SLANT/FIN AUTOMATIC VENT DAMPER For Galaxy, Sentinel and Sentry Series Boilers INSTALLATION INSTRUCTION MANUAL AND TROUBLESHOOTING GUIDE

Similar documents
User s Information Manual

WARNING FLAIR INTERNATIONAL CORPORATION 600 OLD WILLETS PATH HAUPPAUGE, NEW YORK U.S.A. TEL.: (516) FAX: (516) AMERICAN

(Information about THERMAL dampers for gas-fired appliances available on request.) WARNING

User s Information Manual Galaxy GG/GX Series, Sentry S/SX Series and Sentinel SE Series Gas Boilers with Continuous Burning Pilot

ELECTRONIC FIREPLACE DAMPER

ELECTRONIC FIREPLACE DAMPER

SENTRY. High efficiency, cast-iron gas boiler LOWER PROFILE MAKES PROBLEM INSTALLATIONS EASY

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

SENTINEL HOT WATER MODELS SE-70 THROUGH SE-245 GAS-FIRED CAST-IRON BOILERS FOR NATURAL AND L.P. PROPANE GASES INSTALLATION AND OPERATING INSTRUCTIONS

GAS-FIRED CAST-IRON BOILERS FOR NATURAL AND L.P. PROPANE GASES INSTALLATION AND OPERATING INSTRUCTIONS

INSTALLATION INSTRUCTIONS

MODEL HS115-3, HS115-4 & HS115-5 WIRING DIAGRAM ADDENDUM

CSD-1 COMMERCIAL BOILER CONTROLS

D896 Automatic Vent Damper

High efficiency, cast-iron gas boiler

SC2000 CONTROLLER INSTALLATION AND OPERATION MANUAL

SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.) CONGRATULATIONS!

STEAM / GAS APPLICATION GUIDE

LGB Gas fired boiler

Energy Manager INSTALLATION INSTRUCTIONS. Keep these instructions with the boiler at all times for future reference

User s Information Manual Lynx Direct-Vent Sealed Combustion Condensing Boiler Model LX-90, LX-120, LX-150

EUTECTIC EC-10DV Series

EG & PEG Series 5 EGH Series 5

Mighty Venter Power Vent System

VSL II QUICK START GUIDE

Installation Requirements for Models:

Conversion Instructions Logano G234X. Gas boiler. Please read carefully before installing and servicing. Gas boiler

SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.) CONGRATULATIONS!

RSIF power venter USA CAN READ AND SAVE THESE INSTRUCTIONS! Installation and operation manual. Product information Chapters 1 + 2

Crown Boiler Company

POWER VENTER SYSTEM. Model: PVO-300, PVO-600

POWER VENTER. Model: PVE Series

APPLICATION GUIDE. HOT WATER/GAS Modular Boilers CONTENTS INTRODUCTION OF FRESH WATER CODES AND STANDARDS LOCAL CODE APPROVALS

EGH Series 5. Control Supplement. EGH-105 to EGH-125 Natural gas CSD-1 control system

DOMESTIC WATER HEATER OIL FIRED

WATER-TUBE POOL HEATERS

RS Chimney Fan for Gas & Oil Applications

INSTALLER'S GUIDE MASONRY CHIMNEY VENT KIT WARNING: BAYVENT800B 18- CH23D2-05

DIVISION FINNED WATER-TUBE WATER HEATERS

WATER-TUBE POOL HEATERS

INSTALLATION AND SERVICE MANUAL

ASX7-4-IOM-6 J

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners

MGB CAST IRON GAS FIRED BOILERS FOR FORCED HOT WATER With Hydrolevel Control. Models MGB-50J MGB-75J MGB-100J MGB-125J MGB-150J MGB-170J MGB-200J

XIII Troubleshooting

Columbia Boiler Company

XTHERM, TYPE WH - MODELS 1005A- 2005A DIVISION COMMERCIAL, WATER-TUBE, CONDENSING GAS DOMESTIC WATER HEATERS

INSTALLATION AND SERVICE MANUAL

DIVISION COMMERCIAL, GRID-TYPE, FINNED-TUBE, GAS DOMESTIC WATER HEATERS

RSIF Power Venter USA CAN. Product Information. ... Chapters Mechanical Installation. ... Chapter 3. Electrical Installation. ...

