GESTRA. GESTRA Steam Systems TRS English. Installation & Operating Instructions Temperature Switch TRS 5-50

Similar documents
TRG 5-53 TRG 5-54 TRG 5-55 TRG 5-57

GESTRA Steam Systems NRS English. Installation Instructions Level Switch NRS 1-51

GESTRA Steam Systems NRS For TWO Electrodes. English. Installation Instructions Level Switch NRS 1-50

GESTRA. GESTRA Steam Systems NRS For ONE Electrode. English. Installation Instructions Level Switch NRS 1-50

Temperature Sensor TRG Original Installation Instructions English

NRG NRG NRG NRG

Conductivity Electrode LRG Original Installation Instructions English

SMK 22 SMK SMK SMK 22-82

Level Electrode NRG Original Installation Instructions English

GESTRA Steam Systems ER 50-1, ER Installation Instructions Level electrode

GESTRA Steam Systems LRG English. Installation Instructions Conductivity Electrode

Level Electrode NRG NRG Original Installation Instructions English

TRG 5-6x. GESTRA Steam Systems. Installation Instructions

GESTRA Steam Systems NRGS 11-2, NRGS Installation Instructions Level Electrode Types

Installation & Operating Instructions

BK 45 BK 45-U BK 45-LT BK 46

Operating Manual MS220KA and MSR220KA

Safety Temperature Limiter STL 50 Certified to DIN EN (replaces DIN 3440)

Proservo NMS5- / NMS7-

MK 45-1 MK 45-2 MK 45 A-1 MK 45 A-2

ISIS SAFETY SYSTEM Installation guide

Operating Manual MS220DA

LC3000 Level Controller Installation and Maintenance Instructions

Connection. e. g. Pt100. reference limit. yellow Output I. Composition

Operating instructions Safety-monitoring module SRB 302X3. 1 About this document

Liquiphant S, Nivotester FDL60/61, FTL670

Operating instructions Safety-monitoring module SRB 302X3. 1. About this document. Content

GESTRA Steam Systems BK 15. Installation Instructions Steam Trap BK 15, DN 40-50

SensaGuard TM Integrated Latch Installation Instructions

DEB71. Earth Leakage Monitoring Relay. Benefits. Description

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

GESTRA Steam Systems OR 52-5 OR English. Installation & Operating Instructions Oil & Turbidity Detector OR 52-5, OR 52-6

SAFETY MANUAL. Multispectrum IR Flame Detector X3301

FMEDA Report. Failure Modes, Effects and Diagnostic Analysis. KFD0-CS-Ex*.54* and KFD0-CS-Ex*.56* Project: X7300

Original operating instructions Safety switch with guard locking AC901S AC902S

GMA200-MW4. User Manual. Gas detection controller for wall mounting

RE-PR3-E-27 3-Phase Panel Mount 27kW

Functional Safety Manual Oil Leak Detector NAR300 System

Pressure Transmitter cerabar S PMC 731/631 cerabar S PMP 731/635 with ma output signal

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

1.7. Insulation fault evaluators EDS460/490 EDS461/491

1.7. Insulation fault evaluators EDS460/490 EDS461/491

PROTECT SRB 200EXi-1A

Differential Pressure Transmitter deltabar S PMD 230/235 deltabar S FMD 230/630/633 with ma output signal

LINETRAXX RCMA420. Residual current monitor for monitoring AC, DC and pulsed DC currents in TN and TT systems

LINETRAXX VME420. Multi-functional relay for overvoltage, undervoltage and frequency monitoring in AC/DC systems with external supply voltage

GESTRA Steam Systems BK 37 BK 28 BK 29. Installation Instructions Steam Trap BK 37, BK 28, BK 29 BK 37 ASME, BK 28 ASME, BK 29 ASME

Soliphant M with electronic insert FEM52

SITRANS. Temperature transmitter Functional safety for SITRANS TW. Introduction. General safety instructions 2. Device-specific safety instructions

Technical Manual for the Manual Alarm Call Point BG

Safety Control Modules for Emergency Stop Circuits FF-SRS5988 FF-SRS5935 FF-SRS5925 FF-SRS5934 FF-SRS5924 TYPICAL APPLICATIONS APPROVALS DIMENSIONS

SAFETY MANUAL. Intelligent Sensors for H 2 S Gas Applications

SAFETY MANUAL. X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors

RTA421. Technical Information. Limit alarm switch Alarm switch and power supply for monitoring current or voltage signals

Functional safety manual Liquiphant M/S with FEL57 and Nivotester FTL325P

THERMOMAX COLTREC RCX 100 MICROPROCESSOR REFRIGERATION CONTROL SYSTEM ENGLISH.

FUNCTIONAL SAFETY MANUAL

Datasheet - MZM 100 ST2-1P2PWREM-A

Instruction Manual. Alarm Unit For Low Gas Level # Read manual before use! Observe all safety information! Keep manual for future use!

