RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Domed-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description

Similar documents
ESCUTCHEON PLATE SEATING 3/4" NPT SURFACE. 1-1/2" (38,1 mm) CROSS SECTION PENDENT RECESSED PENDENT

Page 1 of 8 DECEMBER 2018 TFP408. Worldwide Contacts.

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Flat-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Horizontal Sidewall Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential 4.9 K-factor Concealed Pendent Sprinkler Flat Plate, Wet Pipe and Dry Pipe Systems General Description

proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. Dry Pipe System Application

proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. Dry Pipe System Application

RAPID RESPONSE Series LFII Residential Sprinklers 5.6 K-factor Horizontal Sidewall, NFPA 13 Optimized Wet Pipe Systems

WRENCH FLATS 1/2" NPT. 7/16" (11,1 mm) NOMINAL MAKE-IN CENTERLINE OF WATERWAY ESCUTCHEON PLATE SEATING SURFACE

RAPID RESPONSE Series LFII Residential Sprinklers 5.8 K-factor Horizontal Sidewall, NFPA 13 Optimized Wet Pipe Systems

WRENCH FLATS 1/2" NPT. 7/16" (11,1 mm) NOMINAL MAKE-IN CENTERLINE OF WATERWAY ESCUTCHEON PLATE SEATING SURFACE

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Pendent Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Horizontal Sidewall Wet Pipe Systems

The Series LFII (TY3596) Residential

Sprinkler Identification Number (SIN) TY4234. Page 1 of 8 APRIL 2012 TFP Technical Services

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description

Sprinkler Identification Numbers

RAPID RESPONSE Series LFII Residential Sprinkler 4.4 K-factor Horizontal Sidewall, Dry Type Wet Pipe System General Description

Series LFII Residential Sprinklers Flat-Plate Concealed Pendent 4.9 K-Factor General Description

Series TY-FRB 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Quick Response, Standard Coverage General Description

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description

Sprinkler Identification Numbers. TY3351 Horizontal TY3451 Vertical. Technical Data

Series TY-B 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Standard Response, Standard Coverage General Description

RAPID RESPONSE Series LFII Residential Sprinkler 4.4 K-factor Horizontal Sidewall, Dry Type Wet Pipe System General Description

Model CHEC 8.0 K-factor Concealed Horizontal Extended Coverage Quick Response Light Hazard, Sidewall Sprinklers General Description

Series TY-B 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General Description

Model SW-20 and SW K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) General Description

Model SW-20 and SW K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response)

WRENCH FLATS NPT 1/2" 7/16" (11,1 mm) NOMINAL MAKE-IN. 1-1/2" (38,1 mm) 2-3/16" (55,6 mm) WRENCH NPT. (12,7 mm) NOMINAL MAKE-IN.

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description

* Temperature rating is FIGURE K-FACTOR QUICK RESPONSE SERIES TY-FRB HORIZONTAL SIDEWALL (TY3331) SPRINKLERS

Series TY-B 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Standard Response, Standard Coverage General Description

Sprinkler Identification Number. Page 1 of 6 AUGUST 2018 TFP288. Worldwide Contacts.

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Series TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard) General Description

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright and Pendent Extended Coverage Light and Ordinary Hazard General Description

Series RFII 5.6 K-factor. Flush II Concealed Pendent Sprinklers

FIGURE 1 MODEL RFIII ECLH CONCEALED HSW SPRINKLER ASSEMBLY AND FEATURES. 5/16" (7,9 mm) MIN. 9/16" (14,3 mm) MAX.

Model ELOC 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick and Standard Response, Extended Coverage

Series TY-FRL 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Series TY-B 5.6 and 8.0 K-factor Upright and Pendent Intermediate Level Sprinklers Standard Response General Description

ILLUSION 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick Response, Standard Coverage General Description

Submittal Packages Detailed with Items and Reviewers

Sprinkler Identification Number TY ECLH HSW, 8.0K, 3/4"NPT

Series LFII Residential Pendent Sprinklers 4.9 K-factor General Description

Sprinkler Identification Numbers

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

ESCUTCHEON PLATE SEATING SURFACE. 1-11/16" (42,7 mm) CROSS SECTION

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description

Model ESFR K-factor Pendent Sprinkler Early Suppression, Fast Response General Description. Sprinkler Identification Number (SIN)

