Australian Journal of Basic and Applied Sciences. Investigation of New Eco Friendly Refrigerant Mixture Alternative to R134a in Domestic Refrigerator

Similar documents
JJMIE Jordan Journal of Mechanical and Industrial Engineering

Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling

Part load performance analysis of vapour compression refrigeration system with hydrocarbon refrigerants

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

International Journal of Multidisciplinary Research and Modern Education (IJMRME) ISSN (Online): (

CHAPTER 1 INTRODUCTION

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

A Review on selecting an Eco-friendly Refrigerant alternate to R134a in Domestic Refrigerators

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator

DEEPAK PALIWAL, S.P.S.RAJPUT

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

International Engineering Research Journal (IERJ) Special Issue Page , June 2016, ISSN

Effect of capillary diameter on the power consumption of VCRS using different refrigerants

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

Department of MCE, Islamic University of Technology 2. Abstract

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

Theoretical performance evaluation of R134a and its low GWP Hydrocarbon alternatives in Domestic Refrigerator

A Comparison Between Refrigerants Used In Air Conditioning

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT

Keywords: Climate change; ozone depletion; Montreal protocol; eco-friendly refrigerant; hydrocarbon refrigerant; performance analysis.

THERMODYNAMIC AND THERMOPHYSICAL ASSESSMENT OF HYDROCARBONS APPLICATION IN HOUSEHOULD REFRIGERATOR

A Review of Hydroflorocarbons (HFC S) Refrigerants as an Alternative to R134a Refrigerant

A Review Paper on Comparative Study of Household- Refrigerator with Alternative Low Global Warming Potential Refrigerants

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

ADVANCES in NATURAL and APPLIED SCIENCES

Assessment of Alternatives to Refrigerant R134a in Automotive Air Conditioning System

Volume 4, Issue 1 (2016) ISSN International Journal of Advance Research and Innovation

SIMULATION OF POTENTIAL REFRIGERANTS FOR RETROFIT REPLACEMENT

Assessment of LPG as a possible alternative to R-12 in domestic refrigerators

Oyelami S., Bolaji B. O.

Volume 6, Issue 3(2018) ISSN International Journal of Advance Research and Innovation

Experimental investigation on the performance of air conditioner using R32 Refrigerant

Performance and exergy analysis of vapour compression refrigeration system using various alternative of R134a.

ENERGY PERFORMANCE ASSESSMENT OF R134A/LPG BLEND AS REPLACEMENT OF R134A IN VAPOR COMPRESSION REFRIGERATION SYSTEM

Study of R161 Refrigerant for Residential Airconditioning

Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.

REPLACING HARMFUL CFC 12 BY ECO-FRIENDLY REFRIGERANT IN MILK CHILLER

A COMPARATIVE STUDY OF REFRIGERANTS R12, R134A, R407 & R717 FOR VAPOUR COMPRESSION REFRIGERATION SYSTEM

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

Evaluation of Vapour Compression Refrigeration System Using Different Refrigerants

Comparative Performance Analysis of Domestic Refrigerator using R12, R134a and R600a Refrigerants

η second law = Second law efficiency

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

PERFORMANCE OF REFRIGERATOR USING R-600A AS REFRIGERANT

CHAPTER 1 INTRODUCTION

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

Thermodynamic study of R134a in Vapour Compression Refrigeration System in Summer Climate

Optimization of Capillary Tube Parameters in Vapour Compression System using Environmentally Friendly Refrigerant R1234yf

ISSN Electronic International Interdisciplinary Research Journal (EIIRJ) Bi-monthly Reviewed Journal Mar- April 2015

IJESRT. (I2OR), Publication Impact Factor: (ISRA), Journal Impact Factor: 2.114

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

International Journal of Advance Engineering and Research Development

Performance Assessment of Three Eco-Friendly Hydro-Fluorocarbon and Hydrocarbon Refrigerant Mixtures as R22 Alternatives in Refrigeration Systems

Performance Study of a Water-to-Water Heat Pump Using Non-azeotropic Refrigerant Mixtures R407C

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Performance Prediction of Domestic Refrigeration System using R436A Refrigerant as alternative Refrigerant to R134a with ANN

A COMPARATIVE STUDY FOR RETROFITTING OF R-12 VAPOUR COMPRESSION REFRIGERATION SYSTEM BY ECO- FRIENDLY REFRIGERANTS R-134A, R-413A, R-423A