EUROFLAT SERIES TYPES C... S... M...

Datasheet - MZM 100 ST-SD2PREM-A

ST Wiring diagram. Product description. Standard temperature controller. Order number

SCHMIDT LED Measured Value Display MD Instructions for Use

HPS-C-MULTI 6. Hotrunner Controllers. Operating manual. Valid for item numbers:

English. Operating manual. Safety temperature limiter STL50 Approved in accordance with: DIN EN (replacing DIN 3440) SIL 2

INSTRUCTION MANUAL (ATEX/IECEx/SIL2) BExBG05D-SIL Flameproof Xenon SIL 2 Beacons For use in Flammable Gas and Dust Atmospheres

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

Datasheet - MZM 100 B ST2-SD2PREM-A

Rosemount Functional Safety Manual. Manual Supplement , Rev AF March 2015

LINETRAXX VMD420. Multi-functional voltage relay for 3(N)AC systems, frequency/overvoltage/undervoltage, phase, phase failure, asymmetry

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

100 & 120 Series Pressure and Temperature Switches Safety Manual

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems)

LC2200 Level Controller Installation and Maintenance Instructions

OPTISENS TUR 2000 Technical Datasheet

Functional Safety Manual June pointek CLS500/LC500

Project planning (original) EN. Functional safety. Inverter i550-cabinet kw

Ordering Key. Dielectric strength

02/11/2015

SAFETY INTEGRITY LEVEL MANUAL. IEC and IEC XP95 and Discovery SIL Approved Product Range

BC3250. Blowdown Controller

ST Wiring diagram. Product description. Four-stage controller. Order number

Flame Safeguards LFE10. Building Technologies HVAC Products

Universal Dimmer N 528D01, 2 x 300VA, AC 230 V 5WG DB01

Instructions for the fan motor control system with integrated wiring terminals SILVER C

Servicing manual. Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C /2002 GB(EN) For trade use

Servicing manual. 600 Series - 11S / 19S / 24S / 24C. Wall-mounted condensing gas boiler. For trade use

BES M30EP-PFC12F-S04G-D12 BES Q40ZU-PFC15B-S04G-D12 BES Q40ZU-PFC20F-S04G-D12 Inductive Safety Sensors User's Manual

USER MANUAL FOR EXPLOSION PROTECTED FLUORESCENT LIGHT FITTING type PSF 218

OilSET Installation and Operating Instructions. Oil Separator Alarm Device with SET/DM3AL sensor

Operating Manual VMD420

Failure Modes, Effects and Diagnostic Analysis. PR electronics A/S Rønde Denmark

KHA6-GT*-Ex1. Thermocouple trip amplifiers. Composition. Hazardous area. Safe area. Function. 230 V AC 1-channel. Input EEx ia IIC

4 Ó â. Contactor RTA421. Contactor with loop power supply for monitoring currentorvoltagesignals. Technical information TI074R/09/en

PCR-300 PCR-300 RC. Installation and Operating Instructions

Process Alarm Module RTA 421

Installation and operating instructions. Temperature difference controller 6 inputs, 3 outputs, integrated data logger for SD card

SIL Safety Guide Series MS Single-Acting Spring-Return Hydraulic Linear Actuators

DTA04. Motor thermistor relay. Benefits. Description

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

Transcription:

GESTRA GESTRA Steam Systems TRS 5-50 EN English Installation & Operating Instructions 819226-03 Temperature Switch TRS 5-50 1

Contents Important notes Page Usage for the intended purpose...4 Function...4 Safety note...5 Directives and standards EC Pressure Equipment Directive 97/23/EC...5 Functional Safety acc. to IEC 61508...5 DIN EN 14597...5 Approvals for Marine Applications...5 LV (Low Voltage) Directive and EMC (Electromagnetic Compatibility)...6 ATEX (Atmosphère Explosible)...6 UL / cul (CSA) Approval...6 Note on the Declaration of Conformity / Declaration by the Manufacturer...6 Functional Safety acc. to IEC 61508 Safety characteristics of the subsystem TRG 5-6.. / TRS 5-50...7 Terms and abbreviations...7 Determination of the Safety Integrity Level (SIL) for safety-related systems...8 Technical data TRS 5-50...9 Name plate / marking...10 In control cabinet: Mounting temperature switch Dimensions TRS 5-50...11 Key...11 Installation in control cabinet...11 Scope of supply...11 In control cabinet: Wiring temperature switch Wiring diagram for temperature switch TRS 5-50...12 Key...12 Connection of supply voltage...13 Connection of safety circuit...13 Equipment used as safety temperature monitor...13 Equipment used as safety temperature limiter, connection of reset/test input...13 Connecting the temperature sensor...13 Connection for actual-value output (optional)...14 2

