MB Therma-Fuser Standalone Motorized Disc VAV Diffuser

Similar documents
MBS Therma-Fuser Standalone Motorized Swirl VAV Diffuser

Therma-Fuser Square Thermally Powered VAV Diffuser

THERMA FUSER SIDEWALL LINEAR VAV DIFFUSER

TLW Therma-Fuser Linear Sidewall Thermally Powered VAV Diffuser

Grilles & Diffusers - Metal

INSTALLATION, BALANCING & MAINTENANCE

INSTALLATION & OPERATIONS MANUAL

INSTALLATION, BALANCING & MAINTENANCE

DESIGNING MODULAR VAV SYSTEMS

CONTROL THE PERIMETER EFFECTIVELY HORIZONTAL/VERTICAL FLOW PATTERN ONBOARD/REMOTE SENSING EXCELLENT THROW & FLOW HEATING AND COOLING CHANGEOVER

Engineering Guide VAV Diffusers. Please refer to the Price Engineer s HVAC Handbook for more information on VAV Diffusers.

ARE BETTER THAN VAV BOXES Lowest energy VAV terminal Easily adapts to office layout change Lowest cost per zone of control

45 Commerce Ave., Unit #2 South Burlington, VT tel: fax:

CLN 3 ATTRACTIVE JOINABLE LINEAR PROFILE UP TO 8 SLOT TRACKS AVAILABLE HEATING AND COOLING TERMINAL REHEAT AVAILABLE

80-6-ISD A Better Solution for Proper Space Air Distribution

Linear Floor Heaters

SEQUENCE OF OPERATIONS

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

photo by PFC Price Fan Column

Industrial Space Heating Direct Gas-Fired Heating. Greenheat 50/50 Recirculation

VCD,VRD,VSD 4/5 GREEN TEMPERATURE OFFSET FOR WINTER HEATING AND COOLING CHANGEOVER MECHANICAL THERMAL MECHANISM

FAN TERMINAL UNITS Constant Volume (Series Flow), Standard Design

Ceiling diffusers. Type DLQL

SINGLE DUCT TERMINAL UNITS

Performance Aire offers three VAV comfort solution packages.

Thermostat Remote Control & Receiver

Product Data. Features/Benefits. 33CS Carrier Comfort System Variable Volume and Temperature (VVT )

Modular Active. Chilled. Beams

EASY VOLUME ADJUSTMENT INCLUDED FLEX CLAMP EXCELLENT THROW & FLOW HEATING AND COOLING TERMINAL REHEAT AVAILABLE

IN020 Rev F Page 1 of 8

EASY VOLUME ADJUSTMENT INCLUDED FLEX CLAMP EXCELLENT THROW & FLOW HEATING AND COOLING TERMINAL REHEAT AVAILABLE

VAV DIFFUSERS PREVENT DUMPING VAV DIFFUSERS SAVE FAN ENERGY ENERGY SAVING - LOW PRESSURE LOSS REHEAT, OCCUPANCY, FLOW MEASUREMENT

Ceiling swirl diffusers

Panel Mounted Heat Exchangers by Dantherm, Inc.

Ceiling swirl diffusers

FIRE RATED PRODUCTS GENERAL PRODUCT OVERVIEW. Fire Rated Products

Units for suspended ceilings Type DID632

Healthy Climate Whole-Home Dehumidifier. Nominal Capacity - 70 to 130 pints per day INDOOR AIR QUALITY HCWHD PRODUCT SPECIFICATIONS.

