LCH. Energence Rooftop Units 60 HZ

Similar documents
Energence Rooftop Units 60 HZ ASHRAE 90.1 COMPLIANT. 13 to 25 Tons Net Cooling Capacity 152,000 to 270,000 Btuh Optional Electric Heat - 15 to 90 kw

E-Series Rooftop Units 60 HZ ASHRAE 90.1 COMPLIANT. 13 to 25 Tons Net Cooling Capacity 152,000 to 270,000 Btuh Optional Electric Heat - 15 to 90 kw

Energence Rooftop Units 60 HZ

LCH. E-Series Rooftop Units 60 HZ

LGH. E-Series Rooftop Units 60 HZ

E-Series Rooftop Units 60 HZ

E-Series Rooftop Units 60 HZ

Energence Ultra-High Efficiency Rooftop Units 60 HZ ASHRAE 90.1 COMPLIANT

LGH. Energence Ultra-High Efficiency Rooftop Units 60 HZ

LGH. Energence Rooftop Units 50 HZ

LGH. E-Series Rooftop Units 50 HZ

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

Landmark Rooftop Units 50 HZ

T CLASS ROOFTOP UNITS 60HZ Bulletin No July 2008 Supersedes August 2007

E-Series Rooftop Units 50 HZ

L SERIES ROOFTOP UNITS 60 HZ

L SERIES ROOFTOP UNITS 60 HZ

2018 LIGHT COMMERCIAL ROOFTOP UNITS. Industry-leading efficiency and innovation to meet your needs

Rooftop Units 60HZ. PACKAGED HEAT PUMPS 13HPP / rhp13 PRODUCT SPECIFICATIONS 13 HPP 36 A P - 1 A RHP 13 A 36 T - 1 A MODEL NUMBER IDENTIFICATION

Performance and rugged durability. Commercial Split Systems Up to 20-Ton TSA/TPA Models

T-SERIES COMMERCIAL SPLIT SYSTEMS R-410A - 60 HZ

T-CLASS Commercial Split Systems Up to 20-Ton TSA/TPA Models

MERIT Series R-410A - Upflow / Horizontal

L SERIES ROOFTOP UNITS 60 HZ

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

L SERIES ROOFTOP UNITS 60 HZ

T-SERIES SPLIT SYSTEM UNITS R-410A - 60 HZ. EER up to to 20 Tons Cooling Capacity - 71,000 to 236,000 Btuh AIR CONDITIONERS TS

MERIT Series R-410A - Upflow / Horizontal

RGE 13 A T - 1 A

MERIT SERIES Up Flow / Horizontal

Corp L2 Revised

Rooftop Ventilator. Models RV and RVE. with Packaged Cooling & Heating

3 to 5 Tons. AIR CONDITIONERS 2scu13. Dry Charge Split System - 60 HZ PRODUCT SPECIFICATIONS. 2 scu 13 lc 1 36 t - 1 a MODEL NUMBER IDENTIFICATION

50Hz AC, HP and Air Handler Units Up to 70 kw. Commercial Split Systems. Reliable, cost-effective and servicefriendly split systems inside and out

T P A 120 S 4 S N 1 Y

CB18/CBS18 Bulletin # September 1994 Supersedes August 1986

AC, HP and Air Handler Units Up to 20 Tons. Commercial Split Systems. Reliable, cost-effective and servicefriendly split systems inside and out

P8SE Series. 14 SEER, Single Phase Packaged Air Conditioner TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 3, 4, 5 Ton Units

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Commercial Packaged Rooftop Units 3- to 50-Ton LC/LG Models UP TO 18.0 SEER, 12.8 EER AND 15.5 IEER

Modular Supply Make-Up Air Unit

2 shp 13 lc 1 36 t - 1 a

Up to 16.1 SEER, Up to 14.3 EER and Up to 15.4 IEER

THE ULTIMATE ROOFTOP SOLUTION

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

48TM GAS HEATING/ELECTRIC COOLING UNITS

48PGD/E/F/L/M/N PG20-28

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

DCC Commercial. Submittal Data Form. 7½ - 12½ Ton Packaged Air Conditioners Up to 11.3 EER Cooling Capacity: 88, ,000 BTU/h

50HJQ004, 005, 006, 007, 008 & 012 SINGLE-PACKAGE HIGH-EFFICIENCY HEAT PUMP UNITS WITH FIELD-INSTALLED ELECTRIC HEAT

Landmark. Commercial Packaged Rooftop Units 2- to 25-Ton KG/KC/KH Models. Up to 13.0 SEER, 14.0 IEER. Performance Marked by Flexibility

48TF GAS HEATING/ ELECTRIC COOLING UNITS

Indirect Gas-Fired Make-Up Air

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

Direct Fired Heater Model AD Specification

Series PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS. Features:

Commercial Packaged Rooftop Units 3- to 50-Ton LC/LG Models. Up to 18.0 SEER, Up to 12.8 EER and 14.5 IEER

62DA,DB,DC,DD,DE,DF07-38

Submittal Data Performance Data Electrical Data

DCC Series. Submittal Data Form 15- & 20-TON, THREE-PHASE PACKAGED AIR CONDITIONERS UP TO 11 EER

Modular Heating & Ventilating Unit Model IGX-HV

DRY CHARGE UNITS. 1.5 to 5 Tons AIR CONDITIONERS LCS13DC PRODUCT SPECIFICATIONS L C S 13 DC MODEL NUMBER IDENTIFICATION

13 GEP A L P - 1 A

Nominal Capacity 024 = 7 kw (2 tons) 036 = 10.5 kw (3 tons) 048 = 14 kw (4 tons) 060 = 17.5 kw (5 tons)

Series. Packaged Rooftop Units, heat pumps and Outdoor air handling Units. Features:

RHEEM PACKAGE GAS/ELECTRIC

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

MACH N-407 Heat Pump Air-Cooled Chiller

THE RIGHT SPEC. RIGHT NOW.

VariCool VAV Engineering Guide

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

Commercial Packaged Rooftop Units 3- to 50-Ton LC/LG Models. Up to 17.0 SEER, Up to 12.8 EER

DCC Series. Submittal Data Form. 7½- to 12½-Ton Three-Phase Packaged Air Conditioners

50TM COMBINATION HEATING/COOLING UNITS

Submittal Data DESCRIPTION STANDARD FEATURES. Base Unit. Cabinet. Refrigerant System. Gas Heat

Direct Gas-Fired Make-Up Air Models DG and DGX

KGA/KGB UNITS WARNING

LRP14HP. Residential - R-410A L RP 14 HP 36 P A MODEL NUMBER IDENTIFICATION. Bulletin No November 2016 Supersedes October 2016

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

Direct Gas-Fired Make-Up Air

T CLASS ROOFTOP UNIT 50HZ 24.8 to 38.8 kw (84,800 to 132,700 Btuh) Bulletin No August 2005 Supersedes December 2004

B24/C22/24 COILS BLOWER COIL UNITS ENGINEERING DATA. Bulletin # June 1994 Supersedes August B24 Blower Unit (With Optional Electric Heat)

DSC Series. Submittal Data Form. 3-5 Ton Packaged Air Conditioner 14 SEER / Up to 12.0 EER

DCC Series. Submittal Data Form. 7½- to 12½-Ton Three-Phase Packaged Air Conditioners Up to 11.3 EER

DCG Commercial. Submittal Data Form

3- to 24-Ton Models. Commercial Packaged Rooftop Units. The most energy-efficient rooftop unit in the industry *

T-SERIES COMMERCIAL SPLIT SYSTEMS 6- TO 20-TON ELP/ELS MODELS UP TO 12.0 EER

Performance and Reliability. CB*, C* and TA* Models

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog

ELITE Series R-410A. SEER up to to 5 Tons Cooling Capacity - 17,800 to 60,000 Btuh AIR CONDITIONERS EL16XC1 PRODUCT SPECIFICATIONS

1.1 This section applies to air handling units for HVAC Systems.

MAC N-407 Air-Cooled Chiller

Healthy Climate Whole-Home Dehumidifier. Nominal Capacity - 70 to 130 pints per day INDOOR AIR QUALITY HCWHD PRODUCT SPECIFICATIONS.

LRP14AC. SEER to 5 Tons Cooling Capacity - 22,600 to 57,000 Btuh Optional Electric Heat - 5 to 20 kw. Residential - R-410A

RN/RQ. Series PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE/ GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNITS.

Chilled Water DOAS Fan Powered Terminal Units

LCA/LGA. PACKAGED L SERIES 50hz. 25 & 30 Ton (87.9 & kw) Bulletin # December 1995 ENGINEERING DATA. Table of Contents

PAR5. Product Specifications

Transcription:

PA C K A G E D E L E C T R I C / E L E C T R I C LCH Energence Rooftop Units 60 HZ Bulletin No. 20556 July 208 P R O D U C T S P E C I F I C AT I O N S Supersedes October 207 ASHRAE 90. COMPLIANT 7.5 to 2.5 Tons Net Cooling Capacity 90,000 to 2,000 Btuh Optional Electric Heat - 7.5 to 60 kw MODEL NUMBER IDENTIFICATION L C H 20 H B N Y Voltage Y = 208/230V-3 phase-60hz G = 60V-3 phase-60hz J = 575V-3 phase-60hz Brand/Family L = Energence Unit Type C = Packaged Electric Cooling w/ optional Electric Heat Major Design Sequence H = st Generation Nominal Cooling Capacity - Tons 092 = 7.5 Tons 02 = 8.5 Tons 20 = 0 Tons 50 = 2.5 Tons Cooling Efficiency H = High Efficiency Minor Design Sequence = st Revision 2 = 2nd Revision 3 = 3rd Revision Factory Installed Electric Heat N = No Heat C = 7.5 kw Electric Heat E = 5 kw Electric Heat G = 22.5 kw Electric Heat J = 30 kw Electric Heat K = 5 kw Electric Heat L = 60 kw Electric Heat Blower Type B = Belt Drive, Constant Air Volume (CAV) M = MSAV (Multi-Stage Air Volume) Supply Air Blower Option, Belt Drive Refrigerant Type = R-0A

FEATURES AND BENEFITS E M D L K J N B C G I H F Unit shown with optional Economizer with Outdoor Air Hoods Lennox Energence packaged rooftop unit product line was created to save energy with intelligence by offering some of the highest energy efficiency ratings available with a powerful, easy to use unit controller. This makes Energence rooftop units perfect for business owners looking for an HVAC product with the lowest total cost of ownership. Energence rooftop units feature: Hinged Access Panels - Provide quick access to components and protect panels and roof from damage during servicing. Isolated Compressor Compartment - Allows performance check during normal compressor operation without disrupting airflow. Corrosion-Resistant Removable, Reversible Drain Pan - Provides application flexibility, durability and improved serviceability. Thermostatic Expansion Valves - Provide peak cooling performance across the entire application range. Scroll Compressors - Standard on all units for reliable, long-term operation. Lennox Environ Coil System (092-20 Models Only) - Smaller, lighter condenser coil. Humiditrol Dehumidification System - Patented system allows for independent control of temperature and humidity, providing enhanced comfort control. Constant Air Volume (CAV) or MSAV (Multi-Stage Air Volume) Supply Air Blower Option - Allows constant or multi-staged air delivery. Auto-Tensioner for Blower Belt - Factory option ensures blower is delivering the proper airflow for comfort, while maximizing efficiency and belt life. MERV 3 Filters - Available as factory or field option, provide an enhanced level of indoor air quality, and can help the building qualify for additional LEED credits. Foil-Faced Insulation - Insulation on all internal surfaces that have contact with airflow helps minimize airborne fibers and improve IAQ. Common Components - Many maintenance items are standard throughout the entire product line, reducing the need to carry different parts to the job or maintain in inventory. Prodigy Control System Standard on every Energence rooftop unit, the Prodigy 2.0 unit controller is the center of the Prodigy Control System. The intuitive user interface makes setup, troubleshooting and service easier than ever. Each unit tracks the runtime of every major component and records the date and time when service or maintenance is performed. SmartWire System The SmartWire system simplifies field sensor or thermostat installation through advanced connectors that are keyed and color-coded to help prevent miswiring. Not only is the wire coloring scheme standardized across all models, each connection is intuitively labeled to make troubleshooting and servicing quick and easy. Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 2

FEATURES AND BENEFITS CONTENTS Blower Data................................ 27 Dimensions - Accessories......................... 39 Dimensions - Unit............................. 38 Electrical/Electric Heat Data........................3 Features And Benefits........................... 2 Humiditrol Dehumidification System Ratings...............25 Model Number Identification........................ Optional Conventional Temperature Control Systems...........36 Options / Accessories........................... 5 Outdoor Sound Data............................35 Prodigy Control System.......................... 8 Ratings...................................2 Sequence Of Operation - MSAV (Multi-Stage Air Volume) Models....2 Specifications................................9 Unit Clearances.............................. 35 Weight Data................................ 37 B COOLING SYSTEM Designed to maximize sensible and latent cooling performance at design conditions. System can operate from 0 F to 25 F without any additional controls. R-0A Refrigerant Non-chlorine based, ozone friendly, R-0A. Scroll Compressors Scroll compressors on all models for high performance, reliability and quiet operation. Resiliently mounted on rubber grommets for quiet operation. APPROVALS AHRI Certified to AHRI Standard 30/360-2007. ETL listed. Efficiency ratings are certified by CSA. Components are bonded for grounding to meet safety standards for servicing required by UL, ULC and National and Canadian Electrical Codes. All models are ASHRAE 90.-200 energy efficiency compliant and meet or exceed requirements of Section 6.8. All models meet DOE 208 energy efficiency standards. MSAV models meet California Code of Regulations, Title 2 and ASHRAE 90.-200 Section 6..3.0 requirements for staged airflow. Energy Star certified units are designed to use less energy, help save money on utility bills, and help protect the environment. The Energy Star Partner of the Year Award signifies that Lennox has made outstanding contributions to design energy efficient units that will lower energy bills, while meeting industry standards for comfort and indoor air quality. Lennox was the first HVAC manufacturer to win this award and has been a four-time recipient since 2003. ISO 900 Registered Manufacturing Quality System. WARRANTY Limited five years on compressors. Limited three years on the Lennox Environ Coil System. Limited three years on Prodigy 2.0 unit controller. Limited five years on Optional High Performance Economizers. Limited one year all other covered components. Compressor Crankcase Heaters Protects against refrigerant migration that can occur during low ambient operation. Thermal Expansion Valves Assures optimal performance throughout the application range. Removable element head. Filter/Driers High capacity filter/drier protects the system from dirt and moisture. High Pressure Switches Protects the compressors from overload conditions such as dirty condenser coils, blocked refrigerant flow, or loss of outdoor fan operation. Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 3

C FEATURES AND BENEFITS COOLING SYSTEM (continued) Low Pressure Switches Protects the compressors from low pressure conditions such as low refrigerant charge, or low/no airflow. Freezestats Protects the evaporator coil from damaging ice build-up due to conditions such as low/no airflow, or low refrigerant charge. Lennox Environ Coil System (092 through 20 models only) Condenser coil features lightweight, all aluminum brazed fin construction. Constructed of three components: a flat extrusion tube, fins inbetween the flat extrusion tube and two refrigerant manifolds. Environ Coil System Features: Improved heat transfer performance due to high primary surface area (flat tubes) versus secondary surface (fins). Smaller internal volume (reduced refrigerant charge). High durability (all aluminum construction). Fewer brazed joints. Compact design (reduces unit weight). Easy maintenance/cleaning. Face-split design. Mounting brackets with rubber inserts secure coil to unit providing vibration dampening and corrosion protection. Conventional Fin/Tube Condenser Coils (50 models only, optional 092-20 models) Copper tube construction, enhanced rippled-edge aluminum fins, flared shoulder tubing connections, silver soldered construction. D Evaporator Coil Copper tube construction, enhanced rippled-edge aluminum fins, flared shoulder tubing connections, silver soldered construction for improved heat transfer. Cross row circuiting with rifled copper tubing optimizes both sensible and latent cooling capacity. Condensate Drain Pan Plastic pan, sloped to meet drainage requirements per ASHRAE 62.. Side or bottom drain connections. Reversible to allow connection at back of unit. Outdoor Coil Fan Motors Thermal overload protected, totally enclosed, permanently lubricated ball bearings, shaft up, wire basket mount. All 50 models feature two-speed motors for optimal performance at low ambient conditions. Outdoor Coil Fans PVC coated fan guard furnished. Required Selections Cooling Capacity Specify nominal cooling capacity of the unit Options/Accessories Factory Installed Conventional Fin/Tube Condenser Coil (replaces Environ Coil System - 092 through 20 models only) Copper tube construction, enhanced rippled-edge aluminum fins, flared shoulder tubing connections, silver soldered construction. NOTE - All 50 models have a fin/ tube coil as standard. Service Valves Fully serviceable brass valves installed in discharge & liquid lines. NOTE - Not available for units equipped with Environ Coil System or Humiditrol Dehumidification option. Factory or Field Installed Condensate Drain Trap Available in copper or PVC. Field installed only, may be factory ordered to ship with unit. Drain Pan Overflow Switch Monitors condensate level in drain pan, shuts down unit if drain becomes clogged. Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page