Contents - continued - In the plant: Wiring temperature sensor Page Connection for temperature sensor...15 Wiring diagram for temperature sensor...15 Factory setting...16 Changing factory settings Changing the configuration...16 Commissioning procedure Start and adjustment of MAX limit...17 Operation, alarm and test Indicators and adjustors...18 Troubleshooting Indication, diagnosis and remedy...19 Measure fluid temperature...20 Check installation and performance Checking switch-off function at T MAX...20 Further Notes Action against high frequency interference...21 Decommissioning / replacing the equipment...21 Disposal...21 3

Important notes Usage for the intended purpose The temperature switch TRS 5-50 is used in conjunction with temperature sensor TRG 5-6.. as safety temperature limiter or monitor, for instance in steam boilers and (pressurised) hot-water plants. When the max. admissible temperature in the superheater or the inlet line is reached, the safety temperature limiter or monitor switches the heating off. The temperature switch TRS 5-50 can be used in combination with the following temperature sensing electrodes: TRG 5-63, TRG 5-64, TRG 5-65, TRG 5-66, TRG 5-67 and TRG 5-68 Function A platinum resistance thermometer Pt 100 to EN 60751 is used as temperature sensor for the temperature switch TRS 5-50. A three-wire configuration is used for the electrical connection. The temperature switch processes the temperature-dependent changes in resistance of the temperature sensor and, during normal operation, the seven-segment LED display shows the adjusted switchoff temperature T MAX ( C) and the actual value T ( C). The switchpoint for MAX temperature can be variably adjusted within the measuring range. Once the MAX temperature is reached both output contacts of the temperature switch open the safety circuit and the seven-segment LED display for T MAX is flashing. In addition the relay contact for external signalling equipment is closed. If the system is configured as safety temperature monitor, the temperature switch does not automatically interlock the deactivation of the heating. As soon as the temperature has fallen below the fixed hysteresis, the safety circuit will be closed again. However, if the system is configured as safety temperature limiter, the temperature switch automatically interlocks the deactivation of the heating. Note that once the temperature has fallen below the fixed hysteresis, the equipment must be reset manually or externally in order to close the safety circuit. Any error or malfunction that occurs in the temperature sensor, the electrical connection or the temperature switch is indicated by the seven-segment LED display and the output contacts will be opened. An automatic self-testing routine monitors the safety functions in the temperature switch and the temperature sensor. In the event of a malfunction the safety circuit opens and switches the heating off. Parameter settings can be changed, a MAX temperature alarm can be simulated and the equipment can be reset by operating the rotary button. For external temperature indication the equipment is optionally available with an actual-value output 4-20 ma. 4

Important Notes - continued - Safety note Safety temperature limiters/monitors are safety devices and must only be installed, wired and commissioned by qualified and competent staff. Retrofitting and maintenance work must only be performed by qualified staff who - through adequate training - have achieved a recognised level of competence. Danger The terminal strips of the equipment are live during operation. This presents the danger of electric shock! Always cut off power supply to the equipment before mounting, removing or connecting the terminal strips! Attention The name plate specifies the technical features of the equipment. Note that any piece of equipment without its specific name plate must neither be commissioned nor operated. Directives and standards EC Pressure Equipment Directive 97/23/EC Safety temperature limiters/monitors are safety accessories as defined in the Pressure Equipment Directive (PED). The temperature switch TRS 5-50 in conjunction with temperature sensors TRG 5-6.. is EC type approved according to EN 12952/EN 12953. These Directives state, among other things, the requirements made on limiting systems and equipment for steam boiler plants and (pressurised) hotwater installations. Functional Safety acc. to IEC 61508 The temperature switch TRS 5-50 in conjunction with temperature sensors TRG 5-6.. is certified to IEC 61508. This standard describes the functional safety of safety-related electrical/electronic/programmable electronic systems. The equipment combination TRG 5-6.. + TRS 5-50 corresponds to a type B subsystem with Safety Integrity Level (SIL) 3. DIN EN 14597 The temperature switch TRS 5-50 in conjunction with temperature sensing electrodes type TRG 5-6.. is type approved according to DIN EN 14597. DIN EN 14597 describes and specifies the requirements made on safety temperature limiters/monitors. Approvals for Marine Applications The temperature switch TRS 5-50 in conjunction with temperature sensors TRG 5-6.. is approved for marine applications. 5

Directives and Standards - continued - LV (Low Voltage) Directive and EMC (Electromagnetic Compatibility) The temperature switch TRS 5-50 meets the requirements of the Low Voltage Directive 2006/95/EC and the EMC Directive 2004/108/EC. ATEX (Atmosphère Explosible) According to the European Directive 94/9/EC the temperature switch TRS 5-50 must not be used in potentially explosive areas. UL / cul (CSA) Approval The equipment meets the requirements of the Directives: UL 508 and CSA C22.2 No. 14-13, Standards for Industrial Control Equipment. File E243189. Note on the Declaration of Conformity / Declaration by the Manufacturer For details on the conformity of our equipment according to the European Directives see our Declaration of Conformity or our Declaration of Manufacturer. The current Declaration of Conformity / Declaration of Manufacturer are available in the Internet under www.gestra.com/documents or can be requested from us. 6