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1

installation instructions Fan Tray System FTA-3/FTA-6

Model NT20e Installation Guide

Electric Duct Heaters

Comfort Ceiling Fan Coil System INDULVENT ec. Draught-free ambient air distribution with cooling capacity up to 2600 W

Duct Heater Product Catalog

Installation/Operation Instructions COMP-COOL50/COMP-COOL50P 50 CFM COMPONENT COOLERS

ASHRAE JOURNAL ON REHEAT

FCC Fan-Coil Units High-Performance, Vertical

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

M Series Fan Filter Units

Installation and Operations Manual

I/O ZONE 560/583 USERS GUIDE

TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application Application Note Building Technologies

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

Units for suspended ceilings

TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note

T7984 A,B,C Electronic Modulating Control Thermostats

TEC210x-2 Series Networked Thermostats

EHH SERIES DRAW THROUGH FAN COILS CFM

KLIMA Active Chilled Beams

Product Data. Features/Benefits. AirManager Control. 33AM Comfort System

Polaris-I-60. active chilled beam. the future of space conditioning

Electric Coils. Blower Coils. Product Information

6502B RF Distribution

EVD-1 Installation, Operation, and Instruction Manual

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

Please Read And Save These Instructions.

IDL20e (2 way discharge) IDS60e (4 way discharge) Inffusers. UDI (vertical discharge) Frequently Asked Questions

Improved Thermal Comfort & Energy Efficiency with low-pressure VAV diffusion design

Modular Heating & Ventilating Unit Model IGX-HV

TEC2100 Series Networked Thermostats

SECTION AIR DUCT ACCESSORIES

Operation & Maintenance Manual

LYRA » ENERGY EFFICIENT CASSETTE CHILLED BEAM AIR DIFFUSION LYRA

Technical Selection. elevent ceiling diffusers. Swirl, Jet, Louvred and Curved ceiling diffusers

Alnor AirGard 410HE Air Flow Monitor for Hazardous Environment Fume Hoods

SmartZone TM System Manual

Active Chilled Beams

BARD MANUFACTURING COMPANY, INC. WG3S-WG5S 2-Stage Cooling with Gas Heat Engineering Specification Guide

DUST FREE CARBON Whole House Air Purifier

Carbon Monoxide (CO) Detecting Ventilation Fan Controller Model 120VC Single Relay (100/25 PPM) (200/35 PPM)

AirTrak. Digital Control System. User Manual. Touchscreen Systems

Bypass Terminal Units. DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.) BYPASS TERMINAL UNITS

FAN POWERED VAV TERMINALS

BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657

Performance Rating of Active Chilled Beams

Proliphix Thermostat Installation Guide. Release 2.0

Operating Instructions READ AND SAVE THESE INSTRUCTIONS

ZonexCommander. ZonexCommander(Plus) Installation and Applications Manual. Network All Your HVAC Equipment

Advanced Air. Hard Wired Damper Control Panels. Systems 10, 11, & 12. Hard-Wired Systems. Bespoke Systems Available. Value Engineered Solutions

Model CV-1FR Riser Check Valves 2 to 12 Inch (DN50 to DN300) General Description. Installation. Technical Data. Page 1 of 6 OCTOBER 2010 TFP950

Homepage > Products > Grilles and Diffusers > Ceiling diffusers > Design ceiling swirl diffusers > Type ADD. Type ADD

DIGI3U. Zoning Systems. Installation Guide. That s all we do. Three-Zone, Universal Controller for Gas/Electric or Heat Pump Applications

SEC Signature Process Gas Analyzer

SF180 Installation Instructions

RP, GP, XP Pro Series Installation Instructions

AdaptAire. Digital Control System. User Manual

HS Series Installation & Operating Instructions RadonAway

Predator Controller Hardware Family

AFA 500 FUME HOOD ALARMS

Transcription:

