TEST REPORT #2. System Drop-in Test of L-40, L-41a and N-40b in Ice Machines

Similar documents
System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller

AHRI Low GWP Alternative Refrigerants Evaluation Program (Low GWP AREP)

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

BRA FACT FINDER Number 19

Reference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved.

TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit

TEST REPORT #6. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

Update on Codes and Standards Research. Karim Amrane, Ph.D. Senior Vice President

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

Test Results from the AHRI Low GWP AREP II (Alternative Refrigerant Evaluation Program) Transport Refrigeration

TEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit

Research to Assist in the Development of Safety Standards and Building Codes for the Use of Flammable Refrigerants

Otherwise, you can continue reading the file on the following pages.

GWP Alternative Refrigerants

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump

2016 Annual Conference

R-407A R-448A R-449A

TEST REPORT #63. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)

REFRIGERANT CHANGEOVER

Test Results from the AHRI Low GWP AREP (Alternative Refrigerant Evaluation Program) Bus Air-Conditioning

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

Warm Case Troubleshooting Guide 9/18/2014

TEST REPORT #12. System Drop-In Tests of Refrigerant Blends N-13a and AC5 in Bus Air- Conditioning Unit Designed for R-134a

Sporlan Valve Division Parker Hannifan/CIC Group

Understanding Applications for Alternate Refrigerants. Ron Bonear Emerson Climate Technologies

January 16 th, 2014 New York City

Low Global Warming Refrigerants For Commercial Refrigeration Systems

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

The Current Path of Refrigerants

System Considerations for Refrigerant Blends with Temperature Glide

EN-CV: LHCb SciFi Common chiller. Martin Doubek September 25, 2017

Transcritical CO2 Bottle Cooler Development

Performance Rating of Automatic Commercial Ice-makers

5. ASSESSMENT RECOMMENDATIONS

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

Low GWP Refrigerants for Air Conditioning Applications

R-404A Alternative with Low Compressor Discharge Temperature

1+ SEER. 25% COP boost possible. Most valves expand your refrigerant EcoFlow expands your options. with silent defrost.

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.

ENERGY EFFICIENCY PERFORMANCE SAVINGS SERVICE MANUAL R-290

SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS

The lowest energy consumption when using R290 LBP fixed speed compressors in a plug in ice cream conservator

Update on Next Generation Low GWP Refrigerants for Chillers Products. Steve Kujak Director, Next Generation Refrigerant Research

PREPARE FOR CHANGE LOW GWP ALTERNATIVES. November 17

A Series Inertia Compressor Applications. Application Bulletin 115

OPERATING INSTRUCTIONS

Vehicle Level Heating and Air Conditioning Description and Operation A/C System - Manual. A/C System - Manual

MASS. MARITIME ACADEMY

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES

10/4/2013. The Changing State of Refrigerants

BASE LEVEL AUDIT REQUIREMENTS REFRIGERATION SYSTEMS 1. SITE DATA COLLECTION. Business Name. Site physical address (Street, Suburb, City)

SECTION REFRIGERATION EQUIPMENT. A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories.

Application Guide. Refrigerant Piping Manual for Small Split Cooling and Heat Pump Systems SS-APG006-EN

Installation, Operation, and Maintenance Information

APPLICATION DATA SHEET

DuPont Refrigerants. John McCormack Business Manager DuPont Chemicals and Fluoroproducts. R22 market and the ISCEON retrofit options

Eclipse Technical Training CME686 CME810 CP686 CP886 CP1086

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support

Understanding Applications for Alternative Refrigerants

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

Understanding Applications for Alternative Refrigerants

Evaluation of HCFC Alternative Refrigerants

Table of Contents SPECIFICATIONS Page 2. FOR THE INSTALLER Page 3. FOR THE PLUMBER Page 4. INSTALLATION Page 5. INITIAL START UP Page 6

Cool Savings Program Report

Seminar 34 Refrigerants Today, Tomorrow, and Beyond

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

R134a Refrigerant Charging Chart Trucks Mybooklibrary

Energy Use in Refrigeration Systems

AHRI 920 Performance Rating and Comparisons of DX-DOAS Unit Efficiency

Negative Superheat? Time to Check Your Tools

MODEL URS-1: FACTORY RETROFIT PROGRAM

March 2014 AHRI Presents Research Findings at Low-GWP AREP Conference

LONG LINE SET APPLICATION R-410A

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

COMPARATIVE STUDY OF NEW ECOLOGICAL GASES

Honeywell Refrigerants. Retrofit Guidelines. R-404A/R-507A to: R-448A Solstice N40

OPERATING INSTRUCTIONS

Aspects of the. Following these key guidelines during a compressor changeout can ensure a successful, more efficient replacement.

