SPECIFICATION FOR GAPLESS METAL OXIDE DISTRIBUTION TYPE SURGE ARRESTERS WITH POLYMERIC HOUSING

Similar documents
Bowthorpe MV Surge Arresters OCP, Open Cage Polymeric series. Energy Division

Bowthorpe EMP surge arrester Distribution metal oxide surge arrester DA0 Series, (IEC)

Energy Division. Bowthorpe MV Surge Arresters OCP, Open Cage Polymeric series

IEC Type Test Report Report No. EU1120-HR Type PDV 100 Polymer Arrester 10,000 A Line Discharge Class 1

ENERGY PRODUCTS DIVISION. Polymeric Surge Arresters Reliable protection for power equipment upto 800kV

Energy Division. DAH series (IEEE) Distribution metal oxide surge arrester

IEC Type Test Report Report No. EU1515-H-00.3 Type PVI-LP Polymer Arrester 10,000 A Line Discharge Class 2

Bowthorpe EMP surge arrester Distribution metal oxide surge arrester DA1 Series, (IEC)

PolyGarde Metal-Oxide Surge Arresters

RAYCHEM MEDIUM VOLTAGE

38-SDMS-03 SPECIFICATIONS FOR LV DIGITAL PANEL METERS

SECTION AUTOMATIC TRANSFER SWITCHES

Test procedure/ method name. method identification. Testing of industrial and explosion isolation valves and tank lining

Eligibility Criteria for Participation [Qualification Requirement (QR)]

This is a preview - click here to buy the full publication. High-voltage switchgear and controlgear

Independent, accredited testing station Member laboratory of STL and LOVAG

CONTENTS AUTOMATIC TRANSFER SWITCHES

TENDER NO. PGVCL/PROC/SMC BOX FOR CT OPERATED METER & Junction Box/867

Table of Contents FOREWORD... 3 INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS REQUIREMENTS...

Rules for Intruder Alarm Systems

Insulation and Protection Enhancing the Reliability of Overhead Power Systems

Energy Division. Raychem Insulation Enhancement Systems

Rules for Classification and Construction Additional Rules and Guidelines

HMN-D2 Insert Series

SPECIFICATION NPS - 210/6 FOR SF6 INSULATED SWITCHGEAR FOR SYSTEM RATED VOLTAGE UP TO 24 kv

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Phone: Fax:

38-SDMS-01 SPECIFICATIONS FOR FAULT INDICATORS FOR UNDERGROUND DISTRIBUTION NETWORKS

Section 8: Switchgear Connections (Straight & Elbows)

This document is a preview generated by EVS

Technical Data. Dimensions

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

Technical Data. General specifications Switching element function Rated operating distance s n 5 mm

TECHNICAL SPECIFICATION FOR SMC AMR METER BOXES MADE FROM THERMOSETTING PLASTIC

INTERNATIONAL STANDARD

Fiji Electricity Authority Transmission Unit 2 Marlow Street, Suva

PAKISTAN STANDARD LED MODULES FOR GENERAL LIGHTING (SAFETY SPECIFICATIONS) PS: _5211/2017 ICS:

17 TH APRIL 2017 Switch Board Monitoring Protecting Switchboard. Courtesy of ABB. Paul Lee

Procedure for the Approval of New Fire Detection and Alarm Technologies

INTERNATIONAL STANDARD

Product Data Sheet 4114 N/17HH-218. The engineer's choice

Transportation. Distribution

HEAT SHRINK CABLE ACCESSORIES: A 40 YEARS PROVEN TECHNOLOGY FOR APPLICATIONS IN HARSH ENVIRONMENTS

TENDER DOCUMENT FOR SUPPLY OF EPOXY MIXING & POURING PLANT

SECTION AUTOMATIC TRANSFER SWITCHES

Remote alarm indicator and test combination MK2430

Technical Data. General specifications Switching element function Rated operating distance s n 8 mm

A three-pole dead-tank SF 6 circuit-breaker incorporating one interrupter per pole in single-pole enclosures with a common operating mechanism

SUGGESTED SPECIFICATION For Series 300 Manual Transfer Switches (3MTS)

Audible warning devices for external alarm

Lloyd s Register Type Approval System Test Specification Number 3

NPS/003/030 Technical Specification for Transformer and Switchgear Cable Boxes and their associated Bushing Assemblies

Cat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE

FALCON SERIES 12 METAL CLAD

PRODUCT SPECIFICATION. 0.5mm Fine Stacking. Hermaphroditic Type BTB Connector

Motor Controller AC Semiconductor Motor Controller Type RSBS23..A2V.2C24

SAMPLE SPECIFICATIONS CONTINUOUS MONITORING SYSTEM (Insitu)

Raychem heat-shrinkable medium voltage terminations IXSU-F/OXSU-F for indoor and out door applications for polymeric cables up to 42 kv

Time Extension: Tender submission deadline is extended up to 12:00 Hrs. of

Type approval qualification of Photovoltaic Modules Procedures and test experiences

INTERNATIONAL STANDARD

Raychem Elastomeric Medium Voltage Push-on and Cold-shrink Applicable Terminations TFTI/TFTO

Universal fault annunciator for panel mounting

C-Bus Four Channel General Input Unit Installation Instructions

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System

AS/NZS :2003 Luminaires - Part 1: General requirements and tests

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005

Energy Trasmission & Distribution Services - Italy. Retrofit solutions for plant modernization. Answers for energy.