MB Therma-Fuser Standalone Motorized Disc VAV Diffuser Models: MB-M MB-S MB-D Master with sensor and controller Slave with controller to follow master Drone with controller for 3rd party control Therma-Fuser Systems MB: Product Overview FORM 122.101 REV 1407 BENEFITS AT A GLANCE. INDIVIDUAL COMFORT OVER A WIDE RANGE OF CONTROL Every Therma-Fuser diffuser is a VAV zone of temperature control providing pleasing comfort in both heating and cooling. A wide range of control with comfort set points adjustable from 55-95 F/13-35 C. The electric motor delivers a consistent response for control of room temperature, and when required, a quick response to commands. The Wall Adjuster provides easy access for unit configuration and for the occupant to adjust comfort set points Patent Pending US and other countries Copyright Acutherm 2014 ROBUST DESIGN WITH LONG LIFE MOTOR The need for any maintenance or repair is minimized through the robust design and a brushless DC stepper motor specifically selected for a long life. The electric motor directly drives a threaded shaft connected with a linkage to the dampers eliminating the need for a failure prone gear box. The control algorithm reduces the motor run time to a minimum reducing energy use and extending the motor life. And, should maintenance be required, the unique design allows for easy access to the motor from the room without removal of the diffuser from the ceiling. ONLY THERMA-FUSER VAV OFFERS THESE BENEFITS Quiet no motor noise Separate temperature set points for VAV heating and VAV cooling. Superior air distribution - more entrainment, even temperature distribution, higher ADPI* and better room air change effectiveness. Lowest energy VAV terminalgreen VAV. Low to no maintenance - 2 year warranty. Easily adapts to office changes. *ADPI (Air Diffusion Performance Index)

VAV Damper Primary Air Supply Air Sensor Controller BUILDING AUTOMATION INTERFACE The MB-M has a 0-10VDC analog input for set point adjustment by a building automation system. The damper can also be forced open or closed through this interface. HOW IT WORKS Model MB Therma-Fuser diffusers are nominal 24 /600mm square ceiling diffusers with built in DDC controller, and VAV damper. A round disc damper opens and closes to meter air flow (hot or cold) into the room in response to room temperature. The damper is modulated by a brushless DC stepper motor. The electric motor, rigorously tested to provide many years of reliable service, directly drives a threaded shaft connected with a linkage to the disc damper. The controller uses an expert system control similar to having an expert sitting there making the adjustments. Unlike PID control, expert system control does not require field tuning. Every 10 seconds it determines if the damper should be adjusted and the amount of any adjustment based on temperature relationships and the rate of change of damper position. MASTER DIFFUSER MB-M master diffusers contain a duct temperature sensor and DDC controller for standalone operation with the Wall Adjuster. ROOM AIR SENSING To monitor average room temperature, a sensor in the Wall Adjuster (Fig. 2) is used similar to a traditional thermostat. The Secondary Air Motor fig.1 Wall Adjuster should not be located on an outside wall or where it could be exposed to direct sunlight at any time during the day. It should be located away from the diffuser, yet exposed to general airflow from the space. A properly applied MB-M will hold the room average within 1.5 F/0.9 C of the temperature selected. COOLING AND HEATING MODES In the cooling mode, the MB-M damper opens on a rise in room temperature. In the heating mode the operation is reversed with the MB-M damper blades closing on a rise in room temperature. Determination of cooling/heating mode is made automatically by comparing supply air temperature to room temperature and set point. The MB-M is in the heating mode if the supply air temperature is warmer than both the room temperature and set point. The MB-M is in the cooling mode if the supply air temperature is cooler than either the room temperature or set point. ADJUSTING SET POINTS The room temperature set point is easily adjusted by pressing the up and down arrows on the Wall Adjuster (see Fig. 2). Adjustment is limited to that set using the set point offset (see Configuration). CONFIGURATION The MB-M diffuser comes factory configured and ready to operate once power is connected. If required, there are six parameters that can be accessed through the menu button on the bottom of the Wall Adjuster: 1. Temperature correction (sensor calibration) 2. Minimum damper position % 3. Maximum damper position % 4. Heating set point 5. Cooling set point 6. Set point offset (limits the range of set point adjustment) In addition, there are dip switches on the back of Wall Adjuster to adjust the display of the Adjuster between warmer/ cooler, numeric and F/ C. OPEN FOR BALANCING When both the up and down arrow buttons on the Wall Adjuster are pressed for a couple seconds the MB-M enters a balancing mode and opens to 100% damper position. When either arrow button is pressed the balancing mode is released and the MB-M will close and then re-open to control the temperature of the room. fig.2 DIMENSIONS NECK SECTION Inlet Designation 6" 8" 10" 12" Inches ± 1/16 5 15 / 16 7 15 /16 9 15 /16 11 15 /16 OD mm ± 3 150 200 250 300 *595±2mm Square with 16±2mm lip available specify 595mm square. 2

