THERMAL SOLUTIONS COAXIAL HEAT EXCHANGERS WKE, WKC

Similar documents
THERMAL SOLUTIONS FINNED TUBES AND HEAT EXCHANGERS FOR GREATER EFFICIENCY

HANDBOOK REGULATOR VALVES. Ed REGULATOR VALVES RP-ED 01/ ENG 1

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

SOLENOID VALVES FOR REFRIGERATING SYSTEMS

General information on refrigerant controllers

Tube-in-tube heat exchanger Type HE

OIL SEPARATORS APPLICATIONS

Check valve Types NRV and NRVH

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

Technical Catalogue. Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: kw 50 Hz

30GX - 50 Hz. Air-Cooled Screw Compressor Liquid Chillers GLOBAL CHILLER. Nominal cooling capacity kw

Tube-in-tube heat exchanger Type HE

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation

WATER CHILLER UNITS AIR COOLED CONDENSER CENTRIFUGAL FANS HEAT PUMP. EWCBZ COOLING ONLY. EWCZ

AQUASNAP AIR CONDITIONING MADE SIMPLE 30RA/30RH AQUASNAP LIQUID CHILLERS HEAT PUMPS

Choose the winning team. Heat transfer technology for industrial cooling and air conditioning

Blow through unit coolers LEX. Standard coolers for cooling & freezing rooms

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N

30RB Air-Cooled Liquid Chillers PRODUCT SELECTION DATA. Easy and fast installation. Compact, reliable and efficient

Güntner Info GVX. with microox technology kw. Always a step ahead: microox condenser system with maximum installation flexibility

SEMI-HERMETIC SCREW COMPRESSORS

30HXC - 50 HZ. Water-Cooled Screw Compressor Liquid Chillers. Nominal cooling capacity kw

EREBA ACCESS. Easy and fast installation Hydronic module available Compact, reliable and efficient USE RANGE CONFORMITY

RD refrigerant distributors, for thermostatic expansion valves REFRIGERATION AND AIR CONDITIONING. Technical leaflet

HYDRONIC RESIDENTIAL

RIGID DC LIQUID CHILLER

Suction Line Accumulators

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

PWM expansion valves 2028

30HX GLOBAL CHILLER LIQUID CHILLER IN HARMONY WITH THE ENVIRONMENT

Liquid Distributor Type RD

water to water heat pumps

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

Revolutionary ETS Colibri valves Engineered to give you maximum flexibility and dependability

Split inverter air-to-water heat pump CERTIFIED BY CERTITA. option 30/35-40/45

AQUASNAP JUNIOR 30RHV

Hi-Pres. Self Contained A/C Unit HI-PRES MARINE & OFFSHORE

70% Save time and money with MCHE standard products. MicroChannel Heat Exchangers. Lower refrigerant charge

Energy-Saving Industrial Water Chillers

EKS/HE. MultiScroll Air-cooled liquid chillers High efficiency. Solution B - Base I - Integrata

30HXC Nominal cooling capacity kw

Process glycol chillers

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

PGDX Rectangular duct coolers with DX coil

30RB Air-Cooled Liquid Chillers with Integrated Hydronic Module. Nominal cooling capacity kw. Easy and fast installation.

30GK. Air-Cooled Liquid Chillers. Nominal cooling capacity kw

DAIKIN Modular Inverter Air Cooled Chiller

A Evaporator B Fan C Terminal box D Hermetically sealed, output regulated digital scroll compressor E Condenser

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers

500 EX Fusion Compressor Series

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

environmental climate control equipment & solutions AQUACOOL Water-to-water heat pump with passive energy recovery

Engineered efficiency - no matter where or what. KMe Coolers Fresh ideas from Searle. GEA Searle

LIVING. For heat recovery in multi-occupancy buildings with extract air ventilation. And excellent return on investment.

Roof top SPACE RPC 315Z R407C MA00

High temperature air-to-water heat pumps

Küba SG commercial

30GX 50 Hz. Air-Cooled Screw Compressor Liquid Chillers GLOBAL CHILLER. Nominal cooling capacity kw

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual

SB Series Brazed Plate Heat Exchanger Installation Manual

Multibox. Flush Individual Room Control for Floor Heating Systems. To be precise.

