Design Standard. Thermal Systems (Chilled Water and Hot Water Systems) Detailed specifications follow. CHW AND HHW SUPPLY TEMPERATURE RESET

Similar documents
AC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT

Computing Services Center

Continuous Commissioning Report

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

November 11, City of Sparks 215 S. 21 st St. Sparks, NV

Description of All Alternatives Considered-

ADDENDUM No: 3 JOSEPHINE COUNTY BUILDING OPERATIONS DEPARTMENT. February 29, NO CHANGE: March 8, 2012 / NOT LATER THAN 2:00 PM

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

High Efficiency Dehumidification System (HEDS)

Civil Engineering Building

Harrington Tower Building

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

COMcheck Software Version Review Mechanical Compliance Certificate

Submitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

Submitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK

DIGI-VAV APPLICATIONS

Auburn University Basketball Arena:

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

Topic 2. ME 414/514 HVAC Systems Overview Topic 2. Equipment. Outline

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT

Madeira City Schools Madeira, Ohio. HVAC Assessment. December 2011 (Revised February 2012)

HVAC Products. SAPHIR AirGo OEM Air Handling Unit Concept

4-Pipe VAV vs. Active Chilled Beams for Labs

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Temperature. In the HVAC area, we talk about two kinds of temperatures.

Paul McCown, PE, CEM, LEED AP, CxA Sr. Mechanical Engineer SSRCx, LLC Nashville, TN USA

BULLETIN. Temperature Controls (Chilled Water) Phase III only (3/11/2010)

4. OVERVIEW OF MECHANICAL SYSTEM

NEW FEATURES IN THE CARRIER HOURLY ANALYSIS PROGRAM v4.80

BES-TECH TECHNOLOGY & SYSTEM INTEGRATION

General HVAC Recommendations

Job Name Control Systems Description Date

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

Technical Assignment 3 11/15/04. Executive Summary

Virginia Tech Standards for Building Automation System

Technical Report Three

SECTION HVAC TABLE OF CONTENTS PART 1 - SYSTEM DESCRIPTION / OUTLINE SPECIFICATIONS FILED SUB BID PROJECT OVERVIEW...

Dehumidifying with Dedicated Outdoor Air

Integrated Automation Instrumentation & Terminal Devices

CONTROLLED CHILLED BEAM PUMP MODULE

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

New PHE applications in construction & HVAC.

Selected Laboratory Energy Efficiency Measures

Continuous Commissioning: A Valuable Partner to Retrofit Projects

Mechanical Compliance Certificate

COMcheck Software Version Mechanical Compliance Certificate

ASHRAE Illinois Chapter 2015 Excellence in Engineering Awards

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings

Submitted to. Texas A&M University at Commerce The Texas A&M University System. Submitted by. Guanghua Wei Craig Campbell David Claridge Dan Turner

FORM EG2 (502) FlexSys Configured Packaged Rooftop Air Conditioning Units

MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN

OSU Alumni Center Phase I Implementation Review. Oregon State University 130 Oak Creek Bldg. Corvallis, Oregon

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

CONTROLLED CHILLED BEAM PUMP MODULE

The M & V Guided Recommissioning Process. Energy & Water Conservation Program. September 2015 MOO

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

Technical Report #3 Mechanical Systems Existing Conditions Evaluation

COMcheck Software Version Mechanical Compliance Certificate

The Temperature and Relative Humidity Control in Cushing Library

Select DOAS, Ceiling Radiant Cooling Panel- Chilled Beam Projects. Updated 9/23/2008

Sustainability Best Practices for HVAC Retrofits. Cal Poly State University, San Luis Obispo. Presented to the UC/CSU/CCC Sustainability Conference

BULLETIN. Temperature Controls (10/2013)

P/N f. HomeWorks QS Palladiom Thermostat Configuration Guide

Existing Building HVAC Systems Description

SEQUENCE OF OPERATIONS

Energy Savings with Direct Digital Control

15900 HVAC INSTRUMENTATION AND CONTROLS

CHAPTER 4. HVAC DELIVERY SYSTEMS

Application Sheet Fan coil unit with staged fan, heating and cooling coil (4 pipe) on triac output including lighting and blinds operation

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS

SECTION ROTARY SCREW WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

Selection of air conditioning systems

COMcheck Software Version Mechanical Compliance Certificate

ASHRAE S DOAS WEBCAST: A DEEPER EXAMINATION OF THE ROLE OF HEAT PIPES

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - "Systems and Equipment.

EarthWise System Seminar

HVAC Efficiency In Healthcare. Presenter Mr. Nate Lincoln

Union County Vocational - Technical Schools Scotch Plains, New Jersey

2009 Washington State Non-Residential Energy Code Scott Rushing, PE, LEED AP - Rushing Company Lisa Rosenow, CSBA, LEED AP NEEC

Physical Plant Complex

Contra Costa Community College District

SECTION AIR HANDLING UNITS WITH COILS. 1. Central Station Air Handling Units. 1. Section Basic Mechanical Requirements.

