Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

Similar documents
AL800ULADA. NAC Power Extender. Installation Guide

AL600ULADA. NAC Power Extender. Installation Guide

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

AL1002ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

AL1042ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

AL602ULADA AL802ULADA AL1002ULADA

AL1042ULADA. NAC Power Extender. Installation Guide (See Application Guide for additional information) Rev

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

ACSI Series 1550K-MD and 1550-MD Motor Drive Electric Latch Retraction

Installation Guide for models:

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

Series. Access Power Controllers. Installation Guide

AL600ULX Series. Power Supply/Charger. Installation Guide

Installation Guide for models:

10-175UL INSTALLATION. Power Supply UL. Access Control Power Supply/Charger. Installation and Specifications Manual

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

SP-1000X. Panic Device Power Controller Installation Guide. Rev

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

ACM8 & ACM8CB. Access Power Controllers Installation Guide. - Fused Outputs - Fused Outputs. - PTC Outputs - PTC Outputs. Models Include: Rev.

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

Rack Mount Series Installation Guide

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

Access Power Controllers with Power Supplies

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)

ACM8 Series UL Listed Sub-Assembly Access Power Controllers. Installation Guide. ACM8 - Eight (8) Fuse Protected Outputs

ACM4 Series UL Listed Sub-Assembly Access Power Controllers

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

FireNET Plus Wiring Instructions

LifeAlarm Fire Alarm Controls

MR-2602 Two Zone Fire Alarm Control Panel

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

Specification/ Data Sheet

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

TECHNICAL DATA OBSOLETE

Booster Power Supply Manual

Release Control Fire Alarm Systems

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

TrueAlert Notification Appliances

30.45 Electric Release PDRP-2001

CONVENTIONAL FIRE ALARM CONTROL UNITS. MR-2300 SERIES Fire Alarm Control Units MEA

PSN-1000 & PSN 1000(E) Installation Manual

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

IP Access FACP Adapters. Installation Guide. Entrada2DMK - IP Access FACP Adapter Kit. Kit Includes: Entrada2DMR - IP Access FACP Receiver

more than just power! Altronix is the professional security industry s leading manufacturer

July 14, 1999 DF C-100.

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

Addressable Fire Alarm Control Panel

Remote NAC Power Supply D7038

Model 17A00 Expansion Enclosure

June 10, 2002 DF C S2424

PN: 51883:D ECN Field Charger/Power Supply FCPS-24FS6 FCPS-24FS8. Document # /14/05 Revision: D

CONVENTIONAL FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels MEA. Features. Description

1. POWERPATH Operation

Interface and EOL Modules 8

IFP-2000 F r a en e h n y h t y PH P D

Commercial and Light Industrial Fire Alarm Control Panel

LifeAlarm Fire Alarm Control Panels

Notification Appliance Circuit Module

Conventional Fire Alarm System 2014 V1.2

Addressable NAC Output Module D327A

MODEL B2 INSTALLATION MANUAL

INSTALLATION GUIDE XR5FC AND XR5SL COMMERCIAL FIRE PANELS

Installation, Operating and Maintenance Manual

/5121/5122 TrueAlert Power Supply Installation Instructions

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

AND ARCHITECT SPECIFICATIONS

XP6-C. Six Circuit Supervised Control Module and SYNC-1 Accessory Card

TrueAlert Addressable Notification Appliances

Operation and Installation Guide. Fire Alarm Control Panel

TrueAlert Addressable Notification Appliances

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

Field Charger/Power Supply FCPS-24S6 FCPS-24S8. Document # /06/03 Revision: C1 PN: 51977:C1 ECN

M O D E L S F I R E G A R D M C V ADVANCE FIRE CONTROL RELEASE DEVICE

RELEASE DEVICE CONTROLS

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

LiftMaster 300 Windsor Drive Oak Brook, IL LiftMaster.com

Conventional Releasing Control Panel

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

Functional Performance Test

I TS-12 1 Y K DO WHAT THEY DON T. Model. INSTALLATION lnstrljctlons. FIRE BURGLARY lnstrumentsrn INC.

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

LED Driver Module. These instructions contain procedures to follow in order to avoid personal injury and damage to equipment.

