FPC-02 Series. Installation and Operating manual

Similar documents
PYROSELF Innovative Snow Sensor and Controller for 2 x 24A loads outputs. Installation and Operating manual

ETNC24-FC-BAC-PIR-01 Owner s manual & Technician Settings

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

Touch Screen Thermostat. MTSC/SUPER/CO2, MTSC24/SUPER/CO2 Series. MTS/SUPER/CO2, MTS24/SUPER/CO2 Series. Owner s manual and technician settings

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

Touch Screen Thermostat. MTSC/SUPER, MTSC24/SUPER Series. MTS/SUPER, MTS24/SUPER Series. Owner s manual and technician settings

ETN-24-SUPER-SF Series

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

FMT24-SUPER-2S-FP-PROG-F Owner s manual & Technician Settings. Installation

SP-1000X. Panic Device Power Controller Installation Guide. Rev

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits

CommStat 4 Controller

OWNER S MANUAL Venstar Inc. 08/07

QD-ENG-68 Controller for Thermoelectric Thermal Management

Model: Touch-RS. 1 Touch-RS

HeatNet Manual Control Adjustment and Operation Instructions for Hydrotherm Firmware Version 2.8

Installation Instructions

Carbon Monoxide Transmitter

ETN24-P/PD-FC-SUPER2. Owner's Manual - Installation and Operating Instructions

OWNER S MANUAL DLFCAB / DLFCHB / DLFDAB / DLFDHB High Wall Ductless System Sizes 09 36

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

Freeze Protection Thermostat TRACON MODEL GPT 3 Installation and Operation Manual

INSTALLATION MANUAL. * If using remote sensors the thermostat must be hardwired. Need Help?

SAFETY INFORMATION AND WARNINGS

Smart Temp. Model

REMOTE CONTROL FOR CHILLER MYCHILLER

RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control

HEAT HEAT HEAT COOL COOL

INSTALLATION MANUAL. Need Help? This manual covers the following models: T915. Power Type. Thermostat Applications Guide. Page.

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to oven before servicing, unless testing requires power.

SOLO User Guide. Description. Installation. Programmable Dual Voltage Thermostat 240 V (120 V)

ADDITIONAL INFORMATION

Installation, Start-Up, and Operating Instructions

Thermostats. Digital Non-Programmable. GEAppliances.com. Owner s Manual & Installation Instructions RAK148D2 RAK164D2

Control manual. Series. Gas-fired direct vent Cast iron boilers. Control adjustment and Operation instructions

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB

ETN-24-SUPER-PROG (US Program - Celsius)

Installation Guide for models:

7-Day. Digital Thermostat. residential. & 2-cool

UPM I. Unit Protection Module. Installation and Operation Manual (2015/06)

I/O ZONE 560/583 AND OPERATION MANUAL

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

INSTALLATION INSTRUCTIONS

Installation Guide for models:

PowerLogic Branch Circuit Power Meter (BCPM)

MANUAL Rev. C 02/15 (800) Environmental Technology, Inc.

F I R E G A R D D C EXTENDED PERFORMANCE RELEASE DEVICE SAFE A N D SECURE

ATA11U03. Non-Programmable Heat Pump Thermostat. Installation Manual. 97B0082N06 Revised: 16 September, 2013 FOR INSTALLER AND OWNER ONLY

OWNER S MANUAL Venstar Inc. 08/07

OWNER S MANUAL Venstar Inc. 08/07

HEAT COOL. Meets Commercial California Title 24

VENSTAR T1070 FAN COIL THERMOSTAT PROGRAMMABLE 2 OR 4 PIPE SYSTEMS OWNER S MANUAL AND INSTALLATION INSTRUCTIONS

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual

1F Non-programmable Electronic Digital Heat Pump Thermostat INSTALLATION AND OPERATION INSTRUCTIONS

RC-101 Heat Pump Real Time Pricing System 2 Stage Heat / 1 Stage Cool

M2500 Engine Controller Installation Manual

I/O ZONE 560/583 USERS GUIDE

CEM-24 Series. Owner's Manual - Installation and Operating Instructions

Refrigerated air dryers

Product Manual SZ1145

Installation, Operation & Service Manual

VTI MODEL itc5000 HEAT TRACING CONTROL SYSTEM OPERATIONS MANUAL

1F Non-Programmable Electronic Digital Multi-Stage Thermostat INSTALLATION AND OPERATION INSTRUCTIONS

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to range before servicing, unless testing requires power.

