DRYING YELLOW-POPLAR IN A SOLAR-DEHUMIDIFIER KILN WITH HEAT STORAGE AND HEAT RECOVERY SYSTEMS

Similar documents
DEHUMIDIFICATION DRYING OF SPRUCE STUDS. M. Y. Cech and F. Pfaff Eastern Forest Products Laboratory Ottawa, Ontario

INDUSTRIAL DEHUMIDIFICATION DRYING OF SOFTWOODS

Brian Bond. Virginia Cooperative Extension Virginia Tech

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

CHAPTER 4. HVAC DELIVERY SYSTEMS

3. (a) Explain the working of a rotary screw compressor. [10] (b) How the capacity control is achieved in refrigerant compressor?

Introduction to Kiln Drying

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Heat pump and energy recovery systems

MIT Architecture Fall 2008 L. Glicksman 4.42 FINAL Open Book

Evaporative Cooling in a Hot-Dry Climate

LOW COST FOOD STORAGE TECHNOLOGY: ENERGY SAVINGS AND PRODUCE STORAGE QUALITY. Ben Weil Luke Doody University of Massachusetts Amherst

Transcritical CO2 Bottle Cooler Development

SOLAR WATER DISTILLATION BY USING WATER IN THE INNER GLASS EVACUATED TUBES

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

Today s Value-Added Performers. The DRY-30 Series Dehumidifiers from DryAire Systems.

DEALING INTELLIGENTLY WITH ENERGY IN A HIGH-ENERGY PROCESS

PhEn-602 Pharmaceutical Facility Design. Notes #7 J. Manfredi

Today s Value-Added Performers. The DRY-40A Series Dehumidifiers from DryAire Systems.

SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES 3/22/2012 REFRIGERATION

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Solar Still - Improved Distillation

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Field Test of Combined Desiccant-Evaporator Cycle Providing Lower Dew Points and Enhanced Dehumidification

Air Conditioning Clinic

Grain and Soybean Drying on Georgia Farms

A/C Cooling Load calculation and measurement

Appendix A. Glossary of Common Terms

System Modeling of Gas Engine Driven Heat Pump

Air Conditioning System with Modified Condenser Ducts and Evaporative Cooling

Timbersoft Hybrid Kiln - moving towards more production orientated eco friendly drying

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Energy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE

Unit Dimension. Unit Nomenclature DEHUMIDIFIER NOMENCLATURE UNIT VOLTAGE: 2: 240/1/60 5: /3/60 9: 480/3/60 8: 600/3/60

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning

THE PSYCHROMETRIC CALCULATOR By: Stanley F. Gallos, The Bastian-Blessing Company INTRODUCTION PROPERTIES OF THE RSES CALCULATOR

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

ATCO How a Cooling Unit Works

Installation, Operation, and Maintenance Information

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

Armstrong Cool-Fog Systems

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012

A GRAPI-IIC MEUCCI or ESTIMATING VENEER!DRYING RATES

Partial Load Performance Of Refrigeration System

Energy Efficient Corn Drying. Kenneth Hellevang, Ph.D., P.E. Professor & Extension Engineer

Section 4 of 6 DOAS Core Technologies

Use this Construction/HVAC Glossary to answer the questions below.

- Murdoch University, Western Australia.

Heat Pumps SA SERIES. Vertical Self-Contained Unit Water-Source Heat Pumps (23-70 tons) Features:

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

Specific Energy Consumption of Heat Pump Drying System

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog

MODELS B1PA024, 030 AND 036

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

Air Conditioning and process cooling Energy Components at a Glance

LAB EQUIPMENT DETAILS

MSP WRAP-AROUND MULTIPLE SMALL PLATE DEHUMIDIFICATION TECHNOLOGY VS. CONVENTIONAL DEHUMIDIFICATION IN DEDICATED OUTDOOR AIR SYSTEMS (DOAS)

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Chapter 14, Problem 27.

GETTING THE MOST OUT OF HYDRONIC HEATING SYSTEMS

HEAT PIPES

COMcheck Software Version Mechanical Compliance Certificate

THE BENEFITS FROM ELIMINATING ROOF VENTING IN DRY KILNS

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

DEVELOPMENT OF A KILN DRIED WOOD SYSTEM USING HEAT PUMP TECHNOLOGY

DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation

Temperature. In the HVAC area, we talk about two kinds of temperatures.

