Information Bulletin

Similar documents
Information Bulletin

Alarm Signalling Equipment: Connection Requirements (Victoria) TAN 06. Technical Advisory Note. Version 1 October 2018

Good Practice Guide GPG

South Australian Regulatory Requirements

Australian/New Zealand Standard

Australian Standard. Fire protection for mobile and transportable equipment AS AS

Developments in Australian Standard AS (Emergency Lighting)

Australian Standard. Gaseous fire extinguishing systems AS (Incorporating Amendment No. 1) AS

AS/NZS :2009. Performance of household electrical appliances Refrigerating appliances AS/NZS :2009

Australian/New Zealand Standard

Fire resistance test on fire collars protecting a concrete slab penetrated by services

Fire-resistance test on fire collars protecting a plasterboard wall penetrated by services

Fire-resistance test on fire collars protecting a concrete slab penetrated by services

AS/NZS :2016

AS/NZS 3190:2011 AS/NZS

Australian/New Zealand Standard

Fire-resistance test on fire collars protecting a plasterboard wall penetrated by services

Australian/New Zealand Standard

FIRE-RESISTANCE TEST ON FIRE COLLARS PROTECTING A PLASTERBOARD WALL PENETRATED BY SERVICES

American National Standard for Electrical Lamp Bases Specifications for Bases (Caps) for Electric Lamps

AS/NZS 3820:2009 (Incorporating Amendment 1) Essential safety requirements for electrical equipment

AS/NZS :2015. Conduit systems for cable management AS/NZS :2015. Part 21: Particular requirements Rigid conduit systems

Technical Bulletin CE marking: from 1st July 2013

GK/GN0612. Guidance on Signalling Lockout Systems to Protect Railway. Undertaking Personnel. Railway Group Guidance for GK/RT0212.

SAA HB THE DOMESTIC KITCHEN HANDBOOK

Australian Standard. Components for the protection of openings in fire-resistant walls. Part 1: Fire-resistant doorsets AS AS 1905.

AS/NZS :2008

AS/NZS 3133:2008 AS/NZS

CONDITIONS OF SERVICE - NBN SERVICES 1. ABOUT

AS/NZS :2011. Household and similar electrical appliances Safety AS/NZS :2011. Part 1: General requirements

CERTIFICATION SAFETY & BEYOND

FIRE-RESISTANCE TEST ON DOWNLIGHT COVERS INSTALLED IN PLASTERBOARD CEILINGS

Australian Standard. Functional safety of electrical/electronic/programmable electronic safety-related systems. Part 0: Functional safety and AS 61508

OWNER S MANUAL. CoolTower CTF07. (English) (CTF07)

AS/NZS :2012. Regulatory compliance mark for electrical and electronic equipment AS/NZS :2012. Part 1: Use of the mark

Australian/New Zealand Standard

Fire Safety Management

AS/NZS :2015

Australian Standard. Automatic fire detection and alarm systems System design, installation, and commissioning AS

Australian/New Zealand Standard

AS/NZS :2015. Conduit systems for cable management AS/NZS :2015. Part 1: General requirements. Australian/New Zealand Standard

Your Key to achieving C.E Marking Compliance

Owner s Manual. PIR-1 IR Learner

AS/NZS :2014. Electrical equipment for coal mines Introduction, inspection and maintenance AS/NZS :2014. Part 1: For hazardous areas

AS Australian Standard. Portable fire extinguishers Guide to servicing. This is a free 7 page sample. Access the full version online.