E F FEATURES AND BENEFITS CABINET Construction Heavy-gauge steel panels and full perimeter heavy-gauge galvanized steel base rail provides structural integrity for transportation, handling, and installation. Base rails have rigging holes. Three sides of the base rail have forklift slots. Raised edges around duct and power entry openings in the bottom of the unit provide additional protection against water entering the building. Airflow Choice Units are shipped in downflow (vertical) configuration, can be field converted to horizontal airflow with optional Horizontal Discharge Kit. Duct Flanges Provided for horizontal duct attachment. Power Entry Electrical lines can be brought through the unit base or through horizontal access knock-outs Exterior Panels Constructed of heavy-gauge, galvanized steel with a two-layer enamel paint finish. Insulation All panels adjacent to conditioned air are fully insulated with nonhygroscopic fiberglass insulation. Unit base is fully insulated. The insulation also serves as an air seal to the roof curb, eliminating the need to add a seal during installation. Hinged Access Panels Hinged tool-less access panels are provided for the filter section, blower/heating section and compressor/controls section. All hinged panels have seals and quarter-turn latching handles to provide a tight air and water seal. Required Selections Airflow Configuration Specify downflow or horizontal. Options/Accessories Factory or Field Installed Return Air Adaptor Plate For same size LC/LG/LH and TC/ TG/TH unit replacement. Installs on return air opening in unit to match return air opening on existing roof curbs. Also see Accessory Air Resistance table. Factory Installed Corrosion Protection A completely flexible immersed coating with an electrodeposited dry film process (AST ElectroFin E-Coat). Meets Mil Spec MIL-P-5308, ASTM B7 Standard Method Salt Spray Testing. Indoor Corrosion Protection: - Coated coil - Coated reheat coil (Humiditrol ) - Painted blower housing - Painted base Outdoor Corrosion Protection: - Coated coil - Painted base Field Installed Combination Coil/Hail Guards Heavy gauge steel frame painted to match cabinet with expanded metal mesh to protect the outdoor coil from damage. Horizontal Discharge Kit Consists of duct covers to block off downflow supply and return air openings for horizontal applications. Also includes return air duct flanges for end return air when economizer is used in horizontal applications. NOTE - When configuring unit for horizontal application with economizer, a separate Horizontal Barometric Relief Damper with Hood must be ordered separately for installation in the return air duct. Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 5

G FEATURES AND BENEFITS BLOWER A wide selection of supply air blower options are available to meet a variety of airflow requirements. Motor Overload protected, equipped with ball bearings. Belt drive motors are offered on all models and are available in several different sizes to maximize air performance. Motor Efficiency All blower motors 5 hp and above meet minimum energy efficiency standards in accordance with the Energy Independence and Security Act (EISA) of 2007. Supply Air Blower Forward curved blades, double inlet, blower wheel is statically and dynamically balanced. Equipped with ball bearings and adjustable pulley (allows speed change). Blower assembly slides out of unit for servicing. Required Selections Select Constant Air Volume (CAV) or MSAV (Multi-Stage Air Volume) Supply Air Blower Option On Constant Air Volume (CAV) models, the supply air blower will provide a constant volume of air. On MSAV (Multi-Stage Air Volume) supply air blower option models the supply air blower will stage the amount of airflow according to compressor stages, heating demand, ventilation demand or smoke alarm. NOTE - Units with the MSAV supply air blower option have the same face split indoor coils as units with the CAV supply air blower option. Part load airflow in cooling mode on MSAV units should not be set below 220 cfm/ nominal full load ton to reduce the risk of evaporator coil freeze-up. H Utilizes a Variable Frequency Drive (VFD) to stage the supply blower airflow. The VFD alters the frequency and voltage of the power supply to the blower to control blower speed. The amount of airflow for each stage can be set according to a parameter in the Prodigy 2.0 unit controller. Unit is shipped from the factory with preset airflow. The MSAV supply air blower option can be ordered with or without an Electronic Bypass Control. If equipped with the bypass control the MSAV features manual (default) or automatic electronic bypass control of the VFD. In case of a VFD malfunction, a VFD alarm is generated by the Prodigy 2.0 unit controller. The VFD can be manually bypassed to continue unit operation at full blower speed. Or the unit controller can be set to automatically switch to full blower speed if a VFD alarm is generated. The VFD has an operational range of 0 to 25 F outdoor air ambient temperature. Lower operating costs are obtained when the blower is operated on lower speeds. Ordering Information Specify motor horsepower and drive kit number when base unit is ordered. Options/Accessories Factory Installed Blower Belt Auto-Tensioner Provides proper tension to belt drive blower belt without the need for regular adjustments. Maintains airflow and proper performance. ELECTRICAL SmartWire System Advanced wiring connectors are keyed and color-coded to prevent miswiring. Wire coloring scheme is standardized across all models. Each connection is intuitively labeled to make troubleshooting and servicing quick and easy. Electrical Plugs Positive connection electrical plugs are used to connect common accessories or maintenance parts for easy removal or installation. Required Selections Voltage Choice Specify when ordering base unit. Options/Accessories Factory Installed Circuit Breakers HACR type. For overload and short circuit protection. Factory wired and mounted in the power entry panel. Current sensitive and temperature activated. Manual reset. Phase/Voltage Detection (Optional for CAV Models Only) Phase detection monitors power supply to assure phase is correct at unit start-up. If phase is incorrect, the unit will not start and an alarm code is reported to the unit controller. Protects unit from being started with incorrect phasing which could lead to issues such as compressors running backwards. Voltage detection monitors power supply voltage to assure proper voltage. If voltage is not correct (over/under voltage conditions) the unit will not start and an alarm code is reported to the unit controller. NOTE - Phase/voltage detection is furnished when the MSAV (Multi-Stage Air Volume) option is ordered. Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 6

I J FEATURES AND BENEFITS ELECTRICAL (continued) Options/Accessories Factory Installed SCR (Silicon Controlled Rectifier) Electric Heat Control The SCR Electric Heat Control modulates small, precise increments of power to the electric heat load eliminating temperature fluctuations associated with mechanical controls. Almost instantaneous operation with no moving parts. Zero-Cross (fast cycling) feature improves electric heater life with less contraction and expansion of the heating elements. The SCR operates when there is no call for heat from the building control system or thermostat. SCR air tempering is controlled by a secondary thermostat and remote duct sensor (ordered separately). A call for heat overrides the SCR and modulates the SCR to 00% heat output. A call for cooling overrides the SCR. NOTE - The SCR option is not available with 5 kw and 60 kw electric heat (208/230V) models. NOTE - Blower Proving Switch is required and must be ordered separately for factory installation. See Controls in the Options/ Accessories table. NOTE - Available for use with conventional thermostat controls or Novar control systems only. Factory or Field Installed Disconnect Switch Accessible from outside of unit, spring loaded weatherproof cover furnished. Electric Heat Helix wound nichrome elements, individual element limit controls, wiring harness. Unit fuse block is furnished as standard. See Options / Accessories tables for ordering information. GFI Service Outlets (2) 5V ground fault circuit interrupter (GFCI) type, non-powered, field-wired. K Field Installed GFI Weatherproof Cover Single-gang cover. Heavy-duty UV-resistant polycarbonate case construction. Hinged base cover with gasket. INDOOR AIR QUALITY Air Filters Disposable 2-inch filters furnished as standard. Options/Accessories Factory or Field Installed Healthy Climate High Efficiency Air Filters Disposable MERV 8 or MERV 3 (Minimum Efficiency Reporting Value based on ASHRAE 52.2) efficiency 2-inch pleated filters. Healthy Climate UVC Germicidal Lamps Germicidal lamps emit ultra-violet (UV-C) energy, which has been proven to be effective in reducing microbes such as viruses, bacteria, yeasts, and molds. This process either destroys the organism or controls its ability to reproduce. UV-C energy greatly reduces the growth and proliferation of mold and other bioaerosols (bacteria and viruses) on illuminated surfaces (particularly coil and drain pan). Lamps are field installed in the blower/evaporator coil section. All necessary hardware for installation is included. Lamps operate on 208/230V power supply. Step-down transformer must be field supplied when used with 60V and 575V rooftop units. Magnetic safety interlock terminates power when access panels are removed. Approved by ETL. Field Installed Replacement Filter Media Kit With Frame Replaces existing pleated filter media. Includes washable metal mesh screen and metal frame with clip for holding replaceable nonpleated filter. Indoor Air Quality (CO 2 ) Sensors Monitors CO 2 levels, reports to the Prodigy 2.0 unit controller which adjusts economizer dampers as needed. Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 7

L PRODIGY CONTROL SYSTEM PRODIGY 2.0 UNIT CONTROLLER The Prodigy 2.0 unit controller is a microprocessor-based controller that provides flexible control of all unit functions. Features: LCD Display - Easy to read menu with buttons for menu navigation during setup and diagnostics. lines x 20 character display. Menu LEDs - Four LEDs (Data, Setup, Service, Settings) aid in menu navigation. Main Menu and Help Buttons - Quick navigation to home screen and built-in help functions. Scroll, Value Adjustment Select and Save Buttons Simplified Setup Procedure - SETUP menu insures proper installation and setup of the rooftop unit. Profile Setup - Copy key settings between units with the same configuration greatly reducing setup time. USB Port - Allows a technician to download and transfer unit information to help verify service was performed. USB drive will also allow updating software on the Prodigy 2.0 Control System to obtain enhanced functionality without the need to change components. Unit Controller Software Unit Self-Test - Unit Controller can perform a rooftop unit self-test to verify individual critical component and system performance. Included is an economizer test function that helps assure the economizer is operating correctly. Time Clock with Run-time Information Built-In Functions Include: Adjustable Blower On/Off Delay Built-in Control Parameter Defaults Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 8 Compressor Time-Off Delay DDC Compatible Dirty Filter Switch Input Discharge Air Temperature Control Display/Sensor Readout Economizer Control Options - See Economizer / Outdoor Air / Exhaust Options. Fresh Air Tempering Extensive Unit Diagnostics - Over 00 diagnostic and status messages in English. Exhaust Fan Control Modes - Fresh air damper position. Permanent Diagnostic Code Storage Field Adjustable Control Parameters - Over 200 different control settings. Indoor Air Quality Input - Demand Control Ventilation ready Low Ambient Controls - Cooling operation down to 0 F. Gas Valve Time Delay Between First and Second Stage Minimum Compressor Run Time Network Capable - Can be daisy chained to other units or controls. Night Setback Mode Return Air Temperature Limit Control Safety Switch Input - Allows Controller to respond to a external safety switch trip. Service Relay Output Smoke Alarm Mode - Four choices (unit off, positive pressure, negative pressure, purge). Staging - Up to 2 heat/2 cool (standard Prodigy 2.0 unit controller thermostat input). Up to 3 cool with additional relay. Up to cool with room sensor or network operation. Strike Three Protection Gas Reheat Control - Simultaneous heating and cooling operation for controlling humidity NOTE - Prodigy Control System features shown vary with the type of rooftop unit the control is installed in. NOTE - See separate Prodigy Control System Product Specifications Bulletin for additional information. for process air applications such as supermarkets. On Demand Dehumidification - Monitors and controls condenser hot gas reheat operation with Humiditrol dehumidification option. Thermostat Bounce Delay Warm Up Mode Delay LED Indicators PC Interface - Connect to the Prodigy 2.0 unit controller from a PC with the Lennox Unit Controller Software. Room Sensor Operation - Controls temperature. Options / Accessories Factory or Field Installed Blower Proving Switch Monitors blower operation, shuts down unit if blower fails. Dirty Filter Switch Senses static pressure increase indicating dirty filter condition. Controls Options Factory or Field Installed Fresh Air Tempering Used in applications with high outside air requirements. The Controller energizes the first stage heat as needed to maintain a minimum supply air temperature for comfort, regardless of the thermostat demand. When ordered as a factory option, the sensor ships with the unit but must be field installed. Smoke Detector Photoelectric type, installed in supply air section, return air section or both sections. Available with power board and single sensor (supply or return) or power board and two sensors (supply and return). Power board located in unit control compartment. Interoperability via BACnet or LonTalk Protocols Communication compatible with third-party automation systems that support the BACnet Application Specific Controller device profile, LonMark Space Comfort Controller functional profile, or LonMark Discharge Air Controller functional profile.

OPTIONS / ACCESSORIES M Controls Options (continued) Commercial Control Systems L Connection Network Control System Complete building automation control system for single or multi-zone applications. Options include local interface, software for local or remote communication, and hardware for networking other control functions. See L Connection Network Control System Product Specifications Bulletin for details. Aftermarket DDC Novar Unit Controller and options. Thermostats Control system and thermostat options. Aftermarket unit controller options. Field Installed General Purpose Control Kit Plug-in control provides additional analog and digital inputs/outputs for field installed options. Humidity Sensor Kit Humidity sensor required with factory installed Humiditrol dehumidification option or Supermarket reheat field selectable option. ECONOMIZER OPTIONS Standard and High Performance Models available. Economizer operation is set and controlled by the Prodigy 2.0 unit controller. Simple plug-in connections from economizer to unit controller for easy installation. All Energence rooftop units are equipped with factory installed CEC Title 2 approved sensors for outside, return and discharge air temperature monitoring. Optional sensors may be used instead of unit sensors to determine whether outdoor air is suitable for free cooling. See Options/Accessories table. N Factory or Field Installed Economizer (Standard and High Performance Common Features) Downflow or Horizontal with Outdoor Air Hood. Outdoor Air Hood is included when economizer is factory installed and is furnished with economizer when ordered for field installation. Downflow Barometric Relief Dampers with Exhaust Hood is also furnished. Standard Economizer Features (Not for Title 2) Gear-driven action, return air and outdoor air dampers, plugin connections to unit, nylon bearings, neoprene seals, 2-volt, fully-modulating spring return motor. NOTE: The Free Cooling default setting for outdoor air temperature sensor is 55 F. High Performance Economizer Features Approved for California Title 2 building standards. Low leakage dampers are Air Movement and Control Association International (AMCA) Class A Certified - Maximum 3 CFM per sq. ft. leakage at in. w.g. ASHRAE 90.-200 compliant. Gear-driven action, high torque 2-volt fully-modulating spring return damper motor, return air and outdoor air dampers, plug-in connections to unit, stainless steel bearings, enhanced neoprene blade edge seals and flexible stainless steel jamb seals to minimize air leakage. NOTE - High Performance Economizers are not approved for use with enthalpy controls in Title 2 applications. NOTE - The Free Cooling setpoint for Title 2 applications must be set based on the Climate Zone where the system is installed. See Section 0. Prescriptive Requirements for Space Conditioning Systems of the California Energy Commission s 203 Building Energy Efficiency Standards. Refer to Installation Instructions for complete setup information. Differential Sensible Control Factory setting. Uses outdoor air and return air sensors that are furnished with the unit. The Prodigy 2.0 unit controller compares outdoor air temperature with return air. When the outdoor air is below the configured setpoint and cooler than return air, the controller activates the economizer. NOTE - Differential Sensible Control can be configured in the field to provide Offset Differential Sensible Control or Single Sensible Control. In Offset Differential Sensible Control mode, the economizer is enabled if the temperature differential (offset) between outdoor air and return air reaches the configured setpoint. In Single Sensible Control mode, the economizer is enabled when outdoor air temperature falls below the configured setpoint. Global Control The unit controller communicates with a DDC system with one global sensor (enthalpy or sensible) to determine whether outside air is suitable for free cooling on all units connected to the control system. Sensor must be field provided. NOTE - Global control with enthalpy is not approved for Title 2 applications. Factory or Field Installed Single Enthalpy Temperature Control (Not for Title 2) Outdoor air enthalpy sensor enables Economizer if the outdoor enthalpy is less than the setpoint of the control. Differential Enthalpy Control (Not for Title 2) Order two Single Enthalpy Controls. One is field installed in the return air section, the other in the outdoor air section. Allows the economizer control to select between outdoor air or return air, whichever has lower enthalpy. Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 9

OPTIONS / ACCESSORIES ECONOMIZER OPTIONS (continued) Field Installed Outdoor Air CFM Control Maintains constant outdoor air volume levels on the supply air fan and varying unit airflows. Using information from a velocity sensor located in the rooftop unit outdoor air section, the Prodigy 2.0 unit controller changes the economizer position to help minimize the effect of supply fan speed changes on outdoor air volume levels. Setpoint for outdoor air volume is established by field testing. NOTE - Not available with Demand Control Ventilation (CO 2 Sensor) or Building Pressure Control. Building Pressure Control Maintains constant building pressure level. Using information from a differential pressure between the outdoor air and the building air, the Prodigy 2.0 unit controller changes the economizer position to help maintain a constant building pressure. NOTE - Not available with Demand Control Ventilation (CO 2 Sensor) or Outdoor Air CFM Control. EXHAUST OPTIONS Factory or Field Installed Power Exhaust Fans Installs internal to unit for downflow applications only with Economizer option. Provides exhaust air pressure relief. Interlocked to run when supply air blower is operating, fans run when outdoor air dampers are 50% open (adjustable), motor is overload protected. Requires Economizer and Downflow Barometric Relief Dampers. Fan is 20 in. diameter with 5 blades (KPWRE0B) with/3 hp motor. Field Installed Horizontal Low Profile Barometric Relief Dampers For use when unit is configured for horizontal applications requiring an economizer. Allows relief of excess air Aluminum blade dampers prevent blow back and outdoor air infiltration during off cycle. Field installed in return air duct. Bird screen and exhaust hood furnished. Requires Horizontal Discharge Kit. OUTDOOR AIR OPTIONS Factory or Field Installed Outdoor Air Damper - Downflow or Horizontal With Air Hood Linked mechanical dampers, 0 to 25% (fixed) outdoor air adjustable, installs in unit. Includes outdoor air hood. Automatic model features fully modulating spring return damper motor with plug-in connection. Manual model features a slide damper. Maximum mixed air temperature in cooling mode: 00 F. ROOF CURBS Nailer strip furnished, mates to unit, US National Roofing Contractors Approved, shipped knocked down. Hybrid Roof Curbs, Downflow Roof curb can be assembled using interlocking tabs to fasten corners together. No tools required. Curb can also be fastened together with furnished hardware. Available in 8,, 8, and 2 inch heights. See Options/Accessories table. Adjustable Pitch Curb Fully adjustable pitch curbs (3/ in. per foot in any direction) provide a level platform for rooftop units allowing flexible installations on roofs with uneven or sloped angles. Uses interlocking tabs to fasten corners together. No tools required. Hardware is furnished to connect upper curb with lower curb. Available in inch height. Adaptor Curbs (not shown) Curbs are regionally sourced. Dimensions will vary based upon the source. Contact your local sales representative for a detailed cut sheet with applicable dimensions. CEILING DIFFUSERS Ceiling Diffusers (Flush or Step-Down) Diffuser face and grilles with white powder coat finish, insulated (UL listed duct liner), diffuser box with collars for duct connection, fixed blades (flush diffusers) and double deflection blades (stepdown diffusers), provisions for suspending, internally sealed (prevents recirculation), removable return air grille, adapts to T-bar ceiling grids or plaster ceilings. Transitions (Supply and Return) Used with diffusers, installs in roof curb, galvanized steel construction, flanges furnished for duct connection to diffusers, fully insulated. Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 0

