Saving Energy in Existing Multifamily Buildings

Similar documents
Combined Space and Water Heating: Making it Work

Residential Water Heating

Minnesota Multifamily Rental Characterization Study

Energy-Efficiency Options for Residential Water Heating

Multifamily Central Ventilation Assessment and Retrofit Techniques

Promoting quality installation of central AC (and heat pump) systems

Triple E New Construction. Doug Manthey Conservation Technologies Chad Trebilcock Minnesota Power

Energy Efficient Options for Residential Water Heating

Energy problems in small apartment buildings

What you need to know about residential furnaces, air conditioners and heat pumps if you re NOT an HVAC professional

COMMERCIAL CONDENSING BOILER OPTIMIZATION

Multifamily Ventilation Assessment and Retrofit Guide

ENERGY FIT HOMES. In accordance with the Department of Labor and Industry s statute , Subd. 11,

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

THE SUSTAINABILITY INSTITUTE

SLAB ON GRADE CONSTRUCTION Meeting the MN Energy Code ( air tightness) for 2017 Energy Design Conference. By Mike D. Wilson Dakota Supply Group

USING INFRARED TECHNOLOGY TO DEFINE ENERGY SAVINGS OPPORTUNITIES. James L. Park Energy Conservation Specialist I-Star Energy Solutions

Consumer Features & Benefits of Energy Efficient Products

High Performance Building Guide 1

In accordance with the Department of Labor and Industry s statute , Subd. 11,

Home Energy Assessment Report

Combining Space and Water Heating with Highly Efficient Results

WATT s Up? What You Can Do To Reduce Your Home Energy Costs

Ventilation. ASHRAE 62.2 COMPLIANCE How do we get there? Bruce Hagen ND Dept. of Commerce.

EXISTING MULTIFAMILY OREGON CASH INCENTIVES. Standard Incentives SAVE MONEY AND ENERGY NOW AND FOR YEARS TO COME.

2014 ELECTRIC EFFICIENCY REBATE APPLICATION

Ventilation for New Low-Rise Residential Buildings July 20, 2015

In accordance with the Department of Labor and Industry s statute , Subd. 11,

Hot Water a Hot Commodity Better Buildings by Design, February 2012 Burlington, VT

2011 NATURAL GAS EFFICIENCY REBATE APPLICATION

HVAC 101. H V A C S y s t e m s

Are you warming up with space heaters?

Energy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE

Heating Efficiency Program COLORADO

General HVAC Recommendations

Overview of Presentation. Airflow Control: Why. Air Barriers and Energy

90% Efficiency without Boiler Replacement TRUE GREEN SOLUTIONS NEW. Patent Pending. EcoFlex 90 + System Modulating Fan-Powered Economizer

Strategies for Building Energy Efficiency

Mayor s Neighborhood Summit

InterNACHI Home Energy Inspection for th Street

ENGINEERING. Edition No. 13 October 2002

Technical Criteria for District Energy Ready Buildings Master Requirement ENG 108 Building Department: ,

Reducing Energy in Heating, Cooling and Lighting

MultiFamily Ventilation Updates: ASHRAE 62.2, Best Practices and Practical Applications RESNET Conference Atlanta, GA

New Jersey Board of Public Utilities and its Clean Energy Program Residential Energy Efficiency Programs. NJCleanEnergy.com

SUPPORTING DOCUMENT RESIDENTIAL ENERGY CODE WORKSHEET (2015) EFFECTIVE JANUARY 1, 2017

SEE WHAT SAVING ENERGY AND MONEY CAN DO FOR YOUR BUSINESS.

Indoor Environmental Quality

Summary of 60-Day Notice: Heating Efficiency

Matt Cooper, PE, BEMP, HBDP, Group 14 Engineering Ken Urbanek, PE, HBDP MKK Consulting Engineers, Inc.

b.) Technical Information:

MF Mechanical Systems. Doug McCleery, PE, CEM March 2, 2016

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

FOOD SERVICE EQUIPMENT REBATES

Better Buildings By Design What are the best HVAC solutions for low-load, high performance homes? February 6-7, 2013

2015 NATURAL GAS EFFICIENCY REBATE APPLICATION

Hot Water Heating and Distribution Possible CASE Initiatives for 2011 T24 Standards

Your Energy Management Partner

Audit Date: Auditor: Jimmie Sparks Client Name: White Bear Lake Audit Phone: x123 Neighborhood Energy Connection

HVAC System Consideration$ 05/14/2012 SAVING MONEY IN HVAC SYSTEMS

It pays to save energy. Guide to Xcel Energy rebates, incentives and programs for residential customers in Minnesota

COMMERCIAL Washington Incentives

Why 100% outside air HTHV heaters have the lowest total installed cost. COMMITTED TO COST CONTAINMENT>>

The Energy Center. Energy Efficiency. from the others.