O-RING UPRIGHT SHIELD WRENCH FLATS WRENCH FLATS FIGURE 1 SERIES TY-B UPRIGHT (TY3153) AND PENDENT (TY3251) SPRINKLERS

Sprinkler Identification Number (SIN)

Series DS-1 Stainless Steel Dry-Type Sprinklers 5.6K Pendent, HSW, and Extended Coverage HSW Standard and Quick Response General Description

special request FACTORY ASSEMBLED UPRIGHT WITH SCREW FIELD ASSEMBLED MODEL S2 SHIELD (SEE INSTALLATION SECTION) WRENCH FLATS *

RAVEN 5.6K Institutional Sprinklers Pendent and Horizontal Sidewall Quick Response, Standard and Extended Coverage General Description

Model TY-FRFS, TY-FS Special, and TY-FS 57, 80, and 115 K-factor Upright and Pendent Flat Spray Sprinklers General Description

Series LFII Residential Flush Pendent Sprinklers 4.2 K-factor General Description

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright, and Pendent Extended Coverage Light and Ordinary Hazard General Description

Series TY-B & TY-FRB, 10 mm Orifice, ISO 7/1-R3/8 Upright, Pendent, and Recessed Pendent Sprinklers Standard and Quick Response General Description

Model TY-FRFS, TY-FS Special, and TY-FS Flat Spray Sprinklers, Upright and Pendent 57, 80, and 115 K-factor General Description

SENJU SPRINKLER CO.,LTD. Residential Flush Pendent Sprinkler Model ZN-RES,K=4.2 (SIN / SS4421) (PTFE gasketed orifice seal design) General Description

RAVEN 5.6K Institutional Sprinklers Pendent and Horizontal Sidewall Quick Response, Standard and Extended Coverage General Description

Series DS-1 Dry-Type Sprinklers 5.6K Pendent, Upright, and Horizontal Sidewall Quick Response, Standard Coverage General Description

Series LFII Residential Horizontal Sidewall Sprinklers 4.4 K-factor General Description

Commercial Flat Concealed Sprinkler, Pendent, Quick Response, Extended Coverage (Light Hazard) Model: RC-QR-EC, K-Factor: 5.

Residential Flush Horizontal Side-Wall Sprinkler Model HF-RES,K=4.2 (SIN / SS4423) (PTFE gasketed orifice seal design)

Model/Sprinkler Identification Number JULY, 2011 WARNINGS

Series LFII Residential Horizontal Sidewall Sprinklers 4.2 K-factor General Description

Data Sheet 4.24 Issue F

Series ELO K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description

Residential Flat Concealed Sprinkler, Pendent, Model: CN-RES, K-Factor: 4.9, SIN: SS8421

Series TY-B 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General Description

SENJU SPRINKLER CO., LTD.

Data Sheet 4.16 Issue D

Residential Lead Free Flat Concealed Sprinkler, Pendent, Model: RC-RES, K-Factor: 4.9, SIN: SS8461

RAPID RESPONSE Series LFII Residential Sprinklers 4.4 K-factor Horizontal Sidewall, Dry Type Wet Pipe and Dry Pipe Systems

Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

Series TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard)

G3/8" DIN ISO 228 THREAD SHOULDER AND DUST CAP MATING SURFACE. STYLE H ESCUTCHEON (SEPARATELY ORDERED) 85 mm DIA. (3-3/8")

Commercial Flat Concealed Sprinkler, Pendent, Quick Response, Standard Coverage, Model: RC-QR, K-Factor: 5.6, SIN: SS9561

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

Automatic Sprinklers

SENJU SPRINKLER CO., LTD.

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

Commercial Flat Concealed Sprinkler, Pendent, Quick & Standard Response, Standard Coverage, Model: CN-QR, K-Factor: 5.

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-Factor General Description

Sprinkler Identification Numbers

5.6K Horizontal Sidewall Standard and Quick Response, Extended Coverage General Description. Model/Sprinkler Identification Numbers (SINs)

In the event of this condition, consult the Authorities Having Jurisdiction for guidance and approval.