OPTIONS / ACCESSORIES HUMIDITROL DEHUMIDIFICATION SYSTEM Factory installed option designed to control humidity. Provides dehumidification on demand using ASHRAE 90. recommended method for comfort conditioning humidity control. Unit comes equipped with one row reheat coil, solenoid valve and humidity controller. In addition to a thermostat or room sensor used for conventional operation, a humidity sensor is required and must be located in the occupied space. Remote Mounted Humidity Sensor Kit is required for field installation. The humidity sensor provides input to the Unit Controller which is used to control activation of the dehumidification operation. Reheat controls are located in the compressor control section of the unit for easy access. Benefits Improves indoor air quality. Helps prevents damage due to high humidity levels. Improves comfort levels by reducing space humidity levels. OPERATION No Dehumidification Demand The unit will operate conventionally whenever there is a demand for cooling or heating and no dehumidification demand. Free cooling is only permitted when there is no demand for dehumidification. Dehumidification Demand Only The Unit Controller is factory set at 60% relative humidity setpoint and can be adjusted at the Unit Controller or with optional Unit Controller Software. For L Connection Network Control Panel (NCP) applications, the humidity setpoint can be adjusted at the NCP. Reheat operation will initiate on a dehumidification demand and does not require a cooling demand. REFRIGERANT SCHEMATIC The unit will operate in the dehumidification mode until the relative humidity of the conditioned space is below the setpoint. The reheat coil is sized to provide 68 F to 75 F supply air during reheat operation. This reduces sensible cooling capacity and extends compressor run time to control humidity when the cooling load is low. A solenoid valve diverts hot gas from the compressor to the reheat coil. The cooled and dehumidified air from the evaporator is reheated as it passes through the reheat coil. The de-superheated and partially condensed refrigerant continues to the outdoor condenser coil where condensing is completed. The unit will continue to operate in this mode until the dehumidification demand is satisfied. See Sequence of Operation for additional information. Dehumidification and Cooling Demand (Thermostat/Room Sensor Application) If both a dehumidification and a full cooling load demand occur, the system will operate in cooling until the cooling demand is satisfied. Then the system will energize the dehumidification mode. Options / Accessories REHEAT COIL EVAPORATOR COIL CONDENSER COIL Humidity Sensor Kit Remote Mounted Humidity sensor required with factory installed Humiditrol Dehumidification Option or Supermarket reheat field selectable option. REFRIGERANT CIRCUIT REFRIGERANT CIRCUIT 2 REHEAT VALVE CHECK VALVE EXPANSION VALVES Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page

SEQUENCE OF OPERATION - MSAV (MULTI-STAGE AIR VOLUME) MODELS Objective: Outline the unit functions as a result of room thermostat or zone sensor demands. Given: When economizer is present, it will function as an integral part of the unit cooling system. When not present, unit will function as if economizer is present but outdoor ambient is high and sensed as not suitable. UNIT OPERATION WITH 2-STAGE THERMOSTAT (2 COOL AND 2 HEAT STAGES, Y, Y2, W, W2) SUPPLY AIR BLOWER SPEED Unit has following supply air blower speed setting: Ventilation speed Cooling Speed - Low Cooling Speed - High Heating speed Smoke speed (Used only in smoke removal option - not discussed) UNIT FEATURES AN ECONOMIZER AND OUTDOOR AIR IS SUITABLE Cooling - Thermostat Mode (Y, Y2) Y Demand: All compressors are off, supply air blower is on low cooling speed to minimize blower power consumption, economizer modulates (minimum to maximum open position) to maintain 55 F supply air temperature (default unit controller setting). Y2 Demand: All compressors are off, supply air blower is on high cooling speed providing higher cooling capacity, and economizer modulates to maintain 55 F supply air temperature. If economizer stays at maximum open for 3 minutes, compressor is energized while supply air blower stays on high cooling speed providing maximum cooling capacity. Outdoor air suitability is determined by the energy state of outdoor ambient (enthalpy or sensible) and its ability to achieve the desired free cooling effects. Outdoor air suitability can also be determined by a third party controller and provided to the rooftop unit via a network connection. UNIT DOES NOT FEATURE AN ECONOMIZER OR OUTDOOR AIR IS NOT SUITABLE Y Demand: Compressor operates and supply air blower operates at low cooling speed. Y2 Demand: All compressors operate and supply air blower operates at high cooling speed. DEHUMIDIFICATION MODE If a unit with Humiditrol Dehumidification Option receives a call for dehumidification, economizer free cooling is locked out. Call For Dehumidification, No Y, Y2 demand: st stage compressor operates, supply air blower operates at high cooling speed, and the reheat valve is energized. Y Demand With A Call For Dehumidification: All compressors operate, supply air blower operates at high cooling speed and the reheat valve is energized. Y2 Demand With A Call For Dehumidification: All compressors operate, supply air blower operates at high cooling speed, and the reheat valve is de-energized. Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 2

SEQUENCE OF OPERATION - MSAV (MULTI-STAGE AIR VOLUME) MODELS UNIT OPERATION WITH 3-STAGE THERMOSTAT OR ZONE SENSOR (3 COOL AND 2 HEAT STAGES, Y, Y2, Y3 AND W, W2) SUPPLY AIR BLOWER SPEED Unit has following supply air blower speed setting: Ventilation speed Cooling Speed - Low Cooling Speed - High Heating speed Smoke speed (Used only in smoke removal option - not discussed) UNIT FEATURES AN ECONOMIZER AND OUTDOOR AIR IS SUITABLE Cooling - Thermostat or Zone Sensor Mode (Y, Y2, Y3) Y Demand: All compressors are off, supply air blower is on low cooling speed to minimize blower power consumption, economizer modulates (minimum to maximum open position) to maintain 55 F supply air temperature (default unit controller setting). Y2 Demand: All compressors are off, supply air blower is on high cooling speed providing higher cooling capacity, and economizer modulates to maintain 55 F supply air temperature. If economizer stays at maximum open for 3 minutes, compressor is energized while supply air blower stays on high cooling speed providing maximum cooling capacity. After compressors are energized the economizer stays at maximum open. Y3 Demand: Compressors and 2 are energized while supply air blower stays on high cooling speed. Outdoor air suitability is determined by the energy state of outdoor ambient (enthalpy or sensible) and its ability to achieve the desired free cooling effects. Outdoor air suitability can also be determined by a third party controller and provided to the rooftop unit via a network connection. UNIT DOES NOT FEATURE AN ECONOMIZER OR OUTDOOR AIR IS NOT SUITABLE Y Demand: Compressor operates and supply air blower operates at low cooling speed. Y2 or Y3 Demand: All compressors operate and supply air blower operates at high cooling speed. DEHUMIDIFICATION MODE If a unit with Humiditrol Dehumidification Option receives a call for dehumidification, economizer free cooling is locked out. Call For Dehumidification, No Y, Y2 demand: st stage compressor operates, supply air blower operates at high cooling speed, and the reheat valve is energized. Y Demand With A Call For Dehumidification: All compressors operate, supply air blower operates at high cooling speed and the reheat valve is energized. Y2 Or Y3 Demand With A Call For Dehumidification: All compressors operate, supply air blower operates at high cooling speed, and the reheat valve is de-energized. Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 3

SEQUENCE OF OPERATION - MSAV (MULTI-STAGE AIR VOLUME) MODELS HEATING MODE (ELECTRIC HEAT) NOTE - HEATING MODE IS THE SAME FOR ALL CONTROL OPTIONS W Demand: st stage electric heat is energized and the supply air blower operates at heating speed. W2 Demand: 2nd stage electric heat is energized and the supply air blower operates at heating speed (5 or 60 kw electric heat option only). MODULATING OUTDOOR AIR DAMPER The minimum damper position for occupied low blower and occupied high blower is adjusted during unit setup to provide minimum fresh air requirements per ASHRAE 62. at the corresponding supply air blower speeds. When supply air blower is off or the unit is in unoccupied mode, the outdoor air damper is closed. When unit is in occupied mode and supply air blower is operating at a speed below the midpoint blower speed, the outdoor air damper is at minimum low blower position. When unit is in occupied mode and supply air blower is operating at a speed equal to or above the midpoint blower speed, the outdoor air damper is at minimum high blower position. NOTE - The midpoint blower speed is an average of the minimum and maximum blower speed (minimum speed + maximum speed divided by 2). POWER EXHAUST OPERATION NOTE - POWER EXHAUST OPERATION IS THE SAME FOR ALL CONTROL OPTIONS Power exhaust blower operates when economizer outdoor air dampers are 50% open (adjustable) and when supply air blower speed is above 70% (adjustable) of full speed. Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page

OPTIONS / ACCESSORIES Item Description COOLING SYSTEM Model Number Catalog Number Unit Model No 092 02 20 50 Condensate Drain Trap PVC - CTRAP20AD2 76W26 OX OX OX OX Copper - CTRAP0AD2 76W27 OX OX OX OX Conventional Fin/Tube Condenser Coil (replaces Environ Coil System) Factory O O O Corrosion Protection Factory O O O O Drain Pan Overflow Switch ESNSR7AD 68W88 OX OX OX OX Refrigerant Type R-0A O O O O Service Valves (not for Environ Coil System or Humiditrol equipped units) Factory O O O O BLOWER - SUPPLY AIR Blower Option CAV (Constant Air Volume) Factory O O O O MSAV (Multi-Stage Air Volume) supply air blower option (With VFD Bypass Control) Factory O O O O MSAV (Multi-Stage Air Volume) supply air blower option (Without VFD Bypass Control) Factory O O O O Motors - Constant Air Volume (CAV) Motors - MSAV Multi-Stage Air Volume supply air Drive Kits See Blower Data Tables for selection Belt Drive (standard efficiency) - 2 hp Factory O O O O Belt Drive (standard or high efficiency) - 3 hp Factory O O O O Belt Drive (standard efficiency) - 5 hp Factory O O O O Belt Drive (standard efficiency) - 2 hp Factory O O O O Belt Drive (standard efficiency) - 3 hp Factory O O O O Belt Drive (standard efficiency) - 5 hp Factory O O O O Kit # 590-890 rpm Factory O O O O Kit #2 800-05 rpm Factory O O O O Kit #3 795-95 rpm Factory O O O O Kit # 730-970 rpm Factory O O O O Kit #5 90-200 rpm Factory O O O O Kit #6 05-300 rpm Factory O O O O Kit #7 730-970 rpm Factory O O O O Kit #8 90-200 rpm Factory O O O O Kit #9 05-300 rpm Factory O O O O Kit #0 900-35 rpm Factory O O O O Kit # 00-35 rpm Factory O O O O Kit #2 25-25 rpm Factory O O O O Blower Belt Auto-Tensioner Factory O O O O CABINET Combination Coil/ Hail Guards Furnished Environ Coil System - CGARD52B- 3T05 X X X Optional Conventional Fin/Tube Condenser Coil - EGARD5B- 3T0 X X X Furnished Conventional Fin/Tube Condenser Coil System - CGARD52B- 3T05 X Horizontal Discharge Kit KHECK00B- 5W25 X X X X Return Air Adaptor Plate (for LC/LG/LH and TC/TG/TH unit replacement) CCONV0B- 5W96 OX OX OX OX NOTE - Catalog and model numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 5

OPTIONS / ACCESSORIES Item Description CONTROLS Model Number Catalog Number Unit Model No 092 02 20 50 Blower Proving Switch CSNSR35FF 53W65 OX OX OX OX Commercial Controls Prodigy Control System - BACnet Module - C0CTRL60AEL 59W5 OX OX OX OX Prodigy Control System - LonTalk Module - C0CTRL65FF 5W27 OX OX OX OX Novar ETM-205 - E0CTRL30B 6W73 OX OX OX OX Novar LSE Factory O O O O L Connection Building Automation System - - - X X X X Dirty Filter Switch ESNSR55B- 53W67 OX OX OX OX General Purpose Control Kit EGPBK30C 3J78 X X X X Fresh Air Tempering CSNSR75AD 58W63 OX OX OX OX Smoke Detector - Supply or Return (Power board and one sensor) CSNSRB-2 K76 OX OX OX OX Smoke Detector - Supply and Return (Power board and two sensors) CSNSR3B-2 K80 OX OX OX OX INDOOR AIR QUALITY Air Filters Healthy Climate High Efficiency Air Filters 20 x 25 x 2 in. (Order per unit) Replacement Media Filter With Metal Mesh Frame (includes non-pleated filter media) Indoor Air Quality (CO 2 ) Sensors MERV 8 - CFLTR5B- 50W6 OX OX OX OX MERV 3 - CFLTR0B- 52W OX OX OX OX CFLTR30B-- Y3063 X X X X Sensor - Wall-mount, off-white plastic cover with LCD display C0SNSR50AEL 77N39 X X X X Sensor - Wall-mount, off-white plastic cover, no display C0SNSR52AEL 87N53 X X X X Sensor - Black plastic case with LCD display, rated for plenum mounting Sensor - Wall-mount, black plastic case, no display, rated for plenum mounting C0SNSR5AEL 87N52 X X X X C0MISC9AE 87N5 X X X X CO 2 Sensor Duct Mounting Kit - for downflow applications C0MISC9AE- 85L3 X X X X Aspiration Box - for duct mounting non-plenum rated CO 2 sensors (87N53 or 77N39) UVC Germicidal Lamps C0MISC6AE- 90N3 X X X X Healthy Climate UVC Light Kit (208/230v-ph) CUVCL0B- 5W62 OX OX OX OX HUMIDITROL DEHUMIDIFICATION CONDENSER REHEAT OPTION Humiditrol Dehumidification Option Factory O O O O Humidity Sensor Kit, Remote mounted (required) C0SNSR3AE- 7M50 X X X X ELECTRICAL Voltage 60 hz 208/230V - 3 phase Factory O O O O 60V - 3 phase Factory O O O O 575V - 3 phase Factory O O O O HACR Circuit Breakers Factory O O O O Disconnect Switch - See Electrical/Electric Heat tables for selection 80 amp - CDISC080B- 5W56 OX OX OX OX GFI Service Outlets 50 amp - CDISC50B- 5W57 OX OX OX OX 5 amp non-powered, field-wired (208/230V, 60V only) LTAGFIK0/5 7M70 OX OX OX OX 20 amp non-powered, field-wired (575V only) CGFCI20FF 67E0 OX OX OX OX Weatherproof Cover for GFI CGFCI99FF 0C89 X X X X Phase/Voltage Detection (Optional for CAV options only, furnished with MSAV option) Factory O O O O Lamps operate on 0-230V single-phase power supply. Step-down transformer may be ordered separately for 60V and 575V units. Alternately, 0V power supply may be used to directly power the UVC ballast(s) NOTE - Catalog and model numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 6

OPTIONS / ACCESSORIES Item Description ELECTRIC HEAT Model Number Catalog Number 7.5 kw 208/230V-3ph - CEH0075B-Y 56W38 OX OX 60V-3ph - CEH0075B-G 56W39 OX OX 575V-3ph - CEH0075B-J 56W0 OX OX Unit Model No 092 02 20 50 5 kw 208/230V-3ph - CEH005B-Y 56W OX OX OX OX 60V-3ph - CEH050B-G 56W2 OX OX OX OX 575V-3ph - CEH050B-J 56W3 OX OX OX OX 22.5 kw 208/230V-3ph - CEH0225B-Y 56W OX OX OX OX 60V-3ph - CEH0225B-G 56W5 OX OX OX OX 575V-3ph - CEH0225B-J 56W6 OX OX OX OX 30 kw 208/230V-3ph - CEH0300B-Y 56W7 OX OX OX OX 60V-3ph - CEH0300B-G 56W8 OX OX OX OX 575V-3ph - CEH0300B-J 56W9 OX OX OX OX 5 kw 208/230V-3ph - CEH050B-Y 56W50 OX OX OX OX 60V-3ph - CEH050B-G 56W5 OX OX OX OX 575V-3ph - CEH050B-J 56W52 OX OX OX OX 60 kw 208/230V-3ph - CEH0600B-Y 55W02 OX OX 60V-3ph - CEH0600B-G 55W03 OX OX 575V-3ph - CEH0600B-J 55W0 OX OX SCR (Silicon Controlled Rectifier) Electric Heat Control Factory O O O O Thermostat (required) Y9682 X X X X Duct Sensor (required) Y9683 X X X X ECONOMIZER Standard Economizer (Not for Title 2) Standard Economizer Downflow or Horizontal - Includes Outdoor Air Hood and Downflow Barometric Relief Dampers with Exhaust Hood Order Horizontal Barometric Relief Dampers separately EECON5B-2 3U6 OX OX OX OX High Performance Economizer (Approved for California Title 2 Building Standards / AMCA Class A Certified) High Performance Economizer Downflow or Horizontal - Includes Outdoor Air Hood and Downflow Barometric Relief Dampers with Exhaust Hood Order Horizontal Barometric Relief Dampers separately Horizontal Barometric Relief Dampers EECON7B- 0U59 OX OX OX OX Horizontal Low Profile Barometric Relief Dampers (Exhaust hood furnished) LAGEDH03/5 53K0 X X X X Economizer Controls Differential Enthalpy (Not for Title 2) Order 2 - CSNSR6FF 53W6 OX OX OX OX Sensible Control Sensor is Furnished Factory O O O O Single Enthalpy (Not for Title 2) CSNSR6FF 53W6 OX OX OX OX Building Pressure Control EGPBK20C 3J77 X X X X Outdoor Air CFM Control EGPBK0C 3J76 X X X X Global Control Sensor Field Provided Factory O O O O OUTDOOR AIR Outdoor Air Dampers With Outdoor Air Hood Motorized CDAMP20B- G28 OX OX OX OX Manual CDAMP0B-2 G29 OX OX OX OX POWER EXHAUST Standard Static 208/230V-3ph - KPWRE0B-Y 53W OX OX OX OX NOTE - The SCR option is not available with 5 kw and 60 kw electric heat (208/230V) models. 60V-3ph - KPWRE0B-G 53W5 OX OX OX OX 575V-3ph - KPWRE0B-J 53W6 OX OX OX OX NOTE - Catalog and model numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 7