Making Sense of the Latest Rulemaking on Acceptable Refrigerants. E360 Webinar

DROP-IN EVALUATION OF REFRIGERANT 1234YF IN A RESIDENTIAL INTEGRAL HEAT PUMP WATER HEATER

Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A ), 120/208/240/1/60, R404A, LT/MT APPS

Filter Driers with Replaceable Core

Flow Capacity Rating of Suction Line Filters and Suction Line Filter Driers

Pressure Enthalpy Charts

Gary Parker Refrigerants Product Manager

Low GWP Refrigerants for Air Conditioning and Chiller Applications

Solstice 452A (R-452A) Reduced GWP and Discharge Temperature for Transport Refrigeration, Plug-Ins and Condensing Units

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

Harold Ag & Mobile Products

Gary Parker Refrigerants Product Manager

Transcription:

Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #2 System Drop-in Test of L-40, L-41a and N-40b in Ice Machines Chuck Schlosser Manitowoc Ice Inc. 2110 South 26 th Street Manitowoc, WI, 54221 November 26, 2012 This report has been made available to the public as part of the author company s participation in the AHRI s Low-GWP AREP.

List of Tested Refrigerants Compositions (Mass%) L-40 R-32/R-152a/R-1234yf/R-1234ze(E) (40/10/20/30) L-41a R-32/R-1234yf/R-1234ze(E) (73/15/12) N-40b R-32/R-125/R-134a/R-1234yf (25/25/20/30)

AHRI Low-GWP AREP Report. From Manitowoc Ice Inc. Written by: Chuck Schlosser Revised August 17, 2012 Purpose: To support the AHRI Low-GWP AREP program, and to test and compare several proposed Low GWP refrigerants that might have potential for usage in ice machine applications. Test Refrigerants: Honeywell L-40, was compared to R-404A. Honeywell N-40b, was compared to R-404A. National Refrigerants 50% R32+50% R134a, was to be compared to R-404A, but samples of the refrigerant were never received. Honeywell L-41a, was compared to R-410A. Application: Ice machines are a medium temperature refrigeration application. Evaporator temperatures pull down to between +10 and 0 ºF during freeze cycles. During the harvest cycle the evaporator is warmed to between 40 ºF and 55 ºF typically. We typically freeze and harvest 3-5 batches of ice per hour depending on conditions. Test Equipment: Two test machines were selected to use in comparing the refrigerants. The first test machine was a Manitowoc model IY1404A-261. This unit is a self contained air-cooled unit, rated for indoor duty. The unit is typically used in larger full service restaurants, larger nightclubs and bars, along with institutional applications. The operating window for this machine is +40 ºF to +110 ºF ambient. This unit uses a hot gas harvest system. The unit is manufactured with a Bristol model R92J343ABCA compressor. The second test machine was a Manitowoc model IB1094YC-161, connected to a model ICVD1095-261 condensing unit using an RC36, (35 feet), line set. This unit has the ice making head section located indoors, and a remote condensing unit located outside, typically on the roof. This unit was designed to fit on top of ice dispensers which are commonly used in fast food restaurants and C store applications. It is designed to produce a lot of ice very quietly in a customer environment. The operating window for the outdoor condensing unit is -20 ºF to +120 ºF ambient. This unit uses a cool vapor harvest system. This unit is manufactured with a Bristol model R92J253ABCA compressor. High Glide Refrigerants: Besides the usual leak concerns associated with high glide refrigerants, we did see a lot of unusual expansion valve hunting during these tests. We do run very low superheat settings, but our valves operate with little of no hunting. Whether this was a result of the refrigerant glide of just slightly different pressures and temperatures associated with the test refrigerants, it was hard to tell. If we went forward with one of these refrigerants, the expansion valve bulb charges would need to be reviewed.