Model/Sprinkler Identification Numbers

Data Sheet 4.19 Issue C

Model WS TM 5.6 K-factor Specific Application Window Sprinklers, Horizontal and Pendent Vertical Sidewall General Description

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

Series ELO-231 Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

FIGURE 1. Model RD107

11.2K * Pendent Extended Coverage, Light and Ordinary Hazard General Description. Model/Sprinkler Identification Numbers (SINs) Technical Data

Model/Sprinkler Identification Number (SIN) Technical Data

Transcription:

Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Domed-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description Sprinklers (TY2234) are decorative, fast response, frangible bulb sprinklers designed for use in residential occupancies such as homes, apartments, dormitories, and hotels. The Cover Plate/Retainer Assembly conceals the sprinkler operating components above the ceiling. The domed profile of the cover plate provides aesthetically appealing sprinkler design with lower flow rates than can be achieved by lower profile cover plates. The separable two-piece design of the Cover Plate and Support Cup Assemblies allows installation of the sprinklers and pressure testing of the fire protection system prior to the installation of the ceiling or application of a finish coating. Also, the separable push-on and thread-off two-piece design of the Sprinkler provides for 1/2 inch (12,7 mm ) of vertical adjustment. The Series LFII Residential Sprinklers (TY2234) are intended for use in the following scenarios: wet and dry pipe residential sprinkler systems for one- and two-family dwellings and mobile homes per NFPA D wet and dry pipe residential sprinkler systems for residential occupancies up to and including four stories in height per NFPA R IMPORTANT Always refer to Technical Data Sheet TFP700 for the INSTALLER WARNING that provides cautions with respect to handling and installation of sprinkler systems and components. Improper handling and installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. wet and dry pipe sprinkler systems for the residential portions of any occupancy per NFPA The Series LFII Residential Sprinklers have been designed with heat sensitivity and water distribution characteristics proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. (TY2234) are shipped with a Disposable Protective Cap. The Protective Cap is temporarily removed for installation, and it must be replaced to protect the sprinkler while the ceiling is being installed or finished. The tip of the Protective Cap can also be used to mark the center of the ceiling hole into plaster board or ceiling tiles by gently pushing the ceiling product against the Protective Cap. When ceiling installation is complete, the Protective Cap must be removed and the Cover Plate Assembly installed. The Protective Cap must be removed to ensure proper performance of the sprinklers. Dry Pipe System Application (TY2234) Listing offers a laboratory approved option for designing dry pipe residential sprinkler systems, whereas, most residential sprinklers are laboratory approved for wet systems only. Through extensive testing, it has been determined that the number of design sprinklers (hydraulic design area) for the Series LFII Residential Domed- (TY2234) need not be increased over the number of design sprinklers (hydraulic design area) as specified for wet pipe sprinkler systems, as is customary for density/area sprinkler systems designed per NFPA. Consequently, the Series LFII Pendent Sprinklers offer the features of non-water filled pipe in addition to not having to increase the number of design sprinklers (hydraulic design area) for systems designed to NFPA, D, or R. Non-water filled pipe will permit options for areas sensitive to freezing. NOTICE (TY2234) described herein must be installed and maintained in compliance with this document and the applicable standards of the National Fire Protection Association, in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintaining their fire protection system and devices in proper operating condition. Contact the installing contractor or sprinkler manufacturer with any questions. Sprinkler Identification Number (SIN) TY2234 Technical Data Approvals UL Listed for use with wet pipe and dry pipe systems C-UL Listed for use only with wet pipe systems NYC Approved under MEA 44-03-E are only listed with the Series LFII Pendent Cover Plates having a factory applied finish. Page 1 of 6 MAY 14 TFP450