OPTIONS / ACCESSORIES Item Description ROOF CURBS Hybrid Roof Curbs, Downflow Model Number Catalog Number Unit Model No 092 02 20 50 8 in. height CCURB70B- F5 X X X X in. height CCURB7B- F55 X X X X 8 in. height CCURB72B- F56 X X X X 2 in. height CCURB73B- F57 X X X X Adjustable Pitch Curb in. height CCURB55B- 5W50 X X X X CEILING DIFFUSERS Step-Down - Order one RTD-95S 3K6 X RTD-35S 3K62 X X RTD-85S 3K63 X Flush - Order one FD-95S 3K56 X FD-35S 3K57 X X FD-85S 3K58 X Transitions (Supply and Return) - Order one CDIFF30B- 2X65 X NOTE - Catalog and model numbers shown are for ordering field installed accessories. OX - Configure To Order (Factory Installed) or Field Installed O = Configure To Order (Factory Installed) X = Field Installed CDIFF3B- 2X66 X X CDIFF32B- 2X67 X Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 8

SPECIFICATIONS General Data Nominal Tonnage 7.5 Ton 7.5 Ton 8.5 Ton 8.5 Ton Model Number LCH092HB LCH092HM LCH02HB LCH02HM Efficiency Type High High High High Blower Type Constant Air MSAV (Multi- Constant Air MSAV (Multi- Volume (CAV) Stage Air Volume) Volume (CAV) Stage Air Volume) Cooling Gross Cooling Capacity - Btuh 93,000 93,000 03,800 03,800 Performance Net Cooling Capacity - Btuh 90,000 90,000 00,000 00,000 AHRI Rated Air Flow - cfm 3000 2800 300 300 Unit Power - kw 7.5 7.5 8. 8. EER (Btuh/Watt) 2.7 2.7 2. 2. 2 IEER (Btuh/Watt) 3.0.0 2.9.0 AHRI Reference No. 2020890 202090508 20208905 202090507 Refrigerant Charge Refrigerant Type R-0A R-0A R-0A R-0A Environ Coil System Circuit 6 lbs. 3 oz. 6 lbs. 3 oz. 6 lbs. 8 oz. 6 lbs. 8 oz. Circuit 2 7 lbs. 2 oz. 7 lbs. 2 oz. 6 lbs. 5 oz. 6 lbs. 5 oz. Environ Coil System Circuit 6 lbs. 3 oz. 6 lbs. 3 oz. 6 lbs. 8 oz. 6 lbs. 8 oz. with Humiditrol Circuit 2 7 lbs. 2 oz. 7 lbs. 2 oz. 6 lbs. 5 oz. 6 lbs. 5 oz. Conventional Fin/Tube Circuit 2 lbs. oz. 2 lbs. oz. 3 lbs. 8 oz. 3 lbs. 8 oz. Coil Option Circuit 2 lbs. 3 oz. lbs. 3 oz. 2 lbs. 7 oz. 2 lbs. 7 oz. Conventional Fin/Tube Circuit 6 lbs. 6 oz. 6 lbs. 6 oz. 7 lbs. 0 oz. 7 lbs. 0 oz. With Humiditrol Circuit 2 lbs. 3 oz. lbs. 3 oz. 2 lbs. 7 oz. 2 lbs. 7 oz. Electric Heat Available - See page 7 7.5, 5, 22.5, 30 & 5 kw Compressor Type (number) Scroll (2) Scroll (2) Scroll (2) Scroll (2) Outdoor Coils Net face area (total) - sq. ft. 28.0 (29.33) 28.0 (29.33) 28.0 (29.33) 28.0 (29.33) Environ Number of rows (3) (3) (3) (3) (Fin/Tube) Fins per inch 20 (20) 20 (20) 20 (20) 20 (20) Outdoor Coil Fans Indoor Coil 3 Indoor Blower and Drive Selection Motor - (No.) hp (2) /3 (2) /3 (2) /3 (2) /3 Motor rpm 075 075 075 075 Motor watts 800 800 800 800 Diameter - (No.) in. (2) 2 (2) 2 (2) 2 (2) 2 Number of blades 3 3 3 3 Air volume - cfm 8800 8800 8800 8800 Net face area (total) - sq. ft. 2.78 2.78 2.78 2.78 Tube diameter - in. 3/8 3/8 3/8 3/8 Number of rows Fins per inch Drain connection - Number and size Expansion device type Nominal motor output Maximum usable motor output (US Only) Motor - Drive kit number () in. NPT coupling Balance port TXV, removable head 2 hp, 3 hp, 5 hp 2.3 hp, 3.5 hp, 5.75 hp 2 hp Kit 590-890 rpm (std. and high efficiency) Kit 2 800-05 rpm (std. and high efficiency) Kit 3 795-95 rpm (std. and high efficiency) 3 hp Kit 730-970 rpm (std. efficiency) Kit 5 90-200 rpm (std. efficiency) Kit 6 05-300 rpm (std. efficiency) Kit 7 730-970 rpm (high efficiency) Kit 8 90-200 rpm (high efficiency) Kit 9 05-300 rpm (high efficiency) 5 hp Kit 0 900-35 rpm (std. efficiency) Kit 00-35 rpm (std. efficiency) Kit 2 25-25 rpm (std. efficiency) Blower wheel nominal diameter x width - in. () 5 X 5 () 5 X 5 () 5 X 5 () 5 X 5 Filters Type of filter Disposable Number and size - in. () 20 x 25 x 2 Electrical characteristics 208/230V, 60V or 575V - 60 hertz - 3 phase NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction. AHRI Certified to AHRI Standard 30/360; 95 F outdoor air temperature and 80 F db/67 F wb entering evaporator air; minimum external duct static pressure. 2 Integrated Energy Efficiency Ratio certified and tested according to AHRI Standard 30/360. 3 Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate. NOTE Units equipped with MSAV (Multi-Stage Air Volume) option are limited to a motor service factor of.0. Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 9

SPECIFICATIONS General Data Nominal Tonnage 0 Ton 0 Ton 2.5 Ton 2.5 Ton Model Number LCH20HB LCH20HM LCH50HB LCH50HM Efficiency Type High High High High Blower Type Constant Air MSAV (Multi- Constant Air MSAV (Multi- Volume (CAV) Stage Air Volume) Volume (CAV) Cooling Gross Cooling Capacity - Btuh 22,000 22,000 8,000 8,000 Performance Net Cooling Capacity - Btuh 8,000 8,000 2,000 2,000 AHRI Rated Air Flow - cfm 3600 3300 3950 3950 Unit Power - kw 9.9 9.8 2.9 2.9 EER (Btuh/Watt) 2.2 2.2.0.0 2 IEER (Btuh/Watt) 3.2.0 2. 3.5 AHRI Reference No. 202088988 2020909 056990 0569906 Refrigerant Charge Stage Air Volume) Refrigerant Type R-0A R-0A R-0A R-0A Environ Coil System Circuit 7 lbs. oz. 7 lbs. oz. - - - - - - Circuit 2 7 lbs. 8 oz. 7 lbs. 8 oz. - - - - - - Environ Coil System Circuit 7 lbs. oz. 7 lbs. oz. - - - - - - with Humiditrol Circuit 2 7 lbs. 8 oz. 7 lbs. 8 oz. - - - - - - Conventional Fin/Tube Circuit lbs. 8 oz. lbs. 8 oz. 2 lbs. 8 oz. 2 lbs. 8 oz. Coil Option Circuit 2 3 lbs. 8 oz. 3 lbs. 8 oz. 0 lbs. 2 oz. 0 lbs. 2 oz. Conventional Fin/Tube Circuit 8 lbs. 0 oz. 8 lbs. 0 oz. 2 lbs. 9 oz. 2 lbs. 9 oz. with Humiditrol Circuit 2 3 lbs. 8 oz. 3 lbs. 8 oz. 2 lbs. 3 oz. 2 lbs. 3 oz. Electric Heat Available - See page 7 5, 22.5, 30, 5 & 60 kw Compressor Type (number) Scroll (2) Scroll (2) Scroll (2) Scroll (2) Outdoor Coils Net face area (total) - sq. ft. 28.0 (29.33) 28.0 (29.33) - - - (25.9) - - - (25.9) Environ Number of rows (3) (3) 3 3 (Fin/Tube) Fins per inch 20 (20) 20 (20) 20 20 Outdoor Coil Fans Indoor Coil 3 Indoor Blower and Drive Selection Motor - (No.) hp (2) /3 (2) /3 (2) /2 (2) /2 Motor rpm 075 075 075/600 075/600 Motor watts 800 800 050 050 Diameter - (No.) in. (2) 2 (2) 2 (2) 2 (2) 2 Number of blades 3 3 3 3 Air volume - cfm 8800 8800 9700 9700 Net face area (total) - sq. ft. 3.5 3.5 3.5 3.5 Tube diameter - in. 3/8 3/8 3/8 3/8 Number of rows Fins per inch Drain connection - Number and size Expansion device type Nominal motor output Maximum usable motor output (US Only) Motor - Drive kit number () in. NPT coupling Balance port TXV, removable head 2 hp, 3 hp, 5 hp 2.3 hp, 3.5 hp, 5.75 hp 2 hp Kit 590-890 rpm (std. and high efficiency) Kit 2 800-05 rpm (std. and high efficiency) Kit 3 795-95 rpm (std. and high efficiency) 3 hp Kit 730-970 rpm (std. efficiency) Kit 5 90-200 rpm (std. efficiency) Kit 6 05-300 rpm (std. efficiency) Kit 7 730-970 rpm (high efficiency) Kit 8 90-200 rpm (high efficiency) Kit 9 05-300 rpm (high efficiency) 5 hp Kit 0 900-35 rpm (std. efficiency) Kit 00-35 rpm (std. efficiency) Kit 2 25-25 rpm (std. efficiency) Blower wheel nominal diameter x width - in. () 5 X 5 () 5 X 5 () 5 X 5 () 5 X 5 Filters Type of filter Disposable Number and size - in. () 20 x 25 x 2 Electrical characteristics 208/230V, 60V or 575V - 60 hertz - 3 phase NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction. AHRI Certified to AHRI Standard 30/360; 95 F outdoor air temperature and 80 F db/67 F wb entering evaporator air; minimum external duct static pressure. 2 Integrated Energy Efficiency Ratio certified and tested according to AHRI Standard 30/360. 3 Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate. NOTE Units equipped with MSAV (Multi-Stage Air Volume) option are limited to a motor service factor of.0. Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 20

RATINGS NOTE For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section. 7.5 TON HIGH EFFICIENCY LCH092HB (ST STAGE) - CONSTANT AIR VOLUME Outdoor Air Temperature Entering Outdoor Coil Entering 65 F 75 F 85 F 95 F Wet Air Comp. Sensible To Comp. Sensible To Comp. Sensible To Comp. Sensible To Bulb Volume Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Temperature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb cfm kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F 200 8.6.95 0.63 0.76 0.93 6.8 2.2 0.6 0.78 0.95.9 2.9 0.65 0.80 0.98 2.9 2.8 0.66 0.83.00 63 F 3000 5.0.96 0.67 0.85.00 9. 2.22 0.68 0.88.00 7.2 2.50 0.70 0.90.00 5.0 2.82 0.72 0.9.00 3600 52.9.97 0.72 0.95.00 50.9 2.22 0.7 0.97.00 8.9 2.50 0.76 0.99.00 6.7 2.82 0.79.00.00 200 5.3.96 0.50 0.6 0.72 9.5 2.22 0.5 0.62 0.73 7.6 2.50 0.5 0.63 0.76 5.5 2.82 0.52 0.6 0.78 67 F 3000 53.9.97 0.53 0.65 0.80 5.9 2.22 0.53 0.66 0.83 9.7 2.50 0.55 0.67 0.86 7.7 2.82 0.56 0.69 0.89 3600 55.9.98 0.55 0.70 0.90 53.7 2.23 0.56 0.7 0.93 5.5 2.5 0.57 0.7 0.96 8.9 2.83 0.58 0.76 0.99 200 5..97 0.39 0.9 0.59 52.2 2.22 0.39 0.9 0.60 50.2 2.50 0.39 0.5 0.60 8.0 2.82 0.39 0.5 0.6 7 F 3000 56.8.98 0.39 0.5 0.63 5.7 2.23 0.0 0.52 0.6 52. 2.5 0.0 0.53 0.65 50. 2.83 0. 0.55 0.67 3600 58.6.99 0. 0.5 0.67 56.5 2.2 0. 0.55 0.69 5. 2.5 0.2 0.56 0.7 5.5 2.83 0.2 0.57 0.73 7.5 TON HIGH EFFICIENCY LCH092HB (2ND STAGE) - CONSTANT AIR VOLUME Outdoor Air Temperature Entering Outdoor Coil Entering 85 F 95 F 05 F 5 F Wet Air Comp. Sensible To Comp. Sensible To Comp. Sensible To Comp. Sensible To Bulb Volume Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Temperature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb cfm kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F 200 87.9 5.9.69.83.98 8.0 5.86.70.85.00 79.8 6.6.72.88.00 75.2 7.55.7.92.00 63 F 3000 92.3 5.20.7.92.00 88.0 5.87.76.95.00 83.5 6.6.78.98.00 78.7 7.5.8.00.00 3600 95.6 5.2.79.00.00 9. 5.87.82.00.00 87.3 6.6.85.00.00 82.9 7.55.88.00.00 200 93.0 5.20.55.66.79 89.0 5.87.55.68.8 8.5 6.6.56.69.8 79.5 7.5.58.7.87 67 F 3000 97.3 5.2.58.7.88 93.0 5.88.59.73.9 88.2 6.65.60.76.9 82.8 7.5.6.78.98 3600 00.6 5.22.6.77.97 95.7 5.88.62.79.99 90.8 6.65.63.82.00 85.2 7.5.6.86.00 200 98.2 5.2.2.53.6 93.8 5.88.2.5.65 89.0 6.65.2.5.67 8.2 7.5.3.56.69 7 F 3000 02.5 5.23.3.56.69 97.9 5.89.3.58.7 92.9 6.65..59.73 87.5 7.5..60.76 3600 05.9 5.2..60.75 00.8 5.89.5.6.77 95. 6.65.5.62.79 89.9 7.5.6.6.8 8.5 TON HIGH EFFICIENCY LCH02HB (ST STAGE) - CONSTANT AIR VOLUME Outdoor Air Temperature Entering Outdoor Coil Entering 65 F 75 F 85 F 95 F Wet Air Comp. Sensible To Comp. Sensible To Comp. Sensible To Comp. Sensible To Bulb Volume Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Temperature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb cfm kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F 2720 52.3 2.3.62.76.96 50. 2..63.78.98 8. 2.73.6.8.00 6.3 3.08.65.8.00 63 F 300 5.8 2..66.87.00 52.7 2.2.67.90.00 50.6 2.73.69.93.00 8. 3.09.7.97.00 080 56.6 2.5.72.97.00 5.6 2.3.7.99.00 52. 2.7.77.00.00 50.3 3.09.80.00.00 2720 55.2 2..9.60.7 53.2 2.2.50.6.73 5.2 2.73.50.62.76 8.7 3.09.50.63.79 67 F 300 57.7 2.5.52.6.82 55.6 2.3.52.65.8 53.3 2.7.5.67.88 50.9 3.09.55.68.92 080 59.7 2.6.55.69.93 57. 2..56.7.96 5.9 2.7.56.73.99 52. 3.0.57.76.00 2720 58.0 2.6.38.8.58 56. 2.3.38.9.59 53.8 2.7.38.9.60 5.3 3.09.38.50.6 7 F 300 60.7 2.6.39.5.62 58. 2..39.5.63 56.0 2.75.39.53.65 53.6 3.0.0.5.67 080 62.5 2.7.0.53.67 60.2 2.5.0.55.68 57.8 2.75.0.56.7 55.0 3.0..56.73 8.5 TON HIGH EFFICIENCY LCH02HB (2ND STAGE) - CONSTANT AIR VOLUME Outdoor Air Temperature Entering Outdoor Coil Entering 85 F 95 F 05 F 5 F Wet Air Comp. Sensible To Comp. Sensible To Comp. Sensible To Comp. Sensible To Bulb Volume Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Temperature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb cfm kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F 2720 98.8 5.5.70.85.00 9. 6.27.72.88.00 89.7 7.0.73.9.00 8.7 8.09.76.95.00 63 F 300 03.3 5.56.76.95.00 98.6 6.27.78.98.00 93.5 7..80.00.00 88.7 8.08.83.00.00 080 06.9 5.56.82.00.00 02.6 6.28.8.00.00 98.2 7.2.88.00.00 93. 8.08.9.00.00 2720 0.3 5.56.55.68.8 99.6 6.28.56.69.8 9.7 7..57.7.87 89.3 8.08.59.73.9 67 F 300 08.8 5.57.59.7.9 03.8 6.29.60.76.9 98.5 7.2.6.78.97 92.7 8.08.62.8.00 080 2.0 5.58.62.80.99 06.6 6.30.63.82.00 0.2 7.2.65.85.00 95.2 8.08.66.89.00 2720 09.6 5.57.2.5.66 0.7 6.29.3.55.67 99.7 7.2.3.56.69 9. 8.08.3.58.7 7 F 300.3 5.59.3.58.72 09.2 6.30..59.7 03.6 7.2.5.60.76 97. 8.08.5.6.78 080 7.8 5.60.5.6.77 2.2 6.3.5.62.80 06. 7.3.6.6.83 00.0 8.08.7.66.86 Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 2