Lubrication cycle IP Enclosure Rating. 110 VAC, 220/230 VAC (50/60 Hz) Alarm Fault Relay Contacts. IP-55 (Liquid tight connector)

VENSTAR T1075 FAN COIL THERMOSTAT 7 DAY PROGRAMMABLE 2 OR 4 PIPE SYSTEMS OWNER S MANUAL AND INSTALLATION INSTRUCTIONS

Model: PRT2-TS / PRT2-NTS EU. Model: Touch Duo

Dual Technology Wall Switch Occupancy Sensor. Manual & Specification

RC-90 / RC-90B Single Stage Heat/Cool Thermostat for Zone Control Systems Installation Instructions

ELECTRONIC COMMUNICATING THERMOSTAT

Smart Temp. ApolloP/n Installation Manual. Version 1.0

Installation and Operation Manual

Heat Transfer Products, Inc. 120 Braley Road East Freetown, MA The first totally integrated multiple boiler management control.

Product Manual SZ1144

DPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1-

Installation Instructions. PS902 Power Supply. These instructions cover the following parts: PS902 Power Supply Specifi cations:

HEAT HEAT HEAT COOL COOL PUMP OWNER S MANUAL 7-DAY TOTALINE

Product Manual SZ1009

Installation and Maintenance Manual IM

INSTALLATION MANUAL. This manual covers TopTech models: TT-N-851. Need Help? Power Type. Thermostat Applications Guide. Page.

Model GIT 4 Gutter Snow and Ice Melting Control

Series. Access Power Controllers. Installation Guide

Years. We Believe Experience Matters. Thermostats & Controls

RCS Residential Control Systems Inc.

SC Installation, Operation & Application Guide

Typical Installation Breaker Box Class A 50 amp, 120/240 volt, GFCI

WATER HEATER ELECTRONIC CONTROLLER USER MANUAL

Two-Channel Gas Controller

Product Manual SZ1022/SZ1031/SZ1035/

SECTION ELECTRIC FLOOR HEATING AND SNOW MELTING EQUIPMENT

2 THERMOSTAT DETAILS 3 REMOVING OLD THERMOSTAT

Networkable Fan Coil Controller Specification and Installation Instructions

Digital Non-Programmable

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

INSTALLATION/OPERATING INSTRUCTIONS BCP-3. Hot Water Reset Control For up to 3 Boilers. How the BCP-3 operates... 1:4 1:3 1:2 1:1.

Transcription:

Installation and Operating manual

Index Introduction.... 3 FPC-02 Installation notes......... 4 Wiring the FPC-02-120V, FPC-02-120V-MDB. 5 Wiring the FPC-02-240V, FPC-02-240V-MDB. 6 Operating instructions. 7 Turning the system ON and OFF. 7 Selecting temperature scale.. 7 Selecting Automatic or Manual mode. 7 Heater indication..... 7 Snow flake icon and digital time indication. 7 Technician settings.. 8 Enter technician settings mode.... 8 P01 - Temperature set point. 8 P02 - Lower limit temperature for heating.. 9 P03 -Time delay before stopping the heater...9 P04 - Manual mode ON time. 10 P05 Not in use.. 10 P06 - Enable/Disable 2 nd temperature sensor (Aquastat) 10 P07 Not in use.. 11 P08 MODBUS MAC Address for building automation (option).... 11 P09 - Test conditions mode.. 12 Save changes and return to normal display...... 12 Restore default values. 12 DIP Switch settings.. 13 DIP switch S2 - Short measuring times (test only)... 13 DIP switches S3 and S4 not in use...... 13 Temperature reading errors... 14 MODBUS communication error.... 14 Temperature sensor not connected or short circuit..... 14 Calibrating and testing the internal GFCI.. 14 MODBUS object list..... 15 Pg. 2

Introduction The power boxes offer smart and easy control for HEAT TRACING SYSTEMS. It can operate one heating zones. Typical applications include pipes, valves and gutters. The backlit LCD screen provides full interface and information to the system status. The FPC-02 offers various operating and programming options such as: - Switchable temperature scales ( F or C) - Adjustable Lower ambient temperature limit to stop - Both Automatic and Manual modes heater (lockout) - Energy saving temperature limit - Commissioning/Test environment - Adjustable heater hold on off delay FPC-02 General system layout Operating panel Aquastat sensor (option) ON FPC-02 Temperature sensor Zone 1 Pipe Sensor Heater Pg. 3