Dehumidifying with Dedicated Outdoor Air

ASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes

Commercial Refrigeration

Dehumidification Systems

TECAM S.A. harmony. 5PZA Direct Expansion. Air Conditioning Equipment Manufacturer. R-410A PRECISION UNIT 2 Ton 6 Ton / 60 Hz. Tecnología Ambiental

International Journal of Advance Research in Engineering, Science & Technology SOLAR HUMIDIFIER

TESTS OF ADSIL COATING

Available online at I-SEEC Proceeding - Science and Engineering (2013) 19 26

Experimental Investigation of a Hybrid Evacuated Tube Solar Collector

Figure 1: Rice solar drier

Management of In-Bin Natural Air Grain Drying Systems to Minimize Energy Cost

AHRI Certification Program Scopes - COOLING

1.1 This section applies to air handling units for HVAC Systems.

Implementation of Energy Saving measures in Existing Buildings

Experimental & Analytical Investigation on Modified Solar Dryer with Recirculation of Air

Ventilation in Humid Climates: Data from Field Experiments

THERMAL ENGINEERING LABORATORY II. To train the students with principles and operation of thermal Engineering equipments.

ENCLOSURE COOLING. Glossary

So far, we have covered the basic concepts of heat transfer and properties.

Relative Humidity in Schools Jim Cummings and Chuck Withers

Refrigeration Systems and Accessories

Selecting an Environmental Test Chamber

Air-Cooling Evaporators

REVIEW OF INNOVATIVE DRYING METHODS

Q1. The diagram shows an experiment to find out what happens to infrared waves when they strike different surfaces.

IJIRST International Journal for Innovative Research in Science & Technology Volume 1 Issue 12 May 2015 ISSN (online):

All rights reserved, Armando B. Corripio, PhD, PE, Solid Dryer Design Introduction Continuous Dryer Design...

Transcription:

DRYING YELLOW-POPLAR IN A SOLAR-DEHUMIDIFIER KILN WITH HEAT STORAGE AND HEAT RECOVERY SYSTEMS Peter Y. S. Chen North Central Forest Experiment Station Carbondale, Illinois and Wayne A. Helmer Southern Illinois University Carbondale, Illinois INTRODUCTION Using the sun's energy is one way to dry lumber without resorting to costly, limited supplies of natural gas and oil. However, solar lumber drying by itself is time-consuming, especially when trying to dry below 15 percent moisture content, and drying times vary with weather variations. Dehumidification lumber drying is another drying technique that can reduce fossil fuel energy consumption. Recent technological advances have made dehumidification kilns very reliable and competitive with conventional steam-heated lumber driers for some applications. The use of different refrigerants and centrifugal compressors as well as other innovations has enabled dehumidifier kilns to operate at temperatures in the normal kiln drying range-- up to 180 F (1). Dehumidification wood drying systems have lower capital costs but can dry wood as quickly as conventional steamheated systems. However, dehumidifier kilns are entirely powered by expensive electrical energy. Research at the North Central Forest Experiment Station, Carbondale, Illinois, has suggested that dehumidification and solar drying can be combined into one system that incorporates the advantages of both methods. The dehumidification unit and energy storage system can provide heat when solar radiation is not available. The solar drying system can provide heat when insulation is available so that less electrical energy is used to drive the dehumidifier. This paper describes the design and construction of a solardehumidifier kiln equipped with a heat storage unit and a heat recovery system, and presents the preliminary results of a test on drying rates, power consumption, energy efficiency, and wood quality with 4/4 yellow-poplar (Liriodendron tulipifera) lumber. DESIGN AND CONSTRUCTION KILN, COLLECTORS AND DEHUMIDIFIER An energy storage unit and a heat recovery system were added to the existing solar-dehumidifier kiln (2)(Fig. 1). Doubleglazed air solar collectors (244 ft 2 ) heated the kiln air or the rock storage system. A 1-hp motor drove the fan that continuously