CONDOR-H (horizontal) / CONDOR-V (vertical)

Roof top SPACE RPC 450Z R407C M011

CZT CZT. High efficiency air to water heat pumps with E.V.I. compressors E.V.I. HP OTHER VERSIONS ACCESSORIES

Figure 1: Overview of CO 2 evaporator types

LZT High efficiency air to water heat pumps with E.V.I. compressors

BRAN Residential chillers and heat pumps. Reversible unit, air source for outdoor installation 4,81-27,2 kw <<< BACK INDEX.

30RH B Nominal cooling capacity kw Nominal heating capacity kw

Advance Split

Dehydrators and Filters

FSW SECTION. Product guide. Expansion Valves, Solenoid Valves Water Valves & Oil Pressure Switches F SECTION. 71

Environmentally friendly refrigeration systems for industrial use

Air-Cooled Variable Speed Drive Screw Chillers. Super Efficient Super Quiet. Cooling Capacity Range kw R134a

MAC-D R410A Series Air-cooled Modular Chiller/Heat pump

Hot gas bypass regulator, type CPCE Liquid gas mixer, type LG (accessory)

30RB/RQ 039S-160S Refrigerant HFC-410A Nominal cooling capacity kw Nominal heating capacity kw

Hi-Pres Cooling Products Catalogue. Product Catalogue

Aquaflair TRAC-TRAF-TRAH

80HMA. Comfort Module Range for Monobloc Heat Pumps. Nominal heating capacity 4-20 kw Nominal cooling capacity 4-20 kw. Features

Technical Information

Hot Water Heating Systems

80HMA. Comfort Module Range for Monobloc Heat Pumps. Compact comfort module. DHW management possibility. Multi zone option control.

Filter Driers with Replaceable Core

Product Data Sheet Refrigeration Dryer DFLO 66 (-W) bis DFLO 2400 (-W)

AIC Brazed Plate Heat Exchanger Operating and Instruction Manual

Flexible. Upgrade and service with ease Extend lifetime with modular design. Thermostatic expansion valves Type TE5-55

The ideal cooler at a competitive price KELVION TEC COMMERCIAL AIR COOLER

NEOSYS. AIR TO WATER LIQUID CHILLER kw. AIR TO WATER HEAT PUMP kw. lennoxemea.com

Technical data LA 60TUR+

LER kw. Indoor motor-driven evaporating units. Motor-driven evaporating units LER PLUS

Temperature Sensor TRG Original Installation Instructions English

Brazed heat exchangers

Air cooler BC50 Blast freezer

Kälte Klima. Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW. Compressors Scroll SCAEY DE 88 04/11 12/10

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

Suction Accumulators. Introduction. Suction Accumulators

kw COOLING kw HEATING

Transcription:

THERMAL SOLUTIONS COAXIAL HEAT EXCHANGERS WKE, WKC

COAXIAL HEAT EXCHANGERS WKE, WKC APPLICATIONS Wieland coaxial heat exchangers are used as evaporators (WKE) or as condensers (WKC). They consist of one or more inner tubes and one outer tube. This tube bundle is coiled in a spiral shape and brazed at the ends with T-fittings. TYPICAL APPLICATIONS Heat pumps for hot water Chillers Cascade heat exchangers in multistage refrigeration systems Temperature control units/climate chambers Air conditioning and heating in marine applications BEST PERFORMANCE WITH OPTIMISED SURFACES COAXIAL EVAPORATORS WKE Coaxial evaporators are the preferred choice in applications where water needs to be cooled significantly. At the same time they also offer reliable superheating of the suction vapour, which is facilitated by the counter-flow layout. A low-noise operation is achieved by spacer rings in the jacket tube. COAXIAL CONDENSERS WKC Coaxial condensers are normally used in applications which require high water temperatures in conjunction with the use of hot gaseous refrigerant. In counter-flow operation this is achieved with an optimised heat exchange. For a low-noise, non-vibration operation, dents are pressed into the jacket tube. Coaxial condensers offer excellent value for money. Wieland coaxial heat exchangers, developed at our in-house thermal engineering laboratory, have inner tubes specially optimised for evaporation respectively condensation. This results in a much higher specific performance and a very compact and comparatively lightweight design. BENEFITS HIGH SPECIFIC PERFORMANCE THROUGH OPTIMISED INNER TUBES COUNTER FLOW FROST-PROOF LOW FOULING LONG LIFE HIGHER SYSTEM PRESSURE THAN 35 BAR ON REQUEST REVERSIBLE OPERATION POSSIBLE STANDARD HEAT EXCHANGERS AVAILABLE FROM STOCK 2