Reliable solutions for electrified railway systems

MSM - Expansion modules

Soft Starter Centrifugal Pump Soft Starter Series

Technical Data. Dimensions

Survey of electrical equipment installed in hazardous areas on tankers

Motor Controller AC Semiconductor Motor Controller Type RSBS23..A2V.2C24..

INDUSTRY /// RAIL T-CONNECTOR RSTI-68R-HT RSTI-CC-68R-HT RAIL APPROVED T-CONNECTORS FOR ROLLING STOCK- TYPE C INTERFACE

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

Operation and use. Functions and characteristics

Translation Supplementary requirements for the testing and certification of Safety relays

FALCON SERIES 12 METAL CLAD

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts

C-Bus Four Channel Analogue Output Unit Installation Instructions

Soft Starter AC Semiconductor Motor Controller Type RSBS23..A2V.2C24..

FT702LT Turbine control wind sensor gives durability a new meaning FT702LT. series

CERTIFICATION BULLETIN

Energy Division. CSJT MV cold shrinkable joint for 3-core cables with resin encapsulation

Inductive slot sensor

RD:30 Specification No. TI/SPC/PSI/AUTOTR/0090 For 50U5/150 MVA, 220/132 kv Auto Transformer

Technical Data. General specifications Switching element function Rated operating distance s n 5 mm

EU RO Mutual Recognition Technical Requirements

Cable Ties JULY The electronic pdf version of this document found through is the officially binding version

Mains Power Filter 970MF10 970MF20. Installation Instructions

SOUTH AFRICAN NATIONAL STANDARD

PART GENERAL 1.01 SECTION INCLUDES

INTERNATIONAL STANDARD

Thermostat Catalog 2004

3kW 6kW, QUBE Fiber Lasers

SENTINEL D - Fault Passage Monitoring

Withdrawable module with vacuum circuit-breaker 3AE and installation accessories kv, ka kv, 40 ka 24 kv, ka

TECHNICAL SPECIFICATION AUTOMATIC SINGLE POLE AND THREE POLE CIRCUIT BREAKERS FOR LV SUPPLIES

Industrial Solid State Contactor TE10S. Static switching of resistive loads and shortwave infrared heating tubes up to 20 kw

INTERNATIONAL STANDARD NORME INTERNATIONALE

Transcription:

SPECIFICATION FOR GAPLESS METAL OXIDE DISTRIBUTION TYPE SURGE ARRESTERS WITH POLYMERIC HOUSING Page 1 of 10

CONTENTS 1 SCOPE 2 DEFINITIONS 2.1 SURGE ARRESTER 2.2 GAPLESS METAL-OXIDE SURGE ARRESTERS 2.3 POLYMERIC HOUSED SURGE ARRESTER 2.4 SHORT CIRCUIT TEST / MODE OF FAILURE PERFORMANCE 2.5 BONDING BETWEEN HOUSING AND METAL-OXIDE RESISTORS / INTERFACIAL SEALING 3 SYSTEM PARAMETERS 4 PRODUCT REQUIREMENTS 4.1 POLYMERIC HOUSING MATERIAL 4.2 HOUSING AND MECHANICAL REQUIREMENTS 4.3 ELECTRICAL REQUIREMENTS 4.4 ACCESSORIES 4.4.1 MOUNTING 4.4.2 TERMINALS 4.4.3 DISCONNECTORS 4.5 CORROSION PROTECTION 4.6 TENDER SAMPLE 5 TESTING 5.1 LOCATION OF TESTS 5.2 TYPE TESTS FOR ARRESTERS WITH POLYMERIC HOUSING 5.3 ROUTINE TESTS 5.4 ACCEPTANCE TESTS 6 MARKING 7 DRAWINGS 8 QUALITY ASSURANCE 9 PACKING AND SHIPMENT SCHEDULE I: TECHNICAL GUARANTEED PARTICULARS Page 2 of 10