Page 2 of 6 SEALING WRENCH FLATS SPRINKLER STRAP (SEE INSTALLATION SECTION) DEFLECTOR THREAD INTO SUPPORT CUP UNTIL MOUNTING SURFACE IS FLUSH WITH CEILING SOLDER TABS (3) For details on these approvals, refer to the Design Criteria section. All listed cover plates and corresponding part numbers having factory applied finishes can be found in the Ordering Procedure section of this data sheet. Working Pressure 175 psi (12,1 bar) Discharge Coefficient K = 4.9 GPM/psi1/2 (70,6 LPM/bar1/2) Temperature Rating 155 F (68 C) Sprinkler with 9 F (59 C) Cover Plate Vertical Adjustment 1/2 inch (12,7 mm) Finishes Refer to Ordering Procedure section. SPRINKLER/SUPPORT CUP COVER PLATE/RETAINER FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL CONCEALED PENDENT SPRINKLERS (TY2234) (Shown with Sprinkler Strap) FRAME (1/2" NPT) BUTTON SUPPORT CUP WITH ROLL FORMED THREADS BULB COMPRESSION SCREW RETAINER WITH THREAD TABS EJECTION SPRING COVER PLATE Physical Characteristics Frame...Brass Button....Bronze Sealing Assembly................ Beryllium Nickel w/ TEFLON Bulb (3 mm)... Glass Compression Screw................. Brass Deflector....Copper Button Ejection Spring....Stainless Steel Support Cup...Steel Cover Plate....Brass Retainer...Brass Cover Plate Ejection Spring....Stainless Steel Operation When exposed to heat from a fire, the Cover Plate, which is normally soldered to the Support Cup at three points, falls away to expose the Sprinkler Assembly. The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb allowing the sprinkler to activate and flow water. Design Criteria Sprinklers (TY2234) are UL and C-UL Listed for installation in accordance with this section. Residential Sprinkler Design Guide When conditions exist that are outside the scope of the provided criteria, refer to the Residential Sprinkler Design Guide TFP490 for the manufacturer's recommendations that may be acceptable to the authority having jurisdiction. System Types Per the UL Listing, wet pipe and dry pipe systems may be utilized. Per the C-UL Listing, only wet pipe systems may be utilized. Refer to Technical Data Sheet TFP485 about the use of Residential Sprinklers in residential dry pipe systems. Ceiling Types Smooth flat horizontal, or beamed, or sloped, in accordance with the Edition of NFPA D, R, or as applicable. Hydraulic Design (NFPA D and R) For systems designed to NFPA D or NFPA R, the minimum required sprinkler flow rate are given in Tables A and B as a function of temperature rating and the maximum allowable coverage areas. The sprinkler flow rate is the minimum required discharge from each of the total number of design sprinklers as specified in NFPA D or NFPA R. The number of design sprinklers specified in NFPA D and R for wet pipe systems is to be applied when designing dry pipe systems. Hydraulic Design (NFPA ) For systems designed to NFPA, the number of design sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the following: The flow rates given in Tables A and B as a function of temperature rating and the maximum allowable coverage area. A minimum discharge of 0.1 gpm/ft 2. over the design area comprised of the four most hydraulically demanding sprinklers for the actual coverage areas being protected by the four sprinklers.