SLAVE DIFFUSER MB-S slave diffusers contain only the DDC controller allowing the diffuser to mimic the master diffuser, opening and closing with the MB-M DRONE DIFFUSER MB-D drone diffusers contain only the DDC controller and use an analog 0-10VDC input to position the damper with a direct 0-100% relationship. With this input, controls by others may be used to control the MB-D diffuser. SUPPLY POWER Each MB diffuser requires 24VAC +3/-1 power supplied. Max power draw is 15VA when the motor is running, but when the motor is idle, the power draw drops to <1VA. Power 24VAC +3 / -1 15VA Max Wall Adjuster Controller fig.3 SYSTEM DESIGN The best control for heating/cooling units supplying air to VAV terminals is a discharge thermostat which maintains a constant supply air temperature. With DX equipment these are a high and low limit. Use a room thermostat for changeover between heating and cooling modes. For hybrid systems (part VAV and part constant volume) control the heating/cooling supply unit with a thermostat in one of the rooms with a constant volume diffuser, preferably the space with the greatest load. For both VAV and hybrid systems, the fan should run continuously. The constant discharge velocity of Therma-Fuser diffusers at varying air flow provides good room circulation which reduces stratification. Keeping heating supply air temperatures as low as possible will further reduce room air stratification to a negligible level. Static pressure at the inlet of the Therma-Fuser diffuser should be between 0.05"wg/12Pa and 0.25"wg/62Pa, at full and partial air flows. Static pressure below 0.05"wg/12Pa will result in low air flow and less induction. Above 0.25"wg/62Pa, Therma-Fuser diffusers operate well but excessive noise may result. Use minimum flow settings where tight shut off is not needed. Size Therma-Fuser VAV diffusers for low static pressure drops - between 0.05 wg/12pa and 0.25 wg/62pa maximum to limit noise. Size the diffusers as large as possible, especially at the end of the duct run, for the lowest possible pressure drop at design air flow. Size the ducts for a maximum pressure drop of the difference between the pressure drops over the first and the last diffusers. If the system turns down more than 30%, static pressure should be controlled. Included in the options for static pressure control are fan speed control and modulating bypass dampers. Modulating zone dampers are recommended where several zones share a higher pressure duct or riser. Manual balancing dampers should be used at the takeoff for each diffuser. Manual balancing dampers may not be required with ducts designed to Acutherm specifications. Acutherm has how to system design brochures for almost every ducted air system. For specific recommendations refer to the brochure for your system. GUIDE SPECIFICATION (Suitable for Section 23 36 16 Variable-Air-Volume Units of the CSI Master Format). 2.2 Standalone motorized VAV diffusers A. Standalone motorized variable air volume diffusers shall be Therma- Fuser model MB manufactured by Acutherm, Hayward CA. B. Standalone motorized VAV diffusers shall be a complete VAV terminal with supply air sensor, "expert system" controller, motor and disc damper contained in a nominal 24in/600mm square diffuser. C. They shall be actuated by a brushless DC stepper motor with a direct linkage to the damper shipped in the open position for balancing should the diffuser not yet be connected to power. D. All VAV diffusers shall provide easy access to the motor from the room without removal of the diffuser should maintenance be required. E. The expert controller shall have the ability to change control response as the space changes. P, PI, PD and PID control shall not be acceptable. F. The housing shall have an offset ridge on each of the four edges to provide better air flow in lay-in installations. G. The manufacturer shall warrant that all VAV diffusers shall be free from defects in materials and workmanship for a period of two years from date of shipment. H. All VAV diffusers shall have a solid (no holes or slots), hinged appearance panel that can be unlatched and folded down to hang allowing hands to be free for adjusting temperature set points. Instructions for the VAV diffuser shall be on the inside of the appearance panel. I. Supply air to the VAV diffuser shall be constant temperature (may be reset to another constant temperature). Supply air shall be limited to no lower than 50 F/10 C on cooling and as low as possible not to exceed 120 F/49 C on heating. For the guide specification in a word format and for specifications for the MB-S Slave and MB-D Drone types, please visit www.acutherm.com, click on: ÜDocuments Ü2x2 ÜMB ÜSpecifications. 3