INDIVIDUAL ADVICE We support you from the very early product planning stages in order for you to obtain optimum results for both the installation and your specific application, thus finding a cost-effective solution. For this, we offer you support in heat transfer engineering and heat exchanger design. QUALITY ASSURANCE To ensure consistent product quality, Wieland-Werke AG has a sophisticated quality control system according to DIN EN ISO 9001 which has been verified and certified by an independent certification company. Our test laboratories in the Central Laboratory and Development Services have been accredited to DIN EN ISO/IEC 17025 and DIN EN ISO 9001 as test and certification laboratories. SOURCES OF SUPPLY MATERIALS Component Material designation Material No. Inner tube(s) Cu-DHP CW024A Jacket tube Cu-DHP CW024A T-fittings Cu-DHP CW024A Other copper alloys and materials (e.g. aluminium or titanium) are available on customer request. PRESSURE EQUIPMENT DIRECTIVE 2014/68/EU Wieland coaxial heat exchangers meet the requirements of the European Pressure Equipment Directive 2014/68/EU. They are normally classified into the categories laid out in tables 2 and 4 and are manufactured and supplied in accordance with the measures designated for this purpose. Operating conditions which exceed these specifications are subject to special requirements which should be agreed separately for each individual case. Larger quantities of standard products are available from stock. For minor quantities or special requests, please contact us. 3

COAXIAL HEAT EXCHANGERS WKE, WKC APPLICATION (in the tubes) WKE (evaporator) Heating medium (inside the coil) (inside the coil) WKC (condenser) Coolant (in the tubes) Max. working pressure [bar] 35 15 35 15 Working temperature [ C] 50 to +150 50 to +150 50 to +150 50 to +150 Media e.g. R134a, R404A, R407C, R410A, R22, R32, R507 (other refrigerants on request) Circulating water (e.g. heating water), groundwater*, water with anti-freeze additives (e.g. Antifrogen N ) (other heating media on request) Table 1 *Individual case assessment recommended; **Up to approx. 5 mg/l free chlorine R134a, R404A, R407C, R410A, R22, R32, R507 (other refrigerants on request) Hot water, circulating water, (e.g. heating water), groundwater*, swimming pool water** (other cooling media on request) INSTALLATION INFORMATION Coaxial heat exchangers should preferably be operated in counter-flow operation. The installation of evaporators WKE preferably allows the refrigerant to enter through the upper connection. If several evaporators of the same size are to be connected in parallel, then it must be ensured that each evaporator is supplied with even pressure both on the refrigerant side and on the heating medium side. Condensers WKC are installed so that the liquefied refrigerant is free to drain away to the bottom. The hot gaseous refrigerant enters the jacket space at the top, whereas the cooling medium (e.g. water) enters the inner tube(s). Coaxial condensers are also installed standing on the windings (winding axis horizontal). If an application requires several condensers to be connected in parallel, then the tubing should be designed in such a way that each condenser can be supplied with even pressure on both the refrigerant side and the cooling medium side. The routing of the hot-gas line should be installed avoiding any vibrations. This is normally achieved by installing vibration dampers (compensators). In order to avoid pulsating noises, we recommend installing a sound muffler between the compressor and the condenser. Please follow the manufacturer s instructions when installing these components. With Wieland coaxial heat exchangers, the following proportions of the refrigerant side volume (taken from table 2 and table 4) should be used as an approximation for the calculation of the refrigerant capacity of the overall system: - for the coaxial evaporator WKE: 40 % - for the coaxial condenser WKC: 30 % PERFORMANCE RATING OVERVIEW The tables 3 and 5 can be used to pre-select your Wieland coaxial heat exchanger according to the performance of the evaporator/condenser. The specified values are based on our own measurements. They should be used as reference values only and apply under the described nominal conditions which conform as far as possible to the corresponding standards (e.g. EN 1117: Liquid cooled refrigerant condensers test procedures for establishing the performance). Operating conditions which vary from these conditions may result in different values. LEGEND Q c_nom [kw] Condenser performance under nominal conditions Q 0_nom [kw] Evaporator performance under nominal conditions Δt sub [K] Subcooling of the refrigerant in the condenser Δt sub_evp [K] Superheating of the suction vapour Δt c [K] t c t w_in temperature difference in the condenser Δt 0 [K] t w_in t 0 temperature difference in the evaporator t 0 [ C] Evaporation temperature of the refrigerant at the evaporator outlet t c [ C] Condensation temperature of the refrigerant in the condenser t sup [ C] Temperature of the hot gas refrigerant t w_in [ C] Water temperature at the inlet [m 3 /h] Water volume flow w [m/s] Water velocity x [ ] Vapour quality at the evaporator inlet p [mbar] Pressure drop 4