RATINGS NOTE For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section. 0 TON HIGH EFFICIENCY LCH20HB (ST STAGE) - CONSTANT AIR VOLUME Outdoor Air Temperature Entering Outdoor Coil Entering 65 F 75 F 85 F 95 F Wet Air Comp. Sensible To Comp. Sensible To Comp. Sensible To Comp. Sensible To Bulb Volume Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Temperature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb cfm kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F 3200 6.5 2.6.6.78.95 59.3 2.96.65.80.97 56.8 3.3.66.82.00 5.3 3.77.67.85.00 63 F 000 6.5 2.6.68.86.00 62.2 2.99.70.89.00 59.5 3.37.7.93.00 56.8 3.80.7.96.00 800 66.8 2.67.73.95.00 6.3 3.02.76.98.00 6.5 3.0.78.00.00 58.8 3.83.8.00.00 3200 6.8 2.65.5.62.73 62.5 2.99.52.63.75 60.0 3.38.52.6.78 57.2 3.8.53.65.80 67 F 000 68. 2.68.53.66.82 65.5 3.03.5.67.8 62.7 3..55.69.88 59.8 3.8.56.70.9 800 70.3 2.7.56.70.9 67.7 3.06.58.73.9 6.7 3..58.75.98 6.6 3.87.60.78.00 3200 68.5 2.69.0.50.60 66.0 3.0.39.50.6 63. 3.2.0.5.62 60.5 3.85.0.52.63 7 F 000 7.5 2.72.0.52.6 68.9 3.07.0.53.65 65.9 3.6..5.67 62.7 3.88..55.68 800 73.9 2.75..55.68 70.9 3.0.2.56.70 67.9 3.8.3.57.73 6.7 3.9.3.58.75 0 TON HIGH EFFICIENCY LCH20HB (2ND STAGE) - CONSTANT AIR VOLUME Outdoor Air Temperature Entering Outdoor Coil Entering 85 F 95 F 05 F 5 F Wet Air Comp. Sensible To Comp. Sensible To Comp. Sensible To Comp. Sensible To Bulb Volume Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Temperature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb cfm kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F 3200 8.3 7.09.67.83.00 3. 8.00.68.86.00 07. 9.0.70.89.00 0. 0.23.72.93.00 63 F 000 23.7 7.6.72.9.00 8.2 8.07.75.97.00 2.2 9..78.00.00 06. 0.29.8.00.00 800 27.9 7.2.79.00.00 22.7 8.3.82.00.00 6.9 9.7.85.00.00.3 0.37.90.00.00 3200 2.8 7.7.53.65.79 9.2 8.08.5.66.8 3. 9.2.5.68.8 06.8 0.30.56.70.89 67 F 000 30.2 7.2.56.70.90 2. 8.6.57.72.93 8. 9.9.58.75.97. 0.36.60.78.00 800 3.2 7.29.59.77.99 27.9 8.2.6.80.00 2.0 9.23.62.82.00. 0.0.6.87.00 3200 3.6 7.26.0.52.63 25.7 8.7..52.6 9.6 9.2..53.66 2.8 0.38..55.68 7 F 000 36.6 7.33.2.55.68 30.6 8.2.2.56.70 23.7 9.27.3.58.72 6.7 0.5.3.59.75 800 0.5 7.38.3.58.7 3. 8.29..60.77 27.3 9.32..62.80 9.5 0.9.5.63.8 2.5 TON HIGH EFFICIENCY LCH50HB (ST STAGE) - CONSTANT AIR VOLUME Outdoor Air Temperature Entering Outdoor Coil Entering 65 F 75 F 85 F 95 F Wet Air Comp. Sensible To Comp. Sensible To Comp. Sensible To Comp. Sensible To Bulb Volume Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Temperature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb cfm kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F 3800 76. 3.6 0.67 0.8 0.96 72.0 3.83 0.67 0.82 0.98 67.0.2 0.68 0.8 0.99 6.7.69 0.68 0.86.00 63 F 00 79.6 3.7 0.7 0.86.00 7.9 3.8 0.7 0.88.00 69.9.25 0.7 0.90.00 6..70 0.73 0.92.00 5000 82.3 3.9 0.7 0.9.00 77.5 3.85 0.7 0.93.00 72.2.26 0.76 0.95.00 66.6.7 0.77 0.98.00 3800 8.9 3.8 0.53 0.65 0.78 77.2 3.85 0.53 0.65 0.79 72.3.26 0.52 0.66 0.80 66.8.7 0.52 0.66 0.82 67 F 00 85.2 3.50 0.55 0.68 0.82 80. 3.86 0.55 0.69 0.8 75..27 0.5 0.69 0.85 69.6.72 0.5 0.70 0.88 5000 87.8 3.5 0.57 0.7 0.87 82.8 3.88 0.57 0.72 0.89 77.6.28 0.57 0.73 0.9 7.8.73 0.56 0.7 0.9 3800 87.7 3.5 0. 0.52 0.63 83.0 3.87 0.0 0.52 0.63 77.8.28 0.38 0.52 0.6 72.3.73 0.37 0.5 0.6 7 F 00 90.7 3.52 0.2 0.5 0.66 85.8 3.89 0. 0.5 0.66 80.6.29 0.0 0.5 0.67 7.8.7 0.38 0.53 0.68 5000 93.6 3.5 0.3 0.56 0.69 88.3 3.90 0. 0.56 0.70 82.9.30 0. 0.56 0.7 77.0.75 0.0 0.56 0.72 2.5 TON HIGH EFFICIENCY LCH50HB (2ND STAGE) - CONSTANT AIR VOLUME Outdoor Air Temperature Entering Outdoor Coil Entering 85 F 95 F 05 F 5 F Wet Air Comp. Sensible To Comp. Sensible To Comp. Sensible To Comp. Sensible To Bulb Volume Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Temperature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb cfm kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F 3800 6.9 9.20 0.69 0.8 0.98 35.7 0.2 0.70 0.86.00 2.2.3 0.70 0.88.00.9 2.62 0.72 0.9.00 63 F 00 53.0 9.23 0.73 0.89.00.3 0.23 0.7 0.9.00 29.5.37 0.75 0.9.00 7.0 2.65 0.77 0.98.00 5000 58.0 9.26 0.76 0.9.00 6.2 0.27 0.77 0.97.00 3.2.0 0.80 0.99.00 2.8 2.67 0.82.00.00 3800 57.9 9.26 0.5 0.67 0.8 6. 0.26 0.53 0.68 0.82 3.6.39 0.52 0.68 0.8 22.2 2.68 0.5 0.69 0.87 67 F 00 6. 9.29 0.56 0.7 0.86 52. 0.30 0.56 0.72 0.88 39.9.3 0.55 0.73 0.90 27. 2.70 0.55 0.75 0.9 5000 69.2 9.32 0.58 0.7 0.9 57. 0.33 0.58 0.75 0.93.6.7 0.58 0.77 0.96 3. 2.73 0.59 0.79 0.99 3800 69.9 9.32 0.39 0.53 0.65 58.0 0.3 0.38 0.52 0.65 5.8.7 0.37 0.52 0.66 32.7 2.7 0.35 0.5 0.67 7 F 00 76.0 9.36 0. 0.55 0.69 63.6 0.36 0.0 0.55 0.70 5..5 0.38 0.5 0.7 37. 2.77 0.37 0.5 0.72 5000 80.9 9.39 0.2 0.57 0.72 68.2 0.39 0. 0.57 0.73 55.3.52 0.0 0.57 0.75. 2.79 0.39 0.58 0.77 Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 22

RATINGS NOTE For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section. 7.5 TON HIGH EFFICIENCY LCH092HM (ST STAGE) - MSAV (Multi-Stage Air Volume) Outdoor Air Temperature Entering Outdoor Coil Entering 65 F 75 F 85 F 95 F Wet Air Comp. Sensible To Comp. Sensible To Comp. Sensible To Comp. Sensible To Bulb Volume Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Temperature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb cfm kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F 680 3.9.9 0.59 0.69 0.8 2. 2.20 0.60 0.70 0.82 0.9 2.8 0.60 0.7 0.8 39.2 2.8 0.6 0.73 0.86 63 F 200 6.9.95 0.6 0.7 0.88 5.2 2.20 0.62 0.76 0.90 3.5 2.9 0.63 0.78 0.93.6 2.8 0.6 0.80 0.95 2520 9.2.96 0.65 0.8 0.96 7.3 2.2 0.66 0.8 0.98 5. 2.9 0.67 0.8.00 3. 2.82 0.69 0.87.00 680 6.6.95 0.8 0.56 0.65 5.2 2.20 0.8 0.57 0.66 3.5 2.9 0.8 0.58 0.68.7 2.8 0.9 0.58 0.69 67 F 200 9.6.96 0.9 0.59 0.70 7.8 2.2 0.50 0.59 0.72 6.0 2.9 0.50 0.60 0.73.0 2.8 0.5 0.6 0.75 2520 5.9.96 0.5 0.62 0.76 50. 2.22 0.52 0.63 0.77 8. 2.50 0.52 0.6 0.79 5.9 2.82 0.53 0.66 0.82 680 9..96 0.38 0.6 0.5 7.8 2.2 0.38 0.7 0.55 6. 2.50 0.39 0.7 0.55.2 2.82 0.38 0.7 0.56 7 F 200 52.5.97 0.38 0.8 0.57 50.7 2.22 0.39 0.8 0.57 8.8 2.50 0.39 0.9 0.58 6.7 2.82 0.39 0.9 0.59 2520 5.6.97 0.39 0.9 0.59 52.7 2.23 0.39 0.50 0.60 50.6 2.5 0.0 0.50 0.62 8. 2.82 0.0 0.5 0.63 7.5 TON HIGH EFFICIENCY LCH092HM (2ND STAGE) - MSAV (Multi-Stage Air Volume) Outdoor Air Temperature Entering Outdoor Coil Entering 85 F 95 F 05 F 5 F Wet Air Comp. Sensible To Comp. Sensible To Comp. Sensible To Comp. Sensible To Bulb Volume Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Temperature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb cfm kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F 200 87.9 5.9.69.83.98 8.0 5.86.70.85.00 79.8 6.6.72.88.00 75.2 7.55.7.92.00 63 F 3000 92.3 5.20.7.92.00 88.0 5.87.76.95.00 83.5 6.6.78.98.00 78.7 7.5.8.00.00 3600 95.6 5.2.79.00.00 9. 5.87.82.00.00 87.3 6.6.85.00.00 82.9 7.55.88.00.00 200 93.0 5.20.55.66.79 89.0 5.87.55.68.8 8.5 6.6.56.69.8 79.5 7.5.58.7.87 67 F 3000 97.3 5.2.58.7.88 93.0 5.88.59.73.9 88.2 6.65.60.76.9 82.8 7.5.6.78.98 3600 00.6 5.22.6.77.97 95.7 5.88.62.79.99 90.8 6.65.63.82.00 85.2 7.5.6.86.00 200 98.2 5.2.2.53.6 93.8 5.88.2.5.65 89.0 6.65.2.5.67 8.2 7.5.3.56.69 7 F 3000 02.5 5.23.3.56.69 97.9 5.89.3.58.7 92.9 6.65..59.73 87.5 7.5..60.76 3600 05.9 5.2..60.75 00.8 5.89.5.6.77 95. 6.65.5.62.79 89.9 7.5.6.6.8 8.5 TON HIGH EFFICIENCY LCH02HM (ST STAGE) - MSAV (Multi-Stage Air Volume) Outdoor Air Temperature Entering Outdoor Coil Entering 65 F 75 F 85 F 95 F Wet Air Comp. Sensible To Comp. Sensible To Comp. Sensible To Comp. Sensible To Bulb Volume Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Temperature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb cfm kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F 920 9.5 2.2 0.6 0.72 0.8 7.8 2. 0.63 0.73 0.86 6. 2.7 0.63 0.75 0.87.2 3.07 0.63 0.76 0.9 63 F 200 52.6 2.3 0.6 0.78 0.92 50.8 2. 0.65 0.79 0.9 8.8 2.72 0.66 0.8 0.96 6.6 3.08 0.68 0.83 0.98 2880 5.8 2. 0.68 0.83 0.99 52.9 2.2 0.69 0.85 50.8 2.73 0.7 0.87 8. 3.08 0.72 0.9 920 52.3 2.3 0.5 0.59 0.69 50.7 2. 0.5 0.6 0.7 8.8 2.72 0.5 0.6 0.7 6.9 3.08 0.5 0.6 0.72 67 F 200 55. 2. 0.52 0.62 0.73 53.6 2.2 0.52 0.63 0.75 5.5 2.73 0.52 0.6 0.77 9.3 3.08 0.53 0.65 0.79 2880 57.8 2.5 0.53 0.65 0.79 55.8 2.3 0.53 0.66 0.8 53.6 2.73 0.5 0.68 0.83 5.2 3.09 0.56 0.7 0.87 920 55.5 2. 0. 0.8 0.57 53.7 2.2 0. 0.9 0.57 5.7 2.73 0.39 0.9 0.58 9.5 3.09 0. 0.9 0.59 7 F 200 58.6 2.5 0. 0.5 0.6 56.5 2.3 0. 0.5 0.6 5. 2.7 0. 0.5 0.6 52 3.09 0. 0.52 0.62 2880 60.9 2.6 0. 0.52 0.63 58.6 2.3 0. 0.52 0.6 56.3 2.7 0. 0.53 0.65 53.9 3.09 0. 0.5 0.67 8.5 TON HIGH EFFICIENCY LCH02HM (2ND STAGE) - MSAV (Multi-Stage Air Volume) Outdoor Air Temperature Entering Outdoor Coil Entering 85 F 95 F 05 F 5 F Wet Air Comp. Sensible To Comp. Sensible To Comp. Sensible To Comp. Sensible To Bulb Volume Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Temperature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb cfm kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F 2720 98.8 5.5.70.85.00 9. 6.27.72.88.00 89.7 7.0.73.9.00 8.7 8.09.76.95.00 63 F 300 03.3 5.56.76.95.00 98.6 6.27.78.98.00 93.5 7..80.00.00 88.7 8.08.83.00.00 080 06.9 5.56.82.00.00 02.6 6.28.8.00.00 98.2 7.2.88.00.00 93. 8.08.9.00.00 2720 0.3 5.56.55.68.8 99.6 6.28.56.69.8 9.7 7..57.7.87 89.3 8.08.59.73.9 67 F 300 08.8 5.57.59.7.9 03.8 6.29.60.76.9 98.5 7.2.6.78.97 92.7 8.08.62.8.00 080 2.0 5.58.62.80.99 06.6 6.30.63.82.00 0.2 7.2.65.85.00 95.2 8.08.66.89.00 2720 09.6 5.57.2.5.66 0.7 6.29.3.55.67 99.7 7.2.3.56.69 9. 8.08.3.58.7 7 F 300.3 5.59.3.58.72 09.2 6.30..59.7 03.6 7.2.5.60.76 97. 8.08.5.6.78 080 7.8 5.60.5.6.77 2.2 6.3.5.62.80 06. 7.3.6.6.83 00.0 8.08.7.66.86 Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 23