ADC150 Automatic Draft Control

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana

1.1 This section applies to air handling units for HVAC Systems.

The ultimate in air handling units: directly and indirectly fired

University of Delaware

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT

BULLETIN. Temperature Controls (Chilled / Hot Water)

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

Sequence of Operations (excerpt)

Transcription:

Design Standard Detailed specifications follow. PART 1 CHW AND HHW SUPPLY TEMPERATURE RESET 1.1 The Utilities & Energy Services Department (UES) at Texas A&M University is actively identifying and implementing strategies to reduce the energy consumption and cost associated with campus heating and cooling requirements while ensuring customer needs are consistently met. Chilled water (CHW) and heating hot water (HHW) supply temperature reset schedules have been in effect on the campus for many years, with supply temperature adjusted based on outside air temperature. The supply temperature for chilled water ranges from 42 to 46 Degrees F and the supply temperature for heating hot water ranges from 130 to 170 Degrees F. The supply temperature reset schedule charts for both CHW and HHW are attached as Appendix A. PART 2 HVAC COIL DESIGN DELTA T 2.1 All CHW cooling coils in facility air handling units (AHUs) and fan coil units (FCUs) shall have a minimum of 14 Degrees F design delta T based on a CHW supply temperature of 42 Degrees F, during peak cooling periods, except for spaces with high internal heat loads, such as server rooms. In spaces with high internal heat load, the system should be designed to meet maximum cooling requirements with a CHW supply temperature of 46 Degrees F. 2.2 For HHW, the minimum AHU and FCU design delta T shall be 30 Degrees F based on a design HHW Supply Temperature, during peak heating periods, of 170 Degrees F. The minimum coil design delta T s specified above are contingent upon maintaining proper coil flow tolerance per 2008 ASHRAE Handbook, pg 12.18, Fig. 34. Coil design delta T (for both CHW and HHW) can be higher than indicated above, but this design requirement must be achieved, unless a modification to this design guideline is approved in advance as indicated at the end of this guideline. Coils shall be designed in accordance with the latest version of ARI Standard 410. 2.3 AHUs having greater than 50 percent outside air supply shall have an energy recovery system incorporated into the design, unless it is proven to not be justifiable based on a life cycle cost analysis. Energy recovery systems shall be designed to operate at a minimum of 70% efficiency and be connected to the Siemens BAS to allow for effective monitoring of the system operation. Pre-filters shall be provided on all energy recovery systems to prevent fouling of the heat transfer element. 2.4 A requirement for testing, balancing and commissioning of both water and air flow shall be included in the specifications for all HVAC systems installed in new buildings and with any significant HVAC system replacement or retrofit.

PART 3 CHW AND HHW DISTRIBUTION SYSTEMS Notes: 3.1 CHW and HHW distribution pumps in the buildings shall be equipped with variable speed drives, with pump speed modulated to maintain sufficient differential pressure at desired flow through all HVAC coils in the building. Variable speed drives shall be connected to the Siemens BAS for effective monitoring and control under all flow conditions. The Siemens BAS shall also monitor the status of CHW and HHW control valves and any valve which hasn t opened a minimum of 20% at least once during any 168 hour (one week) period shall be programmed by the BAS to automatically open fully (during unoccupied periods) for a period of 15 minutes, in order to flush the thermal piping and minimize the potential for microbial growth. 3.2 All AHU and FCU fan motors and CHW and HHW pump motors installed in new buildings and with major system replacement or retrofit shall be specified to meet minimum efficiency requirements of National Electrical Manufacturers Association (NEMA) Standards Publication MG1-2006 (or any later edition) Premium Energy Efficiency Motor Standard, if a Premium Energy Efficiency Motor is available in the required size and rating. All new motors shall be sized to operate with a load factor of between 65 and 100 percent. 3.3 Three-way bypass control valves shall not be installed in any new CHW or HHW system. When HVAC systems in existing buildings are upgraded to include direct digital control (DDC), all existing three-way bypass control valves shall be removed and the DDC control system shall be programmed to provide flushing as previously described. Two-way characterized ball-style control valves shall be used for CHW and HHW flow control, rated to handle pressure drop that exceeds the highest differential pressure that the distribution pump(s) can generate, in order to avoid valve seat deterioration and leak-by. Control valve actuators shall have shut-off ratings that exceed the highest potential branch circuit differential pressure to ensure positive valve closure. Electric valve and damper actuators shall be specified for all HVAC systems that have DDC capability. 1. See the UES Design Standard titled Building Automation Systems for additional requirements. 2. Any deviation from this design standard needs to be reviewed and approved by Utilities & Energy Services (UES).

APPENDIX A CHW & HHW SUPPLY TEMPERATURE RESET SCHEDULES