WATER HEATERS / BOILERS GSB8-E. Gas-Fired Steam Boiler PRODUCT SPECIFICATIONS. AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh GSB E

DIVISION FINNED WATER-TUBE BOILERS

SYSTEM CONTROL KIT. Model: CK-62. Designed for use on SWG Series Power Vent Hoods for controlling oil fired heating appliances with 120 VAC controls.

GSB8. CONSERVATOR Gas-Fired Steam Boiler. AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh GSB S MODEL NUMBER IDENTIFICATION FEATURES

PVE SERIES POWER VENTER SYSTEM MANUAL

WATER HEATERS / BOILERS GWB8-E. Gas-Fired Hot Water Boiler PRODUCT SPECIFICATIONS. AFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh

User s Information Manual

ASX7-5-IOM-3 J

SERIES 35-63J APPLICATIONS FEATURES SPECIFICATIONS AGENCY CERTIFICATIONS

VSL II QUICK START GUIDE

User s Information Manual Models: 45, ,000 Btu/hr

DIVISION FINNED WATER-TUBE BOILERS

CMO32 CMO50 DOMESTIC WATER HEATER OIL-FIRED. Models: CMO32 CMO50

EBC 10 Fan Control USA CAN. Product Information. ... Chapter 1+2. Mechanical Installation. ... Chapter 3. Electrical Installation. ...

DIVISION FINNED WATER-TUBE BOILERS

IMPORTANT INSTRUCTIONS - OPERATING MANUAL

User s Information Manual

TJERNLUND PRODUCTS, INC.

120 VAC SYSTEM CONTROL KIT

SWIMMING POOL & SPA HEATER D-2

CONVERSION TO PROPANE MANUAL M-Series Condensing Boiler. Wall-Mounted, Gas-Fired Boiler

AFUE up to 83.9% Heating Input 50,000 to 299,000 Btuh

READ AND SAVE THESE INSTRUCTIONS READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE OR MAINTAIN THE PRODUCT DESCRIBED. PROTECT YOURSELF AN

FINNED WATER-TUBE POOL HEATERS

WATER MODELS S-34 THROUGH S-150 INSTALLATION AND OPERATING INSTRUCTIONS

DIVISION WALL-HUNG STAINLESS STEEL HEATING BOILERS

STARFIRE IV SERIES 4 WATER OIL FIRED CAST IRON BOILER

24 VAC SYSTEM CONTROL KIT

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVN/P-400 INDIRECT FIRED SPACE HEATERS

COMBUSTION AIR SYSTEM

LGB. Control Supplement. Gas fired boiler. Universal Control System. Series 2 Propane gas. Contents

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVO-400 INDIRECT FIRED SPACE HEATERS

Models 0042B, 0066B, 0090B 0135B & 0180B Type H

100T399-SOLA SUPPLEMENT TO INSTALLATION & OPERATION MANUAL INCLUDED WITH WATER HEATER (SERIAL NUMBERS BEGINNING LK AND LATER)

This manual should be maintained in legible condition and kept adjacent to the heater or in a safe place for future reference.