circulated the air in the kiln. The high temperature dehumidification system used R-114, which allows the higher temperature operation, as a refrigerant. A 2-hp motor drove the open comressor that circulated the refrigerant through the thermostatic expansion valve, the condenser, and the evaporator. HEAT STORAGE SYSTEM The heat storage system for the kiln was a rock storage unit with enough rock volume (128 ft 3 ) to heat the kiln for one day without solar radiation (Fig. 2). A volume thermal capacity of 24.3 Btu/ft 3 / F was used in the design (assumed a 30 percent void fraction). This would supply the kiln with 124,000 Btu of heat, if the heat storage was discharged from an initial temperature of 140 F to a final temperature of 100 F. The rock-bed was 4 feet deep in the direction of flow and had a flow cross sectional area of 4 feet by 8 feet. The design pressure drop across the bed at 1,000 ft /min was 0.16 inch of water. The walls were made of 2x10 studs on 16-inch centers with 3/4-inch plywood used as the inside wall. Steel tie bolts were used to help reduce deflection of the four side walls. Polyethylene sheets provided a vapor barrier on the rock side of the plywood. Nine inches of fiberglass insulation and 1/2 inch of rigid polyurethane board gave the wall and top of the rock bin an R value of about 34. Aluminum siding covered the outside of the storage bin. The weight of the rocks was supported by bond beam blocks covered with a layer of expanded metal lath. The floor of the storage unit was covered with 3 inches of rigid insulation under 3/4-inch-thick plywood. A vapor barrier was also used above the plywood base. The complete storage bin was located on a 6-inch concrete slab. Rocks for the storage unit, obtained from washed river gravel, ranged from 1 to 3 inches in diameter. All air ducts were constructed from 8-inch diameter sheet metal and insulated with 1-1/2 inches of polyurethane foam. Two 8-inch by 48-inch inlet ducts were located at the bottom side of each end of the storage bin. Two 18-inch by 18-inch ducts on the top of the storage unit were attached to two centrifugal blowers (Fig. 1) driven by variable speed 1-hp motors. The blowers were placed on the downstream side of the collectors to reduce infiltration losses into the collectors. Six sets of motorized dampers at the inlet and outlet of the rock storage unit controlled the air flow from the kiln, collector, and the heat storage unit (Fig. 1). Copper-constantan thermocouples were installed in the rock-bed to measure and control the charging/discharging temperature of the storage unit. HEAT RECOVERY SYSTEM A finned heat-pipe heat exchanger was placed in inlet and outlet air flow paths to the dehumidifier to precool the kiln air going into the evaporator so that the humid air was closer to the saturation point, allowing a greater amount of moisture 2

to be removed. The energy extracted from the kiln air in inlet section (dry-bulb temperature dropped from A to B, Fig. 3) was added back in outlet section to the cool, dry air leaving the evaporator (dry-bulb temperature rose from E to F, Fig. 3). The heat-pipe heat exchanger was 6 inches by 9 inches by 24 inches, using heat pipes for the tubes. The heat pipe tubes were 5/8 inch in diameter; the aluminum fins were spaced at 0.07 inch. A heat pipe consists of three basic elements: the sealed pipe, the wick, and the working fluid (3). The wick is placed adjacent to and around the interior wall of the pipe. When heat is applied to one part of the heat pipe, the working fluid boils. The vapor travels down the center of the pipe and condenses on the cooler portion of the wick and pipe wall. The vapor surrenders its latent heat to the pipe wall and the surroundings. Thus, heat is transported from the boiler section (the inlet section) to the condenser section (the outlet section) with little temperature drop. Then the wick transports the liquid back to the boiler section by capillary action. CONTROL The heating and cooling components in the complete wood drying system were controlled by two separate systems: one for the dehumidifier and one for the kiln/collectors/storage system. The heat pump control was activated by a humidistat positioned in the kiln. When the kiln air relative humidity rose above a set value (see Table 1), the dehumidifier was turned on; when the relative humidity fell below that value, the dehumidifier was turned off. The kiln/collectors/storage system was controlled by a differential temperature controller. The controller continuously monitored and compared the kiln dry-bulb temperature, the solar collector outlet temperature, and the top rock-bed storage temperature. It then activated blowers and dampers based upon the differences in those three temperatures. The control strategy was as follows: 1. Heat was supplied to the kiln whenever the kiln drybulb temperature was below the set temperature. a. Heat to the kiln was first supplied by the solar collectors. b. If the solar collectors were not hot enough, then heat was supplied by the storage unit. 2. If the kiln dry-bulb temperature was above the set temperature and the solar collectors were hotter than the storage temperature, then the solar collectors were activated to heat the storage. MATERIALS AND METHODS Two 500 BF charges of green 4/4 yellow-poplar lumber were dried in the summer and fall of 1983. The boards were 8 feet long, 4 to 6 inches wide, and 1-1/16 inches thick.