New Jersey Board of Public Utilities and its Clean Energy Program. Residential Energy Efficiency Programs. NJCleanEnergy.com

Building Division WSEC & IRC Ventilation (Effective July 1, 2016) Residential Buildings Prescriptive Compliance Form

Clearing the Air: Ventilation. RESNET Building Performance Conference San Diego, CA February 17 th, 2015

Reducing Energy in Heating, Cooling and Lighting. Green and Healthy Property Management. Tohn Environmental Strategies & Steven Winter Associates

ENERGY STAR V2.5 & 3 Designed to Qualify AIA Annual Convention

WATER WISE SURV EY. Santa Barbara City College

Best Practices for Condensing Boilers

Ductless and ducted mini splits- with case studies. Heat Pump and Air Condi1oning For Energy Design Conference By Mike D. Wilson- Dakota Supply Group

MAXIMIZING HYDRONIC SYSTEM DESIGN PART III

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT

Savings through the Proper Installation of Combined Heat and Hot Water Systems

* Peak kw is determined by the average kw load reduction occurring between 1PM and 4PM on weekdays during June, July and August.

HOME ENERGY SAVINGS GUIDE

Steven Winter Associates, Inc. J827

Prescriptive Program Rebate Application

WATER HEATING PAGETTE

ThermWise Update. SWEEP Conference November 9, 2009

Designing Energy Efficient Outdoor Air Systems

WHY TANKLESS? HOW TANKLESS WORKS LONGER LASTING CONTINUOUS HOT WATER CLEAN & FRESH WATER ENERGY SAVINGS SPACE SAVINGS. Secondary Heat Exchanger

Daikin Blueprint: Delivering Hot Water with a Chiller

Energy-saving tips. For apartments and condos. pse.com/multifamilyretrofit. Bellevue, WA Puget Sound Energy. P.O. Box /17

Energy Efficiency Practices for the Low- Income Population

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas

New and Emerging HVAC Technologies. Rod Rhoads, GDS Associates Dave McCullaugh, Mitsubishi Electric Trane HVAC US Dave Binz, Cambridge Engineering

Displacement Ventilation in Classrooms

Energy Recovery Ventilation

Montana Weatherization Program WEATHERIZATION FINAL INSPECTION REPORT (Mobile Homes) Client Name Address Contact phone # Inspector Name and QCI#

Retrofitting a Multi-Unit Residential Building To Reduce Purchased Energy by a Factor of 10. Chris Richards

WHY IS BUILDING SCIENCE IMPORTANT?

Insulate your exterior walls. Air seal and insulate your attic

Low-Impact Remodeling

TIO THE LEADER SPRAY BOOTH APPLICATIONS

Medium Mass Boilers. Maxim Power VT

Home Performance Science

Anticipating Depressurization Issues Due to Air Tightness and Ventilation Needs

OPERATING. Salaries, wages, and benefits personnel costs for repairs and maintenance functions, including living or accommodation allowances.

Transcription:

Saving Energy in Existing Multifamily Buildings Duluth Energy Design Conference February, 2015 Corrie Bastian Center for Energy and Environment

In accordance with the Department of Labor and Industry s statute 326.0981, Subd. 11, This educadonal offering is recognized by the Minnesota Department of Labor and Industry as sadsfying 1.5 hours of credit toward Building Officials condnuing educadon requirements. For addidonal condnuing educadon approvals, please see your credit tracking card.