PERFORMANCE GUIDE in I-P UNITS Nomimal Inlet Diameter in Inlet Static Pressure in wg Maximum Flow cfm Maximum Flow Throw* - Feet @ v t =50/100 NC 25% Maximum Flow Throw* - Feet @ v t =50/100 6.05 100 3/2 <15 2/<1 <15.10 140 4/3 17 2/2 <15.11 147 4/3 18 2/2 <15.15 175 5/4 24 3/2 <15.20 210 6/5 27 4/3 <15.25 230 7/6 30 4/3 20 8.05 160 5/3 <15 3/2 <15.10 225 7/5 18 3/2 <15.12 245 7/5 21 3/2 <15.15 275 8/6 25 4/3 <15.20 320 9/7 30 4/3 19.25 350 9/7 34 5/3 24 10.05 260 6/4 <15 3/2 <15.10 370 8/5 25 5/3 <15.12 402 8/6 27 5/3 <15.15 450 9/7 31 5/4 <15.20 520 10/8 35 6/4 21.25 580 11/9 39 6/5 25 12.05 340 8/6 <15 6/3 <15.10 500 10/8 24 6/4 <15.14 580 11/9 29 7/5 18.15 600 11/9 30 7/5 19.20 690 12/10 36 7/5 25.25 780 13/11 39 8/6 29 NC Denotes 750 fpm / 3.81 m/s inlet velocity. * Throw data is for air 20 F/11 C lower than room temperature. Throws for isothermal air are 40 to 50% greater. NC based on L w (10-12 watts reference) -10db Tested in accordance with ANSI/ASHRAE 70, ANSI S12.31, ARI 890, ISO 5219 and ISO 3741. Ratings independently verified by Inchcape Testing Services, ETL Testing Laboratories. 4

PERFORMANCE GUIDE in SI (METRIC) UNITS Inlet Designation Nominal Inlet Dia. mm Inlet Static Pressure Pa Maximum Flow Maximum Flow Throw (m)*@v t = 25% Maximum Flow Throw (m)*@v t = L/s m 3 /h.25 m/s.50 m/s NC.25 m/s.50 m/s NC 6 150 10 43 157 0.9 0.6 <15 0.6 < 0.3 <15 20 59 211 1.1 0.8 16 0.6 0.5 <15 30 73 262 1.3 1.0 20 0.7 0.6 <15 40 86 310 1.6 1.3 25 1.0 0.7 <15 50 99 358 1.8 1.5 27 1.2 0.9 <15 60 107 385 2.1 1.8 29 1.2 0.9 19 8 200 10 69 250 1.4 0.8 <15 0.9 0.6 <15 20 94 339 1.9 1.3 17 0.9 0.6 <15 30 116 417 2.3 1.7 21 1.0 0.7 <15 40 134 484 2.5 1.9 26 1.2 0.9 16 50 151 545 2.8 2.2 30 1.2 0.9 19 60 163 586 2.8 2.2 33 1.5 0.9 23 10 250 10 112 405 1.6 1.2 <15 0.8 0.6 <15 20 154 556 2.2 1.4 21 1.3 0.8 <15 30 190 685 2.6 1.8 27 1.5 1.1 <15 40 219 791 2.8 2.2 32 1.6 1.2 16 50 246 886 3.1 2.5 35 1.8 1.2 21 60 269 968 3.3 2.7 38 1.8 1.5 24 12 300 10 146 525 2.3 1.7 <15 1.8 0.9 <15 20 206 743 2.8 2.2 20 1.8 1.1 <15 30 255 920 3.2 2.6 26 2.0 1.4 17 40 292 1053 3.4 2.8 31 2.1 1.5 20 50 326 1176 3.7 3.1 36 2.1 1.5 25 60 360 1299 3.9 3.3 38 2.4 1.8 28 ( All SI / Metric ratings are soft conversion from I-P ratings ) Denotes 750 fpm / 3.81 m/s inlet velocity. * Throw data is for air 20 F/11 C lower than room temperature. Throws for isothermal air are 40 to 50% greater. NC based on L w (10-12 watts reference) -10db Tested in accordance with ANSI/ASHRAE 70, ANSI S12.31, ARI 890, ISO 5219 and ISO 3741. Ratings independently verified by Inchcape Testing Services, ETL Testing Laboratories. 5