Kiln air velocity was set at 400 ft/min and 250 ft/min at the exit side of the wood stack for summer and fall runs, respectively. The solar collector air velocity was set at 4 ft 3 /ft 2 of the collector area for both runs. This relatively lower air velocity was used to reduce electrical energy consumption, compared to our previous use of 9 ft 3 /ft 2 of collector area, and to increase the outlet temperature of the collector. Six boards in each run were chosen for moisture samples. The humidistat was progressively reduced from 80 to 25 percent relative humidity as the moisture content decreased (Table 1). Test runs were terminated when the average moisture content of the high three sample boards reached 8 percent moisture content. The lumber was conditioned approximately 6 to 8 hours with steam from a 7.5 kw, 25-lb-of-steam/hr electric steam boiler outside the kiln, to relieve the drying stresses in the wood before discharge from the kiln. Boards were weighed before and after drying to calculate the total weight of water removed. Twenty percent of the 150 boards were measured for thickness and width at three different points before and after drying to calculate shrinkage. After kiln drying, these randomly selected boards were measured for twist, bow, and crook. All boards were inspected for surface checking, end checking, and collapse. All boards were also graded before and after drying to estimate the degrade loss due to drying. Two stress specimens were cut from each of the six moisture content sample boards and from each of three randomly selected boards to detect any drying stresses remaining. Electric energy consumed by the compressor motor, the condenser, and the evaporator blowers was recorded by watt-hour meters. The power consumption rates of the collector blowers storage blowers, and the main fan were measured by an ammeter. The hours of operation of the fan and blowers were automatically recorded, and power consumption was then calculated from these data. The ambient and kiln temperatures (both dry- and wet-bulb); inlet and outlet temperatures of the solar collector; and the top, center, and bottom temperatures of the rock-bed heat storage unit were recorded at 10-minute intervals. Also, solar radiation was measured and recorded throughout each run by a pyranometer and a strip-chart recorded. RESULTS AND DISCUSSION The solar-dehumidifier kiln equipped with a rock-bed heat storage bin and a heat-pipe heat recovery system dried and conditioned 4/4 yellow-poplar lumber from green (98 percent) to 8 percent moisture content in 7 to 10 days during summer and fall (Fig. 4). These drying times were nearly identical to the 6- to 9-day drying times of the same kiln without the heat storage and heat recovery systems (Table 2) and to the 6- to 4

10-day drying times of the conventional steam-heated kiln (4). Apparently, the heat storage unit did not shorten the drying time during warmer seasons of the year; however, the energy consumption was reduced. The electrical energy required to dry a charge (approximately 500 BF) of 4/4 yellow-poplar lumber varied less between summer and fall in the new kiln equipped with a heat storage bin than in the same kiln without the heat storage bin (Table 2). The kiln was more energy efficient with recovery and storage systems than without in both summer and fall runs in terms of power (kwh) required to remove a pound of water from the wood (Table 2). The heat storage bin supplied 187,000 and 146,000 Btu of solar heat to the kiln in summer and fall runs, respectively. The heat storage unit worked mainly to raise the initial kiln temperature to the operational temperature of the heat pump and supplied additional heat to the kiln during the first or second night of the run because the storage temperature never exceeded the kiln temperature from then on. The quality of dried lumber was excellent and the light color of the lumber was very attractive. No collapse, surface checking, or end checking were noted at the end of drying. There was a $2.00/MBF degrade loss due to drying, even through only one board out of 150 dropped one grade in the summer run. There was no degrade loss in the fall run (Table 3). The degrade loss apparently was not related to the volumetric shrinkage, but was related to the degree of warpage (Table 3). There was no difference in twist between the summer and fall runs. However, bow and crook warpage showed a highly significant difference between the summer and fall runs (Table 3). The reason was not known. The total degrade loss of yellow-poplar lumber dried in 1983 was identical to that of lumber dried in 1980. Again, the degrade loss appeared to be related to the degree of warpage, but not related to the volumetric shrinkage (Table 4). FUTURE PLANS We plan to test one run per season for one year to determine the effect of season on the drying time, wood quality of 4/4 yellow-poplar and red oak, and the energy efficiency of the drying system equipped with a heat storage and a heat recovery system. 5