RATINGS NOTE For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section. 0 TON HIGH EFFICIENCY LCH20HM (ST STAGE) - MSAV (Multi-Stage Air Volume) Outdoor Air Temperature Entering Outdoor Coil Entering 65 F 75 F 85 F 95 F Wet Air Comp. Sensible To Comp. Sensible To Comp. Sensible To Comp. Sensible To Bulb Volume Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Temperature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb cfm kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F 220 59 2.6 0.68 0.77 0.87 57 2.96 0.68 0.78 0.88 5.9 3.3 0.69 0.8 0.89 52.6 3.78 0.7 0.8 0.9 63 F 2800 62.9 2.6 0.7 0.82 0.92 60.6 2.99 0.72 0.83 0.9 58.2 3.38 0.72 0.8 0.96 55.6 3.82 0.7 0.86 0.98 3360 65.7 2.67 0.7 0.86 0.98 63.3 3.02 0.75 0.87 0.99 60.6 3. 0.76 0.89 58 3.85 0.77 0.9 220 62.5 2.6 0.55 0.65 0.7 60.5 2.99 0.56 0.65 0.75 58.2 3.38 0.56 0.67 0.76 55.8 3.82 0.56 0.67 0.77 67 F 2800 66.2 2.67 0.57 0.68 0.79 6 3.03 0.57 0.69 0.8 6. 3.2 0.58 0.7 0.8 58.9 3.86 0.58 0.7 0.83 3360 69.3 2.7 0.58 0.7 0.83 66.8 3.06 0.59 0.72 0.8 6 3.5 0.6 0.73 0.86 6. 3.88 0.6 0.75 0.88 220 66.3 2.67 0. 0.53 0.62 6 3.03 0. 0.5 0.63 6.6 3.2 0. 0.5 0.6 59. 3.86 0. 0.55 0.65 7 F 2800 70.2 2.7 0. 0.55 0.65 67.8 3.07 0. 0.56 0.67 65. 3.6 0.5 0.56 0.67 62.2 3.9 0.5 0.57 0.68 3360 73. 2.7 0.5 0.57 0.69 70.3 3. 0.5 0.58 0.7 67.6 3.9 0.5 0.59 0.7 6.5 3.93 0.5 0.59 0.72 0 TON HIGH EFFICIENCY LCH20HM (2ND STAGE) - MSAV (Multi-Stage Air Volume) Outdoor Air Temperature Entering Outdoor Coil Entering 85 F 95 F 05 F 5 F Wet Air Comp. Sensible To Comp. Sensible To Comp. Sensible To Comp. Sensible To Bulb Volume Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Temperature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb cfm kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F 3200 8.3 7.09.67.83.00 3. 8.00.68.86.00 07. 9.0.70.89.00 0. 0.23.72.93.00 63 F 000 23.7 7.6.72.9.00 8.2 8.07.75.97.00 2.2 9..78.00.00 06. 0.29.8.00.00 800 27.9 7.2.79.00.00 22.7 8.3.82.00.00 6.9 9.7.85.00.00.3 0.37.90.00.00 3200 2.8 7.7.53.65.79 9.2 8.08.5.66.8 3. 9.2.5.68.8 06.8 0.30.56.70.89 67 F 000 30.2 7.2.56.70.90 2. 8.6.57.72.93 8. 9.9.58.75.97. 0.36.60.78.00 800 3.2 7.29.59.77.99 27.9 8.2.6.80.00 2.0 9.23.62.82.00. 0.0.6.87.00 3200 3.6 7.26.0.52.63 25.7 8.7..52.6 9.6 9.2..53.66 2.8 0.38..55.68 7 F 000 36.6 7.33.2.55.68 30.6 8.2.2.56.70 23.7 9.27.3.58.72 6.7 0.5.3.59.75 800 0.5 7.38.3.58.7 3. 8.29..60.77 27.3 9.32..62.80 9.5 0.9.5.63.8 2.5 TON HIGH EFFICIENCY LCH50HM (ST STAGE) - MSAV (Multi-Stage Air Volume) Outdoor Air Temperature Entering Outdoor Coil Entering 65 F 75 F 85 F 95 F Wet Air Comp. Sensible To Comp. Sensible To Comp. Sensible To Comp. Sensible To Bulb Volume Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Temperature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb cfm kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F 2560 68.8 3. 0.6 0.7 0.8 6.5 3.80 0.63 0.7 0.85 60.0.2 0.62 0.7 0.86 55.3.66 0.62 0.75 0.88 63 F 3200 7.6 3. 0.67 0.79 0.9 70. 3.82 0.67 0.80 0.92 65.2.22 0.67 0.80 0.9 60.3.68 0.67 0.82 0.96 380 76.6 3.5 0.69 0.8 0.93 72.0 3.82 0.69 0.82 0.95 67.2.23 0.69 0.83 0.97 6.9.68 0.69 0.8 0.99 2560 7.2 3. 0.5 0.62 0.7 69.9 3.82 0.50 0.6 0.7 65..23 0.9 0.60 0.7 60.6.69 0.8 0.60 0.72 67 F 3200 80.0 3.6 0.5 0.65 0.76 75.3 3.8 0.53 0.6 0.76 70.6.25 0.52 0.65 0.77 65.3.70 0.5 0.65 0.78 380 82. 3.7 0.55 0.67 0.78 77.5 3.8 0.5 0.66 0.78 72.5.25 0.53 0.66 0.80 67..70 0.52 0.67 0.8 2560 79.9 3.6 0. 0.50 0.59 75.6 3.8 0.39 0.9 0.58 70.8.2 0.37 0.8 0.58 65.9.70 0.35 0.7 0.58 7 F 3200 86.0 3.9 0.2 0.52 0.63 8. 3.86 0.0 0.52 0.62 76.5.27 0.39 0.5 0.63 7..72 0.37 0.50 0.62 380 88.2 3.50 0.2 0.53 0.6 83. 3.87 0. 0.53 0.6 78.3.27 0.0 0.52 0.6 72.9.73 0.38 0.52 0.6 2.5 TON HIGH EFFICIENCY LCH50HM (2ND STAGE) - MSAV (Multi-Stage Air Volume) Outdoor Air Temperature Entering Outdoor Coil Entering 85 F 95 F 05 F 5 F Wet Air Comp. Sensible To Comp. Sensible To Comp. Sensible To Comp. Sensible To Bulb Volume Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Temperature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb cfm kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F 3800 6.9 9.20 0.69 0.8 0.98 35.7 0.2 0.70 0.86.00 2.2.3 0.70 0.88.00.9 2.62 0.72 0.9.00 63 F 00 53.0 9.23 0.73 0.89.00.3 0.23 0.7 0.9.00 29.5.37 0.75 0.9.00 7.0 2.65 0.77 0.98.00 5000 58.0 9.26 0.76 0.9.00 6.2 0.27 0.77 0.97.00 3.2.0 0.80 0.99.00 2.8 2.67 0.82.00.00 3800 57.9 9.26 0.5 0.67 0.8 6. 0.26 0.53 0.68 0.82 3.6.39 0.52 0.68 0.8 22.2 2.68 0.5 0.69 0.87 67 F 00 6. 9.29 0.56 0.7 0.86 52. 0.30 0.56 0.72 0.88 39.9.3 0.55 0.73 0.90 27. 2.70 0.55 0.75 0.9 5000 69.2 9.32 0.58 0.7 0.9 57. 0.33 0.58 0.75 0.93.6.7 0.58 0.77 0.96 3. 2.73 0.59 0.79 0.99 3800 69.9 9.32 0.39 0.53 0.65 58.0 0.3 0.38 0.52 0.65 5.8.7 0.37 0.52 0.66 32.7 2.7 0.35 0.5 0.67 7 F 00 76.0 9.36 0. 0.55 0.69 63.6 0.36 0.0 0.55 0.70 5..5 0.38 0.5 0.7 37. 2.77 0.37 0.5 0.72 5000 80.9 9.39 0.2 0.57 0.72 68.2 0.39 0. 0.57 0.73 55.3.52 0.0 0.57 0.75. 2.79 0.39 0.58 0.77 Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 2

HUMIDITROL DEHUMIDIFICATION SYSTEM RATINGS 7.5 TON HIGH EFFICIENCY LCH092H WITH HUMIDITROL OPERATING (ST STAGE) Outdoor Air Temperature Entering Outdoor Coil Entering 65 F 75 F 85 F 95 F Wet Air Comp. Sensible To Comp. Sensible To Comp. Sensible To Comp. Sensible To Bulb Volume Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Temperature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb cfm kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F 200 26..9 0.7 0.63 0.8 22. 2.2 0.33 0.55 0.79 8.0 2. 0.2 0.7 0.80 2.0 2.6 0.09 0. 0.8 63 F 3000 30.8.9 0.50 0.69 0.89 26.0 2.2 0.36 0.59 0.82 20.6 2. 0.22 0.8 0.8 0.3 2.6 0.09 0.37 0.79 3600 35.5.9 0.5 0.76 0.98 29.9 2.2 0.39 0.63 0.86 20.7 2. 0.2 0.55 0.8 8.5 2.6 0.09 0.6 0.76 200 33.8 2.0 0.35 0.8 0.6 29. 2.2 0.20 0.39 0.58 2.3 2. 0.07 0.30 0.5 7. 2.7-0.05 0.2 0.50 67 F 3000 38.0 2.0 0.36 0.52 0.70 32.8 2.2 0.20 0. 0.62 26.8 2. 0.07 0.30 0.56 6.8 2.7-0.08 0.9 0.50 3600 2. 2.0 0.37 0.56 0.75 36.5 2.2 0.2 0.53 0.66 27.8 2. 0.06 0.53 0.56 6.3 2.7-0.0 0.52 0.7 200.6 2.0 0.22 0.3 0.7 37.0 2.2 0.07 0.23 0.39 30.5 2.5-0.06 0.2 0.3 22.9 2.7-0.9 0.02 0.23 7 F 3000 5. 2.0 0.22 0.35 0.50 39.6 2.2 0.05 0.2 0.2 32.9 2.5-0.0 0.2 0.35 23.3 2.7-0.2 0.0 0.27 3600 8.7 2.0 0.2 0.37 0.53 3. 2.2 0.03 0.25 0.6 3.6 2.5-0.3 0.3 0.39 23.7 2.7-0.30 0.0 0.3 7.5 TON HIGH EFFICIENCY LCH092H WITH HUMIDITROL OPERATING (2ND STAGE) Outdoor Air Temperature Entering Outdoor Coil Entering 65 F 75 F 85 F 95 F Wet Air Comp. Sensible To Comp. Sensible To Comp. Sensible To Comp. Sensible To Bulb Volume Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Temperature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb cfm kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F 200 75.3.0 0.63 0.76 0.89 68.2.5 0.62 0.78 0.92 6.2 5.0 0.6 0.80 0.96 5. 5.5 0.60 0.82.00 63 F 3000 78.8.0 0.68 0.8 0.9 7.2.5 0.68 0.82 0.96 63.5 5.0 0.67 0.82 0.98 55.9 5.5 0.67 0.83.00 3600 82.3.0 0.73 0.90.00 7..5 0.73 0.90.00 65.9 5.0 0.73 0.92.00 57.7 5.5 0.7 0.96.00 200 8.0.0 0.8 0.6 0.73 78.0.5 0.6 0.60 0.7 72.0 5.0 0.3 0.60 0.76 65.5 5.6 0. 0.60 0.77 67 F 3000 88.6.0 0.5 0.65 0.79 8.7.5 0.9 0.6 0.80 7.8 5. 0.7 0.6 0.80 66.9 5.6 0.5 0.63 0.8 3600 93.3. 0.53 0.7 0.8 85..6 0.52 0.69 0.8 77.6 5. 0.50 0.68 0.8 68.3 5.6 0.9 0.68 0.8 200 92.7. 0.33 0.5 0.58 87.8.6 0.29 0.3 0.57 82.9 5. 0.25 0.0 0.55 75.5 5.6 0.22 0.38 0.5 7 F 3000 98.5. 0.3 0.8 0.63 92.3.6 0.30 0.6 0.62 86.2 5. 0.26 0. 0.62 76.9 5.6 0.22 0.2 0.6 3600 0.2. 0.3 0.5 0.68 96.8.6 0.30 0.9 0.68 89. 5. 0.27 0.8 0.68 78.3 5.6 0.23 0.6 0.68 8.5 TON HIGH EFFICIENCY LCH02H WITH HUMIDITROL OPERATING (ST STAGE) Outdoor Air Temperature Entering Outdoor Coil Entering 65 F 75 F 85 F 95 F Wet Air Comp. Sensible To Comp. Sensible To Comp. Sensible To Comp. Sensible To Bulb Volume Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Temperature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb cfm kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F 200 3.2 2. 0.9 0.66 0.83 27. 2.3 0.3 0.58 0.89 8. 2.6 0.22 0.9 0.9 9.3 2.9 0.09 0..00 63 F 3000 39. 2. 0.53 0.7 0.89 29.2 2.3 0.37 0.60 0.92 9.0 2.6 0.2 0.53 0.96 8.8 2.8 0.2 0.8.00 3600 2. 2. 0.56 0.75 0.9 3.0 2.3 0.39 0.69 0.96 9.6 2.6 0.26 0.63 0.98 8.2 2.8 0. 0.57.00 200 2.5 2. 0.33 0.50 0.66 35.0 2. 0.9 0.37 0.63 25. 2.6 0.06 0.27 0.59 5.8 2.9-0.07 0.9 0.56 67 F 3000 7.0 2. 0.5 0.57 0.70 37.6 2. 0.20 0. 0.66 26.7 2.6 0.06 0.32 0.62 5.9 2.9-0.07 0.2 0.59 3600 5.5 2.2 0.56 0.65 0.73 0.3 2. 0.2 0.9 0.69 28. 2.6 0.06 0.37 0.67 6.0 2.9-0.08 0.29 0.65 200 50.7 2. 0.8 0.33 0.9 2.6 2. 0.05 0.20 0.37 32. 2.7-0.09 0.0 0.29 22.2 2.9-0.23-0.0 0.2 7 F 3000 5.9 2.2 0.37 0. 0.5 6. 2. 0.06 0.23 0.0 3.5 2.7-0. 0. 0.32 23.0 2.9-0.26 0.00 0.25 3600 59.0 2.2 0.56 0.5 0.52 9.5 2. 0.7 0.30 0.3 36.6 2.7-0. 0. 0.37 23.7 2.9-0.29 0.00 0.30 8.5 TON HIGH EFFICIENCY LCH02H WITH HUMIDITROL OPERATING (2ND STAGE) Outdoor Air Temperature Entering Outdoor Coil Entering 65 F 75 F 85 F 95 F Wet Air Comp. Sensible To Comp. Sensible To Comp. Sensible To Comp. Sensible To Bulb Volume Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Temperature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb cfm kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F 2720 85.3.3 0.6 0.8 0.98 77.9.9 0.63 0.83 0.99 69.3 5. 0.6 0.8 0.99 57.8 6.0 0.60 0.86.00 63 F 300 89.2. 0.70 0.8 0.99 8.7.9 0.69 0.8 0.99 72.0 5.5 0.69 0.8.00 58.9 6.0 0.68 0.8.00 080 93.. 0.75 0.87.00 85.5.9 0.75 0.88.00 7.6 5.5 0.76 0.9.00 59.9 6.0 0.76 0.95.00 2720 00.8. 0.8 0.63 0.78 90.0.9 0.5 0.63 0.78 78.8 5.5 0.2 0.62 0.78 67.6 6. 0.0 0.62 0.78 67 F 300 0.5. 0.5 0.66 0.8 9.6 5.0 0.9 0.65 0.8 82. 5.5 0.6 0.6 0.8 69.7 6. 0. 0.62 0.8 080 08.2.5 0.55 0.69 0.8 99. 5.0 0.52 0.68 0.8 85.5 5.6 0.50 0.68 0.8 7.8 6. 0.8 0.67 0.8 2720 0.. 0.32 0.5 0.58 99.2 5.0 0.28 0.2 0.57 88.3 5.6 0.23 0.0 0.56 77. 6.2 0.9 0.37 0.55 7 F 300 5.8.5 0.33 0.8 0.63 0. 5.0 0.29 0.6 0.63 92.3 5.6 0.2 0.3 0.62 80.6 6.2 0.20 0. 0.62 080 2.5.5 0.3 0.5 0.68 08.9 5. 0.29 0.9 0.68 96.3 5.6 0.25 0.6 0.68 83.7 6.2 0.20 0. 0.68 Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 25