Functional Safety acc. to IEC 61508 Safety characteristics of the subsystem TRG 5-6.. / TRS 5-50 The temperature switch TRS 5-50 in conjunction with temperature sensors TRG 5-6.. is certified to IEC 61508. The equipment combination TRG 5-6.. / TRS 5-50 corresponds to a type B subsystem with Safety Integrity Level (SIL) 3. Type B means that the behaviour under fault conditions of the used components cannot be completely determined. The functional safety of the equipment combination refers to the detection and evaluation of the temperature and, as a consequence, the contact position of the output relays. The design of the equipment combination TRG 5-6.. / TRS 5-50 corresponds to the architecture 1oo2. This architecture consists of two channels that detect and diagnose faults in each other. If a fault is detected, the equipment combination TRG 5-6.. / TRS 5-50 will go to the safe state, which means that the contacts of both output relays will open the safety circuit. The equipment is suitable for machines and installations up to performance level "e". Safety characteristics SIL Architecture Lifetime (a) Proof Test Interval (a) General 3 1oo2 20 20 SFF PFD av PFH av λ DU Temperature switch TRS 5-50 alone 99.6 % 2.69* x 10-5 3.07 x 10-9 2.95 x 10-9 /h Temperature switch TRS 5-50 in combination with temperature sensor TRG 5-6.. * if required once a year 98.2 % 1.71* x 10-4 1.96 x 10-8 1.95 x 10-8 /h Fig. 1 Terms and abbreviations Terms Abbreviations Safety Integrity Level SIL Lifetime (a) Safe Failure Fraction SFF Probability Failure per Demand (Low Demand) PFD av Probability Failure per Hour PFH av λdu Description Classification of the Safety Integrity Level acc. to IEC 61508 Functional safety: Lifetime in years Percentage of failures without the potential to put the safety-related system into a dangerous state Average probability of failure on demand for low demand mode (once a year) Probability failure per hour Failure rate for all dangerous undetected failures (per hour) of a channel of a subsystem Fig. 2 7

Functional safety acc. to IEC 61508 - continued - Determination of the Safety Integrity Level (SIL) for safety-related systems Temperature sensor, temperature switch and actuators (auxiliary contactor in safety circuit) are subsystems and together constitute a safety-related system that executes a safety function. The specification of the safety-related characteristics Fig. 1 refers to the temperature sensor and the temperature switch including the output contacts. The actuator (e. g. an auxiliary contactor in the safety circuit) is installation specific and, according to IEC 61508, must be considered separately for the whole safety-related system. Table Fig. 3 shows the dependence of the Safety Integrity Level (SIL)on the average probability of failure on demand of a safety function for the whole safety-related system (PFD sys ). The "Low demand mode" is here considered for a safety temperature limiter, which means that the frequency of demands for operation of the safety-related system is no greater than one per year. Low demand mode PFD sys Safety Integrity Level (SIL) 10-5... < 10-4 4 10-4... < 10-3 3 10-3... < 10-2 2 10-2... < 10-1 1 Fig. 3 The table in Fig. 4 indicates the attainable Safety Integrity Level (SIL) as a function of the Safe Failure Fraction (SFF) and the Hardware Fault Tolerance (HFT) for safety-related systems. Fig. 4 Hardware Fault Tolerance (HFT) for type B Safe Failure Fraction (SFF) 0 1 2 SIL 1 SIL 2 < 60 % SIL 1 SIL 2 SIL 3 60 % < 90 % SIL 2 SIL 3 SIL 4 90 % < 99 % SIL 3 SIL 4 SIL 4 99 % 8

Technical data TRS 5-50 Supply voltage 24 VDC +/ 20%, 0.3 A; 100-240 VAC + 10/ 15%, 47-63 Hz, 0.2 A Fuse external M 0.5 A Power consumption 7 VA Wiring temperature sensor 1 input for temperature sensor TRG 5-63, TRG 5-64, TRG 5-65, TRG 5-66, TRG 5-67 and TRG 5-68, (platinum resistance thermometer Pt 100 to EN 60751), with 3 poles and screen. Connection for external test & reset 1 volt-free input, 24 VDC, for connecting external reset and test button. Safety circuit 2 volt free make contacts, 6 A 250 V AC / 30 V DC cos ϕ = 1 (external slow-blow fuse 2 A). Inductive loads must be provided with interference suppressors (RC combinations) as specified by the manufacturer. Signal outputs 1 analogue output 4-20 ma (0 650 C), max. load 500 ohm, e. g. for actual-value indication (optional). 1 voltage-free output for instantaneous external signalling, 24 V DC, max. 100 ma (semiconductor output). Limit range 0 C to 600 C Reset hysteresis -3 K, fixed setting. Indicators and adjustors 1 rotary button with integrated pushbutton for setting the MAX temperature and testing and resetting the equipment. 1 pushbutton (hidden) for enabling the setting. 1 two-pole code switch for configuration. 2 seven-segment three-digit LED dispaly for MAX temperature and actual value. Housing Housing material: base: polycarbonate, black; front: polycarbonate, grey Conductor size: 1 x 4.0 mm² solid per wire or 1 x 2.5 mm 2 per stranded wire with sleeve to DIN 46228 or 2 x 1.4 mm 2 per stranded wire with sleeve to DIN 46228; Terminal strips can be detached Fixing of housing: Mounting clip on supporting rail TH 35, EN 60715 Electrical safety Degree of contamination: 2, overvoltage category III to EN 61010-01. Protection Housing: IP 40 to EN 60529 Terminal strip: IP 20 to EN 60529 Weight approx. 0.5 kg 9

