 Note: A single receptacle supplying a permanently installed sump pump (in pits) does not require GFCI protection. It is recommended that the sump pump receptacle not be provided with GFCI protection. 12.0 ADDITIONAL WIRING: 12.1 Guidelines for Initiating Devices for Phase I Emergency Recall Operation: Installed in compliance with NFPA 72. See ASME A17.1/CSA B44, Section 2.27.3.2. 12.1.1 Elevator control circuits must functionally interface with fire alarm initiating devices as required by ASME A17.1/CSA B44, 2.27.3.2. As a life-safety system, the integrity of the signalization from the fire alarm system is very important. The wiring practices of the interface circuits between the fire alarm system and the elevator control circuits is governed by NFPA 72. 12.1.2 NFPA 72 requires that the field installed wiring between the fire alarm control unit and the elevator control circuit interface be monitored for signal integrity. The design for monitoring is the responsibility of the fire alarm system contractor. 12.1.3 Furthermore, to maintain the signal integrity on the elevator side of the interface, relays or modules must be placed in a secure location per NFPA 72, so that the wiring from the interface relay or module is unlikely to be subjected to external faults. 12.1.4 NFPA requires such interface relays or modules to be physically located within three feet of the controlled circuit. Practically, this means that the field installed wiring is either by direct entry in dedicated conduit to the elevator controller, or within the confines of the elevator machine room, control room, or control space (e.g. within wiring duct). See diagram 12.1 for an illustration of incorrect and correct interface wiring practices. 12.2 Communications: Communication lines, one per car, to be brought into the machine room by others, for hookup by the elevator contractor. 13.0 ALTERNATE POWER REQUIREMENTS: 13.1 Alternate power may be either standby or emergency. The requirements specified for standby power and emergency power shall conform to NFPA 70 and local code. For example, display of car position at fire command station. 13.2 Elevator contractors require that the standby (emergency) power system be sized to provide the required operation of the elevators. 13.3 The maximum electrical demand on the standby (emergency) power system depends upon the number of elevators to be simultaneously started. The required per car starting/acceleration power is provided by the elevator contractor on the Power Supply Confirmation Data Forms. 13.4 The duration of the accelerating load on the standby (emergency) power system varies depending on elevator contract speed. It is important to note that the accelerating load on the power system can persist for periods of several seconds each time the elevator(s) runs. 13.5 The standby (emergency) power system must be capable of absorbing the regenerative power from the elevators, in compliance with NFPA 70, Article 620, to prevent overspeed during regeneration. The maximum per car regenerative power is provided by the elevator contractor on the Power Supply Confirmation Data Forms. 13.6 For standby (emergency) power operation of one car out of a group, avoid reducing the size of the standby (emergency) power feeders and the protective device. Static power converters usually have isolation or autotransformers. Each car's transformer may remain connected to the line. On energizing, the transformers have large peak magnetizing in-rush currents lasting for several cycles of the ac line. A reduced size circuit breaker will likely trip. 14.0 ADDITIONAL DISCONNECTING MEANS: When sprinklers are provided in an elevator machinery space, machine room, control space, or control room, or hoistway see ASME A17.1/CSA B44, Section 2.8.2.3 for requirements. 15.0 POWER DISTRIBUTION SYSTEM: 15.1 NFPA 70 requires all main feeder and branch circuit full load, starting and accelerating currents of the elevator(s) electrical system must be completely coordinated with the time-current characteristic of the elevator(s) branch circuit protection device(s). Also, the short circuit component of elevator(s) main, feeder and branch circuit device(s) must be coordinated. In particular, the time-current characteristics thermal, thermal magnetic or magnetic branch circuit protection 30-Oct-13 Page 4-3

devices that service main, feeder and branch circuits must be analyzed for compliance with selective coordination. The omission of selective coordination will result in a total or partial elevator system blackout. 15.2 In addition to selective coordination of main, feeder and branch circuit protection devices, electronically controlled circuit protection devices should be rms current sensing to avoid nuisance tripping. Electronically controlled circuit protection devices which are not rms current sensing may trip under normal operating conditions as a result of measuring peak or harmonic currents of variable voltage and/or variable frequency elevator drives. The application of electronic circuit protection devices with solid-state elevator drive systems should be verified with the device manufacturer. 15.3 When variable frequency drives are used to control ac motors and a ground fault or earth leakage device is provided, it should be specified as "Product For Inverter Use" or be designed so that its sensitivity is reduced at high frequencies. 16.0 REFERENCES: 16.1 The following Codes and Standards are referenced: 16.1.1 Safety Code for Elevators and Escalators, ASME A17.1/CSA B44. 16.1.2 National Electrical Code, NFPA 70. 16.1.3 National Code, NFPA 72. 16.2 Power Supply Confirmation Data Forms: An information bulletin that states the characteristics of the equipment's electrical load demand upon the power supply system. It is intended as a "Universal Approach" which all elevator contractors can use to obtain required information prior to manufacture and to establish the conditions expected as part of the elevator, escalator or moving walk installation. Page 4-4 30-Oct-13

DIAGRAM 12.1(a) Elevator Control Enclosure Initiating Devices INCORRECT METHOD Unsupervised wiring is subject to faults or external disturbance. Signal integrity not assured. 30-Oct-13 Page 4-5

DIAGRAM 12.1(b) Initiating Devices Shortest Practical Distance Elevator Control Enclosure MAIN Elevator Control Room, Control Space, Machinery Room, Machinery Space, Hoistway All Other Levels Relays and/or s are located outside of restricted spaces such as the hoistway or pit. Initiating Devices Control Panel Shortest Practical Distance Annunciator(s) Elevator Control Enclosure MAIN Control Panel Elevator Control Room, Control Space, Machinery Room, Machinery Space, Hoistway All Other Levels Annunciator(s) Correct Methods Installed wiring is supervised and monitored between the fire alarm system and the fire alarm interface. Signals to elevator control circuits are secure due to close proximity to elevator control enclosure. Signal Integrity is assured. Page 4-6 NEII-1 2000-2011, National Elevator Industry Inc., Salem, NY. NEII and NEII logo Registered, U.S. Patent and Trademark Office. 18-Nov-11