LITERATURE CITED 1. Chen, P. Y. S. and W. A. Helmer. lumber drying. For. Prod. J. 1982. Principles of 32(5):24-28. 2. Chen, P. Y. S., W. A. Helmer, H. N. Rosen, and D. J. Barton. 1982. Experimental solar-dehumidification kiln for lumber drying. For. Prod. J. 32(9):35-41. 3. Kent, A. C., H. N. Rosen, and D. A. Crotty. 1981. Energy conservation in wood dryers using vent air energy recovery devices. For. Prod. J. 31(2):43-49. 4. Rasmussen, E. F. 1961. Dry kiln operator's manual. U. S. Dept. Agric. For. Serv. Agr. Hanb. 188, p. 144. Forest Products Laboratory, Forest Service, U. S. Department of Agriculture, Madison, Wisconsin. Table 1.--Assumed average board moisture content and kiln humidity control setting Assumed average Humidistat setting board moisture content (RH) >50 40-50 35-40 30-35 25-30 <25 80 75 65 50 35 25 6

Table 2.-- Comparison of drying time, power consumption, and energy efficiency of drying 4/4 yellow-poplar from green to 8 percent moisture content in a solardehumidifier kiln with and without heat storage' Kiln type Summer Fall Green MC With storage 102 93 (%) Without storage 94 99 Final MC With storage 7.7 8.4 (%) Without storage 7.2 7.7 Drying time With storage 7 10 (days) Without storage 6 9 Water removed With storage 1,278 1,292 (lbs) Without storage 969 1,150 Power consumption With storage 372 411 (kwh) Without storage 323 501 Energy efficiency With storage 0.29(990) 0.32(1,093) [kwh (Btu)/lb. of water removed] Without storage 0.33(1,127) 0.44(1,503) 1 Data from Chen et al. (2). 7

Table 3.--Drying data for 4/4 yellow-poplar lumber Runs Summer Fall September 26- Dates (1983) July 5-12 October 6 MC (%) Green 102 93 Dry 7.7 8.4 Drying time (days) 7 10 Volumetric shrinkage (%) 11.0 11.5 Warpage (in.): Twist 0.20 NS 0.15 Bow 0.31 ** 0.13'. Crook 0.38 ** 0.13 Degrade loss ($/MBF) 2.08 0.00 Water removed (lb.) 1,278 1,292 Power consumption (kwh): Dehumidifier 183 272 Kiln fan 142 88 Collector blowers 38 40 Storage blowers 9 11 Total 372 411 NS - Nonsignificant ** - Significant at 1% level

Table 4.-- Comparison of wood quality of 4/4 yellow-poplar dried in a solar-dehumidifier kiln with and without heat storage' Kiln type Summer Fall Warpage (in.) Twist With storage 0.20 0.15 Without storage 0.17 0.08 Bow With storage 0.31 0.13 Without storage 0.09 0.10 Crook With storage 0.38 0.13 Without storage 0.25 0.22 Volumetric shrinkage With storage 11.0 11.5 (%) Without storage 10.9 10.6 Degrade loss With storage 2.08 0.00 ($/MBF) Without storage 1.46 0.62 1 Data from Chen et al. (2).

DAMPER BLOWER Figure 1.--Solar-dehumidifier kiln with heat storage and heat recovery systems 34" PLYWOOD 9" FIBERGLAS 1/2" THERMAX SIDING 34" PLYWOOD ) /7,,, / r r/ e/..),// 1////%17// I/M/f f,./,,,, WIZ,/,./W,/ BOND METAL LATH VAPOR BARRIER 2 X 10 STUD CEMENT BEAM 3/4" PLYWOOD SLAB BLOCKS 3" RIGID INSULATION DRAIN Figure 2.--Rock-bed energy storage system--side view 1 0

DRY BULB TEMP. Figure 3.--Dehumidifier heat recovery system 100 0--e Summer 1983 A A Fall 1983 0 I I I I 2 4 6 8 10 12 DRYING TIME (Days) Figure 4.--Drying curves for summer and fall runs 11