Electric Release Panel Wiring Tips

Installation Instructions. PS902 Power Supply. These instructions cover the following parts: PS902 Power Supply Specifi cations:

Fire Burglary Instruments Inc. XL-2G Gold Control/Communicator Installation Training Seminar Rev. 5/96

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

Control/Communicator 5110XM. Installation Instructions Installation Instructions Installation Instructions N8026 4/96

SILENT KNIGHT Installation Manual. Distributed Power Module. Part Number G, 08/03

Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual

Transcription:

Installation Guide for AL800UL-ADA NAC Power Extender Rev. 090500

Overview: The Altronix AL800UL-ADA is an extremely cost effective 8 amps voltage regulated remote power supply /battery charger. The AL800UL-ADA may be connected to any 12 or 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification Appliance Circuit (NAC) expansion (supports ADA requirements) and will provide auxiliary power to support system accessories. The unit delivers regulated and filtered 24 or 12 volt power via four (4) Class B, two (2) Class A or two (2) Class B and one (1) Class A Notification Appliance Circuits. Additionally, a separate 50mA auxiliary output with reset for four (4)-wire smoke detectors. The 8 amps rated supply current can be divided between the four (4) outputs for powering notification appliances. Each output is rated at 2 amps max., and can be independently programmed for Steady, Temporal Code 3 or *Strobe Synchronization. All outputs may be programmed for Input to Output Follower Mode (output will follow input. i.e. March Time Input, March Time Output). An individual output of 4 amps is achieved by paralleling 2 outputs. The AL800UL-ADA in non-alarm condition provides independent loop supervision for Class A and/or Class B FACP NAC circuits. In the event of a loop trouble the FACP will be notified via the AL800UL- ADA s steered input (input 1 or input 2). In addition, there are common trouble output terminals (NC, C, NO) which are used to indicate general loop/system trouble. A common trouble input is provided for optional NC (normally closed) devices to report trouble to the FACP. Two (2) FACP signaling outputs can be connected to AL800UL-ADA s inputs. These inputs can then be directed to control supervision and power delivery to any combination of the four (4) outputs. Specifications: UL Listed (UL864) CSFM - California State Fire Marshal Approved MEA - NYC Department of Buildings Approved NFPA 72 Compliant. Input 115VAC/60 Hz, 3.2 amps Field selectable 24VDC or 12VDC voltage regulated power limited outputs. 24VDC or 12VDC rated @ 8 amps max. Typical 8.6 mv output voltage ripple. Separate 50mA auxiliary output with built-in and remote reset capability. Two (2) outputs may be paralleled for more power on an indicating circuit. Two (2) Class A or two (2) Class B FACP inputs. Two (2) NC dry contact trigger inputs Programmable supervised indicating circuit outputs: Four (4) Class B or Two (2) Class A or One (1) Class A and Two (2) Class B. Temporal Code 3, *Strobe Sync Mode, Steady Mode, Input to Output Follower Mode (maintains synchronization of notification appliances circuit) March Time Compatible with 12 or 24VDC fire panels. Filtered and electronically regulated output. Output loop supervision steered to input 1 or input 2. Common trouble input and output. Ground fault detection. Built-in charger for sealed lead acid or gel type batteries. Automatic switchover to stand-by battery when AC Fails. Zero voltage drop when switching over to battery backup. Thermal and short circuit protection with auto reset. Circuit breaker battery protection. Input and output status LED indicators. AC fail supervision (form "C" contact, 1 amp 28VDC or 115VAC). Factory set for 1 minute with optional 6 hour delay setting (field selectable). Battery presence and low battery supervision (form "C" contact, 1 amp / 28VDC or 115VAC). Unit includes power supply, red enclosure, cam lock, open frame transformer and battery leads. Enclosure dimensions: 15.5"H x 12"W x 4.5"D *See pg. 3 AL800UL-ADA - ADA Compliant NAC Power Extender Installation Guide 2 Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.

