KR Series Air Defrost Unit Coolers Operating and Installation Manual

Similar documents
KR Electrical Defrost Unit Coolers (PN E108318_E)

SM/SV-Space Master Unit Coolers (E R.0)

Installation, Operation, and Maintenance Information

SM/SV Series Space Master Unit Coolers Operating and Installation Manual

STC Series Twin Unit Coolers (E329630_A)

DT/DTX Series Unit Coolers (R0 E316013)

KTL Two-Way Low Profile Evaporators

High Profile Evaporator

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

PRODUCT. TWB Two-Way Air Defrost Unit Coolers PRODUCT DATA & INSTALLATION. High Temperature (35 o F / 1.7 o C or Higher) Applications

LOW PROFILE UNIT COOLER. Technical Guide. Models RLC Air Defrost ELC/EFC Electric Defrost GLC Hot Gas Defrost. CH-LOPTB May,

Low Profile Unit Coolers

Condensing Unit Installation and Operating Instructions

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N

Low Profile Unit Coolers

Condensing Unit Installation and Operating Instructions

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

T-SERIES Air Conditioner. T50 Model INSTRUCTION MANUAL nvent Rev. F P/N

Drop-In Refrigeration System

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

T-Series Air Conditioner T15 Model

PROAIR Air Conditioner. CR43 Model INSTRUCTION MANUAL nvent Rev. H P/N

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

KR Series COMPACT UNIT COOLERS. Technical Bulletin: KRUC_005_ Products that provide lasting solutions.

IOM 410. Installation Operation Maintenance Information. UNIT COOLERS Super-Flo (SD Models) Easy-Flo (EF Models) Table of Contents

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

T-Series Air Conditioner T53 Model

Half Round Evaporators

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL nvent Rev. I P/N

Low Flow Unit Coolers

Center Mount Unit Coolers

T-Series Air Conditioner T20 Model

Unit Coolers. Installation and Operations Manual. Table of Contents. H-IM-UC November 2017 Part No

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP MODELS: TABLE OF CONTENTS LIST OF FIGURES

V-SERIES Air Conditioner. VA08 Model INSTRUCTION MANUAL nvent Rev. F P/N

GENESIS Air Conditioners. All Models INSTRUCTION MANUAL nvent Rev. K P/N

Low Velocity Center Mount Unit Cooler. Technical Guide. Models LWA - Air Defrost LWE - Electric Defrost LWG - Hot Gas Defrost.

Lo-Aire Unit Coolers. Technical Guide. bn-lftb May Models LO Air Defrost LOD Electric Defrost LOG Hot Gas Defrost.

Air Cooled Condenser Installation and Operating Instructions

Air-Cooled Fluid Cooling Units (P/N E R2)

INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC LIST OF SECTIONS LIST OF FIGURES

TLV Low Velocity Evaporators

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS FOR INDUSTRIAL COOLERS

KTL Two-Way Low Profile Unit Coolers

BTL Two-Way Low Profile Evaporators

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

CABINET PARTS For Models: ED5LHEXTD00 (Universal Silver)

Installation, Operation, and Maintenance Information

WIBR SERIES. Unit Coolers - Technical Catalog Hunt St - Pryor, OK Fax

INSTALLATION INSTRUCTIONS

OWNER S MANUAL. Vintage Signature Series models: AC750, AC1050, AC1100, AC1250, AC1500, AC1750. Proudly Made in the USA.

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES

LOW PROFILE UNIT COOLER

an ISO 9001:2008 Registered Company GOLL ST. - SAN ANTONIO, TX ph fax MINI SPACE SAVER HEAT /COOL

maintenance should only be performed by a trained, qualified person. Consumer service is recommended only for filter replacement.

Service Step by Step Trouble-Shooting Check-List

Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS

CABINET PARTS. For Models: ASD2522WRW01, ASD2522WRB01, ASD2522WRS01, ASD2522WRD01 (White) (Black) (Stainless) (Universal Silver)

SECTION (15530) - REFRIGERANT PIPING

INSTALLATION and OPERATING. INSTRUCTIONS for. SMZP26 Series. elf-contained Freezers

COMFORT PACK INSTALLATION AND MAINTENANCE INSTRUCTIONS

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS WALK-IN COOLERS SERIES LS-LP-LA-LV

SECTION (15530) - REFRIGERANT PIPING

CABINET PARTS For Models: ED5RHEXNL00 (Stainless VCM)

INSTALLATION INSTRUCTIONS

RPI Industries, Inc.