DIMENSIONS AND WEIGHTS OF COAXIAL EVAPORATORS WKE Model Number of inner tubes Maximum installation dimensions Connection dimensions (see drawing) Heating medium Other dimensions Volume [ l ] Classification PED 2014/68/EU Heating medium Appr. weight A B H d 1 * in d 2 * out d 3 * a h l 1 l 2 l 3 D [kg] WKE 10 *** 1 330 325 130 16 13 13 290 94 312 65 24 25 0.8 0.4 WKE 16 2 340 390 190 28 22 22 290 140 384 91 41 35.6 1.8 0.9 WKE 24 3 435 465 175 28 18 18 380 122 457 125 102 43 2.4 1.3 WKE 44 5 605 600 220 35 22 28 530 150 564 123 54 54 4.9 2.9 sound engineering practice sound engineering practice Category 1, Module A Category 1, Module A Table 2 All dimensions in mm (unless specified otherwise); *Internal soldering ends; ***For WKE 10 the fitting on the refrigerant side can also be used as external soldering end d4 with Ø 16 mm (e.g. for tube Ø 18 x 1.0 mm). 4.1 8.1 11.1 24.7 EVAPORATORS WKE Example: : R134a; t 0 = 0 C; x = 20 %; Δt sup_evp = ca. 5 K Heating medium: water; w 0.5 to 2 m/s Type p Q 0 R134a Q 0 R404A/R507 Q 0 R410A Δt 0 [K] 6.0 9.0 12.0 15.0 6.0 9.0 12.0 15.0 6.0 9.0 12.0 15.0 Units m 3 /h mbar kw kw kw kw kw kw kw kw kw kw kw kw WKE 10 0.4 56 1.5 2.2 3.4 4.2 2.0 2.9 4.5 5.6 1.8 2.7 4.2 5.2 0.6 108 1.9 2.9 4.4 5.5 2.6 3.9 5.9 7.4 2.4 3.6 5.5 6.9 0.8 177 2.4 3.6 5.2 6.5 3.2 4.8 7.0 8.8 3.0 4.5 6.5 8.2 1.0 263 2.9 4.4 6.0 7.5 3.9 5.9 8.0 10.0 3.6 5.5 7.5 9.4 1.2 364 3.2 4.9 6.8 8.5 4.3 6.5 9.1 11.3 4.0 6.0 8.4 