OUT1 OUT3 OUT2 OUT4 UPPER TERMINALS LOWER TERMINALS Power Supply Specifications: AC Input: Output: Battery: Stand-by Current: Resistor: (end of line) 115VAC / 3.2 amps @ 60Hz 12-24VDC. Maximum 2.0 amps per output. Total of 8 amps in Alarm Condition. For 12VDC operation use a 12VDC / 12AH battery For 24VDC operation use two (2) 12VDC / 12AH batteries connected in series 75mA (2200 ohm) Stand-by Specifications: Stand-by Batteries Stand-by Time Alarm Output Aux Output Total Amps/Minutes Current 24VDC/12AH 24 Hours 8 Amps/15 Minutes 50mA (use two (2) 12VDC batteries in series) 60 Hours 8 Amps/5 Minutes - 12VDC/12AH 24 Hours 8 Amps/15 Minutes 50mA 60 Hours 8 Amps/5 Minutes - Installation Instructions: The AL800UL-ADA should be installed in accordance with article 760 of The National Electrical Code or NFPA 72 as well as all applicable Local Codes. 1. Mount the AL800UL-ADA in a desired location. It is recommended to first review the following tables for screw terminals, switch selection and LED status indications. This will greatly facilitate installation hook-up. Carefully review: Power Supply Specifications (pg. 2) Typical Application Diagrams (pg. 5) Terminal Identification Table (pg. 4) Output Programming Selection Table (pg. 3) LED Status Indication Table (pg. 3) 2. Connect the black and white transformer leads of AL800UL-ADA to a separate unswitched AC circuit (115VAC, 50/60Hz) dedicated to the Fire Alarm System (Fig. 1). 3. Set switch SW1 on Power Supply Board for desired output voltage. Open for 24VDC (factory set), Close for 12VDC. Note: It is good operating practice to measure and verify output voltage before connecting devices to ensure proper operation of equipment. 4. Connect battery to terminals marked [+ BAT -] on the Power Supply Board (battery leads included). Use two (2) 12VDC batteries connected in series for 24VDC operation. 5. Set output selection switches marked (OUT1 through OUT4) to follow corresponding input (IN1 & IN2) and desired output signal type (Temporal Code 3, Strobe synchronization, Steady output or input to output synchronization) (see output programming selection table pg. 3). 6. Connect FACP output to desired AL800LGK logic board inputs and notification appliances to desired AL800LGK logic board outputs (see typical application diagrams pg. 6). 7. For connection of smoke detectors, digital dialer (see optional hookup diagram pg. 6). 8. To report a ground fault connect negative (-) terminal of the auxiliary output marked [-AUX] to earth ground. BAT FAIL NO NC C AC FAIL C NC NO AC TROUBLE DELAY OPTI DC J1 SW2 SW1 AL801ULB POWER SUPPLY --- AUX + AUX RESET + OUT1 -- NO "REMOTE " C --- DC + VR1 AL800LGK + OUT2 -- + OUT3 -- + OUT4 -- SW1 OPEN = 24V CLOSED = 12V + DC --- + BAT --- AC AC IN1+ IN1-- IN2+ IN2-- C "DRY1" NC RET1+ RET1-- RET2+ RET2-- C "DRY2" NC BROOKLYN, NY 11220 MADE IN USA AC OUT1 OUT2 OUT3 OUT4 INP1 INP2 FAULT NO C NC C "FAULT" NC Black Lead Fig. 1 XFMR White Lead 115VAC input 50/60 Hz, 3.2 amps Green Lead (ground) General Information: For all Class B hookups SW1 & SW2 on the AL800LGK logic board must be open. For all Class A hookups SW1 & SW2 on the AL800LGK logic board must be closed. AC Fail condition will report approximately one (1) minute after loss of AC. To delay report for 6 hours cut jumper J1 on the Power Supply Board (AC trouble output delay option). If this mode is selected the Power Supply Board must be reset by removing all power to it for 30 seconds. Low battery condition will report at approximately 21VDC (24VDC output setting) 3