OWNER S MANUAL. Vintage Classic HEAT COOL models. Proudly Made in the USA

CABINET PARTS REFRIGERATOR. For Models: ED5VHGXMQ00, ED5VHGXMT00, ED5VHGXMB00 (White) (Biscuit) (Black) 8 03 Litho In U.S.A. (kdj)

Condensing Unit and Refrigeration System Installation & Operations Manual R448A/R449A

A Series T 3. Unit Coolers - Technical Catalog. Product Benefits: Comdustrial TM Refrigeration. Adaptability- Durability- Serviceability-

REFRIGERANT PIPING

SPX SERIES PACKAGED AIR CONDITIONING/HEAT PUMP UNITS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

INSTALLATION AND COMMISSIONING MANUAL. Neos 100S Integra 20X, 30S, 35X, 40X, 50X

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

INSTALLATION INSTRUCTIONS

an ISO 9001:2008 Registered Company MINI SPACE SAVER HEAT /COOL/DEFROST QUZ-A VUZ-A

Installation Instructions

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

WKS 4000 SERIES (USA only) --INSTALLATION INSTRUCTIONS--

ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL

SM/SV Series PRODUCT COOLERS. Technical Bulletin: SMSV_001_ Products that provide lasting solutions.

INSTALLATION and OPERATION INSTRUCTIONS

Super-Flo Low Profile Unit Cooler

REFRIGERATION SYSTEMS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS FOR LOW PROFILE-UNIT COOLERS AND DUAL FLOW UNIT COOLER

CABINET PARTS For Model: ED5GTGXNQ14, ED5GTGXNB14 (White) (Black)

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

TABLE OF CONTENTS INTRODUCTION. NOTE: Read the entire instruction manual before starting the installation.

CABINET PARTS For Model: KSSS48QJX00 (Stainless Steel)

BLG-HGP Model Bottom Mounted Full-Length Swing Glass Door Freezer Merchandisers

Installation Instruction

CABINET PARTS For Models: ASD2522WRS07 (Stainless)

INSTALLATION INSTRUCTIONS

Transcription:

KR Series Air Defrost Unit Coolers Operating and Installation Manual KR Air Defrost Unit Coolers (PN E108317_L)

TABLE OF CONTENTS 1 RECEIPT OF EQUIPMENT... 2 1.1 INSPECTION... 2 1.2 LOSS OF GAS HOLDING CHARGE... 2 2 LOCATION RECOMMENDATIONS... 2 3 UNIT MOUNTING... 2 4 DRAIN LINE... 4 5 REFRIGERATION PIPING... 4 6 REFRIGERANT DISTRIBUTOR... 6 7 EXPANSION VALVE... 7 8 WIRING... 8 9 PRE-STARTUP...10 10 REPLACEMENT PARTS...10 TABLES Table 1 Unit Dimensions and Connections Sizes... 3 Table 2 Distributor Nozzle Selections... 6 Table 3 Recommended Expansion Valves... 7 Table 4 Units Electrical Information... 8 Table 5 Replacement Parts... 11 FIGURES Figure 1 Unit Dimensions... 3 Figure 2 Multiple Unit Coolers Controlled By A Single Solenoid... 5 Figure 3 Multiple Unit Coolers Controlled By Multiple Solenoids... 5 Figure 4 Air Defrost Wiring Diagram... 9 Figure 5 Air Defrost Wiring Diagram with Timer... 9 Figure 6 Replacement Parts... 10 KR Air Defrost Unit Coolers (PN E108317_L) 1