Page 3 of 6 Coverage Area a x (m x m) 12 x 12 (3,7 x 3,7) 14 x 14 (4,3 x 4,3) 16 x 16 (4,9 x 4,9) 18 x 18 (5,5 x 5,5) x (6,1 x 6,1) 12 (3,7) 14 (4,3) 16 (4,9) 18 (5,5) (6,1) WET PIPE SYSTEM Minimum Flow and Residual Pressure b, c Ordinary Temp. Rating 155 F (68 C) Flow GPM (L/min) 17 (64,3) (75,7) Pressure PSI (bar) 7.0 (0,48) 7.0 (0,48) 7.0(0,48) 12.0 (0,83) 16.7 (1,15) Deflector to Ceiling Smooth Ceilings 1/4 to 3/4 inches Beamed Ceilings per NFPA D or R Installed in Beam 1/4 to 3/4 inches below bottom of beam Installation Type Concealed Minimum 8 (2,4) a. For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. b. Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design under the Design Criteria section. c. For NFPA residential applications, the greater of 0.1 gpm/ft. 2 over the design area or the flow in accordance with the criteria in this table must be used. TABLE A WET PIPE SYSTEMS SERIES LFII RESIDENTIAL DOMED-PLATE CONCEALED PENDENT SPRINKLERS (TY2234) NFPA D, R, AND HYDRAULIC DESIGN CRITERIA Coverage Area a x (m x m) 12 x 12 (3,7 x 3,7) 14 x 14 (4,3 x 4,3) 16 x 16 (4,9 x 4,9) 18 x 18 (5,5 x 5,5) x (6,1 x 6,1) 12 (3,7) 14 (4,3) 16 (4,9) 18 (5,5) (6,1) DRY PIPE SYSTEM Minimum Flow and Residual Pressure b, c Ordinary Temp Rating 155 F (71 C) Flow GPM (L/min) 14 (53,0) 15 (56,8) (75,7) 22 (83,3) Pressure PSI (bar) 7.0 (0,48) 8.2 (0,57) 9.4 (0,65) 16.7 (1,15).2 (1,39) Deflector to Ceiling Smooth Ceilings 1/4 to 3/4 inches Beamed Ceilings per NFPA D or R Installed in Beam 1/4 to 3/4 inches below bottom of beam Installation Type Concealed Minimum a. For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. 8 (2,4) b. Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design under the Design Criteria section. c. For NFPA residential applications, the greater of 0.1 gpm/ft. 2 over the design area or the flow in accordance with the criteria in this table must be used. TABLE B DRY PIPE SYSTEM SERIES LFII RESIDENTIAL DOMED-PLATE CONCEALED PENDENT SPRINKLERS (TY2234) NFPA D, R, AND HYDRAULIC DESIGN CRITERIA

Page 4 of 6 1/2" NPT 2-1/2" DIA. (63,5 mm) 1/2" (12,7 mm) THREADED ADJUSTMENT 3/32" GAP (2,4 mm) FACE OF SPRINKLER FITTING 1-3/16"±1/4" (30,2 mm ±6,4 mm) SPRINKLER- SUPPORT CUP COVER PLATE RETAINER MOUNTING SURFACE COVER- RETAINER SPRINKLER- SUPPORT CUP 3-5/16" DIA. (84,1 mm) 15/16" (23,8 mm) The number of design sprinklers specified in NFPA D and R for wet pipe systems is to be applied when designing dry pipe systems. Dry Pipe System Water Delivery When using the Series LFII Residential Pendent Sprinklers (TY2234) in dry pipe sprinkler systems, the time for water delivery must not exceed 15 seconds for the most remote operating sprinkler. Obstruction to Water Distribution Sprinklers are to be located in accordance with the obstruction rules of NFPA D, R, and as applicable for residential sprinklers as well as with the obstruction criteria described within the Technical Data Sheet TFP490. Operational Sensitivity The sprinklers are to be installed relative to the ceiling mounting surface as shown in Figure 2. Plate Concealed Pendent Sprinklers must not be used in applications where the air pressure above the ceiling is greater than that below. Down drafts through the Support Cup could delay sprinkler operation in a fire situation. Sprinkler The minimum spacing between sprinklers is 8 feet (2,4 m). The maximum spacing between sprinklers cannot exceed the length of the coverage area (Table A or B) being hydraulically calculated (e.g., maximum 12 feet for a 12 ft. x 12 ft. coverage area, or feet for a ft. x ft. coverage area). TIP PROTECTIVE CAP Installation Sprinklers (TY2234) must be installed in accordance with this section. General Instructions Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 inch (1,6 mm). A leak-tight 1/2 inch NPT sprinkler joint should be obtained by applying a minimum-to-maximum torque of 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). Higher levels of torque can distort the sprinkler Inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in an Escutcheon Plate by under- or over-tightening the Sprinkler. Re-adjust the position of the sprinkler fitting to suit. Step 1. Install the sprinkler in the pendent position and with the centerline of the sprinkler perpendicular to the mounting surface. Step 2. Remove the Protective Cap. Refer to NFPA for guidance regarding removal of protective straps and caps Step 3. With pipe thread sealant applied to the pipe threads, and using the W-Type 7 Wrench shown in Figure 3, install and tighten the Sprinkler/Support Cup Assembly into the fitting. The W-Type 7 Wrench will accept a 1/2 inch ratchet drive. 1/4" (6,4 mm) 3/4" (19,1 mm) WRENCH RECESS OPERATED SPRINKLER FIGURE 2 DOMED CONCEALED COVER FOR USE WITH RAPID RESPONSE SERIES LFII RESIDENTIAL CONCEALED PENDENT SPRINKLERS (TY2234) (Shown with Protective Cap) PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA FIGURE 3 W-TYPE 7 RECESSED SPRINKLER WRENCH Step 4. Replace the Protective Cap by pushing it upwards until it bottoms out against the Support Cup. The Protective Cap helps prevent damage to the Deflector and Arms during ceiling installation and/or during application of the finish coating of the ceiling. It may also be used to locate the center of the clearance hole by gently pushing the ceiling material against the center point of the Cap. As long as the Sprinkler Strap (Figure 1) or the Protective Cap (Figure 2) remains in place, the system is considered to be Out Of Service. Step 5. After the ceiling has been completed with the 2-1/2 inch (63 mm) diameter clearance hole and in preparation for installing the Cover Plate/ Retainer Assembly, remove and discard the Protective Cap and the Sprinkler Strap.