or approximately 10.5VDC (12VDC output setting). Battery presence detection will report approximately 5 minutes after battery remains undetected (missing or removed). It is recommended (not required) to control visual notification appliances (strobes) via input 1 ( IN1) and audible notification appliances (horns) via input 2 ( IN2). This allows audible notification appliances (horns) to be silenced while visual notification appliances (strobes) continue to operate. Output Programming Selection Table: Outputs must be programmed independently (OUT1 - OUT4) Function Switch Positions Descriptions OFF Input/Output 4 Output will be controlled by input 1 (IN1). Select 4 Output will be controlled by input 2 (IN2). Temporal Code 3 3 Enables Temporal Code 3 signal generation output. Mode This mode will accept a steady or a pulsing input. 3 Disables Temporal Code 3 signal generation output Input to Output 1 Output follows signal it receives from the corresponding input (i.e. FACP Follower Mode Sync module - maintains synchronization of notification appliance circuit. 1 Disables Input to Output Follower Mode. Steady Mode 1, 2, 3 A steady output signal will be generated. This mode will accept steady or pulsing input. March Time 2, 3 Enables a March Time output which will sound 60 beats (60 beats per minute) per minute. This mode will accept a steady or pulsing input. Strobe Sync 2 Enables Strobe synchronization mode 1 (50 ms pulse every 1 second). Mode 1 Will accept a steady or pulsing input. (Gentex ) *Strobe Sync 1, 2, 3 Enables Strobe synchronization mode 2 (30 ms pulse every.95 second). Mode 2 Will accept a steady or pulsing input. (System Sensor ) Strobe Sync 1, 2 Enables Strobe synchronization mode 3 (40 ms pulse every 1 second). Mode 3 Will accept a steady or pulsing input. (Faraday) Strobe Sync 1, 3 Enables Strobe synchronization mode 4 (60 ms pulse every 1 second). Mode 4 Will accept a steady or pulsing input. (Amseco) *Strobe Sync Mode Information Sychronization is defined as the simultaneous flash of all visual signals in a given field of view. LED Status Indication Table: LED OFF BLINKING Out 1 Normal Alarm Condition Trouble Condition Out 2 Normal Alarm Condition Trouble Condition Out 3 Normal Alarm Condition Trouble Condition Out 4 Normal Alarm Condition Trouble Condition Input 1 Normal Alarm Condition Trouble Condition Input 2 Normal Alarm Condition Trouble Condition Fault Normal System Trouble N/A AC AC Loss AC present N/A DC No DC Output DC present N/A Output Dip Switches IN>OUT SYNC (AL800LGK Board) 4

Terminal Identification Table: AL800LGK Logic Board Terminal Legend IN1+, IN1- IN2+, IN2- RET1+, RET1- RET2+, RET2- C DRY1 N.C. C DRY2 N.C. (Dry input trigger) Function/Description These terminals connect to the 12 or 24VDC FACP notification appliance circuit outputs. (Class A or Class B) Input trigger voltage is 9-30VDC @ 5mA min. Terminal polarity is shown in alarm condition. During an alarm condition these inputs will cause the selected outputs chosen to drive notification appliances. The designated outputs are set by output switches OUT1 through OUT4 (see Output Programming Selection Table pg. 4). A trouble condition on an output loop will cause the corresponding input to trip the FACP by opening the FACP loop. An alarm condition will always override trouble to drive notification appliances. For Class A hookups these terminal pairs return to FACP NAC1 and/or NAC2. For Class B hookups the FACP resistor from the NAC1 and/or NAC2 outputs are terminatedat these terminals. Optionally, other notification appliances or additional signaling circuit power supplies may be connected to these terminals. If this option is chosen the resistor must be terminated at the last device. An open across these terminal pairs will cause the selected outputs chosen to drive notification appliances. The designated outputs are set by output switches OUT1 through OUT4 (see Output Programming Selection Table pg. 4). Note these inputs are unidirectional and will not report a trouble condition to the FACP. + OUT1 - Notification appliances are connected to these outputs (see typical application diagrams + OUT2 - pg. 6). Each power limited output will supply 2 amps. Two (2) outputs may + OUT3 - be connected in parallel for a maximum NAC output capability of 4 amps. Total supply + OUT4 - current is 8 amps. Outputs are controlled by designated input 1 (IN1) or input 2 (IN2) (see Output Programming Selection Table pg. 4). C FAULT N.C. An open circuit across this pair of terminals will cause IN1 and IN2 to simultaneously (Common signal a trouble condition back to the FACP (Typically used to report AC or BAT Fail). trouble input) N.C., C, N.O. These are dry contact trouble outputs that follow any general loop/system trouble conditions. (Common (Typically used to trigger a digital communicator or other reporting device). trouble output) - AUX+ This separate 50mA auxiliary output is typically used to power 4-wire smoke detectors. It can be reset (voltage drops out) by pressing the momentary aux reset switch on the AL800LGK logic board or via the N.O. REMOTE C terminals. (fig. 4 pg. 6) N.O. C A momentary dry contact closure across these terminals interrupts the - AUX+ REMOTE power output to reset 4-wire smoke detectors Power Supply Board Terminal Function/Description Legend AC FAIL Form C dry contacts used to signal the loss of AC, with AC present terminals N.O. and C are C, N.C., N.O. open, N.C. and C are closed. When loss of AC occurs terminals N.O. and C close, N.C. and C are open. BAT FAIL Form C dry contacts used to signal low battery voltage or loss of battery voltage. N.O., N.C., C Under normal conditions terminals N.O. and C are open, N.C. and C are closed. During a trouble condition terminals N.O. and C are closed, and N.C. and C are open. BAT+, BAT- Stand-by battery input (leads provided). Use two (2) 12VDC batteries wired in series for 24VDC operation. 5