2014 Acutherm FORM 122.101 REV 1407 MB Therma-Fuser Standalone Motorized Disc Diffuser TWO YEAR WARRANTY Acutherm warrants that its Model MB diffuser, exclusive of any options and accessories (whether factory or field installed) shall be free from defective material or workmanship for a period of two (2) years from the date of shipment and agrees to repair or replace, at its option, any parts that fail during said two (2) year period due to any such defects which would not have occurred had reasonable care and proper usage and all parts and controls remain unaltered. Acutherm makes NO WARRANTY OF MERCHANTABILITY OF PRODUCTS OR OF THEIR FITNESS FOR ANY PURPOSE OR ANY OTHER EXPRESS OR IMPLIED WARRANTY WHICH EXTENDS BEYOND THE LIMITED WARRANTY ABOVE. ACUTHERM S LIABILITY FOR ANY AND ALL LOSSES AND DAMAGES RESULTING FROM DEFECTS SHALL IN NO EVENT EXCEED THE COST OF REPAIR OR REPLACEMENT OF PARTS FOUND DEFECTIVE UPON EXAMINATION BY ACUTHERM. IN NO EVENT SHALL ACUTHERM BE LIABLE FOR INCIDENTAL, INDIRECT OR CONSEQUENTIONAL DAMAGES OR DAMAGES FOR INJURY TO PERSONS OR PROPERTY. Acutherm shall not be responsible for freight to or from its plant in connection with the inspection, repair or replacement of parts under the terms of this limited warranty nor for cost of removal or installation. ACUTHERM PRODUCT GUIDE Square VAV Diffusers Round VAV Diffusers Linear VAV Diffusers Accessories Pressure Control Temperature control Square VAV Diffusers Round VAV Diffusers Linear VAV Diffusers Accessories Pressure Control Temperature control PRODUCT INFORMATION DESCRIPTION Use the following model number nomenclature to order Therma-Fuser diffusers, options and accessories. Product (1) Model MB (2) Type (3) Size Product 1. Model: MB Motorized Disc Therma-Fuser diffuser 2. Type: M master, S slave, and D drone 3. Size: nominal 6, 8, 10, or 12 inch inlet Options (1) Remote Adjust ADJ-M (2) Insulation (3) Security Hanger (4) Sheared Housing Options 1. Remote Adjust: ADJ-M Motorized Wall Adjuster 2. Insulation: I for attic/plenum side insulation 3. Security Hanger: H two hangers on opposite corners 4. Sheared Housing: 595 for 600mm metric grid ceilings, T1 for 23 3 /16 and T2 for 22 3 /4 Accessories (1) Ceiling Frame Accessories 1. Ceiling Frame: TFHD for hard ceiling, TF4DB for 4 drop box, TF1DB for 17 /16 drop box, TFSP for spline, TFT1 for tegular 9 /16 T-bar, TFT2 for tegular 1 T-bar, and TFAL for air lifter (no ceiling) diffuser AVAILABLE ONLINE Access digital brochures, CAD files, performance data and more! www.acutherm.com CALL US Talk to our customization and specification experts +1 800 544 1840 EMAIL SUPPORT Send us your questions and we ll get you the answers you need. info@acutherm.com ACUTHERM HEADQUARTERS 1766 Sabre Street Hayward CA 94545, USA Tel: +1 510 785 0510 Fax: +1 510 785 2517