Installation, Operation and Service Manual

RS Chimney Fan for Gas & Oil Applications

GPC PASTA PRO INSTALLATION & USER OPERATION MANUAL

WPSB SERIES II GAS-FIRED HOT WATER BOILERS

RS chimney fan for gas and oil applications

RS Chimney Fan For Gas & Oil Applications. Installation & Operating Manual USA CAN

USER S INFORMATION MANUAL

INSTALLATION AND SERVICE MANUAL

RS Chimney Fan for Solid Fuel Applications

SYSTEM CONTROL KIT Model: CK-41P

GALAXY HOT WATER BOILERS INSTALLATION AND OPERATING INSTRUCTIONS. Models GG-75H through GG-399H and Models GXH-105 through GXH-190

INSTALLATION AND OPERATING INSTRUCTIONS TABLE OF CONTENTS IMPORTANT

MODEL EH ELECTRIC BOILER OPERATION AND INSTALLATION INSTRUCTIONS

RSHT Volko Supply USA CAN READ AND SAVE THESE INSTRUCTIONS! Installation and operation manual

VICTORYII. Cast-iron, power vent gas boiler BOILER FOR OLDER HOMES.

Transcription:

INSTALLATION INSTRUCTION MANUAL AND TROUBLESHOOTING GUIDE SLANT/FIN AUTOMATIC VENT DAMPER For Galaxy, Sentinel and Sentry Series Boilers The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1-latest edition. In addition, where required by the authority having jurisdiction, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, No. CSD-1. The vent damper shipped with your boiler may be a different model than illustrated above. THIS MANUAL MUST BE LEFT WITH OWNER AND SHOULD BE HUNG ON OR ADJACENT TO THE BOILER FOR REFERENCE. WARNING By failing to follow the WARNING instructions listed below, a hazardous condition such as explosion, carbon monoxide poisoning, fire or all of these could result. This device is design certified by C.S.A. for use only on specific Slant/Fin Corporation gas boiler models. These boilers must also be equipped with a plate or rating plate which states that the boiler must* (may*) be used with a Slant/Fin Corp. automatic vent damper device and indicates the proper vent damper model or part number (See Table 1). * Boilers under 300,000 Btu/hr. input MUST use a vent damper. Note: GG-75 HES (Constant circulation), MAY use a vent damper. Boilers with 300,000 Btu/hr. input or greater equipped with IID (intermittent pilot ignition) MAY use a vent damper. Boilers with 300,000 Btu/hr. input equipped with continuous pilot and VR8300A gas valve MAY use a vent damper. This device must be installed and inspected annually by a qualified installer in accordance with the Slant/Fin vent damper installation instructions, Slant/Fin boiler installation instructions and the vent damper manufacturer's installation instructions included with this damper. If improperly installed, a hazardous condition such as explosion or carbon monoxide poisoning could result. If installed improperly, all vent damper and boiler warranties shall be voided. Use of this device on boilers other than those indicated above is not permitted. CAUTION: When servicing controls all wires must be labeled prior to disconnection. Wiring errors can cause improper and dangerous operation. This device must be installed on the outlet end of the draft hood of the boiler as close to the draft hood as practicable, and without modification of the draft hood (see figures 3 through 7). The inlet size of the vent damper must be the same nominal trade size as the outlet of the draft hood. See Table 1 for the boiler models and their corresponding vent damper models. The device must be located in a venting system or section of a venting system so that it serves only the single appliance for which it is installed. Clearances of not less than 6 inches (152 mm) must be maintained from combustible materials, with provisions for access. If the boiler will not fire, DO NOT jump any of the safety controls (the vent damper circuit is part of the safety control circuit). Check page 12 of this manual for troubleshooting guide. Part No. 41-1676. Printed in U.S.A. 405 Publication No. VD-40, Rev. U