Typical Application Diagrams: Fig. 2 SW2 SW1 --- AUX + AUX RESET + OUT1 -- NO "REMOTE " C --- DC + + OUT2 -- + OUT3 -- + OUT4 -- AL800LGK OUT1 OUT3 OUT2 OUT4 OUT1 OUT2 OUT3 OUT4 INP1 INP2 FAULT IN1+ IN1-- IN2+ IN2-- C "DRY1" NC UPPER TERMINALS RET1+ RET1-- RET2+ RET2-- C "DRY2" NC LOWER TERMINALS NO C NC C "FAULT" NC Class B hookup: Switches SW1 & SW2 on AL800LGK logic board must be in the open position. It is recommended (not required) to control visual notification appliances (strobes) via Input 1 (IN1) & to control audible notifcation appliances (horns) via Input 2 (IN2). This facilitates the ability to silence audible notification appliances (horns) independently of visual notification appliances (strobes) during certain operations. Note: If common trouble (C FAULT N.C.) or dry contact (C DRY1 N.C. & C DRY2 N.C.) input options are not used, these terminal pairs must be shorted (connect jumper) to remain inactive. For optional hookups (see Fig. 4 pg. 7). From FACP NAC1 Optional paralleled Class B output From FACP NAC2 To FACP NAC1 or next signaling device or AL800UL-ADA To FACP NAC2 or next signaling device or AL800UL-ADA Two outputs may be connected in parallel for a maximum NAC output capability of 4 amps. When paralleling two (2) outputs, bridge (pos +) to (pos +) and (neg -) to (neg -). Both of the corresponding output switches must be set to follow the same input. Install two (2) ohm resistors in parallel across the last notification appliance. Paralleled output circuit configuration is non-power limited. Fig. 3 SW2 SW1 --- AUX + AUX RESET + OUT1 -- NO "REMOTE " C --- DC + AL800LGK + OUT2 -- + OUT3 -- + OUT4 -- OUT1 OUT3 OUT2 OUT4 OUT1 OUT2 OUT3 OUT4 INP1 INP2 FAULT IN1+ IN1-- IN2+ IN2-- C "DRY1" NC UPPER TERMINALS RET1+ RET1-- RET2+ RET2-- C "DRY2" NC LOWER TERMINALS NO C NC C "FAULT" NC Class A hookup: Switches SW1 & SW2 on AL800LGK logic board must be in the closed position for proper termination of NAC. Loop 1 starts on Output 1 and terminates on Output 3. Loop 2 starts on Output 2 and terminates on Output 4. Both of the corresponding output switches must be set to follow the same input. It is recommended (not required) to control visual notification appliances (strobes) via Input 1 (IN1) & to control audible notifcation appliances (horns) via Input 2 (IN2). This facilitates the ability to silence audible notification appliances (horns) independently of visual notification appliances (strobes) during certain operations. From FACP NAC1 Return to FACP From FACP NAC2 Return to FACP Note: If common trouble (C FAULT N.C.) or dry contact (C DRY1 N.C. & C DRY2 N.C.) input options are not used, these terminal pairs must be shorted (connect jumper) to remain inactive. For optional hookups (Fig. 4 pg. 6). Legend Horn Strobes Horn Strobes OPEN SWITCH Switch Detail 6 CLOSED SWITCH