Technical data - continued - TRS 5-50 - continued - Ambient temperature when system is switched on: 0... 55 C during operation: -10... 55 C Transport temperature 20... +80 C (<100 hours), defrosting time of the de-energized equipment before it can be put into operation: 24 hours: 24 hours. Storage temperature 20... +70 C, defrosting time of the de-energized equipment before it can be put into operation: 24 hours. Relative humidity max. 95%, no moisture condensation Site altitude max. 2000 m Approvals: EC Type approval PED Pressure Equipment Directive 97/23/EC, EN 12952-11, EN 12953-09: Requirements made on limiting equipment for boilers. Functional Safety acc. to EN 61508: Functional safety of safety-related electrical/ SIL 3 electronic/programmable electronic systems Type approval DIN EN 14597: Requirements made on safety temperature limiters/monitors DIN Registration number DIN STW/STB 1230 Marine applications Rules and guidelines of classification societies, GL 47399-12 HH UL /cul (CSA) Approval ApprovalUL 508 and CSA C22.2 No. 14-13, Standards for Industrial Control Equipment. File E243189. Name plate / marking Safety note Ambient temperature Please enter limit value. Wiring diagram Betriebsanleitung beachten See installation instructions 100-240V~ 7 VA Voir instructions de -15/+10% montage Tamb = 55 C (131 F) IP 40 (IP20) TMAX = C STB STW DIN STW / STB 1230 Pt100 TRS 5-50 + + - 1 2 3 1 2 3 Funktionale Sicherheit Functional safety Sécurité fonctionnelle IEC 61508 SIL 3 6 7 + - Reset/Test 24VDC Temperaturschalter Temperature switch Commutateur de température Wirkweise Typ 2BK + JPV 14 15 16 17 20 21 23 24 26 27 + - OUT / 4-20mA L M 0,5A N Alarm 100 ma 24VDC + - TRS 5-50 250V T 2,0A Sicherheitstemperaturbegrenzer / - wächter Self-monitoring temperature limiter/monitor Limiteur de température de sécurité / Dispositif de surveillance de température de sécurité 0525 Type designation Supply voltage / Power consumption Protection DIN registrations no. Safety circuit Wire link, provided on site Fuse, provided on site Fig. 5 Manufacturer GESTRA AG Münchener Str. 77 D-28215 Bremen Serial number Disposal note 10

In control cabinet: Mounting temperature switch Dimensions TRS 5-50 100 120 15 1 74 4 3 Fig. 6 2 Key 1 Upper terminal strip 2 Lower terminal strip 3 Housing 4 Supporting rail type TH 35, EN 60715 Installation in control cabinet The temperature switch TRS 5-50 is clipped onto the support rail type TH 35, EN 60715 in the control cabinet. Fig. 6 4 Please enter the defined limit value on the nameplate before mounting the equipment. Scope of supply TRS 5-50 1 Temperature switch TRS 5-50 1 Installation & operating manual 11

(-) (+) In control cabinet: Wiring temperature switch Wiring diagram for temperature switch TRS 5-50 L N (+) (-) N L 5 6 7 8 7 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 9 1 2 3 0 a Fig. 7 (-) (+) b Key 5 Connection of supply voltage with fuse 0.5 A (semi-delay) provided on site 6 Signal output for external alarm 24 V DC 100 ma (semiconducator output) 7 Safety circuit, input and output 8 Wire link, on site, if equipment is used as safety temperature limiter acc. to TRD, EN 12952 / EN 12953 9 Wiring diagram for temperature sensor 0 Reset/test input, 24 VDC a Actual value output 4-20 ma (0 650 C) (optional) b Central earthing point (CEP) in control cabinet 12