1 RECEIPT OF EQUIPMENT 1.1 INSPECTION All equipment should be carefully checked for damage or shortages as soon as it is received. Each shipment should be carefully checked against the bill of lading. If any damage or shortage is evident, a notation must be made on the delivery receipt before it is signed and a claim should then be filed against the freight carrier. 1.2 LOSS OF GAS HOLDING CHARGE Each unit cooler is leak tested, evacuated to remove moisture and then shipped with a gas holding charge. Absence of this charge may indicate a leak has developed in transit. The system should not be charged with refrigerant until it is verified that there is no leak or the source of the leak is located. 2 LOCATION RECOMMENDATIONS Air defrost unit coolers must have proper airflow to maintain a uniform room temperature and have a complete defrost. These units are draw thru design thus drawing air thru the cooling coil and discharging it into the room via the unit fans. For best performance it is desirable to arrange the air discharge toward the door of the cooler to minimize the entrance of warm moist air when the door is open. The unit must be at least 12 inches from the wall to assure proper air intake. 3 UNIT MOUNTING The unit cooler may be suspended with 3/8" diameter hanger rods or flush mounted to the ceiling using 5/16 minimum lag screws with flat washers. Rods should be double nutted top and bottom. The unit must be level in all directions to insure proper drainage of condensate. Suspended units must have sufficient clearance above for cleaning the top. KR Air Defrost Unit Coolers (PN E108317_L) 2

Figure 1 Unit Dimensions Table 1 Unit Dimensions and Connections Sizes MODEL DIMENSIONS (INCHES) CONNECTIONS ODS (IN) NUMBERS A B C LIQUID SUCTION KR16A-040-18 29-1/8 1/2 5/8 KR16A-054-18 29-1/8 1/2 5/8 KR16A-060-18 29-1/8 1/2 5/8 KR26A-072-36 47-1/8 1/2 7/8 KR26A-089-36 47-1/8 1/2 7/8 KR26A-105-36 47-1/8 1/2 7/8 KR26A-115-36 47-1/8 1/2 7/8 KR26A-125-36 47-1/8 1/2 7/8 KR36A-134-54 65-1/8 1/2 7/8 KR36A-159-54 65-1/8 1/2 7/8 KR36A-170-54 65-1/8 1/2 1 1/8 KR46A-216 36 72 83-1/8 1/2 1 1/8 KR56A-242 54 90 101-1/8 1/2 1 1/8 KR66A-310 54 108 119-1/8 1/2 1 1/8 KR66A-340 54 108 119-1/8 1/2 1 3/8 KR14A-058-18 29-1/8 1/2 5/8 KR24A-096-36 47-1/8 1/2 7/8 KR24A-117-36 47-1/8 1/2 7/8 KR34A-143-54 65-1/8 1/2 7/8 KR34A-173-54 65-1/8 1/2 1 1/8 KR44A-191 36 72 83-1/8 1/2 1 1/8 KR44A-232 36 72 83-1/8 1/2 1 1/8 KR54A-290 54 90 101-1/8 1/2 1 1/8 KR64A-348 54 108 119-1/8 1/2 1 3/8 KR Air Defrost Unit Coolers (PN E108317_L) 3

4 DRAIN LINE The drain line should be as short and as steeply pitched as possible with a minimum of 1/4" drop per running foot. Any traps in the drain line must be located in an ambient above freezing. If the temperature surrounding the trap or drain line is below freezing it must be wrapped with a drain line heater. Be sure to also wrap the unit drain coupling. Cover the drain line, drain coupling and heat tape with insulation. Be sure to follow the manufacturer's recommendation when installing the drain line heat tape. A union is recommended for ease of installation and future servicing. The union should be located as close to the drain pan as possible. Use two wrenches when tightening to prevent the drain fitting from twisting and damaging the unit. Support long runs of drain line (i.e. more than a few feet) by hangers to avoid damage to the drain pan. 5 REFRIGERATION PIPING System design must conform to all codes, laws and regulations applying to the site of installation. In addition the safety code for mechanical refrigeration. Refrigerant line sizes and piping techniques should be obtained from the ASHRAE Guide or equivalent reference. Under no circumstances should the refrigerant connection size of the unit be used as the basis for sizing the lines. The horizontal suction line should slope away from the unit toward the compressor. Vertical suction risers may require a trap at the bottom of the riser for proper oil return. For Food Service installations seal any joint between unit cooler and cooler wall with a sealant Listed by the National Sanitation Foundation. Special Instructions for Units Using Carbon Dioxide (R744) These unit coolers are intended to utilize carbon dioxide only in a secondary loop or a cascade system. As such, unit installation must comply with the following instructions: A. If the refrigeration system is de-energized, venting of the R744 through the pressure regulating relief valves on the refrigeration system can occur. In such cases, the system may need to be recharged with R744, but in any case, the pressure regulating relief valve(s) are not to be defeated or capped. The relief setting shall not be altered. B. A sufficient number of pressure relief and pressure regulating relief valves may need to be provided based on the system capacity and located such that no stop valve is provided between the relief valves and the parts or section of the system being protected. To properly protect and control systems using pumped liquid overfeed R744, the solenoid, isolation, and pressure relief valves shall be arranged as shown in either Figure 2 or 3, according to the solenoid valve arrangement. To handle the requirements of liquid R744 high pressure solenoid valves are to be used. KR Air Defrost Unit Coolers (PN E108317_L) 4