Topics Who is CEE Perspective: Understanding the industry Energy use in multifamily buildings Retrofit highlights Energy impact Marketability Ensuring success: I, O & M best practices Pg. 3

Who is CEE The Center for Energy and Environment (CEE) is a nonprofit organization that promotes energy efficiency to strengthen the economy while improving the environment We conduct research and develop programs so that: Businesses operate more efficiently and profitably; Government agencies and nonprofits spend less on facilities and functions; Utilities achieve their energy-efficiency goals at least-cost; and Households save money and improve comfort. Pg. 4

What we do Energy Program Design and Delivery Engineering Services Innovation Exchange Research Education and Outreach Sound Insulation Program Public Policy Lending Center Pg. 5

CEE multifamily experience Facility assessments of over 2,000 buildings in Minnesota Completed over 20 research projects Pg. 6

Current multifamily research projects Condensing boiler optimization Multifamily ventilation optimization Demand Controller recirculation loop controls Multifamily aerosol envelope air sealing Indoor pool optimization All funded through the MN Department of Commerce s Conservation Applied Research and Development grant program. The ConservaDon Applied Research and Development (CARD) grant program is funded by MN ratepayers, and administered by the Minnesota Department of Commerce, Division of Energy Resources Pg. 7

Current multifamily energy efficiency programs Energy Star multifamily 3 rd party verifier One Stop Efficiency Shop lighting program with Xcel Energy Multifamily Energy Savings program with MN Energy Resources Pg. 8

UNDERSTANDING MULTIFAMILY BUILDINGS

What we know about multifamily buildings Multifamily buildings are a tough energy efficiency nut to crack Why? Split incentive / diverging interests between resident and owner Lots of players in the orchestra Perception that technical challenges outweigh financial benefits Pg. 10

Market research on multifamily building owners and managers reveals perceptions of energy efficiency Expensive Complex maintenance and upkeep Realized savings are questionable Improved comfort is a big benefit Has to be durable Trustworthy energy efficiency advice is needed Pg. 11

MN multifamily buildings are Relatively young and fit buildings 78% Post-War and newer stock Natural gas = common heating fuel (~66%) Central hydronic = common heat system (83%) 4-6 BTU/a2/HDD Pg. 12 SOURCE: Minnesota MulDfamily Rental CharacterizaDon Study, Energy Center of Wisconsin and Franklin Energy, 2013; sampled 120 bldgs in MN (78 in Twin CiDes, 66 Greater MN)

And yet outliers in (almost) every category Pg. 13 SOURCE: Minnesota MulDfamily Rental CharacterizaDon Study, Energy Center of Wisconsin and Franklin Energy, 2013; sampled 120 bldgs in MN (78 in Twin CiDes, 66 Greater MN)

Water and space heating costs dominate = 40% Average Multifamily Utility Costs (per unit / year) = 15% = 10% = 34% SOURCE: Minnesota MulDfamily Rental CharacterizaDon Study, Energy Center of Wisconsin and Franklin Energy, 2013; sampled 120 bldgs in MN (78 in Twin CiDes, 66 Greater MN) Pg. 14

And yet they are a small piece of the expense pie Average MN Multifamily operating expenses Repairs 27% Other 3% MarkeUng 2% Payroll & Benefits 19% Insurance 4% Source: 2013 MN Mul* Housing Associa*on Expense survey. 388 muldfamily properdes surveyed Trash, Cable, Misc. 4% Taxes 17% Gas 4% UUliUes = 12% Elec. 3% Water & Sewer 5% Admin 4% Mgmnt Fee 8% Pg. 15

i.e. Energy efficiency marketability goes well beyond payback A good investment q Has aggressive energy paybacks q Lowers O & M costs q Improves building comfort q Makes things easier for staff q Is tried and true q Is easy to implement q Makes everyone look smart

MARKETABLE ENERGY EFFICIENCY STRATEGIES FOR MN MULTIFAMILY

Good opportunities for energy savings beyond the laundry list Optimizing existing condensing boilers Building ventilation modifications Demand-based hot water recirculation loop controls Aerosol envelope air sealing Pg. 18

Acknowledgements Projects discussed are supported in part by a grant from the Minnesota Department of Commerce, Division of Energy Resources through a Conservation Applied Research and Development (CARD) program Pg. 19

Optimizing condensing boilers

Achieving rated efficiency (>90% efficiency) CONDENSING TEMPS Return water temperature Pg. 21

Conventional boiler

Condensing boiler Pg. 23

Condensing? Pg. 24

Benefits 4-10% of gained efficiency Eliminate short-cycling Getting what you paid extra for

The key: driving down return water temperature Maximize heat transfer at heating elements Send lower temp water out to the building Make sure boiler output matches demand Make sure your piping isn t dumping supply water into return Make sure domestic hot water is not integrated with space heating boiler