1 SCOPE This specification covers the design, manufacture, testing, supply and performance requirements for gapless metal oxide, polymeric housed distribution type surge arresters for outdoor use. 2 DEFINITIONS 2.1 SURGE ARRESTER A device designed to protect electrical apparatus from high transient over voltages. 2.2 GAPLESS METAL-OXIDE SURGE ARRESTER A surge arrester having one or several non-linear metal-oxide resistors with highly non-linear voltage-current characteristics, connected in series, but having no integrated series or parallel spark gaps. 2.3 POLYMERIC HOUSED SURGE ARRESTER A surge arrester with a housing made of polymeric material without air voids neither between the housing and the metal-oxide resistors nor the housing itself. Arresters must have directly moulded housings. Arresters manufactured by slip-on, pre moulded housing will not be accepted in view of the weak interface between the housing and the assembled disc. 2.4 SHORT CIRCUIT TEST / MODE OF FAILURE PERFORMANCE Behaviour of the arrester during and after a simulated internal failure with different power frequency short circuit currents. 2.5 BONDING BETWEEN HOUSING AND METAL-OXIDE RESISTORS/ INTERFACIAL SEALING The adhesion between the polymeric housing and the metal-oxide resistors or any other metalic or non-metalic parts inside the housing must be strong enough, homogeneous, rubust and resistant to thermal cycles and environmental stresses. Page 3 of 10

3 SYSTEM PARAMETERS The arrester must be able to operate under the system parameters mentioned in this specification. Nominal System Voltage Frequency Grounding of Neutral Temporary Overvoltage (Earth Fault Factor ) Highest System Voltage Short Circuit Levels Insulation Withstand Level (BIL) 11 KV 50 Hz Solidly) 10.4 KV for 10 sec. 12 KV 20 KA 75 KV 4 PRODUCT REQUIREMENTS 4.1 POLYMERIC HOUSING MATERIAL The polymer material which is used for the arrester housing must be tracking and erosion resistant, stabilized against UV radiation and have proven records of at least 15 years in similar applications (like MV/HV cable terminations, insulators and arresters) in country. 4.2 HOUSING AND MECHANICAL REQUIREMENTS The arrester shall meet the following specifications: Creepage Length Pull Strength Cantilever Load Torsion 300 mm (min.) 1000 N (min) 75 Nm (min) 30 Nm (min) 4.3 ELECTRICAL REQUIREMENTS The arrester shall meet the following specifications based on IEC 60099-4: Arrester Max. Cont. Operating Voltage Uc 8 KV rms Arrester Rated Voltage Ur 10 KV rms Nominal Discharge Current In 5 ka p Long Duration Discharge Class 75A, 1000µs Max. Residual Voltage @ In 26.1 kvp Lightning Impulse 1,2/50µs Withstand 75 KVp Voltage Wet Power Frequency Withstand Voltage 28 KV rms Page 4 of 10

4.4 ACCESSORIES The mounting accessories shall be designed to match all mechanical and electrical requirements specified for the arrester. 4.4.1 Mounting Arresters shall be suitable for vertical and horizontal mounting. 4.4.2 Terminals Terminals shall be made of M10 bolts to allow the connection of line and ground leads. 4.4.3 Disconnectors The earth end shall get connected to the earth terminal of the arrester through disconnector. The function of the disconnector is that in the event of, operation of surge arrester, the current shall pass to earth and the disconnector shall disconnect (isolate) the earth terminal and it shall remain suspended on the mounting of the arrester. There by it will be disconnected from the earth and shall provide visual indication to the patrolling personnel. The line can be recharged without isolating the damaged arrester. The Suggestive arrangements of disconnector is given in the drawing attached here with 4.5 CORROSION PROTECTION The arrester and all its accessories shall be adequately protected against corrosion. All exposed ferrous components, unless of stainless steel or other non-corrosive metal, shall be hot-dip galvanized. Hardware shall be of stainless steel. 4.6 TENDER SAMPLE ONE tender sample of offered Polymeric surge arrester with disconnector will have to be submitted along with the offer. 5 TESTING The arresters shall be tested in accordance with the following latest standards - IEC 60099-4/ 2004-05 Standard Page 5 of 10