10.6 1.4 483 3.5 5.2 7.5 9.3 4.6 7.0 10.0 12.5 4.3 6.5 9.3 11.6 1.6 617 3.7 5.5 8.2 10.2 4.9 7.4 10.9 13.6 4.6 6.9 10.2 12.7 WKE 16 1.0 65 2.5 4.2 6.1 9.0 3.4 5.6 8.2 12.1 3.2 5.3 7.6 11.2 1.5 126 3.5 5.9 8.5 10.6 4.7 7.9 11.4 14.2 4.4 7.3 10.6 13.2 2.0 206 4.3 7.1 10.3 12.5 5.8 9.5 13.8 16.7 5.4 8.8 12.9 15.6 2.5 306 4.9 8.5 11.8 13.8 6.6 11.3 15.8 18.4 6.1 10.6 14.7 17.2 3.0 424 5.5 9.2 12.8 15.3 7.3 12.4 17.1 20.5 6.8 11.5 15.9 19.1 3.5 562 5.6 9.5 13.4 16.7 7.5 12.8 17.9 22.4 7.0 11.9 16.7 20.8 WKE 24 1.5 58 3.7 6.9 9.4 13.2 4.9 9.2 12.6 17.6 4.6 8.5 11.7 16.4 2.0 95 4.3 7.9 11.1 15.4 5.8 10.6 14.8 20.6 5.4 9.9 13.8 19.2 2.5 141 5.0 9.0 12.6 17.6 6.7 12.1 16.9 23.6 6.2 11.2 15.7 22.0 3.0 195 5.5 9.9 14.2 19.3 7.4 13.3 19.0 25.8 6.9 12.4 17.7 24.0 3.5 258 6.2 10.9 15.6 20.8 8.2 14.5 20.9 27.8 7.7 13.5 19.5 25.9 4.0 330 6.5 11.6 17.0 22.5 8.8 15.6 22.8 30.1 8.2 14.5 21.2 28.0 4.5 410 6.9 12.2 18.3 23.4 9.3 16.4 24.5 31.3 8.6 15.3 22.8 29.2 WKE 44 2.0 58 6.2 13.1 16.5 19.9 8.2 17.5 22.0 26.6 7.7 16.3 20.5 24.8 3.0 120 8.4 15.8 20.8 27.0 11.2 21.1 27.8 36.1 10.5 19.7 25.9 33.6 4.0 205 10.3 17.7 24.6 32.1 13.8 23.7 33.0 43.0 12.9 22.1 30.7 40.0 5.0 311 12.0 20.0 28.0 36.6 16.1 26.8 37.5 48.9 15.0 25.0 34.9 45.6 6.0 440 13.4 21.9 31.0 41.1 17.9 29.3 41.4 55.0 16.7 27.3 38.6 51.3 7.0 590 14.6 23.3 33.6 43.6 19.5 31.1 44.9 58.3 18.1 29.0 41.9 54.3 Table 3 Pressure drop data att w_in =20 C; performance data at t 0 = 0 C 5