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

Chapter 2. Alternatives to HCFCs and their Characteristics

Refrigerants Retrofit as Alternative for R12 and R134a in Household Refrigerators

Design of LPG Refrigeration System

Experimental performance evaluation of vapour compression refrigeration system without nano particles

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications:

HFC/HC BLEND FOR CAR CLIMATE CONTROL WITH MINERAL OIL AS LUBRICANT

EXPERIMENTAL INVESTIGATION OF A REFRIGERATOR BY USING ALTERNATIVE ECO FRIENDLY REFRIGERANTS (R600A & HC MIXTURE)

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

Thermodynamic Cycle Analysis of Mobile Air Conditioning System Using HFO-1234yf as an Alternative Replacement of HFC-134a

Volume 3, Issue 4 (2015) ISSN International Journal of Advance Research and Innovation

Experimental study of R600a and R436a to replace R134a in a domestic refrigerator and freezer

Study of Behavior of Refrigerant Mixtures in Domestic Refrigerator- Practical Research

STUDY AND PERFORMANCE ANALYSIS OF ECO-FRIENDLY REFRIGERANT FOR RETROFITTING R22 IN RESPECT TO BANGLADESH

Design and Fabrication of Liquefied Petroleum Gas Refrigeration System and Comparison with Domestic Refrigerator

Main Anthropogenic Sources of Greenhouse Gases Refrigerants

Thermodynamics I. Refrigeration and Heat Pump Cycles

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

TYPICAL INITIAL OUTPUT OF A CO 2 HEAT PUMP

Evaluation of HCFC Alternative Refrigerants

Performance Evaluation of Vapour Compression System with R22 and Environment-Friendly Refrigerant

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

ISSN: [Sachuthananthan * et al., 5(10): October, 2016] Impact Factor: 4.116

Pure Butane as Refrigerant in Domestic Refrigerator Freezer

Technology Application of Environmental Friendly Refrigeration (Green Refrigeration) on Cold Storage for Fishery Industry

ADVANCES in NATURAL and APPLIED SCIENCES

ENERGY, EXERGY AND SUSTAINABILITY ANALYSIS OF TWO-STAGE VAPOUR COMPRESSION REFRIGERATION SYSTEM

Volume 2, Issue 4 (2014) ISSN International Journal of Advance Research and Innovation

Use of fourth generation ecofriendly refrigerants in two and three cascade refrigeration systems for reducing global warming and ozone depletion

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

Low GWP Refrigerants for Air Conditioning Applications

Transcription:

ISSN:1991-8178 Australian Journal of Basic and Applied Sciences Journal home page: www.ajbasweb.com Investigation of New Eco Friendly Refrigerant Mixture Alternative to R134a in Domestic Refrigerator 1 A. Baskaran and 2 P. Koshy Mathews 1 Associate Professor, Department of Mechanical Engineering, P. A. College of Engineering and Technology, Pollachi 642002, India 2 Dean, Kalaivani College of Technology, Coimbatore 641105, India A R T I C L E I N F O Article history: Received 12 November 2014 Received in revised form 26 December 2014 Accepted 29 January 2015 Available online 10 February 2015 Keywords: Refrigerant blend, COP, R134a, RE170, R600a A B S T R A C T In the present study, the possibility of using refrigerant blend of RE170 and R600a as alternative to the refrigerant R134a in domestic refrigerator working on Vapour Compression System has been assessed theoretically. R134a is currently used as the refrigerant in refrigerator replacing the ozone depleting refrigerant R12. Although R134a has no ozone depletion potential, it has relatively larger global warming potential (1300). For this reason the performance of refrigerant mixtures containing RE170 and R600a are measured. The performance characteristics of domestic refrigerator were studied over a wide range of evaporation temperatures (-30 C to 30 C) and condensation temperatures (30 C, 40 C, 50 C) for working fluids R134a and refrigerant mixtures RE170/R600a.This study has been carried out by comparing parameters such as pressure ratio, refrigerating effect, isentropic work, coefficient of performance, compressor power, volumetric cooling capacity discharge temperature and mass flow rate. The present study indicates a drop in replacement for R134a with blend (RE170/R 600a) with the mass fractions of 80%/20%. 2015 AENSI Publisher All rights reserved. To Cite This Article: A. Baskaran and P. Koshy Mathews., Investigation of New Eco friendly Refrigerant Mixture alternative to R134a in Domestic Refrigerator. Aust. J. Basic & Appl. Sci., 9(5): 297-306, 2015 INTRODUCTION For the past half century, chlorofluorocarbons (CFCs) have been used extensively in the field of refrigeration due to their favorable characteristics. In particular, CFC12 has been predominantly used for small refrigeration units including domestic refrigerator/freezers. Since the advent of the Montreal Protocol, and as the CFC12 has high ODP and GWP the refrigeration industry has been trying to find out the best substitutes for ozone depleting substances. For a past decade, HFC134a has been used to replace CFC12 used in refrigerators and automobile air conditioners. HFC134a has such favorable characteristics as zero ozone depleting potential (ODP), non-flammability, stability, and similar vapor pressure to that of CFC12. A recent study, however, showed that the performance of HFC134a in refrigerators with a proper compressor and lubricant is quite comparable to that of CFC12. In 1997 the Kyoto protocol was agreed by many nations calling for the reduction in emissions of greenhouse gases including HFCs. Since the Global warming potential (GWP) of HFC134a is relatively high (GWP1300) and also expensive, the production and use of HFC134a will be terminated in the near future. The research and development in the field of Refrigeration and Air-Conditioning apply the use of natural refrigerants is not only associated with the need to preserve the environment itself, and also has great importance in the latent need for enhanced efficiency energy equipment. Such a feature is observed in Decision XIX/6 of the Montreal Protocol. Hydrocarbons, such as liquefied petroleum gas (LPG) and Di methyl ether are environmentally friendly and their products are available in abundance in nature. In this sense, the use of these substances as refrigerants in domestic refrigerators is very attractive. Sekhar, et al. (2004) investigated the mixture of HFC134a/hydrocarbons in two systems of low temperature (household refrigerator and freezer) and two medium-temperature systems (vending machine and bottle cooler). The authors concluded that a mixture containing 9% of hydrocarbon mixtures (mass) has the best performance, resulting in 10-30 % and 5-15% reduction in energy consumption in systems of medium and low temperature, respectively. Fatouh and El Kafafy (2006) evaluated theoretically a mixture of hydrocarbons composed of Corresponding Author: A. Baskaran, Associate Professor, Department of Mechanical Engineering, P. A. College of Engineering and Technology, Pollachi 642002, India E-mail:boss120367@gmail.com