ISO 6183 INTERNATIONAL STANDARD. Fire protection equipment Carbon dioxide extinguishing systems for use on premises Design and installation

Type 5 Certifications:

Fire Policy. Fire Safety Order (2005) Dangerous Substances and Explosive Atmospheres Regulations (2002)

American National Standard for Roadway and Area Lighting Equipment Elliptically Shaped, Enclosed Side-Mounted Luminaires

NZS 7901:2014. Electricity and gas industries Safety management systems for public safety NZS 7901:2014. New Zealand Standard

Dispute over the requirement for fire door signage to hotel suites at 124 Devon Street West, New Plymouth

GLOW WIRE TESTING FOR THE APPLIANCE INDUSTRY

NEMA Standards Publication ICS (R 2007) Adjustable Speed Electrical Power Drive Systems

Australian/New Zealand Standard TM

SCHEME OF TESTING AND INSPECTION FOR CERTIFICATION OF PORTABLE FIRE EXTINGUISHER- PERFORMANCE AND CONSTRUCTION AS PER IS 15683: 2006

Application Form. Qualified Accreditation

U S E R M A N U A L UBH1RF HEAT ALARM

AS/NZS :2016. Refrigerating systems and heat pumps Safety and environmental requirements AS/NZS :2016. Part 3: Installation site

Capital Projects Group Fire Extinguishers Specification

Life Safety Code Comparison

Australian/New Zealand Standard

Australian/New Zealand Standard

Guidance from the Group of Notified Bodies for the Construction Products Regulation 305/2011/EU

Guidance. Service of Hydrocarbon Refrigerant Equipment in a Retail Environment

DIVISION C ADMINISTRATIVE PROVISIONS

AS AS Australian Standard. Potting mixes. This is a free 7 page sample. Access the full version online.

Burn Injury Investigation Report Preparing a Live Fire Prop for Use Miami-Dade County Fire Rescue Department, November 18, 2011

Guidance Note No 21/1. CE Marking Windows and doorsets to BS EN 16034

Australian/New Zealand Standard

Evacuated Tube Solar Hot Water System. Owners Manual. Version 5.4

Fire Collars for Floor Wastes Understanding BCA Compliance Options

American National Standard

CONTRACTOR WHS HAZARD STANDARD LASER SAFETY EXTERNAL USE ONLY

American National Standard for Electrical Intermediate Metal Conduit

DIMENSIONAL STANDARD FOR 1/4" QUICK CONNECT COUPLER PLUGS AND SOCKETS FOR PORTABLE PRESSURE WASHERS

DIMENSIONAL STANDARD FOR M22 THREAD CONNECT COUPLER RECEPTACLES AND PLUG COLLARS FOR PORTABLE PRESSURE WASHERS

Medical electrical equipment

EXTINGUISHER MAINTENANCE METHOD STATEMENT.

AS/NZS 4234:2008 AS/NZS

CONFORMITY ASSESSMENT GUIDELINES. Version 1.0

AS/NZS :2015. Plumbing and drainage AS/NZS :2015. Part 4: Heated water services. Australian/New Zealand Standard

NEMA Standards Publication SB Fire Service Annunciator and Interface

Australian/New Zealand Standard

7.0 SAMPLE PERMITS, FORMS AND CHECKLISTS SELF INSPECTION CHECKLIST

AS/NZS IEC :2013

RHPK3000_IB_FA_ SALT & PEPPER MILLS 2 YEAR WARRANTY RHPK3000

For Roadway and Area Lighting Equipment Ingress Protection (Resistance to Dust, Solid Objects, and Moisture) for Luminaire Enclosures

Australian Standard. Electroacoustics Sound calibrators AS IEC This is a free 7 page sample. Access the full version online.

Australian Standard. Fire detection, warning, control and intercom systems Control and indicating equipment. Part 1: Fire

OWNER S MANUAL. Convair Tower Heater CTH09. (English) (CTH09)

ACCEPT HAIER NEW ZEALAND INVESTMENT HOLDING COMPANY LIMITED S $1.20 CASH OFFER FOR ALL YOUR SHARES IN FISHER & PAYKEL APPLIANCES HOLDINGS LIMITED.