When we look close at the results, the model IY1404A-261, which uses a hot gas harvest cycle, we saw very consistent results with all refrigerants. The model IB1074YC-161, which uses a cool vapor harvest system, worked real well with N-40b, and not as good with L-40 and L41a. While the reasons for this are not full understood, one thought is the refrigerant may be separating in the receiver tank, since we pull our cool vapor off the top of the receiver for the harvest cycle. We also use an accumulator in these systems, and we pull vapor off the top of the accumulator through the J tube. It is possible that the refrigerant we are pumping during the harvest cycle may not be what we think it is. This theory would have to be explored in greater detail if a high glide refrigerant was selected. Test Procedure: All testing was done in accordance with AHRI Standard 810; and ASHRAE standard 29. Tests were conducted at 90/70 ºF, (90 ºF ambient / 70 ºF water), temperatures. This is the standard AHRI rating condition, and the point used to compare the performance of the various refrigerants against each other, against baseline data, and certified data. Ice was measured in pounds of ice produced per day, and energy was measured in kilowatt hours required to produce 100 pounds of ice. In all cases, we waited for the units to become stable at the test conditions, and than recorded six test runs, and the results were averaged, and mean data was reported. Testing was also done on the self contained IY1404A-261 at 40/50, 70/50 and 110/90, and on the IB1094YC-161 at -20/50, 70/50, and 120/90 just to see what happened to the new refrigerants when operated at the edges of the equipment s design envelope. For the two refrigerants compared to R-404A; L-40, and N-40b, we tested both stock machines at 90/70 to verify they were typical and within AHRI tolerances. We than removed the R-404A refrigerant, removed the compressors and drained the oil, and replaced it with new POE oil, reinstalled the compressors, replaced the expansion valves with new same size adjustable expansion valves, (Manitowoc ice machines use fixed setting non-adjustable expansion valves), and replaced the filter drier. After evacuation, the system was charged with new refrigerant. Due to the high glide with the new refrigerants, we charged with liquid refrigerant only. We started out our charge searches at about 75% of the nameplate R-404A refrigerant charge, and followed our standard charge search procedures; we worked in 2 ounce increments on the IY1404A-261; and in 8 ounce increments on the IY1094YC-161 system, (remote systems have much larger refrigerant charge sizes). Ice machines run with very low superheat setting on their expansion valves, and we did have to adjust the valves to match the superheat settings as close as possible to the standard R-404A valve settings. Ice machines use a suction-liquid line heat exchange to get higher superheat back at the compressor. The heat exchanger was not modified for these tests. No other components were changed or modified for the testing when we compared to R-404A refrigerant. Between testing each refrigerant, we would remove the compressor, and drained the oil and replaced it with new POE oil, and replaced the filter drier, to keep cross contamination to a minimum.

The Honeywell L-41a refrigerant was compared to R-410A in the same two ice machines. Since the standard refrigerant in these two machines is R-404A, the machines had to be rebuilt with R-410A components, and retested with R-410A to get a reference point to compare L-41a against. We asked our suppliers such as Bristol, Danfoss, and Sporlan to provide equivalent R-410A components to use in our units for this test. We replaced the compressors, expansion valves, head pressure control valves, and pressure switches with equivalent R-410A parts, condenser coils remained the same. With R-410A, we used a Bristol model H82J173ABCA compressor in the IB1094YC system, and a Bristol model H82J243ABCA used in the IY1404A system. A charge search was run on both systems using R-410A refrigerant to establish a new performance baseline. Test Results: Performance at Rating 90/70 Rating Condition IY1404A-261 Test Unit; R-404A Comparison R-404A 46 oz 1180#/day ---- 4.88 Kwh/100# ---- AHRI Certified Rating R-404A 46 oz 1227#/day ---- 4.88 Kwh/100# ---- Baseline on Test Unit L-40 41 oz 1231#/day +3.2% 4.70 Kwh/100# -3.7% N-40b 47 oz 1227#/day 0.0% 4.84 Kwh/100# -0.8% IB1094YC-161 Test Unit; R-404A Comparison R-404A 180 oz 910#/day ---- 4.85 Kwh/100# --- AHRI Certified Rating R-404A 180 oz 928#/day ---- 4.83 Kwh/100# --- Baseline on Test Unit L-40 184 oz 861#/day -7.3% 5.32 Kwh/100# +10.1% N-40b 144 oz 960#/day +3.4% 4.67 Kwh/100# -3.3% IY1404A-261 Test Unit; R-410A Comparison R-410A 44 oz 1037#/day --- 4.26 Kwh/100# --- Baseline on Test Unit L-41a 38 oz 1030#/day -0.7% 4.08 Kwh/100# -4.3%

IB1094YC-161 Test Unit; R-410A Comparison R-410A 240 oz 753#/day --- 4.64 Kwh/100# --- Baseline on Test Unit L-41a 240 oz 679#/day -9.9% 4.91 Kwh/100# +5.8% Ice Capacity at Other Test Conditions: IY1404A-261 Test Unit Refrig. 40/50 F 70/50 F 110/90 F 90/70 F Notes R-404A 1520#/day 1540#/day 910#/day Typical Values R-404A 1180#/day AHRI Certified Value L-40 1519#/day 1481#/day 932#/day 1231#/day N-40b 1542#/day 1537#/day 920#/day 1227#/day L-41a 1278#/day 1166#/day 761#/day 1030#/day IB1094YC-161 Test Unit Refrig. -20/50 F 70/50 F 120/90 F 90/70 F Notes R-404A 1050#/day 1070#/day 670#/day Typical Values R-404A 910#/day AHRI Certified Value L-40 962#/day 963#/day 580#/day 861#/day N-40b 1063#/day 1035#/day 672#/day 960#/day L-41a 755#/day 675#/day 469#/day 679#/day

Summary: The compressors we used for the R-410A / L-41a testing were different, and undersized, so results can only be compared to each other, and not to the R-404A, L-40, and N-40b results. Over all, the Honeywell N-40b, had good capacity over the full range of operating conditions, and good energy efficiency, and it is rated an A1 refrigerant. The GWP was higher than some of the other candidates.