INTRODUCTION This product is an automatic, motorized stack damper that has been developed to increase the efficiency of heating systems by reducing standby losses from the heating apparatus and the conditioned air space. The damper closes the chimney vent when the burner is off and fully opens it when combustion is required. The concept is similar to the opening and closing of a fireplace flue, except that the operation is completely automatic. An interlock has been added which prevents burner operation unless the damper is in an open position. A closed damper substantially reduces standby losses on boilers. DESCRIPTION The unit must be installed after the appliance draft diverter and as close to it as practicable, without modification of the draft hood. When the damper is in the closed position, it will prevent residual heat in the heating appliance from being drawn up the chimney vent by its natural draft. If located within a heated area, a closed damper will also prevent conditioned air from being pulled through the draft diverter and up the chimney by the same stack effect. When combustion is required, the damper will rotate to its open position BEFORE an integral end switch activates the burner circuit. If the damper does not rotate to its open position, the burner circuit will not be activated. When the heating requirement has been satisfied, the burner will go off immediately, and the damper will rotate to its fully closed position. Potential fuel savings can vary based on the following factors: 1. Geographical location of dwelling 2. The size of heating plant relative to heat loss of dwelling 3. Location of heating plant within dwelling 4. Diameter of venting system 5. Total height of chimney above heating plant 6. Outdoor temperatures over a given period of time 7. Sustained wind velocities over a given period of time 8. Settings of operating and limit controls on heating plant 9. Source of domestic hot water, temperature of water, and amount used 10. Room thermostat settings 11. Infiltration factors of dwelling 12. Number of heating zones 13. Day/night thermostats 14. Presence of other vents and exfiltration factors 15. Chimney vent friction GENERAL INFORMATION VENT SIZE APPROXIMATE SHIPPING WT. IN POUNDS 4" 5 5" 6 6" 7 7" 8 8" 10 9" 11 10" 12 ELECTRICAL Minimum Wiring Requirements 24VAC,18 gauge, 90 C Thermostat Anticipation Flair...0.1 AMP + control circuit Honeywell Inc...0.2 AMP + control circuit Johnson...0.2 AMP + control circuit Effikal...0.1 AMP + control circuit FEATURES 100,000 trouble-free operations in life cycle test Burner "OFF" before start of damper close Normal burner operations with damper disabled open No burner operation with damper disabled closed External damper position indicator Direct drive, no-linkage and switch for burner off/on cycle Low voltage (24V) circuitry compatible with standing pilot and intermittent ignition devices CSA retrofit certification ANSI Z21.66 - latest edition "Freewheeling" permits free rotation of vane during installation without motor damage Both operator motor and operator control (P.C. board) are replaceable INSTALLATION INSTRUCTIONS I. Before you start to install 1. Read this installation manual, vent damper manufacturer s instructions, the "WARNING" label attached to the top of the boiler, the "WARNING" on the wiring diagram and the DANGER label on the vent damper carton. 2. Perform pre-installation inspection as required by ANSI specification Z21.66. See manufacturer s vent damper instructions. 3. Turn off all electrical power, gas supply and wait for system to cool (for previous installed boilers). 4. Select a proper, convenient location (see figures 3, 4, 6 and 7). 5. Carefully unpack the unit. DO NOT FORCE IT OPEN OR CLOSED! Forcing the damper may damage the gear train and void the warranty. WARNING DANGER Once you have begun vent damper installation procedure, DO NOT restore electric power and gas supply until installation and inspection have been completed (in order to prevent the main burners from operating). DO NOT operate the boiler until the vent damper harness "RECEPTACLE B" is plugged into "MALE PLUG" (as described in the installation instructions), and the vent damper installation and check-out procedures have been completed. Failure to observe this warning may create a hazardous condition that could cause an explosion or carbon monoxide poisoning. II. Now, proceed as follows for Boilers with input under 300,000 Btu/hr.: 1. Remove the front cover of the boiler (Galaxy models only) exposing the wiring compartment. With all electrical power to boiler off, locate MALE PLUG. Refer to the wiring diagram attached to boiler. A copy of the wiring diagram may also be found in the boiler installation manual. To find the correct wiring diagram in installation manual, match the number found in the lower right hand corner of the boiler wiring diagram with the identical number on one of the diagrams in the manual. 3