Excess air can dictate boiler efficiency Measured as % Oxygen in flue gas ADJUSTMENT RANGE Pg. 27 Image source: industrialheadng.com

Condensing boiler sensitivity to excess air Controlling excess air very important Excess air reduces concentration of water vapor Dewpoint decreases Low Excess Air High Excess Air Pg. 28

Oxygen levels in flue gas Pg. 29

Heating elements: You re stuck with them It isn t cost effective to add more Dirty or blocked radiation affects heat transfer

Control boilers for lowest possible output Optimized outdoor reset Finding the lowest max output temp for the building Sequencing and staging for optimal efficiency

Control the boiler so it doesn t exceed demand 20 F in March Pg. 32

Outdoor reset lowers boiler water temperature As outdoor temps get warmer, the building heating load gets smaller and the boiler water temperature can be lowered. 180 F 160 F 140 F 120 F 100 F Boiler water temperature, no control Boiler water temperature with outdoor reset 80 F Space 75 F 60 F 40 F 20 F 0 F - 20 F Pg. 33

Optimizing outdoor reset Min OAT for condensing moved from 34 F to 22 F Boiler water temp Outdoor temp Adjusted supply curve Adjusted return curve

Outdoor reset adjustment 14 unit building: 9.5% space heating savings (no cost) Reduced building over-heating

At replacement: Identify boiler control limitations This boiler control s non-adjustable minimum outside temp of 0 F is not ideal for MN

Boiler sequence and firing stage controls: matching output to load for best efficiency Lower output firing stages have increased thermal efficiency Image source: Lochinvar.com

Boiler cascade strategies Image source: lochinvar.com

Sequencing boilers: mixed efficiency 41 unit building: 11% space heating savings 3 year payback Reduced short-cycling

Sequencing/staging: All firing on at once because they can t talk to each other 32 unit building: 6% space heating savings 5 year payback Reduced short-cycling

Little difference between boiler supply and return temperatures indicates potential for improvement Another testament to keeping a daily boiler log! 1- Adjust reset temps as low as possible 2- VFD pump control optimizes heat transfer as zones open and close

Variable speed pumps (VFDs, VSDs) Reduce the pump flow during part-load (when zones close) Allows for lowered return water temperature more potential boiler condensing conditions Electricity savings

Boiler room piping: address at replacement Building loop RETURN 1 2 3 4 Not ideal: Adjacent boilers warm return water

Better piping Building loop RETURN 1 2 3 4

Domestic hot water can dictate return water temps Traditional coil-in tank requires high boiler temperatures, limiting boiler efficiency during DHW call Water heater 130 F 180 F Boiler Pg. 45

Summary: getting condensing boilers to condense! Proper oxygen levels in flue gas contribute to optimal condensing conditions Maintaining aggressive control settings prolongs condensing capabilities VFD pump controls reduce pump speeds at part loads to optimize heat transfer Boiler room piping can dictate return water temps Indirect (sidearm) water heaters will limit DHW efficiency Pg. 46

Optimizing ventilation systems

Optimizing ventilation systems ISSUES High fan power use Excessive ventilation airflow Occupant complaints of drafts, odors Duct leakage Clogging and other flow balancing problems Difficult/costly to measure and quantify energy savings associated with retrofitting Pg. 48

Central ventilation systems Central apartment exhaust Central corridor/make up air systems Pg. 49

Corridor ventilation improvements Reduce fan speed to provide code required ventilation flow ISSUES Design flow rates were much higher than current required flow Faulty controls/sensors Flow rates not verified Pg. 50

Corridor ventilation retrofit in Minneapolis Project: Re-sheave fan for lower flow 4,700cfm reduced 9,611 therms saved 7,244 kwh saved $6,899 annual savings <6 month payback Pg. 51

Central exhaust improvements Reduce & balance flow Seal inlets, curbs & ducts Install high efficiency fans ISSUES Design flow rates were much higher than current required flow Unbalanced flow Flows difficult to verify and seldom measured Pg. 52

Central exhaust retrofit in Minneapolis Project: 1- Replace operable balancing louvers with fixed orifices 2- Replace belt drive exhaust fans with high-efficiency type 2,299 cfm reduced 4,706 therms saved 21,979 kwh saved $5,037 annual savings 7 year payback Reduced odors and noise Pg. 53