In control cabinet: Wiring temperature switch - continued - Connection of supply voltage The equipment is supplied with 24 V DC or 100-240 V AC and fused with an external semi-delay fuse 0.5 A. For the supply of the temperature switch TRS 5-50 with 24 V DC use a safety extra-low voltage (SELV) power supply unit. Connection of safety circuit The safety circuit (make contacts of output relays) is opened via terminals 23/24 and 26/27 of the temperature switch. In order for the equipment to be used as safety temperature monitor/safety temperature limiter and to attain Safety Integrity Level SIL 3 the logical AND function of the output contacts must be performed externally (e. g. through series connection of contacts via wire link between terminals 24 and 26). Provide a slow-blow fuse 2 A for the output contacts (terminals 23/24 and 26/27) of the safety circuit. Equipment used as safety temperature monitor If the system is configured as safety temperature monitor, the temperature switch does not automatically interlock the deactivation of the heating. As soon as the temperature has fallen below the nonadjustable hysteresis, the safety circuit will be closed again. Equipment used as safety temperature limiter, connection of reset/test input If the system is configured as safety temperature limiter, the temperature switch automatically interlocks the deactivation of the heating. Note that once the temperature has fallen below the non-adjusted hysteresis, the equipment must be reset manually or externally in order to close the safety circuit. The equipment can be tested or reset externally by means of a voltage pulse at the reset/test input. For this purpose connect a 24 V DC voltage source with pushbutton to terminals 6 and 7. For the connection use screened multi-core control cable with a min. conductor size 0.25 mm 2, e. g. LiYCY 2 x 0.25 mm 2, max. length 10 m. Connecting the temperature sensor To connect the equipment use screened multi-core control cable with a min. conductor size 0.5 mm 2, e. g. LiYCY 3 x 0.5 mm 2, max. length: 100 m. Wire terminal strip in accordance with the wiring diagram. Fig. 7 Note that only the cable gland of the temperature sensor provides the screen. 13

In control cabinet: Wiring temperature switch - continued - Connection for actual-value output (optional) For the connection use screened multi-core control cable with a min. conductor size 0.5 mm 2, e. g. LiYCY 2 x 0.5 mm 2, max. length 100 m. The current output 4-20 ma corresponds to a temperature of 0 650 C. Please observe the max. load of 500 ohm. Wire terminal strip (terminals 14/15) in accordance with the wiring diagram. Fig. 7 Do not use this output for activating safety circuits. Connect the screen only once to the central earthing point (CEP) in the control cabinet. Connection for signal output To connect external signalling equipment use screened multi-core control cable with a min. conductor size 0.5 mm 2, e. g. LiYCY 2 x 0.5 mm 2, max. length: 100 m. In the event of an alarm or error message, the signal output (terminals 20, 21) closes. Do not use this output for activating safety circuits. Tools Attention n Fuse the temperature switch TRS 5-50 with an external semi-delay fuse 0.5 A. n Any item of equipment that you want to connect to the terminals 6/7, 14/15 and 20/21 of the temperature switch must be electrically isolated from dangerous contact voltages as per DIN EN 61140, e. g. through double or reinforced isolation according to DIN EN 61010-1 or DIN EN 60730-1 or DIN EN 60950-1. n To protect the relay contacts fuse safety circuit with 2 A (slow blow). n When switching off inductive loads, voltage spikes are produced that may impair the operation of control and measuring systems. Connected inductive loads must be provided with suppressors such as RC combinations as specified by the manufacturer. n When used as safety temperature monitor/ safety temperature limiter according to TRD, EN 12952 / EN 12953 connect terminals 24 and 26 by adding a wire link. n Make sure that connecting cables leading to the temperature sensor and/or any other external equipment are segregated and run separately from power cables. n Do not use unused terminals as support point terminals. n Screwdriver for slotted screws, size 3.5 x 100 mm, completely insulated according to VDE 0680-1. 14

In the plant: Wiring temperature sensor Connection for temperature sensor The temperature switch TRS 5-50 is designed for use in conjunction with temperature sensors TRG 5-63, TRG 5-64, TRG 5-65, TRG 5-66, TRG 5-67 and TRG 5-68. To connect the equipment use screened multi-core control cable with a min. conductor size 0.5 mm 2, e. g. LiYCY 3 x 0.5 mm 2, max. length: 100 m. Note that only the cable gland of the temperature sensor provides the screen. Attention n Please follow the instructions given in the installation & operating manual for the TRG 5-6x. n Make sure that connecting cables leading to the equipment are segregated and run separately from power cables. Wiring diagram for temperature sensor TRG 5-63, TRG 5-65, TRG 5-66, TRG 5-67 1 3 2 TRG 5-64 TRG 5-68 3 2 1 3 6 red 3 6 5 yellow 5 2 black Fig. 8 black Note Additional equipment such as indicating devices can be connected to the terminals marked in yellow and black of the TRG 5-64 and TRG 5-68.. 15

Factory setting Temperature Switch TRS 5-50 n MAX limit = 25 C n Reset hysteresis: -3 K (fixed setting) n Configuration: Safety temperature monitor n Code switch c : S1, S2 OFF Changing factory settings Danger The upper terminal strip of the equipment is live during operation. This presents the danger of electric shock! Always cut off power supply to the equipment before mounting, removing or connecting the terminal strips! Changing the configuration The code switch c setting determines the configuration of the temperature switch (safety temperature monitor or limiter). If you want to configure the temperature switch as safety temperature limiter please proceed as follows: n Cut off supply voltage. n Lower terminal strip: Unscrew left and right fixing screws and remove the terminal strip. Fig. 9 n Set S1 and S2 of the code switch c to ON = safety temperature limiter. n Attach lower terminal strip and fasten fixing screws. n Apply supply voltage. Equipment is restarted. c 16 Fig. 9 Note Please indicate on the nameplate whether the temperature switch is used as safety temperature monitor or as safety temperature limiter.