Figure 2 Multiple Unit Coolers Controlled By A Single Solenoid Figure 3 Multiple Unit Coolers Controlled By Multiple Solenoids KR Air Defrost Unit Coolers (PN E108317_L) 5

6 REFRIGERANT DISTRIBUTOR Distributor nozzles are included using a refrigerant distributor with a changeable nozzle design on most units. The nozzle(s) are packed in individual plastic envelopes along with a retainer ring and instruction card. The instruction card tells what refrigerant the nozzle is to be used with. There may be 1, 2 or 3 envelopes with nozzles located near the distributor. The nozzles provided with the unit have been selected for design conditions of 9 F to 11 F T.D. and 95 F liquid refrigerant at the expansion valve inlet. If the unit will be operated at conditions that are substantially different from these conditions, it may be necessary to select a different size nozzle. Contact the factory for advice. The nozzle must be installed before the expansion valve is installed. There are nozzle identification numbers stamped on one side of the nozzle. Be sure to insert the nozzle into the distributor with these numbers visible in case identification is required later. The nozzle is held in place by a retainer ring that is easily inserted or removed with a pair of needle nose pliers. The standard distributor nozzles provided with the units are listed in Table 2. Table 2 Distributor Nozzle Selections DISTRIBUTOR NOZZLE SELECTIONS R-404A / MODEL NUMBERS R-134a R-22 R-507 KR16A-040 - - - KR16A-054 L-1/2 L-1/2 L-3/4 KR16A-060 L-3/4 L-1/2 L-1 KR26A-072 L-3/4 L-1/2 L-1 KR26A-089 L-1 L-3/4 L-1 1/2 KR26A-105 L-1 1/2 L-1 L-1 1/2 KR26A-115 L-1 1/2 L-1 L-1 1/2 KR26A-125 L-1 1/2 L-1 L-1 1/2 KR36A-134 L-1 1/2 L-1 1/2 L-2 KR36A-159 L-2 L-1 1/2 L-2 1/2 KR36A-170 L-2 L-1 1/2 L-2 1/2 KR46A-216 L-2 1 /2 L-2 L-3 KR56A-242 L-3 L-2 L-3 KR66A-310 - L-2 1/2 L-3 KR66A-340 - L-3 L-4 KR14A-058 L-1/2 L-1/3 L-1/2 KR24A-096 L-1 L-1/2 L-1 KR24A-117 L-1 L-3/4 L-1 KR34A-143 L-1 1/2 L-3/4 L-1 KR34A-173 L-2 L-1 L-1 1/2 KR44A-191 L-2 L-1 L-1 1/2 KR44A-232 L-2 L-1 1/2 L-2 KR54A-290 L-2 1 /2 L-1 1/2 L-2 1/2 KR64A-348 J-3 J-2 J-2 1/2 Distributor nozzle selections are based on +25 F suction temperature, 10 F T.D. and 95 F liquid temperature. KR Air Defrost Unit Coolers (PN E108317_L) 6