Optional Hookup Diagram: BAT FAIL NC C NO AC FAIL NC C NO Fig. 4 A D RL2 BAT FAIL NC C NO RL3 Fire Alarm Control Panel (FACP) AC FAIL NC C NO AC TROUBLE DELAY OPTI IC2 IC3 AL801ULB POWER SUPPLY OPEN = 24V SW1 CLOSED = 12V XFMR RLY1 PTC2 DC ALTRIX CORP. J2 + DC --- + BAT --- AC AC AC Black Lead White Lead Resistor from FACP + 4-wire Smoke Detector -- + 4-wire Smoke Detector -- Power Supervision Relay (Not Supplied) N.O. Reset Switch -- AUX + AUX RESET SW2 SW1 + OUT1 -- -- DC + NO "REMOTE" C AL800LGK + OUT2 -- + OUT3 -- + OUT4 -- OUT1 OUT3 OUT2 OUT4 OUT1 OUT2 OUT3 OUT4 INP1 INP2 FAULT IN1+ IN1-- IN2+ IN2-- C "DRY1" NC UPPER TERMINALS RET1+ RET1-- RET2+ RET2-- C "DRY2" NC LOWER TERMINALS NO C NC C "FAULT" NC 115 VAC/60 Hz, 3.2 amps (Connect to seperate unswitched AC circuit) These circuits are used to monitor AC and Bat Fail and will cause a simultaneous trouble condition to the FACP's IN1 and IN2 Addressable Control Module Trigger Output See Note 2 Digital Communicator or Local Annuicator Dry output Contact (Form "C" contacts) Optional hookups: 1- Battery and AC monitoring: AC or Battery Fail condition will cause the common trouble input (C FAULT N.C.) to report back to the FACP via input 1 and input 2. The common trouble input may also be used for other optional supervisory monitoring. To report AC and Battery Trouble connect the battery and AC Fail relay output shown in Fig. 4 above to the common trouble input. 2- Dry contact input (IN1DRY, IN2DRY) (IN1DRY, IN2DRY) can be used to alarm output from an addressable module (these inputs are unidirection and cannot report back to trigger module). Note: If common trouble (C FAULT N.C.) or dry contact (C DRY1 N.C. & C DRY2 N.C.) input options are not used, these terminal pairs must be shorted (connect jumper) to remain inactive. 3- Auxiliary output (-AUX+) provides 12VDC or 24VDC at 50mA max. The output voltage is determined by the setting of switch marked SW1 on the Power Supply Board. It can be reset by a momentary closure across terminals (N.O. REMOTE C) or by pressing AUX RESET button on the AL800LGK logic board. 7

Typical Sync Module hookups Fig. 5: Synchronization using one (1) synchronization module with four (4) outputs. Note: When using this configuration you must enable the Input to Output Follower Mode (Dip Switch 1 ) and disable the Strobe Sync Mode (Dip Switch 2 OFF). FACP (Fire Alarm Control Panel) Sync Module AL800UL-ADA ADA Compliant NAC Power Extender Fig. 6: Synchronization using multiple synchronization modules. Note: When using this configuration you must disable the Input to Output Follower Mode (Dip Switch 1 OFF) and disable the Strobe Sync Mode (Dip Switch 2 OFF). Sync Module FACP (Fire Alarm Control Panel) AL800UL-ADA ADA Compliant NAC Power Extender Sync Module Legend Horn Strobes Horn Strobes 8

Typical Application Diagram for Connecting Horn/Strobes with Independent Control of Horns and --- AUX + AUX RESET --- DC + NO "REMOTE " C AL800LGK OUT1 OUT3 OUT2 OUT4 OUT1 OUT2 OUT3 OUT4 INP1 INP2 FAULT NO C NC C "FAULT" NC SW2 SW1 + OUT1 -- + OUT2 -- + OUT3 -- + OUT4 -- IN1+ IN1-- IN2+ IN2-- C "DRY1" NC UPPER TERMINALS RET1+ RET1-- RET2+ RET2-- C "DRY2" NC LOWER TERMINALS When using combination horn/strobes. Follow manufacturer s instructions for powering horns and strobes independently. Legend Horn Strobes Horn Strobes 9

Maintenance: Unit should be tested at least once a year for the proper operation as follows: Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level (see power supply output specifications chart). Battery Test: Under normal load conditions check that the battery is fully charged. Check specified voltage both at battery terminal and at the board terminals marked [- BAT +] to insure there is no break in the battery connection wires. Note: Maximum charging current is 700mA. Note: Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed. 10

Enclosure Dimensions: 15.5 H x 12 W x 4.5 D 2.25" 3.68" 4.56" 12" 1.22" 1.22" 4.5".875" 9.97" 1.3" 1.22" 1" 1" 2" 2" 8" 13.25" 13.53" 3.25" 2.2" 1.25" 1" 15.5" 1.22" 2.25" 3.68" 4.56" 11

Notes: MEMBER 12 Altronix Corp. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A. IIAL800ULADA - Rev. 062600