Commissioning procedure Start and adjustment of MAX limit Fig. 10 Indication of limit value 543 Rotary button with integrated pushbutton Start 520 Pushbutton (hidden) for enabling the setting. Hole 3 mm Indication of actual value / error code Status and action Display Function Switch on supply voltage. All segments and decimal points of the displays for T MAX and T are tested one after another. They all light up once and then go out. System and segment test, takes approx. 15 sec. The system then switches back to normal operating mode. Please observe the system and segment test. If segments or points are missing replace the temperature switch. Actual value T ( C) below limit T MAX ( C) Actual value T ( C) above limit T MAX ( C) Display T MAX ( C) Display T ( C) Actual value Display T MAX ( C) is flashing Display T ( C) Actual value Indication of the adjusted limit Indication of the actual value Safety temp. monitor: Safety circuit open, signal output closed Safety temp. limiter: Safety circuit open and interlocked, signal output closed Adjusting the MAX limit Activity Seven-segment displays Function Use a 2.5 mm pin to press the (hidden) pushbutton T MAX ( C): Indication of limit value, first digit (000) is flashing. T ( C): Indication of limit value Enables the setting of the limit values. During input both displays (Tmax and T) show the limit value. Should these two indicated values differ from each other replace the temperature switch. Turn rotary button. Press push-button. Each time you press the button the system moves to the next digit. Press push-button. If no operation is performed: First digit (0000) flashing. Second or third digit is flashing. (from left to right) T MAX ( C): Indication of limit value T ( C): Indication of the actual value Set the limit value. To increase the value turn rotary button to the right, to decrease turn it to the left. Confirm your input. Enter the limit value on the nameplate. After 10 sec. the system switches back to normal operating mode. 17

Operation, alarm and test Indicators and adjustors 543 520 Indication of actual value / error code Fig. 10 Indication of limit value Rotary button with integrated pushbutton Pushbutton (hidden) for enabling the setting. Hole 3 mm Operation Status and action Display Function Actual value T ( C) below limit T MAX ( C) Display T MAX ( C) Display T ( C) Actual value Indication of the adjusted limit Indication of the actual value Actual value T ( C) above limit T MAX ( C) Alarm Display T MAX ( C) is flashing Display T ( C) Actual value Safety temp. monitor: Safety circuit open, signal output closed Safety temp. limiter: Safety circuit open and interlocked, signal output closed Actual value T ( C) must be 3 C below limit T MAX ( C) Press the pushbutton of the rotary button of the temperature switch or the external reset/ test button. Safety temperature limiter: Reset alarm Display T MAX ( C) is flashing Safety circuit closed, signal output open. Display T ( C) Actual value 18 Press the pushbutton of the rotary button of the temperature switch or the external reset/ test button. When you release the button the system switches back to normal operating mode. Press the pushbutton of the rotary button of the temperature switch or the external reset/test button. Press again the pushbutton or the external reset/test button to reset the system. Safety temperature monitor: Test T MAX ( C): Indication of limit value is flashing. T ( C): Indication of limit value Safety temperature limiter: Test T MAX ( C): Indication of limit value is flashing. T ( C): Indication of limit value While pushbutton is held down: Safety circuit open, signal output closed Replace the temperature switch if the test does not finish successfully. Safety circuit open and interlocked, signal output closed. After pressing the button twice: Safety circuit closed, signal output open. Replace the temperature switch if the test does not finish successfully.

Troubleshooting Indication, diagnosis and remedy Attention Before carrying out the fault diagnosis please check: Supply voltage: Is the equipment supplied with the voltage specified on the name plate? Wiring: Is the wiring in accordance with the wiring diagram? Faults indicated by the seven-segment display on the right side Error code Error Remedy E.01 E.02 E.03... E.06 and E.08 Temperature sensor defective, temperature reading too low Temperature sensor defective, temperature reading too high Temperature switch defective. An error was detected during one or more self-testing routine(s). Check whether the temperature sensor outputs correct readings (see Fig. 11). If there are any deviations please replace the measuring element with a new one. Check the sensor lines (short circuit, interruption?). Switch the temperature switch off and on again. If the error code re-appears, replace the temperature switch. Set the code switch according to the desired equipment function. E.07 The code switch c setting is incorrect. When contacting our Technical Service team please state the indicated error code. In the event of a malfunction a MAX alarm will be triggered. 19