AS/NZS 3111:2009. Approval and test specification Miniature overcurrent circuitbreakers AS/NZS 3111:2009. Australian/New Zealand Standard

Australian/New Zealand Standard

AS/NZS :2014

AS/NZS 4012:1999 AS/NZS

BMA INFORMATION BULLETIN No. 97 FIRE FIGHTING EQUIPMENT

volume 11 environmental assessment section 2 environmental impact assessment Part 4 ha 204/08 scoping of environmental impact assessments

Australian/New Zealand Standard

Combined Hand-Washing Systems

Fire Protection, Inspection and Testing Qualifications Forums. Jeremy Rose (Artibus Innovation) Chris Wyborn (FPA Australia)

Transcription:

Date of manufacture stamping of portable fire extinguisher cylinders Version 1.1 Approved for release July 2014

1.0 Purpose Statement The purpose of this document is to provide information on the date of manufacture stamping of portable fire extinguishers and the impact that the manufacture and supply process has on the likely date of manufacture stamp to be found on extinguishers purchased from manufacturers. 2.0 Audience This is intended for: (i) FPA Australia members; 3.0 Background (ii) Portable fire extinguisher suppliers; (iii) Portable fire extinguisher distributors and retailers; and, (iv) Purchasers and end users of portable fire extinguishers. A portable fire extinguisher cylinder is a gas cylinder. The Australian Standard for gas cylinders is AS 2030.1 2009, Gas cylinders General requirements, which is legislated in the Work Health and Safety Legislation of most states and territories. AS 2030.1 states in its scope that The requirements for gas cylinders in fire extinguisher systems and fire extinguishers, apply only where suitable requirements are not given in another Australian Standard. AS 1841.1 20, Portable fire extinguishers General requirements covers gas cylinder requirements, therefore portable fire extinguishers cylinders need only meet the requirements of AS 1841.1, not AS 2030.1. The exception to this is that AS 1841.1 refers back to AS 2030.1 for CO 2 type extinguishers. Therefore cylinders for CO 2 type extinguishers must meet the requirements of AS 2030.1. As such, the cylinder requirements for fire extinguishers are as follows: Non-CO 2 extinguishers must meet the cylinder requirements of AS 1841.1. C0 2 extinguishers must meet the cylinder requirements of AS 2030.1. Date of manufacture stamping of Version 1.1 Page 2

4.0 Date of manufacture stamping AS 1841.1 Clause 9.2 requires each portable fire extinguisher cylinder to be: Externally and visibly marked with the date of manufacture by stamping, etching, engraving or embossing on the extinguisher body or permanent attachment. As a minimum, this mark is to include the month and year of manufacture in the form MM/YY or MM/YYYY. Figure 1 Sample extinguisher date stamp For CO 2 type extinguisher cylinders, AS 1841.1 directs to AS 2030.1 which in turn directs to AS 2030.5 2009, Gas cylinders Filling, inspection and testing of refillable cylinders. Clause 10.3 of AS 2030.5 requires manufacturer s marks to be permanently marked on the cylinder including the date of original test. While Appendix D of AS 2030.5 provides some guidance to the form of this marking, it is not defined. However, it is generally in a recognisable format of MM/YYYY or YYYY/MM, see Figure 2. Figure 2 Sample CO 2 extinguisher date stamp 4.1 Location of date of manufacture stamp The location of the date of manufacture stamp is not specified in either AS 1841.1 or AS 2030.5. The only direction given in AS 1841.1 is that The depth of stamping shall be such as to maintain the minimum wall thickness at all relevant points of the pressure envelope. AS 2030.5 is more limited, with the only relevant information being the following advice found in Note 3 of informative Appendix D: Marks should be stamped on the thickened portion of a seamless gas cylinder. As such, the date of manufacture stamp may be found anywhere on a portable fire extinguisher cylinder, including its base. 4.2 When is a cylinder stamped with the date of manufacture and what does this mean? For cylinders to AS 1841.1, the date stamp indicates the date of manufacture for the cylinder. For CO 2 type it is the date of original test. In both cases this mark is made during the construction, inspection and testing of the cylinder. Date of manufacture stamping of Version 1.1 Page 3