COAXIAL HEAT EXCHANGERS WKE, WKC DIMENSIONS AND WEIGHTS OF COAXIAL CONDENSERS WKC Model Number of inner tubes Maximum installation dimensions Connection dimensions (see drawing) Coolant Other dimensions Volume [ l ] Classification PED Coolant 2014/68/EU Appr. weight A B H d 2 * and d 3 * d 4 ** d 1 * a h l 1 l 2 l 3 D [kg] WKC 10 1 225 270 135 12.7 15.9 16 190 98 262 55 26 25 0.3 0.6 WKC 15 1 230 290 235 16 19 18 190 196 282 71 28 28 0.8 1.0 WKC 20 1 350 360 220 21.7 25.5 22 300 172 350 77 36 35.6 1.75 1.8 WKC 45 4 520 530 225 28 31.9 35 445 152 522 142 76 54 2.9 3.7 Table 4 All dimensions in mm (unless specified otherwise); *Internal soldering ends; **External soldering ends sound engineering practice sound engineering practice Category 1, Module A Category 1, Module A 3.5 7.5 10.5 21.0 CONDENSERS WKC Example: : R134a; t c = 45 C; t sup = ca. 65 C; Δt sub = 4 K Coolant: water; w 0.5 bis 2 m/s Type p Q c R134a Q c R404A/R507 Q c R410A Δt c [K] 7.0 10.0 15.0 20.0 7.0 10.0 15.0 20.0 7.0 10.0 15.0 20.0 Units m 3 /h mbar kw kw kw kw kw kw kw kw kw kw kw kw WKC 10 0.2 30 1.5 2.2 3.3 4.4 1.8 2.5 3.7 5.0 1.8 2.5 3.7 5.0 0.4 91 2.2 3.1 4.6 6.2 2.5 3.5 5.2 7.0 2.5 3.5 5.2 7.0 0.6 185 2.7 4.0 5.9 7.9 3.1 4.5 6.7 9.0 3.1 4.5 6.7 9.0 0.8 311 3.3 4.8 7.2 9.7 3.8 5.5 8.2 11.0 3.8 5.5 8.2 11.0 1.0 469 4.0 5.6 8.4 11.3 4.5 6.4 9.6 12.8 4.5 6.4 9.6 12.8 WKC 15 0.3 33 2.5 3.5 5.3 7.0 2.8 4.0 6.0 8.0 2.8 4.0 6.0 8.0 0.4 51 3.1 4.4 6.6 8.8 3.5 5.0 7.5 10.0 3.5 5.0 7.5 10.0 0.8 159 5.4 7.7 11.5 15.3 6.1 8.7 13.1 17.4 6.1 8.7 13.1 17.4 1.2 323 7.3 10.4 15.6 20.8 8.3 11.8 17.7 23.6 8.3 11.8 17.7 23.6 1.6 543 8.6 12.3 18.5 24.6 9.8 14.0 21.0 28.0 9.8 14.0 21.0 28.0 WKC 20 0.7 36 4.6 6.6 9.9 13.2 5.3 7.5 11.3 15.0 5.3 7.5 11.3 15.0 1.0 63 6.2 8.8 13.2 17.6 7.0 10.0 15.0 20.0 7.0 10.0 15.0 20.0 1.5 123 8.6 12.3 18.5 24.6 9.8 14.0 21.0 28.0 9.8 14.0 21.0 28.0 2.0 201 11.1 15.8 23.8 31.7 12.6 18.0 27.0 36.0 12.6 18.0 27.0 36.0 2.7 343 13.4 19.2 28.8 38.4 15.3 21.8 32.7 43.6 15.3 21.8 32.7 43.6 WKC 45 1.4 32 9.2 13.6 20.7 27.3 10.5 15.5 23.5 31.0 10.5 15.5 23.5 31.0 2.0 60 12.8 18.9 28.2 37.8 14.5 21.5 32.0 43.0 14.5 21.5 32.0 43.0 3.0 125 17.6 26.4 40.5 52.8 20.0 30.0 46.0 60.0 20.0 30.0 46.0 60.0 4.0 213 22.0 33.4 50.2 66.9 25.0 38.0 57.0 76.0 25.0 38.0 57.0 76.0 5.0 324 25.5 39.6 59.0 79.2 29.0 45.0 67.0 90.0 29.0 45.0 67.0 90.0 5.4 375 27.3 41.4 61.6 82.7 31.0 47.0 70.0 94.0 31.0 47.0 70.0 94.0 Table 5 Pressure drop data at T w_in =20 C; performance data at t c = 45 C 6

Evaporators WKE 1 inlet 2 outlet 3 Heating medium inlet 4 Heating medium outlet Condensers WKC 1 Coolant outlet (e.g. heating water) 2 Coolant inlet (e.g. heating water) 3 outlet 4 inlet 7

ninnovative SPIRIT. OUTSTANDING RESULTS. For further information please contact Wieland-Werke AG Thermal Solutions Andreas Moritz Phone +49 731 944 1017 E-mail andreas.moritz@wieland.com WIELAND-THERMALSOLUTIONS.COM This printed matter is not subject to revision. No claims can be derived from it unless there is evidence of intent or gross negligence. The product characteristics are not guaranteed and do not replace our experts' advice. 171020_PR_EN_R/Th_0,0_GSK (GSK/Ri)