5.1 LOCATION OF TESTS Routine tests and acceptance tests shall be carried out at the supplier s factory. Type tests shall be carried out in the laboratories of an NABL accredited independent test institute/ Govt. approved lab. Relevant type test certificates are mandatory and shall be issued by the NABL accredited independent institute/govt. approved lab. 5.2 TYPE TEST FOR ARRESTERS WITH POLYMERIC HOUSING All the tenderers must submit copies of type test certificates alongwith laboratory approved drawings for the products offered by them. Type tests should be carried out in accordance with the latest version of specified standard at Govt. approved / NABL accredited lab and test reports should not be older than 5 years as on date of opening the tender. Surge arresters offered shall be manufactured with the same configuration & raw materials as used in the surge arrester for which type test reports are submitted. a. Insulation Withstand Test on Arrester Housing b. Residual Voltage Tests c. Long Duration Current Impulse Withstand Test d. Operating Duty Test e. Partial Discharge Voltage Test f. Accelerated ageing test g. Power frequency voltage versus time characteristics h. Weather Ageing Test The arrester shall prove its resistance against pollution by passing following type test: - l000hrs salt fog test at maximum continuous operating voltage Uc applied. i. Short Circuit Test/Mode of Failure Test The arrester shall prove its withstand capability with respect to internal failures by passing the following type tests: Short Circuit Test in accordance with IEC 60099-4/2004-05 Standard. The recommended procedure shall be used for testing. The minimum symmetric fault current shall be 20KA rms for a minimum of 0.2s for high current short circuit test. The fault current shall be initiated preferably by prefailing the arrester within 5 ± 3 minutes with a power frequent AC voltage. For low current short circuit test, the test shall be performed Page 6 of 10

5.3 ROUTINE TESTS only by over voltage method. During the test no parts must be ejected and the arrester has to maintain its integrity. All flames must self extinguish within one minute after the test The manufacturer shall carry out the following routine tests on each single arrester in accordance with IEC 60099-4/ 2004-05 Standard. - AC Reference Voltage Test (final arrester) - Partial Discharge Test (final arrester including hardwares/accessories) - Residual Voltage Test (final arrester or metal-oxide resistors) The manufacturer shall provide a routine test report including all relevant details with respect to the test limits. On request, the manufacturer shall also provide a routine test protocol including all measuring results. Sample test are not acceptable. 5.4 ACCEPTANCE TESTS The acceptance tests shall be carried out as per IEC: 60099-4/ 2004-05 standard. 1. Power frequency reference voltage test 2. Lightning impulse residual voltage test 3. Internal partial discharge test 4. Visual examination & Dimensional verification 6. MARKING Each arrester shall be provided with a nameplate, bearing the following information, as a minimum, in English language: - Arrester Type - IEC standard - Continuous Operating Voltage Uc - Rate Voltage Ur - Nominal Discharge Current - Rated Short Circuit Current - Manufacturers name or trademark - Month & Year of manufacture - Date of supply with period of guarantee - PROPERTY OF MGVCL Page 7 of 10

7. DRAWINGS The tenderer shall furnish catalogues, literature and detailed dimensional drawings of complete arrester with disconnector showing clearances, polymeric housing details & name plate details. 8. QUALITY ASSURANCE The manufacturer shall be certified in accordance with ISO 9001. The supplier has to provide a copy of a valid certificate along with his quote. Relevant manuals shall be presented upon request. 9. PACKING AND SHIPMENT Arresters shall be securely packed, complete with all accessories, in strong non-returnable boxes, in such a manner as to prevent damage during shipment. Page 8 of 10

SCHEDULE 1 : GUARANTEED TECHNICAL PARTICULARS REQUIREMENTS FOR GAPLESS METAL OXIDE DISTRIBUTION TYPE ARRESTERS WITH POLYMERIC HOUSING Table to be filled in by the manufacturer / Definitions according to IEC 60099-4 Sr.No. Description 1. Name of Manufacturer Offered by Bidder 2. Arrester Type or Designation 3. Arrester Continuous Operating Voltage Uc KV rms 4. Arrester Rated Voltage Ur KV rms 5. Nominal Discharge Current In KA 6. Line Discharge Class 7. High Current Discharge Current 4/10µs KA 8. Long Duration Current Amplitude A 9. Long Duration Current Duration µs 10. Rated Short Circuit Current Isc a. High current KA b. Low current A 11. Pull Strength N 12. Cantilever Strength Nm 13. Torque strength Nm 14. Total Height of Arrester mm 15. Creepage Length mm 16. Flashover Distance mm 17. Lightning Impulse 1,2/50µs Withstand Level KVp 18. Wet Power Frequency Withstand level KV rms Page 9 of 10

19. Housing Type 20. Housing Material 21. Colour of Housing 22. Void-free Design (State) Yes / No 23. Bonding/Interfacial Sealing (state) Yes / No 24. Reference Current ma 25. Reference Voltage Range (min/max) KV 26. Max. Partial Discharge Level pc 27. TOV Curve enclosed? Yes/No 28. Arrester will be able to operate under the system parameters mentioned in cl.no.3? Maximum Residual Voltage of Arrester for: Yes/No 29. 30. 31. 32. Lightning Current Impulse 8/20 µs at 2.5kA 5 ka 10 ka Steep Lightning Current Impulse 1/10 µs at Nominal Discharge Current In Minimum recommended Center-to-Center Distance between Arresters Minimum recommended Distance from Center of Arrester to nearest Grounded Object Whether earth disconnector, as mentioned in the specification, is provided KV KV KV KV mm mm Yes/No Page 10 of 10