Page 5 of 6 NOTE: Refer to Technical Data Sheet TFP700 regarding instructions for the removal of the Sprinkler Strap. Step 6. Push the Cover Plate/Retainer Assembly into the Support Cup, and as necessary, make the final adjustment of the Cover Plate with respect to the ceiling by turning the Cover Plate/Retainer Assembly clockwise until its flange just comes in contact with the ceiling. If it becomes necessary to remove the Cover Plate, it can be removed by unscrewing in a counter-clockwise direction. If the Cover Plate/Retainer Assembly cannot be engaged with the Support Cup or the Cover Plate/Retainer Assembly cannot be engaged sufficiently to contact the ceiling, the Sprinkler Fitting must be repositioned. Care and Maintenance Sprinklers (TY2234) must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities and notify all personnel who may be affected by this action. Absence of a Cover Plate may delay sprinkler operation in a fire situation. The owner must assure that the sprinklers are not used for hanging any objects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; otherwise, nonoperation in the event of a fire or inadvertent operation may result. When properly installed, there is a nominal 3/32 inch (2,4 mm) air gap between the lip of the Cover Plate and the ceiling, as shown in Figure 2. This air gap is necessary for proper operation of the sprinkler by allowing heat flow from a fire to pass below and above the Cover Plate to help assure appropriate release of the Cover Plate in a fire situation. If the ceiling needs repainting after sprinkler installation, exercise care to ensure that the new paint does not seal off any of the air gap. Failure to do so may impair sprinkler operation. Factory painted Cover Plates must not be repainted. They should be replaced, if necessary, by factory painted units. Non-factory applied paint may adversely delay or prevent sprinkler operation in the event of a fire. Do not pull the Cover Plate relative to the Retainer. Separation may result. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or otherwise altered after leaving the factory. Modified or overheated sprinklers must be replaced. Care must be exercised to avoid damage to the sprinklers - before, during, and after installation. Sprinklers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installation Section.) The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protec tion Association (e.g., NFPA 25), in addition to the standards of any authorities having jurisdiction. Contact the installing contractor or sprinkler manufacturer regarding any questions. Automatic sprinkler systems are recommended to be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes. Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name and Part Number (P/N). Sprinkler Assembly Specify: Series LFII (TY2234), K = 4.9, Pendent Sprinkler without Cover Plate Assembly, P/N 51-873-1-155 Cover Plate Assembly Specify: Series LFII (TY2234), K = 4.9, Pendent Sprinkler Cover Plate Assembly with (specify) finish, P/N (specify): Pure White* (RAL9010)...P/N 56-873-3-5 Signal White (RAL9003)....P/N 56-873-4-5 Chrome....P/N 56-873-9-5 Custom... P/N 56-873-X-5 * Eastern Hemisphere sales only. Sprinkler Wrench Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001

Page 6 of 6 GLOBAL HEADQUARTERS 1400 Pennbrook Parkway, Lansdale, PA 19446 Telephone +1-215-362-0700 Copyright 14 Tyco Fire Products, LP. All rights reserved. TEFLON is trademark of The DuPont Corporation