Installation PLEASE READ THIS MANUAL AND THE SAFETY WARNINGS CAREFULLY BEFORE INSTALLING AND USING THE CONTROLLER AND SAVE IT FOR FUTURE USE Installation notes Familiarize yourself with the markings, warnings, components and terminology. The FPC-02 power boxes and its accessories must be installed by a qualified electrician in accordance with local regulations and the requirements of the NEC (NFPA 72 ) and the CEC part 1. WARNING: Ensure the power is disconnect from all circuits before mounting the power box and making any connections. Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death. Installer must ensure the installation of approved disconnect means, for all power supply circuits feeding this unit. The power boxes are suitable for indoor wall mount installation only. Ensure wiring according to the provided schematics using copper conductors only. Make sure the wire gauge (AWG) is suitable for the circuit amperage draw, as specified in the NEC/CEC table 1. Ensure that the main breakers (fuses) are suitable for the heating systems rating (80% load). Grounding means must comply with local regulations and CEC/NEC. Ensure that the heating system/de-icing system connected to this unit complies with the UL 499 or UL 515 & CSA 22.2 # 130.3 standard and is certified / listed by an NRTL. Ensure that all wiring is rated for the application at 60 C (140 F as per UL 515 CSA 22.2 #130 clause 12 table 12.1. Beware that any holes punched for conduit are to compromise the integrity of the enclosure ratings. Ground fault equipment protection (GFEP) The ground fault interrupter/residual current detector installed in this system is a Non class A GFCI, intended for equipment protection. Familiar yourself with its operation and required setting. The GFEP should be tested monthly. Please refer to the GFEP testing instructions on page 14 of this manual. Pg. 4

Wiring the FPC-02 Heater load connection Provide terminals L, N with up to 120 VAC, 30 AMP. Make sure the wire Gauge (AWG) is suitable for the circuit Amperage draw, as specified in the NEC/ CEC table 1. Caution: Incorrect voltage may cause fire or seriously damage the unit. FPC-02-120V N N L L NO NC HE C C 1 2 Main Supply 120 VAC Branch circuit protection and disconnect provided by installer. Max. 30A Heater Load connection 120 VAC, 30A GFEP Indication Dry Contact (NO/NC) *See table Heat Indication (24VAC) PYROULS (By Meitav-tec) Aquastat (option) FPC-02-120V-MDB N N L L NO NC HE C C 1 2 A B RS485 Main Supply 120 VAC Branch circuit protection and disconnect provided by installer. Max. 30A Heater Load connection 120 VAC, 30A GFEP Indication Dry Contact (NO/NC) *See table Heat Indication (24VAC) MODBUS Communication cable 2x22AWG Twisted, Shielded PYROULS (By Meitav-tec) Aquastat (option) *GFEP Indication - Dry Contact NO - COM NC - COM GFEP Tripped GFEP NOT Tripped SHORT OPEN OPEN SHORT Pg. 5

Wiring the FPC-02 Heater load connection Provide terminals L, N with up to 240 VAC, 30 AMP. Make sure the wire Gauge (AWG) is suitable for the circuit Amperage draw, as specified in the NEC/ CEC table 1. Caution: Incorrect voltage may cause fire or seriously damage the unit. FPC-02-240V L1 L1 L2 L2 NO NC HE C C 1 2 Main Supply 240 VAC Branch circuit protection and disconnect provided by installer. Max. 30A Heater Load connection 240 VAC, 30A GFEP Indication Dry Contact (NO/NC) *See table Heat Indication (24VAC) PYROULS (By Meitav-tec) Aquastat (option) FPC-02-240V-MDB L1 L1 L2 L2 NO NC HE C C 1 2 A B Main Supply 240 VAC Branch circuit protection and disconnect provided by installer. Max. 30A Heater Load connection 240 VAC, 30A GFEP Indication Dry Contact (NO/NC) *See table Heat Indication (24VAC) RS485 MODBUS Communication cable 2x22AWG Twisted, Shielded PYROULS (By Meitav-tec) Aquastat (option) *GFEP Indication - Dry Contact NO - COM NC - COM GFEP Tripped GFEP NOT Tripped SHORT OPEN OPEN SHORT Pg. 6