7 EXPANSION VALVE Table 3 Recommended Expansion Valves MODEL BTUH@ +25'F SUCTION TEMPERATURE NUMBERS 10'F T.D. R-134a R-22 R-404A * KR16A-040 4,000 SBFJE-AA-C SBFVE-AA-C SBFSE-AA-C EGJE-1/4-C EGVE-1/3-C EGSE-1/4-C KR16A-054 5,400 KR14A-058 5,800 SBFJE-AA-C SBFVE-AA-C SBFSE-AA-C KR16A-060 6,000 EGJE-1/2-C EGVE-1/2-C EGSE-1/2-C KR26A-072 7,200 SBFVE-AA-C KR26A-089 8,900 SBFJE-A-C EGVE-3/4-C SBFSE-A-C EGJE-1-C EGSE-1/2-C KR24A-096 9,600 KR26A-105 10,500 SBFSE-A-C KR26A-115 11,500 SBFVE-A-C EGSE-1-C KR24A-117 11,600 EGVE-1-C KR26A-125 12,500 KR36A-134 13,400 KR34A-143 14,400 KR36A-159 15,900 SBFVE-A-C KR36A-170 17,000 EGVE-1½-C KR34A-173 17,400 KR44A-191 19,200 KR46A-216 21,600 SBFJE-B-C SBFSE-B-C KR44A-232 23,200 EGJE-1½-C SBFVE-B-C EGSE-1½-C KR56A-242 24,200 EGVE-2-C KR54A-290 29,000 SBFJE-C-C SBFVE-B-C SBFSE-B-C KR66A-310 31,000 EGJE-2-C EGVE-3-C EGSE-2-C KR66A-340 34,000 SBFSE-C-C KR64A-348 34,800 *If R507 is used, change S to P. For example, SBFSE-B-C (R404A) becomes SBFPE-B-C (R- 507). Before installing the unit, install the expansion valve and connect the equalizer tube (not required on single fan units). Expansion valves are adjusted at the factory prior to shipment. The setting will be okay for many applications, but in other applications adjustments may need to be made. It is important that the operation of the expansion valve be checked out after the system has balanced out at the desired room temperature. If the coil is being starved it is necessary to reduce the superheat setting of the valve by turning the adjusting stem counter-clockwise. If the superheat is too low it is necessary to increase the superheat setting of the valve by turning the adjusting stem clockwise. It is recommended that for a 10 F to 12 F T.D. system, the valve should be adjusted to maintain 5 F to 6 F superheat. To prevent overshooting the desired setting, only one turn of the stem should be made at a time. As much as 30 minutes may be required for the new balance to take place after an adjustment is made. Always tighten the adjusting stem packing nut and replace the seal cap tightly after the adjustment is complete. KR Air Defrost Unit Coolers (PN E108317_L) 7

8 WIRING WARNING: All power to the evaporator must be off before opening any compartments, cleaning or performing maintenance. The electrical data for the unit is marked on the unit nameplate. Field wiring should comply with N.E.C. and local codes. The field wiring compartment is constructed as part of the unit cooler enclosure. Wiring connections are made at the terminal block provided inside the unit on the end opposite the refrigerant connections. The unit must be grounded. Refer to Table 4 for unit amps. Table 4 Units Electrical Information UNIT TOTAL FULL LOAD AMPS MODEL PSC MOTORS EC MOTORS SHADED POLE MOTORS NUMBER 115/1/60 208/230/1/60 115/1/60 208/230/1/60 460/1/60 KR16A-040 0.6 0.3 0.8 0.4 0.6 KR16A-054 0.6 0.3 0.8 0.4 0.6 KR16A-060 0.6 0.3 0.8 0.4 0.6 KR26A-072 1.2 0.6 1.6 0.8 1.2 KR26A-089 1.2 0.6 1.6 0.8 1.2 KR26A-105 1.2 0.6 1.6 0.8 1.2 KR26A-115 1.2 0.6 1.6 0.8 1.2 KR26A-125 1.2 0.6 1.6 0.8 1.2 KR36A-134 1.8 0.9 2.4 1.2 1.8 KR36A-159 1.8 0.9 2.4 1.2 1.8 KR36A-170 1.8 0.9 2.4 1.2 1.8 KR46A-216 2.4 1.2 3.2 1.6 2.4 KR56A-242 3.0 1.5 4.0 2.0 3.0 KR66A-310 3.6 1.8 4.8 2.4 3.6 KR66A-340 3.6 1.8 4.8 2.4 3.6 KR14A-058 0.6 0.3 0.8 0.4 0.6 KR24A-096 1.2 0.6 1.6 0.8 1.2 KR24A-117 1.2 0.6 1.6 0.8 1.2 KR34A-143 1.8 0.9 2.4 1.2 1.8 KR34A-173 1.8 0.9 2.4 1.2 1.8 KR44A-191 2.4 1.2 3.2 1.6 2.4 KR44A-232 2.4 1.2 3.2 1.6 2.4 KR54A-290 3.0 1.5 4.0 2.0 3.0 KR64A-348 3.6 1.8 4.8 2.4 3.6 KR Air Defrost Unit Coolers (PN E108317_L) 8