5.0 Impact of the manufacture and supply process on the likely date of manufacture stamp to be found on extinguishers purchased from manufacturers All portable fire extinguishers are currently manufactured overseas; none are made in Australia. There are several steps in the manufacture and supply process from manufacture of the portable fire extinguisher cylinder to the arrival of the complete and charged extinguisher at the manufacturer in Australia. The time period across these steps can be quite lengthy. These steps are as follows: 1. Portable extinguisher cylinder manufactured; 2. Completed portable fire extinguishers manufactured (that is, extinguisher components added to the cylinder to make it into an extinguisher and, where appropriate, extinguisher charged); 3. Dangerous goods sea freight to Australia; and 4. Local distribution to manufacturer in Australia. In ideal circumstances, this process may occur in one month or even less. However, due to the number of steps involved, and particularly the fact that these extinguishers are manufactured overseas, delays at any step can result in complete extinguishers not arriving at the manufacturer until two or three months after manufacturing commenced. Furthermore, it should be noted that depending on stock levels at the manufacturer, extinguishers may not be sold for several months more while old stock is cleared first. All of the above means that a supplier, distributor or end user purchasing portable fire extinguishers from a manufacturer should expect the likely date of manufacture of the extinguishers to be 3 to 6 months from the date at time of purchase. For example, if purchasing an extinguisher in May 2014, it would not be unusual to purchase an extinguisher with a date of manufacturer of February 2014 or even November 2013. In this example, given the above steps involved, being able to purchase an extinguisher manufactured in May 2014 would be a rare occurrence. Date of manufacture stamping of Version 1.1 Page 4

6.0 What to do if you find an extinguisher with date of manufacture stamp ahead of the current date FPA Australia members have observed some extinguishers have appeared in the marketplace with date of manufacture stamps that are ahead of the current date (e.g. July 2014 when it is only May 2014). This means such stamping has not occurred as per the requirement of AS 1841.1 and AS 2030.5 and may invalidate the product certification of those extinguishers. As such, FPA Australia would recommend anyone who comes across such extinguishers to notify the certification body that certifies those extinguishers to take appropriate action to confirm how this has occurred and whether the certification of that extinguisher is still valid. FPA Australia is also interested such occurrences and would value being informed and involved in this process also. 7.0 Impact of date of manufacture stamps on the servicing of portable fire extinguishers Portable fire extinguishers are typically serviced in accordance with AS 1851, which requires a fiveyearly hydrostatic pressure testing (six-yearly if using AS 1851-1995). When this test first needs to be carried out is defined by the date of manufacture stamp on the extinguisher rather than the date of the purchase or installation of the extinguisher. Extinguishers that are pressure tested are then marked and future pressure tests are carried out based on the date of the last hydrostatic pressure test. 8.0 Conclusion Portable fire extinguisher cylinders are stamped with the date of manufacture during the manufacture, inspection and testing of the cylinder. However, due to steps involved in the manufacture and supply process, the likely date of manufacture stamp on extinguishers purchased from a manufacturer is to be 3 to 6 months behind the current date. 9.0 References Australian Standards published by Standards Australia International Ltd: AS 1841.1 20, Portable fire extinguishers General requirements AS 1851 2012, Routine service of fire protection systems and equipment AS 1851.1 1995, Maintenance of fire protection equipment - Portable fire extinguishers and fire blankets AS 2030.1 2009, Gas cylinders General requirements AS 2030.5 2009, Gas cylinders Filling, inspection and testing of refillable cylinders Date of manufacture stamping of Version 1.1 Page 5

10.0 Disclaimer The opinions expressed in this correspondence reflect those of FPA Australia however are subject to change based on receipt of further information regarding the subject matter. You should interpret the technical opinion or information provided carefully and consider the context of how this opinion / information will be used in conjunction with the requirements of regulation (state and/or federal); relevant standards, codes or specifications; certification; accreditation; manufacturer s documentation and advice; and any other relevant requirements, instructions or guidelines. FPA Australia does not accept any responsibility or liability for the accuracy of the opinion / information provided, nor do they accept either directly or indirectly any liabilities, losses and damages arising from the use and application of this opinion / information. Copyright 2014 Fire Protection Association Australia. Material distributed by FPA Australia is subject to copyright. Any information within this publication may not be reproduced in printed or electronic form without permission from FPA Australia. For more information, please see www.fpaa.com.au or contact FPA Australia on: 1300 731 922. Date of manufacture stamping of Version 1.1 Page 6