HUMIDITROL DEHUMIDIFICATION SYSTEM RATINGS 0 TON HIGH EFFICIENCY LCH20H WITH HUMIDITROL OPERATING (ST STAGE) Outdoor Air Temperature Entering Outdoor Coil Entering 65 F 75 F 85 F 95 F Wet Air Comp. Sensible To Comp. Sensible To Comp. Sensible To Comp. Sensible To Bulb Volume Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Temperature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb cfm kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F 3200 9.5 2.6.8.70.92 2.3 2.9.39.66.9 35. 3.2.22.60.98 27.9 3.5.0.6.00 63 F 000 59.0 2.6.56.82.00 9. 2.9.5.8.00 39. 3.2.3.80.93 29.2 3.5 -.0.77.97 800 68.6 2.6.62.92.00 55.9 2.9.56.96.00 3.2 3.2..00.00 30.5 3.5 -.02.97.80 3200 6.2 2.7.30.9.66 52. 3.0.20..6 3.5 3.3.0.30.59 3.7 3.6 -.06.08.50 67 F 000 68.2 2.7.3.55.77 57.7 3.0.23.9.75 7. 3.3.05.38.75 36.5 3.6 -.2.5.72 800 75.2 2.7.37.62.87 62.9 3.0.26.57.89 50.7 3.3.06.50.92 38. 3.6 -.8.28.98 3200 73.0 2.7.7.32.8 62.5 3.0.06.2.2 52.0 3.3 -.2..3.5 3.6 -.3.03.9 7 F 000 77. 2.7.7.35.5 66.2 3.0.05.28.50 55. 3.3 -..5.2 3.9 3.6 -.23 -.0.28 800 8.9 2.8.9.39.6 70.0 3..06.3.57 58. 3. -.6.8.5 6.3 3.7 -.3 -.09.0 0 TON HIGH EFFICIENCY LCH20H WITH HUMIDITROL OPERATING (2ND STAGE) Outdoor Air Temperature Entering Outdoor Coil Entering 65 F 75 F 85 F 95 F Wet Air Comp. Sensible To Comp. Sensible To Comp. Sensible To Comp. Sensible To Bulb Volume Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Temperature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb cfm kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F 3200 0.7 5..6.73.86 95.0 6..58.75.9 85.3 6.8.56.76.95 75.5 7.5.53.77.00 63 F 000.8 5.5.63.78.93 03. 6.2.62.78.95 9.9 6.8.60.79.98 80.5 7.5.59.79.00 800 25.0 5.5.65.82.99.8 6.2.65.82.00 98.6 6.9.65.82.00 85. 7.5.6.82.00 3200 8.9 5.5.5.57.69 08.5 6.2.2.57.7 98. 6.9.39.56.73 87.7 7.6.36.56.7 67 F 000 28.7 5.6.7.60.7 7.3 6.3..59.75 05.9 6.9.2.59.75 9.5 7.6.39.58.76 800 38. 5.6.8.6.79 26. 6.3.6.62.79 3.8 7.0..6.78 0. 7.6.2.60.78 3200 33. 5.6.29..53 22.0 6.3.26.39.5 0.9 7.0.23.36.50 99.8 7.7.20.3.9 7 F 000 2.5 5.7.30.3.56 3.2 6..27..55 9.9 7..23.38.53 08.6 7.7.9.36.52 800 5.9 5.8.3.5.59 0. 6..27.2.58 28.9 7..23.0.57 7.5 7.7.9.37.56 2.5 TON HIGH EFFICIENCY LCH50H WITH HUMIDITROL OPERATING (ST STAGE) Outdoor Air Temperature Entering Outdoor Coil Entering 65 F 75 F 85 F 95 F Wet Air Comp. Sensible To Comp. Sensible To Comp. Sensible To Comp. Sensible To Bulb Volume Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Temperature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb cfm kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F 3800 55.2 3..8.70.9 5.8 3.8.0.67.9 36...25.6.97 27.0.5.33.5.99 63 F 00 58.2 3.5.53.77.00 7.9 3.8.5.76.00 37.6..3.73.00 27.3.5.22.69.00 5000 6.2 3.5.57.8.00 50.0 3.8.50.85.00 38.8..33.73.90 27.6.5.0.89.00 3800 63.7 3.5.29.8.66 53.8 3.9.20..63.0.2.0.32.59 3..6.03.2.52 67 F 00 66.6 3.6.32.5.73 56. 3.9.2.6.72 5.7.2.05.36.68 35.3.6 -.0.9.65 5000 69. 3.6.33.55.79 58. 3.9.2.5.79 7..2.08.2.79 36..6 -.0.25.60 3800 72.2 3.6.5.3.7 6.9.0.05.23.2 5.6.3 -.0.2.35.3.6 -.28 -.07.22 7 F 00 7.9 3.7.6.33.5 6..0.05.25.5 53.8.3 -...39 3.3.7 -.29 -.06.27 5000 77.7 3.7.6.35.55 66.9.0.05.28.5 56.. -.2.6.5 5.3.7 -.30 -.0.33 2.5 TON HIGH EFFICIENCY LCH50H WITH HUMIDITROL OPERATING (2ND STAGE) Outdoor Air Temperature Entering Outdoor Coil Entering 65 F 75 F 85 F 95 F Wet Air Comp. Sensible To Comp. Sensible To Comp. Sensible To Comp. Sensible To Bulb Volume Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Cool Motor Ratio (S/T) Temperature Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb Cap. Input Dry Bulb cfm kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F kbtuh kw 75 F 80 F 85 F 3800 22.7 7.3.63.79.96 0.6 8.0.62.80.99 98.6 8.8.6.8.00 86.5 9.6.60.82.00 63 F 00 27. 7.3.66.82.97. 8..65.83.00 0. 8.8.65.8.00 88. 9.6.6.85.00 5000 32. 7.3.69.8.99 8.2 8..69.86.00 0.2 8.9.69.87.00 90.3 9.6.69.88.00 3800 37.7 7.5.7.62.76 2.7 8.2..6.78.8 9.0.2.60.79 98.8 9.8.39.60.80 67 F 00 2.5 7.5.9.6.79 28.7 8.3.6.63.80 5.0 9.0..63.8 0.3 9.8.2.62.83 5000 7.2 7.6.50.66.8 32.7 8.3.8.65.82 8.2 9..6.65.8 03.7 9.8..65.85 3800 52.7 7.7.3..57 38.8 8..27.2.56 25.0 9.2.23.39.55. 0.0.9.37.55 7 F 00 57.5 7.7.3.6.60 3. 8.5.27.3.60 28.6 9.2.23..59.2 0.0.9.39.59 5000 62. 7.8.3.7.63 7.3 8.5.27.5.63 32.2 9.3.23.3.63 7.2 0.0.9..63 Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 26

BLOWER DATA 092 AND 02 BELT DRIVE BLOWER BASE UNIT BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY (NO HEAT SECTION) WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE. FOR ALL UNITS ADD: Wet indoor coil air resistance of selected unit. 2 Any factory installed options air resistance (heat section, economizer, etc.) 3 Any field installed accessories air resistance (duct resistance, diffuser, etc.) Then determine from blower table blower motor output required. See page 29 for blower motors and drives. See page 29 for wet coil and option/accessory air resistance data. MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT (Maximum Static Pressure - 2.0 in. w.g.) 7.5 kw, 5 kw, 22.5 kw, 30 kw and 5 kw - 2800 cfm Static Pressure in. w.g. Air 0.2 0. 0.6 0.8.0.2..6.8 2.0 2.2 2. 2.6 Volume cfm RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 750 8 0.2 59 0. 68 0.57 688 0.7 758 0.82 82 0.93 885.08 9.23 99.39 038.5 082.68 2.82 66.95 2000 93 0.29 56 0.7 629 0.6 700 0.77 768 0.9 832.02 892.7 96.33 995.9 0.66 085.8 26.97 67 2.2 2250 507 0.37 57 0.56 63 0.72 72 0.86 779 0.99 82.3 900.28 953. 00.6 05.78 088.95 28 2.2 68 2.3 2500 52 0.6 588 0.6 657 0.8 727 0.95 792.09 853.2 909. 960.57 007.7 050.93 09 2. 30 2.29 70 2.8 2750 537 0.56 60 0.7 67 0.9 73.06 806.2 865.36 920.53 969.7 0.89 055 2.08 095 2.27 33 2.7 72 2.66 3000 55 0.67 622 0.86 692.02 760.8 822.3 878.5 93.68 979.86 02 2.06 06 2.26 099 2.6 36 2.65 7 2.85 3250 572 0.78 6 0.98 72.5 778.32 838.9 892.66 93.8 989 2.03 030 2.2 068 2.5 05 2.65 2.85 78 3.06 3500 592 0.9 663.2 733.3 798.7 855.65 907.83 956 2.02 000 2.22 039 2. 076 2.65 2.86 6 3.07 83 3.27 3750 6.0 687.28 756.7 88.65 872.83 923 2.02 970 2.22 0 2.3 09 2.65 08 2.87 8 3.09 52 3.29 89 3.5 000 639.22 73.8 780.66 838.83 890 2.02 939 2.22 98 2. 023 2.66 059 2.89 093 3. 26 3.33 60 3.5 97 3.77 250 667.3 7.69 805.86 859 2.02 909 2.22 956 2.5 998 2.68 036 2.92 070 3.5 03 3.37 35 3.59 69 3.8 207.05 Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 27

BLOWER DATA 20 AND 50 BELT DRIVE BLOWER BASE UNIT BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY (NO HEAT SECTION) WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE. FOR ALL UNITS ADD: Wet indoor coil air resistance of selected unit. 2 Any factory installed options air resistance (heat section, economizer, etc.) 3 Any field installed accessories air resistance (duct resistance, diffuser, etc.) Then determine from blower table blower motor output required. See page 29 for blower motors and drives. See page 29 for wet coil and option/accessory air resistance data. MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT (Maximum Static Pressure - 2.0 in. w.g.) 5 kw, 22.5 kw, 30 kw and 5 kw - 2800 cfm 60 kw - 000 cfm Static Pressure in. w.g. Air 0.2 0. 0.6 0.8.0.2..6.8 2.0 2.2 2. 2.6 Volume cfm RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2000 97 0.25 558 0. 62 0.6 69 0.7 76 0.85 830 0.99 889.6 93.3 99.52 05.7 096.89 6 2.08 97 2.27 2250 5 0.3 573 0.52 638 0.68 708 0.82 776 0.9 839.09 896.26 98.5 998.6 08.83 098 2.0 9 2.2 200 2. 2500 527 0. 589 0.62 65 0.78 723 0.9 789.05 850.2 90.39 955.58 003.77 052.96 0 2. 52 2.33 203 2.53 2750 55 0.55 606 0.72 672 0.88 70.03 80.7 86.3 9.53 962.72 00.92 057 2.0 05 2.29 5 2.7 206 2.68 3000 56 0.66 626 0.8 692.0 759.6 89.32 87.9 92.68 97.88 07 2.08 063 2.26 0 2. 58 2.63 208 2.83 3250 585 0.79 68 0.98 7. 778.3 836.8 887.66 935.86 98 2.06 026 2.26 07 2.5 7 2.63 63 2.80 23 3.00 3500 607 0.93 672.3 737.3 798.8 852.66 90.85 98 2.05 993 2.26 037 2.6 08 2.65 25 2.83 7 3.0 22 3.2 3750 632.0 698.3 762.50 89.67 869.86 95 2.05 96 2.25 005 2.7 09 2.68 092 2.88 36 3.05 8 3.2 23 3.5 000 660.30 726.52 787.70 838.87 885 2.06 930 2.26 97 2.8 08 2.7 062 2.93 05 3.2 9 3.30 9 3.9 25 3.72 250 69.53 755.75 80.9 857 2.07 90 2.27 95 2.50 990 2.7 03 2.98 077 3.20 20 3.39 63 3.58 20 3.79 262.03 500 72.78 783.98 83 2.2 87 2.28 97 2.50 962 2.75 006 3.02 05 3.27 09 3.9 37 3.70 8 3.89 228. 28.38 750 757 2.05 809 2.20 85 2.33 89 2.5 935 2.76 980 3.05 025 3.33 070 3.59 3 3.82 56.03 20.2 29.7 303.75 5000 787 2.3 83 2.3 870 2.57 90 2.78 95 3.06 000 3.38 06 3.68 09 3.95 35.9 78.0 22.62 272.86 325 5.3 5250 8 2.55 852 2.66 889 2.83 930 3.09 975 3. 023 3.76 070.08 5.35 59.59 203.8 28 5.03 297 5.27 350 5.53 5500 835 2.78 87 2.9 909 3.3 952 3. 999 3.8 09.8 096.5 2.79 86 5.03 229 5.2 275 5.6 32 5.69 - - - - - - 5750 85 3.0 890 3.9 930 3.8 977 3.86 027.27 078.66 26.99 7 5.26 2 5.9 258 5.70 - - - - - - - - - - - - - - - - - - 6000 87 3.26 90 3.53 955 3.90 006.3 060.80 5.9 58 5.5 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 6250 890 3.57 93 3.9 985. 0.9 096 5.38 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 28

BLOWER DATA FACTORY INSTALLED BELT DRIVE KIT SPECIFICATIONS Motor Efficiency Nominal hp Maximum hp Drive Kit Number RPM Range Standard & High 2 2.3 590-890 Standard & High 2 2.3 2 800-05 Standard & High 2 2.3 3 795-95 Standard 3 3.5 730-970 Standard 3 3.5 5 90-200 Standard 3 3.5 6 05-300 High 3 3.5 7 730-970 High 3 3.5 8 90-200 High 3 3.5 9 05-300 Standard 5 5.75 0 900-35 Standard 5 5.75 00-35 Standard 5 5.75 2 25-25 NOTE - Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate. NOTE Units equipped with MSAV (Multi-Stage Air Volume) option are limited to a motor service factor of.0. POWER EXHAUST FAN PERFORMANCE Return Air System Static Pressure in. w.g. Air Volume Exhausted cfm 0 375 0.05 2955 0.0 2685 0.5 20 0.20 265 0.25 920 0.30 20 0.35 200 FACTORY INSTALLED OPTIONS/FIELD INSTALLED ACCESSORY AIR RESISTANCE - in. w.g. Air Volume cfm Wet Indoor Coil 092, 02 20, 50 Electric Heat Economizer Humiditrol Condenser Reheat Coil Filters MERV 8 MERV 3 Return Air Adaptor Plate 750 0.0 0.0 0.03 0.05 0.02 0.0 0.03 0.00 2000 0.05 0.05 0.03 0.06 0.02 0.0 0.03 0.00 2250 0.06 0.06 0.0 0.08 0.02 0.0 0.0 0.00 2500 0.07 0.07 0.0 0. 0.03 0.0 0.05 0.00 2750 0.08 0.08 0.05 0.2 0.03 0.02 0.05 0.00 3000 0.0 0.09 0.06 0.3 0.03 0.02 0.06 0.02 3250 0. 0.0 0.06 0.5 0.0 0.02 0.06 0.02 3500 0.2 0. 0.09 0.5 0.0 0.03 0.07 0.0 3750 0. 0.3 0.09 0.5 0.05 0.03 0.08 0.07 000 0.5 0. 0.09 0.9 0.05 0.0 0.08 0.09 250 0.7 0.5 0.3 0.9 0.06 0.0 0.09 0. 500 0.9 0.7 0. 0.22 0.07 0.0 0.09 0.2 750 0.20 0.8 0.7 0.25 0.07 0.05 0.0 0.6 5000 0.22 0.20 0.20 0.29 0.08 0.06 0.0 0.8 5250 0.2 0.22 0.22 0.32 0.08 0.06 0. 0.9 5500 0.25 0.23 0.25 0.3 0.09 0.07 0.2 0.22 5750 0.27 0.25 0.3 0.5 0.0 0.07 0.2 0.25 6000 0.29 0.27 0.33 0.52 0.0 0.08 0.3 0.27 Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 29

BLOWER DATA CEILING DIFFUSERS AIR RESISTANCE - in. w.g. Unit Size 092 Models 02 & 20 Models 50 Models Air Volume cfm RTD Step-Down Diffuser 2 Ends Open Side, 2 Ends Open All Ends & Sides Open FD Flush Diffuser 200 0.2 0.8 0.5 0. 2600 0.2 0.2 0.8 0.7 2800 0.27 0.2 0.2 0.20 3000 0.32 0.29 0.25 0.25 3200 0. 0.37 0.32 0.3 300 0.50 0.5 0.39 0.37 3600 0.6 0.5 0.8 0. 3800 0.73 0.63 0.57 0.5 3600 0.36 0.28 0.23 0.5 3800 0.0 0.32 0.26 0.8 000 0. 0.36 0.29 0.2 200 0.9 0.0 0.33 0.2 00 0.5 0. 0.37 0.27 600 0.60 0.9 0.2 0.3 800 0.65 0.53 0.6 0.35 5000 0.69 0.58 0.50 0.39 5200 0.75 0.62 0.5 0.3 200 0.22 0.9 0.6 0.0 00 0.28 0.2 0.20 0.2 600 0.3 0.29 0.2 0.5 800 0.0 0.3 0.29 0.9 5000 0.6 0.39 0.3 0.23 5200 0.52 0. 0.39 0.27 500 0.58 0.9 0.3 0.3 5600 0.6 0.5 0.7 0.35 5800 0.70 0.59 0.5 0.39 CEILING DIFFUSER AIR THROW DATA Model No. 092 Models 02, 20 Models 50 Models Air Volume Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 30 Effective Throw Range RTD Step-Down FD Flush cfm ft. ft. 2600 2-29 9-2 2800 25-30 20-28 3000 27-33 2-29 3200 28-35 22-29 300 30-37 22-30 3600 25-33 22-29 3800 27-35 22-30 000 29-37 2-33 200 32-0 26-35 00 3-2 28-37 5600 39-9 28-37 5800 2-5 29-38 6000-5 0-50 6200 5-55 2-5 600 6-55 3-52 6600 7-56 5-56 Throw is the horizontal or vertical distance an air stream travels on leaving the outlet or diffuser before the maximum velocity is reduced to 50 ft. per minute. Four sides open.

ELECTRICAL/ELECTRIC HEAT DATA 7.5 TON 7.5 TON HIGH EFFICIENCY (R-0A) LCH092H Voltage - 60hz 208/230V - 3 Ph 60V - 3 Ph 575V - 3 Ph Compressor Rated Load Amps.6 5.5.7 Locked Rotor Amps 86 37 3 Compressor 2 Rated Load Amps.6 5.5.7 Outdoor Fan Motors (2) Power Exhaust () 0.33 HP Locked Rotor Amps 86 37 3 Full Load Amps 2..3 (total) (.8) (2.6) (2) Full Load Amps 2..3 Service Outlet 5V GFI (amps) 5 5 20 Indoor Blower Motor 2 Maximum Overcurrent Protection 3 Minimum Circuit Ampacity ELECTRIC HEAT DATA Horsepower 2 3 5 2 3 5 2 3 5 Full Load Amps 7.5 0.6 6.7 3..8 7.6 2.7 3.9 6. Unit Only 5 50 60 20 25 30 20 20 25 With () 0.33 HP Power Exhaust 50 50 60 25 25 30 20 20 25 Unit Only 39 2 9 9 20 2 6 7 20 With () 0.33 HP Power Exhaust 52 20 22 25 7 8 2 Electric Heat Voltage 208V 20V 208V 20V 208V 20V 80V 80V 80V 600V 600V 600V 2 Maximum Overcurrent Protection 3 Minimum Circuit Ampacity 2 Maximum Overcurrent Protection 3 Minimum Circuit Ampacity Unit+ Electric Heat Unit+ Electric Heat Unit+ Electric Heat and () 0.33 HP Power Exhaust Unit+ Electric Heat and () 0.33 HP Power Exhaust ELECTRICAL ACCESSORIES Disconnect 7.5 kw 5 5 50 50 60 60 20 25 30 20 20 25 5 kw 50 60 60 60 60 70 30 30 35 25 25 30 22.5 kw 70 80 80 90 80 90 0 0 5 35 35 35 30 kw 90 00 00 0 00 25 50 60 60 0 5 5 5 kw 50 50 50 50 50 75 80 80 80 60 60 70 7.5 kw 39 39 2 2 9 9 9 20 2 6 7 20 5 kw 9 55 53 59 60 66 27 29 33 22 23 26 22.5 kw 69 78 72 8 80 89 39 0 3 32 35 30 kw 88 00 92 0 00 2 50 52 55 0 5 kw 27 5 3 9 39 57 72 7 78 58 60 62 7.5 kw 50 50 50 50 60 60 25 25 30 20 20 25 5 kw 60 60 60 70 70 70 30 35 35 25 25 30 22.5 kw 80 90 80 90 90 00 0 5 5 35 35 0 30 kw 00 0 00 0 0 25 60 60 60 5 5 5 5 kw 50 50 50 75 50 75 80 80 80 60 70 70 7.5 kw 52 52 20 22 25 7 8 2 5 kw 52 58 56 62 63 69 29 3 3 23 25 27 22.5 kw 72 8 75 8 83 92 0 2 5 32 3 36 30 kw 9 03 95 07 03 5 5 53 57 3 5 5 kw 30 8 3 52 2 60 7 76 79 59 6 6 7.5 kw 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5 kw 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 22.5 kw 5W56 5W56 5W56 5W56 5W57 5W57 5W56 5W56 5W56 5W56 5W56 5W56 NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps. Extremes of operating range are plus and minus 0% of line voltage. 2 HACR type breaker or fuse. 30 kw 5W57 5W57 5W57 5W57 5W57 5W57 5W56 5W56 5W56 5W56 5W56 5W56 5 kw 5W57 5W57 5W57 5W57 5W57 5W57 5W56 5W56 5W56 5W56 5W56 5W56 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Factory installed circuit breaker not available. Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 3