Figure 4 Air Defrost Wiring Diagram Figure 5 Air Defrost Wiring Diagram with Timer KR Air Defrost Unit Coolers (PN E108317_L) 9

9 PRE-STARTUP Check fan set screws, electrical terminals and all other fasteners for tightness. Be sure the thermostatic expansion valve bulb is properly located and strapped. 10 REPLACEMENT PARTS Listed below are the major replacement parts. When ordering parts it is imperative that you obtain the complete model and serial number of the unit. Figure 6 Replacement Parts KR Air Defrost Unit Coolers (PN E108317_L) 10

Table 5 Replacement Parts Item General Description Options Description Krack Aftermarket Part Number 1 MOTOR SP 460V E206446 PSC 115V E206447 PSC 230V E206448 EC 115V E410410001 EC 208/230V E410410001 2 MOTOR MOUNT MOTOR MOUNT E316578 3 FAN BLADE LOW NOISE FAN BLADE E316580 4 FAN GUARD PLASTIC E316655 WIRE E316579 5 HEADER COVER FRONT HEADER COVER FRONT E108007 6 HEADER COVER BACK HEADER COVER BACK E108031 7 RB COVER FRONT RB COVER FRONT E108009 8 RB COVER BACK RB COVER BACK E108010 9 HANGER HANGER E108013 10 FAN/TOP PANEL 1 FAN E108001 2 FAN E108002 3 FAN E108003 4 FAN E108004 5 FAN E108005 6 FAN E108006 11 DRAIN PAN 1 FAN CE107073 2 FAN CE107075 3 FAN CE107076 4 FAN CE107077 5 FAN CE107078 6 FAN CE107079 12 WIRING HARNESS 1 FAN 115-230V E206449 2 FAN 115-230V E206450 3 FAN 115-230V E206451 4 FAN 115-230V E206452 5 FAN 115-230V E206453 6 FAN 115-230V E206454 1 FAN 460V E206518 2 FAN 460V E206519 3 FAN 460V E206520 4 FAN 460V E206521 5 FAN 460V E206522 6 FAN 460V E206523 13 ALUMINUM DRAIN FITTING E206462 14 ALUMINUM CONDUIT COUPLING E206463 15 DRAIN FITTING GASKET E206464 16 THERMOSTATS DEFROST TERM (14T32) E206100 HEATER SAFETY (14T21) 109560 FAN DELAY (14T31) E201818 KP-73 E205004 17 PAN HEATERS 1 FAN 115V E201883 1 FAN 230V E201884 2 FAN 115V E201889 KR Air Defrost Unit Coolers (PN E108317_L) 11

2 FAN 230V E201890 3 FAN 115V E201892 3 FAN 230V E201893 4 FAN 115V E201895 4 FAN 230V E201896 5 FAN 115V E201898 5 FAN 230V E201899 6 FAN 115V E201901 6 FAN 230V E201902 18 DRAIN PAN HEATER BRACKET E107025 19 FACE HEATER SUPPORT CLIP E102007 20 COIL HEATERS 230V 1 FAN E206455 230V 2 FAN E206457 230V 3 FAN E206458 230V 4 FAN E206459 230V 5 FAN E206460 230V 6 FAN E206461 21 EXPANSION VALVE SBFVE-A-ZP40 E205324 SBFSE-A-ZP E205360 EGVE-2-ZP40 E205735 EGVE-1 1/2-ZP40 E205792 EGVE-1-ZP40 E205821 EGVE-3/4-ZP40 E205838 EGVE-1/2-ZP40 E205854 SBFSE-B-ZP E205920 SBFVE-B-ZP40 E205927 SBFVE-AA-ZP40 E205973 EGVE-3-ZP40 E206058 EGSE-2-ZP E206165 SBFSE-AA-ZP E206169 EGSE-1-ZP E206178 EGSE-1/2-ZP E206212 EGSE-1/4-ZP E206235 EGSE-1½-ZP E206317 SBFVE-C-ZP40 E206600 SBFSE-C-ZP E311124 22 LONG THROW ADAPTERS GALVANIZED E202347 KR Air Defrost Unit Coolers (PN E108317_L) 12