Troubleshooting - continued - Measure fluid temperature Use table Fig. 11 to ascertain the current temperature of the fluid via the resistance value of the Pt 100 directly on the temperature sensor. Please follow the instructions given in the installation & operating manual for the TRG 5-6x. C 0 10 20 30 40 50 60 70 80 90 100 Ω/deg 0 100.00 103.90 107.79 111.67 115.54 119.40 123.24 127.07 130.89 134.70 138.50 0.385 100 138.50 142.28 146.06 149.82 153.57 157.32 161.04 164.76 168.47 172.16 175.84 0.373 200 175.84 179.51 183.17 186.82 190.46 194.08 197.70 201.30 204.88 208.46 212.03 0.361 300 212.03 215.58 219.13 222.66 226.18 229.69 233.19 236.67 240.15 243.61 247.06 0.350 400 247.06 250.50 253.93 257.34 260.75 264.14 267.52 270.89 274.25 277.60 280.93 0.338 500 280.93 284.26 287.57 290.87 294.16 297.43 300.70 303.95 307.20 310.43 313.65 0.327 600 313.65 316.86 320.05 323.24 326.41 329.57 332.72 335.86 338.99 342.10 345.21 0.315 700 345.21 384.30 351.38 354.45 357.51 360.55 363.59 366.61 369.62 372.62 375.61 0.304 800 375.61 378.59 381.55 384.50 387.45 390.38 0.295 Basic values of the measuring resistors according to IEC 751 for Pt100. Fig. 11 Attention Please replace the measuring element if the temperature measured by the temperature sensor deviates from the plant temperature. The measuring element must also be replaced by a new one if a malfunction occurred and the rated service pressure and temperature limits were exceeded. Check installation and performance Checking switch-off function at T MAX Check the switch-off function at T MAX n during commissioing n once a year n whenever you exchange the temperature sensing element n whenever you exchange the temperature switch To test the switch-off function at T MAX exceed the adjusted temperature limit. The equipment must respond as if there were an alarm. Safety temp. monitor: Safety circuit open, signal output closed Safety temp. limiter: Safety circuit open and interlocked, signal output closed. 20

Further Notes Action against high frequency interference High frequency interference can occur for example as a result of out-of-phase switching operations. Should such interference occur and lead to sporadic failures, we recommend the following actions in order to suppress any interference. n Provide inductive loads with RC combinations according to manufacturer's specification to ensure interference suppression. n Make sure that all connecting cables leading to the conductivity electrode or to the conductivity transmitter are segregated and run separately from power cables. n Increase the distance to sources of interference. n Check the connection of the screen of the temperature sensor. n HF interference suppression by means of hinged-shell ferrite rings. Decommissioning / replacing the equipment n Switch off supply voltage and cut off power supply to the equipment! n Lower and upper terminal strips: Unscrew left and right fixing screws and remove the terminal strip. Fig. 12 n Release the white fixing slide at the bottom of the equipment and take the equipment off the supporting rail. Fig. 12 Disposal For the disposal of the equipment observe the pertinent legal regulations concerning waste disposal. If faults occur that are not listed above or cannot be corrected, please contact our service centre or authorized agency in your country. 21

For your Notes 22

For your Notes 23

GESTRA Agencies all over the world: www.gestra.com Great Britain Flowserve GB Limited Abex Road Newbury, Berkshire RG14 5EY Tel. 0044 16 35 / 46 99 90 Fax 0044 16 35 / 3 60 34 E-Mail gestraukinfo@flowserve.com Web www.flowserve.com Singapore Flowserve Pte. Ltd. 12 Tuas Avenue 20 Singapore 63882 Tel. 0065 / 68 79 89 00 Fax 0065 / 68 62 49 40 E-Mail fcd_gestra_singapore@flowserve.com Web www.gestra.com South Africa Flowserve SA (Pty) Ltd. Unit No. 1 Director Road Spartan Extension 2 Kempton Park 1613 Tel. 0027 11 / 9 23 73 00 Fax 0027 11 / 9 74 64 20 E-Mail tvniekerk@flowserve.com Web www.flowserve.com USA Flowserve GESTRA U.S. 2341 Ampere Drive Louisville, KY 40299 Tel. 001 502 / 267-22 05 Fax 001 502 / 266-53 97 E-Mail fcd-gestra-usa@flowserve.com GESTRA AG P. O Box 10 54 60, D-28054 Bremen Münchener Str. 77, D-28215 Bremen Tel. 0049 (0) 421 / 35 03-0 Fax 0049 (0) 421 / 35 03-393 E-mail gestra.ag@flowserve.com Web www.gestra.com 819226-03/03-2014cm (808885-03) GESTRA AG Bremen Printed in Germany 24