2. This device must be installed on top of the draft hood or diverter in position as shown in figures 3, 4, 5, 6 and 7. The vent damper must be installed so that the damper position indicator is in a visible location after installation for position indicator description. The arrow imprint on the damper should point in direction of vent gas flow (towards chimney). Flue pipe (other than flue collector on boiler) insertion depth for the male end should not exceed one inch into the vent damper. Be sure the vent damper is well seated and fasten with 3 sheet metal screws. Screws should be no longer than 1/2 inch. 3. Be sure that undersized vent pipe does not block movement of damper vane 4. NOTE: Galaxy 300,000 Btu/hr. Standing Pilot boilers, and Intermittent Pilot (IID) boilers 300,000 Btu/hr and larger may have a vent damper (see page 1). They are factory wired with MALE PLUG and RECEPTA- CLE A. To install the vent damper, cut the RED wire connected between number 3 and 4 of RECEPTA- CLE A (the only wire connected to this receptacle) and then disconnect RECEPTACLE A from MALE PLUG. Remove RECEPTACLE A from job site and discard. Boilers that must have a vent damper (boilers with input under 300,000 Btu/hr.) are factory wired with MALE PLUG only. 5. a) Galaxy boilers: Attach the flexible metallic conduit vent damper harness to the right hand side of the jacket by passing the free end ( RECEPTACLE B ) of the harness through the 7/8" diameter hole in the top of the jacket, and using the BX connector at the free end of the metallic conduit, fasten to jacket. Connect RECEPTACLE B into MALE PLUG (see correct wiring diagram). Attach the other side of the vent damper harness to vent damper operator (if not attached) and connect Molex connector to operator receptacle. For more information, see Galaxy installation manual, GG-40. b) Sentry and Sentinel boilers: All Slant/Fin Sentry and Sentinel boilers are supplied with vent damper. MALE PLUG and RECEPTACLE B are in control box. For vent damper installation instruction see Sentry installation manual, S-40 or Sentinel installation manual SE-40. 6. All Slant/Fin Corp. Galaxy steam boilers equipped with intermittent pilot ignition and continuous (standing) pilot systems are factory wired except for the wires to the low water cut-off and pressure cut-off. Wire these controls with wire provided with boiler (see boiler wiring diagram on boiler). Then follow previous instructions shown in 4 and 5 above. 7. Follow instruction for electrical wiring in boiler installation manual (Galaxy, GG-40; Sentry, S-40 or Sentinel SE-40) or restore electrical power and turn on gas supply (for previously installed boilers). See wiring diagram attached to the boiler or in boiler installation manual. III. After Installation 1. Operate system through two complete cycles to check for opening and closing in proper sequence, and proper burner operation. Damper must be in open position when boiler main burners are operating. 2. Perform installation checks as required by ANSI specification Z21.66. See manufacturer s vent damper instructions. 3. Replace the front cover of the boiler. (Galaxy models only.) 4. Check the troubleshooting section if problems arise with the installation. For more information, see Slant/Fin boiler installation manual GG-40 for Galaxy, S-40 for Sentry, SE-40 for Sentinel, and the vent damper manufacturer's booklet shipped with the vent damper. VENT DAMPER SUITABILITY Check the rating plate attached to the boiler for proper vent damper part number to use on the boiler. WARNING - IMPORTANT Damper circuit is designed to be controlled by low voltage controls. DO NOT use line voltage operating controls to interrupt supply voltage to the L8148E and L8124E aquastats or system transformer on steam system. CAUTION Label all wires prior to disconnection when servicing control. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing 4