Operating instructions Turning the system ON and OFF Press and hold the [ON] button for 0.5 seconds to turn the system ON or OFF. The words ON or OFF will appear on display. When ON, the green LED on the front panel will also turn ON. Selecting temperature scale Press the [+] button for Celsius. Press the [-] button for Fahrenheit. Selecting Automatic or Manual mode Press the [SELECT] button to switch between modes: Automatic Heating will start and stop automatically depending on the set point and ambient temperatures. Manual ON Heating will start regardless of the set point and ambient temperatures and will stop after a preset time (pls. refer to the Manual ON section in the tech. settings). Note: Mode will always return to Automatic after switching the unit OFF and ON. Heater indication Black icon Heater ON White icon Heater OFF Heater ON Heater OFF When ON, the red LED on the front panel indicating heater operation will also turn ON. Snow flake icon and digital time indication A solid snow flake icon will appear on display during normal heater operation. A blinking snow flake icon will appear on display during heater off delay or when manual mode is activated. The digital clock will count down the remaining time until the heater is turned off. The snow flake icon will disappear from display as long as the heater is turned off. Pg. 7

Technician settings Use the technician settings mode to view and adjust the following parameters: P01 P02 P03 P04 P05 Temperature set point Lower ambient temperature limit to stop the heater Time delay before stopping the heater ON time for manual mode Not in use P06 Enable/Disable 2 nd temperature sensor logic (Aquastat) P07 Not in use P08 MODBUS MAC Address for home automation system (option) P09 Commissioning / Test mode Restore defaults Enter technician settings mode Disconnect power and open the internal door by releasing the two screws. Move DIP switch S1 located on the side of thermostat to ON position. Press the [SELECT] and [+] buttons simultaneously to move forward to the next technician parameter. Press the [SELECT] and [-] buttons simultaneously to return to the previous technician parameter. Enter technician settings mode Save changes and exit technician settings mode Move DIP switch S1 located on the side of thermostat to OFF position. Important: Changes made to technician parameters will not take effect as long as DIP switch S1 is in ON position. Parameters: P01 - Temperature set point Move DIP switch S1 located on the side of thermostat to ON position. P01 and the temperature set point will appear on display. Use the [+] and [-] buttons to adjust the temperature set point. Range: 5 60 F / -15 +15 C, Default: 37 F / 3 C As long as the ambient temperature is lower than the temperature set point P01, the FPC-02 will turn ON. Save changes and exit technician settings mode Temperature set point Pg. 8

Technician settings (Cont ) P02 - Lower limit temperature for heating Press the [SELECT] and [+] buttons simultaneously. P02 and the low limit temperature will appear on display. When the temperature on the temperature sensor drops below the low temperature limit, the heating system will stop. Use the [+] and [-] buttons to adjust the temperature set point. Range: -40 +23 F / -40-5 C Default: -40 F / -40 C Press the [SELECT] and [+] buttons simultaneously again. The word ON or OFF will appear on display. Use the [+] and [-] buttons enable (ON) or disable (OFF) the P02 parameter. If disabled, the heating system will operate without low temperature limitations. P03 -Time delay before stopping the heater Press the [SELECT] and [+] buttons simultaneously. P03, dl and the time delay before stopping the heater (Hold ON) will appear on display. The hours will blink. Use the [+] and [-] buttons to adjust the hours of the time delay. Range: 0000...9999 minutes Default: 120 minutes Note 1. The time delay countdown will start when the ambient temperatures rises above the set point temperature. Note 2. The staggering sequence will continue during the time delay period. P02 enabled Low limit Temperature P02 disabled Time delay (minutes) Pg. 9 Cont

Technician settings (Cont ) P04 - Manual mode ON time Press the [SELECT] and [+] buttons simultaneously. P04, On and the time Manual ON mode time period will appear on display. The hours will blink. The delay time parameter defines a time frame in which the heater remains ON after receiving an Manual ON command. Use the [+] and [-] buttons to adjust the hours of the working time. Range: 00...99 hours Default: 03 hours Press the [SELECT] and [+] buttons simultaneously again. The minutes will blink. Use the [+] and [-] buttons to adjust the minutes of the working time. Range: 00...59 minutes Default: 00 minutes Manual ON (minutes) P05 Not in use Press the [SELECT] and [+] buttons simultaneously. P05 will appear on display. Proceed to P06. P06 Enable/Disable Temperature sensor / Aquastat logic Press the [SELECT] and [+] buttons simultaneously. P06 and the number 0 or 1 will appear on display. Use the [+] and [-] buttons to select between: 0 - Logic set by both TEMPERATURE SENSOR and AQUASTAT (default). 1 - Logic set by TEMPERATURE sensor only. 2 - Logic set by AQUASTAT sensor only Logic by temperature sensor and aquastat Logic by temperature sensor only Logic by aquastat sensor only Pg. 10 Cont