298 A. Baskaran and P. Koshy Mathews, 2015 60% and 40% R290/R600 as a better drop-in replacement for domestic refrigerators based on HFC -134a under abnormal weather conditions, subtropical and tropical regions. Mohanraj et al. (2007) presented an experimental results of the energy efficient hydrocarbons mixture consisting of 45% HC290 (propane) and 55% HC600a (isobutane) as drop-in replacement for the HFC134a under various loads (40 g, 50 g, 70 g, 90 g) in a household refrigerator of 165 liters (class tropical) using synthetic oil as a lubricant and R134a (100 g). Tests were performed at room temperature of 30 C, without thermal load and the refrigerator door closed as ISO 8187. The results showed that the load of 70 g of the hydrocarbon mixture has a better COP, lower power consumption, lower pull down and low temperature discharge in relation to the R134a and the equipment need not change. Dimethyl ether (RE170, DME) makes a better refrigerant than R290 / R600a blends as it has no temperature glide and doesn t separate during leakage. It has been extensively adopted by the aerosol industry as the most cost effective replacement for R134a in propellant applications (Nicholas Cox, 2010). Valentine Apostol etl (2009) conducted a comparative thermodynamic study considering a single-stage vapor-compression refrigeration system (VCRS) using as working fluids DME, R717, R12, R134A, R22 (pure substances) and R404A, R407C (zoetrope mixtures), respectively. The result of this study is that DME could be used as a refrigerant and, more, that DME could be a good substitution alternative for R12 and R134a. The Dimethyl ether (DME, C2H6O) possesses a range of desirable properties as a replacement for R- 134a. These include better heat transfer characteristics than R-134a, a pressure/temperature relationship very close to R-134a, compatibility with mineral oils, low cost and ready availability. It is also highly environmentally friendly. (ODP =0; GWP =1; atmospheric lifetime = 6 days). DME is compatible with most materials commonly found in refrigeration systems (Adamson, B.M, 1998). Ki-Jung Park, et al, (2010), investigated both numerically and experimentally in an effort to replace HFC134a used in the refrigeration system of domestic water purifiers. Test results show that the energy consumption and the compressor discharge temperature of R429A is 28.9% and 13.4 0 C lower than that of HFC134a with 50% of the refrigerant charge, Overall,R429Ais a new long term environmentally safe refrigerant and it is a good alternative for HFC134a requiring little change in the refrigeration system of the domestic water purifiers. Ki-Jung Park et al. (2010) investigated both numerically and experimentally in an effort to replace HFC134a used in the refrigeration system of domestic water purifiers. Test results show that the energy consumption and the compressor discharge temperature of R510A is 22.3% and 3.7 0 C lower than that of HFC134a with 50% of the refrigerant charge, Overall, R510Ais a new long term environmentally safe refrigerant and it is a good alternative for HFC134a requiring little change in the refrigeration system of the domestic water purifiers. Selection of Mixtures: For drop-in acceptance of a working fluid in a refrigeration system that already exists, some important performance characteristics such as operating pressure, volumetric cooling capacity, coefficient of performance and compressor discharge temperature should be considered. (Fatouh and El Kafafy, 2006). The refrigerant must have a minimum number of essential characteristics favorable like low density in the liquid phase, high latent heat of vaporization, low specific volume in the vapor phase and low specific heat in the liquid phase. Volumetric cooling capacity and performance compared with the original refrigerant are required to accept a working fluid as a replacement. Thermodynamic Cycle Analysis: The cycle analysis was performed for HFC134a and DME/R600a in the composition of 0.0 to 1.0 mass fractions of DME by CYCLE_D 4.0 Software. All thermodynamic properties needed for the simulation were computed by REFPROP program. Table 1 lists the simulation conditions used in the analysis while Fig.1 illustrates the Volumetric Refrigerating Capacity (VRC) and COP for HFC134a and mixtures DME/R600a at various concentrations. Baseline COP and VRC of HFC134a are 2.467and 682.1 kj/m 3, respectively. The predicted COP of the mixture is 2.621 (+6.24%) higher than that of HFC134a in the composition range of 0.8 mass fraction of DME. The VRC increases linearly as DME is added and at 0.8 mass fraction of DME, the VRC of the mixture becomes very close to that of HFC134a. Since the same compressor is used in the experiments, the composition of the mixture to be analyzed is fixed to be 0.8 mass fraction of DME. Effect of Dimethyl-Ether Mass Fraction: The condensation and evaporation pressure decreases with the increase in mass fraction of the DME. The influence of the DME mass fraction on the performance of domestic refrigerator for mixture is shown in the fig. (1, 2). In mixture it is observed that the VRC increases with the increase in mass fraction.it is also observed that COP slightly increases as the mass fraction of dimethyl-ether increases. The main reason behind this is the rate of change of refrigerating effect which is higher than that of the specific work. Thus the average COP increases approximately 5.12% when the mass fraction rises for mixture.

COP VRC(KJ/m 3 ) 299 A. Baskaran and P. Koshy Mathews, 2015 Table 1: Effect on VRC and COP at various mass fractions of DME under simulation condition of T cod = 45 0 C T evap = -25 0 C T sh = 20 0 C. MF(DME) VRC COP 0.1 427.9 2.564 0.2 477.7 2.569 0.3 524.5 2.575 0.4 567.4 2.581 0.5 605.6 2.589 0.6 637.9 2.599 0.7 662.6 2.61 0.8 679.8 2.621 0.9 690.6 2.633 1 696.3 2.646 750 TC=45 0 C TE=-10 0 C Tsup=20 0 C VRC of R134a =682.1KJ/m 3 VRC of MIX =679.8KJ/m 3 700 650 600 550 500 450 400 0.0 0.2 0.4 0.6 0.8 1.0 Mass fraction of DME Fig. 1: VRC of RE170/R600a (mixture) as a function of Mass Fractions of DME. 3.5 TC=45 0 C TE=-10 0 C Tsup=20 0 C COP of R134a =2.467 COP of MIX =2.621 3.0 2.5 2.0 1.5 1.0 0.0 0.2 0.4 0.6 0.8 1.0 Mass fraction of DME Fig. 2: COP of RE170/R600a (mixture) as a function of Mass Fractions of DME.