ELECTRICAL/ELECTRIC HEAT DATA 8.5 TON 8.5 TON HIGH EFFICIENCY (R-0A) LCH02H Voltage - 60hz 208/230V - 3 Ph 60V - 3 Ph 575V - 3 Ph Compressor Rated Load Amps 5.5.7 Locked Rotor Amps 86 37 3 Compressor 2 Rated Load Amps 5.5.7 Outdoor Fan Motors (2) Power Exhaust () 0.33 HP Locked Rotor Amps 86 37 3 Full Load Amps 2..3 (total) (.8) (2.6) (2) Full Load Amps 2..3 Service Outlet 5V GFI (amps) 5 5 20 Indoor Blower Motor 2 Maximum Overcurrent Protection 3 Minimum Circuit Ampacity ELECTRIC HEAT DATA Horsepower 2 3 5 2 3 5 2 3 5 Full Load Amps 7.5 0.6 6.7 3..8 7.6 2.7 3.9 6. Unit Only 5 50 60 20 25 30 20 20 25 With () 0.33 HP Power Exhaust 50 50 60 25 25 30 20 20 25 Unit Only 38 8 9 20 2 6 7 20 With () 0.33 HP Power Exhaust 0 3 5 20 22 25 7 8 2 Electric Heat Voltage 208V 20V 208V 20V 208V 20V 80V 80V 80V 600V 600V 600V 2 Maximum Overcurrent Protection 3 Minimum Circuit Ampacity 2 Maximum Overcurrent Protection 3 Minimum Circuit Ampacity Unit+ Electric Heat Unit+ Electric Heat Unit+ Electric Heat and () 0.33 HP Power Exhaust Unit+ Electric Heat and () 0.33 HP Power Exhaust ELECTRICAL ACCESSORIES Disconnect 7.5 kw 5 5 50 50 60 60 20 25 30 20 20 25 5 kw 50 60 60 60 60 70 30 30 35 25 25 30 22.5 kw 70 80 80 90 80 90 0 0 5 35 35 35 30 kw 90 00 00 0 00 25 50 60 60 0 5 5 5 kw 50 50 50 50 50 75 80 80 80 60 60 70 7.5 kw 38 38 8 8 9 20 2 6 7 20 5 kw 9 55 53 59 60 66 27 29 33 22 23 26 22.5 kw 69 78 72 8 80 89 39 0 3 32 35 30 kw 88 00 92 0 00 2 50 52 55 0 5 kw 27 5 3 9 39 57 72 7 78 58 60 62 7.5 kw 50 50 50 50 60 60 25 25 30 20 20 25 5 kw 60 60 60 70 70 70 30 35 35 25 25 30 22.5 kw 80 90 80 90 90 00 0 5 5 35 35 0 30 kw 00 0 00 0 0 25 60 60 60 5 5 5 5 kw 50 50 50 75 50 75 80 80 80 60 70 70 7.5 kw 0 0 3 3 5 5 20 22 25 7 8 2 5 kw 52 58 56 62 63 69 29 3 3 23 25 27 22.5 kw 72 8 75 8 83 92 0 2 5 32 3 36 30 kw 9 03 95 07 03 5 5 53 57 3 5 5 kw 30 8 3 52 2 60 7 76 79 59 6 6 7.5 kw 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5 kw 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 22.5 kw 5W56 5W56 5W56 5W56 5W57 5W57 5W56 5W56 5W56 5W56 5W56 5W56 NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps. Extremes of operating range are plus and minus 0% of line voltage. 2 HACR type breaker or fuse. 30 kw 5W57 5W57 5W57 5W57 5W57 5W57 5W56 5W56 5W56 5W56 5W56 5W56 5 kw 5W57 5W57 5W57 5W57 5W57 5W57 5W56 5W56 5W56 5W56 5W56 5W56 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Factory installed circuit breaker not available. Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 32

ELECTRICAL/ELECTRIC HEAT DATA 0 TON 0 TON HIGH EFFICIENCY (R-0A) LCH20H Voltage - 60hz 208/230V - 3 Ph 60V - 3 Ph 575V - 3 Ph Compressor Rated Load Amps 3.5 8 5 Locked Rotor Amps 09 59 0 Compressor 2 Rated Load Amps 3.5 8 5 Outdoor Fan Motors (2) Power Exhaust () 0.33 HP Locked Rotor Amps 09 59 0 Full Load Amps 2..3 (total) (.8) (2.6) (2) Full Load Amps 2..3 Service Outlet 5V GFI (amps) 5 5 20 Indoor Blower Motor 2 Maximum Overcurrent Protection 3 Minimum Circuit Ampacity ELECTRIC HEAT DATA Horsepower 2 3 5 2 3 5 2 3 5 Full Load Amps 7.5 0.6 6.7 3..8 7.6 2.7 3.9 6. Unit Only 50 50 60 30 30 35 20 20 25 With () 0.33 HP Power Exhaust 50 60 70 30 30 35 20 20 25 Unit Only 3 6 53 2 26 29 6 8 20 With () 0.33 HP Power Exhaust 6 9 56 26 27 30 7 9 2 Electric Heat Voltage 208V 20V 208V 20V 208V 20V 80V 80V 80V 600V 600V 600V 2 Maximum Overcurrent Protection 3 Minimum Circuit Ampacity 2 Maximum Overcurrent Protection 3 Minimum Circuit Ampacity Unit+ Electric Heat Unit+ Electric Heat Unit+ Electric Heat and () 0.33 HP Power Exhaust Unit+ Electric Heat and () 0.33 HP Power Exhaust ELECTRICAL ACCESSORIES Disconnect 5 kw 50 60 60 60 60 70 30 30 35 25 25 30 22.5 kw 70 80 80 90 80 90 0 0 5 35 35 35 30 kw 90 00 00 0 00 25 50 60 60 0 5 5 5 kw 50 50 50 50 50 75 80 80 80 60 60 70 60 kw 50 75 50 75 50 75 80 80 90 70 70 70 5 kw 9 55 53 59 60 66 27 29 33 22 23 26 22.5 kw 69 78 72 8 80 89 39 0 3 32 35 30 kw 88 00 92 0 00 2 50 52 55 0 5 kw 27 5 3 9 39 57 72 7 78 58 60 62 60 kw 35 5 39 58 6 66 77 79 82 62 63 66 5 kw 60 60 60 70 70 70 30 35 35 25 25 30 22.5 kw 80 90 80 90 90 00 0 5 5 35 35 0 30 kw 00 0 00 0 0 25 60 60 60 5 5 5 5 kw 50 50 50 75 50 75 80 80 80 60 70 70 60 kw 50 75 50 75 50 75 80 80 90 70 70 70 5 kw 52 58 56 62 63 69 29 3 3 23 25 27 22.5 kw 72 8 75 8 83 92 0 2 5 32 3 36 30 kw 9 03 95 07 03 5 5 53 57 3 5 5 kw 30 8 3 52 2 60 7 76 79 59 6 6 60 kw 38 57 2 6 9 69 79 80 8 63 6 67 5 kw 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 22.5 kw 5W56 5W56 5W56 5W56 5W57 5W57 5W56 5W56 5W56 5W56 5W56 5W56 NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps. Extremes of operating range are plus and minus 0% of line voltage. 2 HACR type breaker or fuse. 30 kw 5W57 5W57 5W57 5W57 5W57 5W57 5W56 5W56 5W56 5W56 5W56 5W56 5 kw 5W57 5W57 5W57 5W57 5W57 5W57 5W56 5W56 5W56 5W56 5W56 5W56 60 kw 5 N/A 5 N/A 5 N/A 5 N/A 5 N/A 5 N/A 5W56 5W56 5 N/A 5W56 5W56 5W56 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Factory installed circuit breaker not available. 5 Disconnect must be field furnished. Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 33

ELECTRICAL/ELECTRIC HEAT DATA 2.5 TON 2.5 TON HIGH EFFICIENCY (R-0A) LCH50H Voltage - 60hz 208/230V - 3 Ph 60V - 3 Ph 575V - 3 Ph Compressor Rated Load Amps 9.6 8.2 6.6 Locked Rotor Amps 36 66. 55.3 Compressor 2 Rated Load Amps 22. 0.6 7.7 Outdoor Fan Motors (2) Power Exhaust () 0.33 HP Locked Rotor Amps 9 75 5 Full Load Amps 3.2.7.5 (total) (6.) (3.) (3) Full Load Amps 2..3 Service Outlet 5V GFI (amps) 5 5 20 Indoor Blower Motor 2 Maximum Overcurrent Protection 3 Minimum Circuit Ampacity ELECTRIC HEAT DATA Horsepower 2 3 5 2 3 5 2 3 5 Full Load Amps 7.5 0.6 6.7 3..8 7.6 2.7 3.9 6. Unit Only 80 80 90 35 35 0 25 30 30 With () 0.33 HP Power Exhaust 80 80 90 35 0 0 30 30 30 Unit Only 62 65 7 28 30 33 22 23 25 With () 0.33 HP Power Exhaust 6 67 73 30 3 3 23 2 26 Electric Heat Voltage 208V 20V 208V 20V 208V 20V 80V 80V 80V 600V 600V 600V 2 Maximum Overcurrent Protection 3 Minimum Circuit Ampacity 2 Maximum Overcurrent Protection 3 Minimum Circuit Ampacity Unit+ Electric Heat Unit+ Electric Heat Unit+ Electric Heat and () 0.33 HP Power Exhaust Unit+ Electric Heat and () 0.33 HP Power Exhaust ELECTRICAL ACCESSORIES Disconnect 5 kw 70 70 80 80 80 80 30 30 35 25 25 30 22.5 kw 70 80 80 90 80 90 0 0 5 35 35 35 30 kw 90 00 00 0 00 25 50 60 60 0 5 5 5 kw 50 50 50 50 50 75 80 80 80 60 60 70 60 kw 50 75 50 75 50 75 80 80 90 70 70 70 5 kw 58 58 6 6 67 67 27 29 33 22 23 26 22.5 kw 69 78 72 8 80 89 39 0 3 32 35 30 kw 88 00 92 0 00 2 50 52 55 0 5 kw 27 5 3 9 39 57 72 7 78 58 60 62 60 kw 35 5 39 58 6 66 77 79 82 62 63 66 5 kw 70 70 80 80 80 80 30 35 35 25 25 30 22.5 kw 80 90 80 90 90 00 0 5 5 35 35 0 30 kw 00 0 00 0 0 25 60 60 60 5 5 5 5 kw 50 50 50 75 50 75 80 80 80 60 70 70 60 kw 50 75 50 75 50 75 80 80 90 70 70 70 5 kw 60 60 6 6 70 70 29 3 3 23 25 27 22.5 kw 72 8 75 8 83 92 0 2 5 32 3 36 30 kw 9 03 95 07 03 5 5 53 57 3 5 5 kw 30 8 3 52 2 60 7 76 79 59 6 6 60 kw 38 57 2 6 9 69 79 80 8 63 6 67 5 kw 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 5W56 22.5 kw 5W56 5W56 5W56 5W56 5W57 5W57 5W56 5W56 5W56 5W56 5W56 5W56 NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps. Extremes of operating range are plus and minus 0% of line voltage. 2 HACR type breaker or fuse. 30 kw 5W57 5W57 5W57 5W57 5W57 5W57 5W56 5W56 5W56 5W56 5W56 5W56 5 kw 5W57 5W57 5W57 5W57 5W57 5W57 5W56 5W56 5W56 5W56 5W56 5W56 60 kw 5 N/A 5 N/A 5 N/A 5 N/A 5 N/A 5 N/A 5W56 5W56 5W57 5W56 5W56 5W56 3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Factory installed circuit breaker not available. 5 Disconnect must be field furnished. Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 3

ELECTRIC HEAT CAPACITIES Volts Input kw Input 7.5 kw 5 kw 22.5 kw 30 kw 5 kw 60 kw Btuh Output No. of Stages kw Input Btuh Output No. of Stages kw Input Btuh Output No. of Stages kw Input Btuh Output No. of Stages kw Input Btuh Output No. of Stages kw Input Btuh Output 208 5.6 9,00.3 38,600 6.9 57,700 2 22.5 76,800 2 33.8 5,300 2 5.0 53,600 2 220 6.3 2,500 2.6 3,000 8.9 6,500 2 25.2 86,000 2 37.8 29,000 2 50. 72,000 2 230 6.9 23,600 3.8 7,00 20.7 70,700 2 27.5 93,900 2.3,000 2 55. 88,000 2 20 7.5 25,600 5.0 5,200 22.5 76,800 2 30.0 02,00 2 5.0 53,600 2 60.0 20,800 2 0 6.9 2,500 2.6 3,000 8.9 6,500 2 25.2 86,000 2 37.8 29,000 2 50. 72,000 2 60 6.9 23,600 3.8 7,00 20.7 70,700 2 27.5 93,900 2.3,000 2 55. 88,000 2 80 7.5 25,600 5.0 5,200 22.5 76,800 2 30.0 02,00 2 5.0 53,600 2 60.0 20,800 2 550 6.3 2,500 2.6 3,000 8.9 6,500 2 25.2 86,000 2 37.8 29,000 2 50. 72,000 2 575 6.9 23,600 3.8 7,00 20.7 70,700 2 27.5 93,900 2.3,000 2 55. 88,000 2 600 7.5 25,600 5.0 5,200 22.5 76,800 2 30.0 02,00 2 5.0 53,600 2 60.0 20,800 2 No. of Stages UNIT CLEARANCES - INCHES (MM) C OPTIONAL OUTDOOR AIR HOOD D DB A Unit Clearance A B C D Top Clearance in. mm in. mm in. mm in. mm Service Clearance 60 52 36 9 36 93 60 52 Minimum Operation Clearance 36 9 36 9 36 9 36 9 NOTE - Entire perimeter of unit base requires support when elevated above the mounting surface. Service Clearance - Required for removal of serviceable parts. Minimum Operation Clearance - Required clearance for proper unit operation. Unobstructed OUTDOOR SOUND DATA Octave Band Linear Sound Power Levels db, re 0 Unit -2 Watts - Center Frequency - Hz Model Number 25 250 500 000 2000 000 8000 Sound Rating Number (SRN) (dba) 092, 02 and 20 76 79 8 83 79 73 66 88 50 75 8 87 85 80 7 70 90 Note - The octave sound power data does not include tonal corrections. Sound Rating Number according to AHRI Standard 270-95 or AHRI Standard 370-200 (includes pure tone penalty). SRN is the overall A-Weighted Sound Power Level, (LWA), db (00 Hz to 0,000 Hz). Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 35

OPTIONAL CONVENTIONAL TEMPERATURE CONTROL SYSTEMS Item Model No. (Description) COMFORTSENSE 8500 COMMERCIAL 5/2 DAY PROGRAMMABLE THERMOSTAT - ZONING/NON-ZONING Optional Accessories Multi-Stage, Communicating Thermostat Zoning and Non-Zoning Models with or without CO 2 Sensing Intuitive Touchscreen Interface Menu-driven Programming Remote Indoor Temperature Sensing (up to nine averaging sensors) Compressor Short-Cycle Protection Relative Humidity Sensor Remote Occupancy Sensing Outside Air Temperature Display Scheduling - Two separate schedules for work days or non-work days Four Time Periods Per Day (non-zoning models, standalone mode) Scheduled Occupancy Control Holiday Scheduling Performance Reports (non-zoning models, standalone mode) Reminders - Two Custom and Routine System Checkup (non-zoning models) Dehumidification/Humiditrol Control Backlit Display Wallplate Furnished C0STAT0FFL (Zoning) C0STAT3FFL (Zoning with CO 2 Sensing) C0STAT03FFL (Non-Zoning) C0STAT22FFL (Non-Zoning with CO 2 Sensing) Catalog No. Remote non-adjustable wall mount 0k temperature sensor C0SNZN0AE2 7W37 Remote non-adjustable wall mount k temperature sensor C0SNZN08AE 9L6 X57 X58 X55 X56 Locking cover (clear) C0MISC5AE- 39P2 Up to nine of the same type remote temperature sensors can be connected in parallel. Zonebus Network Cable (Purple) - Zoning Models Twisted pair 00% shielded communication cable, Red and Black 22 AWG, purple jacket, rated at 75 C, 300V, Plenum rated Insulation - Low smoke PVC, NEC, CMP Sysbus Network Cable (Yellow) - Non-Zoning Models Twisted pair 00% shielded communication cable, Red and Black 22 AWG, yellow jacket, rated at 75 C, 300V, Plenum rated Insulation - Low smoke PVC, NEC, CMP 500 ft. box - C0MISC05AE- 23W99 000 ft. box - C0MISC06AE- 2W00 2500 ft. roll - C0MISC07AE- 2W0 500 ft. box - C0MISC00AE- 27M9 000 ft. box - C0MISC0AE- 9L63 2500 ft. roll - C0MISC0AE- 68M25 Energence Packaged Electric / Electric 7.5 to 2.5 Ton / Page 36