VENT DAMPER MODEL NUMBER In Table 1, the proper Slant/Fin Corp. vent damper model numbers are shown adjacent to the specific Slant/Fin Corp. boilers with which these vent dampers may be used. WARNING THIS DEVICE CANNOT BE USED WITH BOILERS WITH 300,000 BTU/HR. INPUT OR GREATER EQUIPPED WITH CONTINUOUS PILOT (see note). OTHER VENT DAMPERS OR DEVICES WITH SIMILAR PURPOSE ARE NOT PERMITTED. Table 1. NOTE: BOILERS WITH 300,000 BTU/HR. EQUIPPED WITH HONEYWELL VR 8300A GAS VALVE MAY USE A VENT DAMPER. Vent Size Use Slant/Fin Vent For Slant/Fin Boiler Model No. Inches Damper Part No. S-34, S-60, SE-70 4 41-2704# GG-75H, GXH-105, GXHA-100, GXHA-120, S-90, SE-105, SE-140 5 41-2705# GG-100H, GG-125H, GG-150H, GG-175H, GXH-125, GXHA-160, S-120, SX-150, SE-175 6 41-2706# GG-200H, GG-225H, GXH-150, GXH-170, GXH-190, GXH-210, GXH-230, GXHA-200, GXH-250, GXH-275, S-150, SX-180, SX-210, SE-210, SE-245 7 41-2707# GX-225, GX-250,GG-250H, GG-275H, GG-300, GG-325, GXH-300 8 41-2708# GG-350, GG-350H, GG-375, GXH-300H 9 41-2709 GG-375H, GG-399H 10 41-2710# May have suffix E, D, P, PZ, etc. # May be any 3 digits. DIMENSIONS Figure 1. Figure 2. * May be plugged with plug provided, ONLY if boiler is equipped with an intermittent ignition pilot. Note on Honeywell vent dampers there is only the 7/8 dia. hole and no knockout. For more information on specific vent dampers see manufacturer s manual included. Table 2. Vent Size 4" 5" 6" 7" 8" 9" 10" A 9 5 16" 10 5 16" 11 5 16" 12 5 16" 13 5 16" 14 5 16" 15 5 16" 5

NOTE: READ MANUFACTURER'S INSTRUCTION MANUAL INCLUDED IN VENT DAMPER CARTON. Figure 3. Vertical Installation Figure 5. Figure 4. Horizontal or Sloping Installation Figure 6. Figure 7. 6

TROUBLESHOOTING GUIDE (listed in order of probability) SYMPTOM POSSIBLE CAUSE REMEDY Heating required and burner will not operate. Damper open. Burner operates normally. Burner shuts down normally, but damper will not close. Burner will not operate. Damper closed and will not open. Burner will not operate. Damper operates normally. Burner operates before damper is open. Damper vane stops in other than fully open or fully closed position. Intermittent burner operation. (Damper operates normally.) Burner operates with damper closed. Thermostat is set wrong. No electrical power. Defective burner components. Damaged or defective damper operator. Damper is blocked open. Damaged or defective damper operator. No call for heat. Damper is blocked closed. Broken return spring (if equipped). Defective burner components. Damper is blocked. Missing roll pin damper stop. Broken coupling. Broken return spring (if equipped). Broken spring stop (if equipped). Burner access door open. Bent or broken coupling. Bad ground. Damaged or defective switch. Reset room thermostat to call for heat. Turn on switch, replace fuse, reset circuit breaker, or repair wiring. Check, repair or replace burner components, gas valve, pilot, IID, IID sensor, etc. Replace damper operator. Check for free damper movement, and remove blockage. Replace damper operator. Reset thermostat (heat or hot water) to call for heating. Check for free damper movement and remove blockage. Recheck and correct any wiring errors in line and low voltage circuits. Check, repair or replace burner components. Check for maximum 90 damper movement. If less than 90, remove blockage. Replace stainless steel roll pin. Inspect and replace drive assembly. Re-install door and fasten with wing nuts. Replace damper operator. INSTALLATION AND SERVICE SHOULD BE PERFORMED BY A QUALIFIED INSTALLING OR SERVICE AGENCY. SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 Phone: (516) 484-2600 FAX: (516) 484-5921 Canada: Slant/Fin LTD/LTEE, Mississauga, Ontario www.slantfin.com