Evaporating pressure(kpa) 300 A. Baskaran and P. Koshy Mathews, 2015 Method of Analysis: The software CYCLE_D 4.0 vapour compression cycle design program was used for the analysis to find the performance of the system. The ideal refrigeration cycle is considered with the following conditions. System cooling capacity (kw) = 1.00 Compressor isentropic efficiency = 1.00 Compressor volumetric efficiency = 1.00 Electric motor efficiency = 1.00 Pressure drop in the suction line = 0.0 Pressure drop in the discharge line = 0.0 Evaporator: average sat. Temp =-30⁰C to +10⁰C Condenser: average sat. Temp = 50⁰C Degree of Super heating = 10⁰C Degree of Sub cooling = 5⁰C The analysis of the variation of physical properties and performance parameters such as evaporation pressure (P evap ), pressure ratio, isentropic compression work (W), refrigerating effect (RE), power per ton of refrigeration, volumetric refrigeration capacity (VRC), discharge temperature (T Dis ), mass flow rate (MFR) and coefficient of performance (COP) of R134a and mixture are investigated in this theoretical study and they are plotted against the evaporating temperature (T evap ) as shown in the figures from 3 to 12. Table 2 shows the operation results and deviation of alternative refrigerant mixture from the values of R134a. Table 2: Operation on standard vapour-compression cycle using R134a and alternative Refrigerant mixture at T cod=50 0 C and T evap =-10 0 C with superheating 10 0 C and Sub Cooling 5 0 C. Parameters R134a MIXTURE Deviation % Evaporating pressure (kpa) 200.6 186.1-7.22 Compression Ratio 6.57 6.04-8.07 Refrigeration Effect (kj/kg) 137.3 302.3 120.26 Compressor Work (kj/kg) 41.42 86.61 109.1 Coefficient of Performance(COP) 3.315 3.491 5.31 Volumetric refrigerant capacity (kjm -3 ) 1314 1259-4.14 Discharge Temperature( C) 66.3 71.5 7.8 Compressor Power(kW) 0.302 0.29-5.3 Mass Flow Rate (kg/sec) 7.28 3.31-54.6 Power per ton of refrigeration (kw) 1.057 1.003-5.11 450 400 350 300 250 200 150 100 50 Fig. 3: Evaporating Pressure Vs evaporating temperature.

Refrigerating effect (kj/kg) Pressure ratio 301 A. Baskaran and P. Koshy Mathews, 2015 16 14 12 10 8 6 4 2 Fig. 4: Pressure Ratio Vs evaporating temperature. 320 300 280 260 240 220 200 180 160 140 120 Fig. 5: Refrigerating effect Vs evaporating temperature.

COP Compressor work (kj/kg) 302 A. Baskaran and P. Koshy Mathews, 2015 140 120 100 80 60 40 20 Fig. 6: Compression Work Vs evaporating temperature. 6.5 6.0 5.5 5.0 4.5 4.0 3.5 3.0 2.5 2.0 1.5 Fig. 7: COP Vs evaporating temperature.

Compressor power (kw) VRC(kJ/m 3 ) 303 A. Baskaran and P. Koshy Mathews, 2015 3000 2500 2000 1500 1000 500 Fig. 8: Volumetric refrigerating capacity Vs evaporating temperature. 0.50 0.45 0.40 0.35 0.30 0.25 0.20 0.15 Fig. 9: Compressor Power Vs evaporating temperature.

MFR*10-3 (kg/sec) Discharge Temperature ( 0 C) 304 A. Baskaran and P. Koshy Mathews, 2015 82 80 78 76 74 72 70 68 66 64 62 Fig. 10: Discharge temperature Vs evaporating temperature. 8 7 6 5 4 3 Fig. 11: Mass flow rate Vs evaporating temperature.