Installing fixed balancing orifices Replace balancing devices prone to clogging or tampering Seal duct leakage at inlet Install fixed orifice sized for correct flow, sealed to ceiling Pg. 54

Replacing exhaust fans 1. Seal leakage below fans at curb 2. Replace with EC fans with adjustable speed controls 3. Verify flow is correct Pg. 55

Trash chutes can affect ventilation performance Trash rooms may exhaust too much air Lack of air sealing can cause odor transfer Ventilation flow may be increased to compensate Pg. 56

Addressing the trash chute Keep trash room doors closed Seal trash room off from rest of building If no door, seal chute to compactor/trash bin Reduce trash room exhaust fan flow rate Reduce chute cap opening $1,500 savings annually from reduced stack flow Pg. 57

Stay tuned Ventilation assessment manual this spring Guide for assessment and retrofitting central supply and exhaust systems (and trash chutes) Audience: HVAC contractors and energy consultants Project report this summer Energy savings opportunities found in 18 buildings Retrofit outcomes on 6 buildings Pg. 58

Controlling hot water recirculation loops

Hot water recirculation loops Image source: HMG, Inc

DHW energy losses Image source: HMG, Inc. MulDfamily Central DomesDc Hot Water DistribuDon systems. 2013

Enovative s Demand Controller Control stops pump when there is no building demand or the recirculation loop temp is above 100F Pump run time reduced from 24/7 to average 14 mins/day (ARIES Collaborative/Building America study in 2014) Pg. 62

Variables that affect predicted savings Tank efficiency Insulation on recirc loop pipes Seasonal consumption Incoming cold water temp Building consumption habits Crossover DHW Savings Range: 5-15% Average: 9% Pg. 63

Rochester installation 3-story 39 unit building Built in 1955 Failed water heaters Shower heads and faucet aerators installed along with building assessment 10% DHW savings from Demand Controller Payback = 4 years 540 therms saved, 14 therms / unit Pg. 64

Aerosol envelope air sealing Concept: Pressurize apartment unit Spray air sealing fog Sealant parucles build up on gaps as they exit the envelope

Multifamily compartmentalization Creating an interior air barrier around each unit Reduced stack effect Reduced noise transfer Reduced odor transfer/improved IAQ Increased comfort Increased energy efficiency Pg. 66

Nuts and bolts PREP WORK Horizontal surfaces covered Windows, exterior doors covered Finished floor covered (ideal before flooring is installed) Door handles covered Plumbing fixtures covered Ceiling fans covered Radiators covered Sprinkler head openings covered Remove outlet/switch plates Pg. 67

Nuts and bolts SET UP/SEAL Blower door and nozzles 100Pa pressurization ~ 90% RH maintained CLEAN UP Open windows, purge Remove masking Pg. 68

Preliminary results Air tightness result: 114 to 25 CFM50 total unit leakage (8 units sealed) Averaged 0.45 ACH50 78% to 95% tighter than the new code requirement of 3.0 ACH50 12-13 times tighter than Energy Star requirement for multifamily Pg. 69

Leakage reduced over injection period Pg. 70

Sealed penetrations Pg. 71

Sealed penetrations Pg. 72

Identifying the opportunity IDEAL CANDIDATES Moderate rehabs floors and cabinets New construction NOT IDEAL Where carpet is installed If occupied Pg. 73

Air sealing at lower cost? Aerosol Prep Sealing process Simultaneous air leakage testing ensures results Manual air sealing i.e. caulking/foaming Architectural specification Labor Air leakage test => Uncertain results Vs. Pg. 74

Marketable? BENEFITS Reduced mid and high range noise transfer Reduced odor transfer Improved comfort Simultaneous air leakage testing ensures results Expedited process, labor savings potential CONSIDERATONS Cost Not a solution for large air leak gaps Rehab or new construction only Balanced ventilation is crucial Pg. 75

Stay tuned for more info (Jan 2016) Study will look at : 6 test sites; Rehabs and new construction in MN Enabling commercialization of process Air leakage reductions Sound attenuation ID leak site locations with fluorescent dye/black light photography Evaluation of time and materials required Pg. 76

More info CEE programs and research: mncee.org Pg. 77

Questions? Corrie Bastian cbastian@mncee.org 612.244.2425