Technician settings (Cont ) P07 Not in use Press the [SELECT] and [+] buttons simultaneously. P07 will appear on display. Proceed to P08. P08 MODBUS MAC Address (for MDB models only) Press the [SELECT] and [+] buttons simultaneously. P08 and the MODBUS MAC Address will appear on display. Use the [+] and [-] buttons to set the MAC Address of the unit. Setting the MAC address for the unit will make it available through the home automation system. Range: 0 60. Select 0 for NO COMMUNICATION system (default). MODBUS MAC Address Pg. 11 Cont

Technician settings (Cont ) P09 - Test conditions mode / Technician commissioning mode Turn ON test conditions to check the functionality of the system regardless of temperature sensors parameters (i.e. during the summer). In test conditions, the Ambient temperature is always -7 C/19 F. Press the [SELECT] and [+] buttons simultaneously. P09 will appear on display. The hours will blink. Use the [+] button to enter test/commissioning mode the word Test will appear on display. Use the [-] button to manually exit test/commissioning mode the word Test will disappear from display. Note: If the technician did not manually exit test/commissioning mode, the unit will automatically return to normal mode after 5 hours. Test conditions mode Save changes and return to normal display In order to save changes and return to normal display, move DIP switch S1 back to OFF position. Important: Changes made to technician parameters will not take effect as long as DIP switch S1 is in ON position. Restore default values Move DIP switch S1 to ON position. Press and hold the [ON] button for 10 seconds. The controller will beep. Move DIP switch S1 back to OFF position. Pg. 12

Technician settings (Cont ) DIP switch S2 - Short measuring times (test only) Use DIP switch S2 to short the - ON - Short measuring times for test/commissioning only (measuring times will be divided by 60). - OFF - Normal operation. Short measuring times: A real 1 hour will take 1 minute and a real 1 minute will take 1 second. DIP switches S3 and S4 Not in use (must be in OFF position) S3 OFF, S4 OFF Pg. 13

System Errors Error 1 MODBUS Communication error Aux1 Will appear on display. Communication error Error 2 Temperature sensor is not connected or short circuit SensErr 1 Will appear on display. Temperature Sensor error GFEP The GFEP is designed to provide protection for electrical equipment. GFEP TEST The GFEP should be tested monthly. Press the blue T test button to trip the outlet and break the circuit. The YELLOW LED on the front panel should lit. Lift the RESET GFEP button to return to normal operation and reestablish power and protection. Test button Reset button Pg. 14

Object list (for MDB models only) OBJECT LIST FOR FPC-02-MDB Series rev. 1.0 MODBUS RTU Mode, Address Slave 1-60, Baud Rate 9600, n, 8, 1 All Registers Signed Integer 16 bit, R - Register Read Only, R/W - Register Read/Write Dec,[Hex] Value Description Read/Write 0, [0000] -13 F.. 54 F/ -40..+16 C Measured Temperature R 1, [0001] 5 F... 59 F /-15 C...+15 C P01 Temperature set point R/W 2, [0002] -40 F... +23 F/-40 C...-5 C P02 Lower temperature limit for heating R/W 3, [0003] min (0-9999) P03 Time delay before stopping the heater R/W 4, [0004] min (0-9999) P04 Manual mode ON time R/W 5, [0005] 60 P05 Not in use R 6, [0006] 0,1,2 P06 Enable/Disable temp. sensor/aquastat logic R/W 7, [0007] P07 Not in use R/W 8, [0008] 0/1 P09 Test conditions mode R/W 9, [0009] 0/1/2 Heater 1 (0-OFF, 1-ON, 2-Not in use) R/W 10, [000A] 0/1/2 Not in use R/W 11, [000B] 0/1/2 Not in use R/W 12, [000C] 0/1/2 Not in use R/W 13, [000D] 0/1/2 Not in use R/W 14, [000E] 0/1 Aquastat Signal (0-OFF, 1-ON) R 15, [000F] 0/1 SW1 R 16, [0010] 0/1 SW2 R 17, [0011] 0/1 SW3 Not in use R 18, [0012] 0/1 SW4 Not in use R 19, [0013] 0/1 ON/OFF (0-OFF, 1-ON) R/W 20, [0014] 0/1 Celsius/Fahrenheit (0-F, 1-C) R/W Pg. 14