P/TR(kW) 305 A. Baskaran and P. Koshy Mathews, 2015 1.8 1.6 1.4 1.2 1.0 0.8 0.6 0.4 Fig. 12: Power per ton of refrigeration Vs evaporating Temperature. RESULTS AND DISCUSSION The changes in evaporating pressure (P evap) and pressure ratio with the evaporation temperature (T evap ) are shown in the fig 3 and 4 for listed refrigerants. The pressure ratio of refrigerant mixture substituted for R134a was 8.07% lower than that of R134a as shown in the table 2 for the constant condensation and evaporation temperatures of 50⁰C and -10⁰C respectively. Fig 5 and 9 show that the refrigerating effects (RE) increase with increasing evaporation temperature (T evap ) while the compressor power (W comp ) decreases with increasing T evap for the constant condensation temperature of 50⁰C and the evaporation temperature ranging from -30⁰C to 10⁰C. The alternative refrigerant mixture has much higher refrigerating effect and isentropic compression work than R134a in the Fig (5, 6) and as shown in the table 2. The variation of the performance coefficients (COP) with evaporating temperatures (T evap ) is illustrated in the Fig 7. It is found that the coefficient of performance (COP) increases as the evaporation temperature (T evap ) increases for the constant condensation temperature of 50⁰C and the evaporation temperature ranging from -30⁰C to 10⁰C. The performance coefficient (COP) of the alternating refrigerant mixture was found to be higher than that of R134a. The power needed for refrigeration with evaporation temperature (T evap ) was shown in Fig 9 and 12. The variation in volumetric refrigeration capacity, discharge temperature and mass flow rate were illustrated in Fig 8, Fig 10 and Fig 11 in order to verify the advantages of cycle. Comparison with Investigated Refrigerant Mixture: The refrigeration effect of mixture RE170/R600a is 116% to 124% higher than that of R134a at (-30 C to 10 C) evaporator temperature and 50 C condenser temperature. The average pressure ratio for the mixture RE170/R600a is nearly (5.03% to 11.97%) lower than that of R134a. Specific work of the mixture RE170/R600a is 109.06% to109.62% higher than that of R134a at (- 30 C to 10 C) evaporator temperature and 50 C condenser temperature. The COP of the alternative refrigerants is higher than that of R134a by about 3.47% to 7.56% over the range of operating conditions. The Compressor power for the alternative refrigerant is lower than that of R134a by about 2.96% to 7.17% over the range of operating conditions. The mass flow rate of the alternative refrigerant is lower than that of R134a by about 53.89% to 55.52% over the range of operating conditions Conclusions: In the present study, a theoretical investigation has been performed to evaluate the performance characteristics of the domestic refrigerator working with R134a and RE170 (80%) / R600a (20%)

306 A. Baskaran and P. Koshy Mathews, 2015 Mixture. The volumetric cooling capacity of R134a and alternative refrigerant mixture are same over the considered range of operating conditions. So it is concluded that the mixture is drop in replacement for R134a. The identified alternative offers desirable environmental requirements, that is zero ozone depletion potential (ODP) and lower global warming potential (GWP). REFERENCES Sekhar, S.J. and D.M. Lal, 2004. HFC134a/HC600a/HC290 Mixture a Retrofit for CFC12 System. International Journal of Refrigeration, 28: 735-743. Fatouh, M. and M. El-Kafafy, 2006. Assessment of Propane/Commercial Butane Mixtures as Possible Alternatives to R134a in Domestic Refrigerators, Energy Conversion and Management, 47: 2644-2658. Mohanraj, M., S. Jayaraj and C. Muraleedharan, 2007. Improved Energy Efficiency for HFC134aDomestic Refrigerator Retrofitted with Hydrocarbon Mixture (HC290/HC600a) as Drop-in Substitute, Energy for Sustainable Development, 11(4): 29-33. Nicholas Cox, 2010. Developments and opportunities using hydrocarbons refrigerant blends. Presented to Transforming Technologies Conference, London. www.earth care products.co.uk. Valentine Apostol, 2009. Thermodynamic Study Regarding the Use of Dimethylether as Eco Refrigerant REV. CHIM. (Bucureti) 60 Nr. 7, 2009. http/www.revistadechimie.ro. Adamson, B.M., 1998. Dimethyl Ether As An R- 12 Replacement IIR - Commissions B & E - Oslo, Norway. Ki-Jung Park, Dong Gyu Kang and C.S. Dongsoo Jung, 2010. Cooling Performance of Alternative Refrigerant R429A in Domestic Water Purifiers Department of Mechanical Engineering, Inha University, Incheon, Korea. Ki-Jung Park Yohan Lee Dongsoo Jung, 2010. Cooling performance of R510A in domestic water purifiers The Journal of Mechanical Science and Technology, 24(4): 873-878. REFPROP: Reference fluid thermodynamic and transport properties. NIST Standard reference data base 23-version 9.0, Gaithersburg (MD): National institute of standards and technology. Cycle, D., Vapour compression cycle design NIST Standard reference data base 23-version 4.0 Gaithersburg (MD): National institute of standards and technology.