Spray Polyurethane Foam and Open-Combustion Appliances

Similar documents
TASKS REGARDING COMBUSTION AIR

Combustion Safety. RESNET Conference San Antonio, TX February 27, Presented by Rich Moore Lightly Treading Energy & Design Denver, CO

Combustion Safety Testing: What we learn from Standards and Research. Objectives. Objectives 2/24/2016

Montana Weatherization Program WEATHERIZATION FINAL INSPECTION REPORT (Mobile Homes) Client Name Address Contact phone # Inspector Name and QCI#

State of ALASKA, Weatherization Assistance Program. Technical Support Document. Combustion Safety

Energy Saver 101: Home Energy Audits

SnuggPro DATA COLLECTION FORM

The Heating System and Ventilation and Combustion Air

Green Building Practice Summary 3/10/2011

COMBUSTION SAFETY BASICS

BPI 1200 and ASHRAE Standards

RESNET National Conference New Orleans, La. February 15, 2009 Presented by Rich Moore Invisible Energy Denver, CO

COMBUSTION APPLIANCE SAFETY INSPECTION FOR VENTED APPLIANCES*

RESNET National Conference New Orleans, LA. February 16, 2009 Presented by Rich Moore Invisible Energy Denver, CO

BUILDING PERFORMANCE INSTITUTE TECHNICAL STANDARDS

Energy Design Conference 2016 Test Protocols & Results: Airport Sound Program and Building America Field Tests

about your house Assessing the Comfort and Safety of Your Home s Mechanical Systems

Combustion Appliance Safety Testing Guidelines

Introductions HERS Industry HERS Ratings ACCA Standard 12 Resources

EnergyMeasure HOME DATA COLLECTION FORM

Uniform Dwelling Code 2017 Updates SPS 323

New Jersey Home Performance with ENERGY STAR Home Performance Audit/ Software Data Collection-2011

2015 MECHANICAL CODE REQUIREMENTS

Home Performance Science

Ventilation for New Low-Rise Residential Buildings July 20, 2015

Retrofit Installer-Mechanical

Ventilation. ASHRAE 62.2 COMPLIANCE How do we get there? Bruce Hagen ND Dept. of Commerce.

Second Revision No. 3 implements the text of Committee Input No. 36 as proposed in the First Draft Report, along with the following amendments:

Indiana WX Oil Furnace Inspection Guide

Whole House Combustion Appliance Safety Test Procedure for Pacific Gas and Electric Company (PG&E) Advanced Home Upgrade 2019

MBPA Home Performance FIELD DATA COLLECTION FORM

Objectives. Home Performance Diagnostics with the House of Pressure (Part 1) How can Pressure effect Building Performance?

RESNET Rating Field Inspector Field Evaluation Form

Home Energy Retrofit Coordinating Committee (HERCC) Combustion Safety Testing Protocols

VENTING CLEARANCES. BBT NORTH AMERICA Bosch Group. Bosch Water Heating 340 Mad River Park, Waitsfield, VT TWH-V-26 page 1 of 6 rev 01/06

BPI ANALYST ENVELOPE AUDIT FIELD EXAM CHECKLIST

PART 5: HVAC & DHW SYSTEMS

Introduction Service Pipe Application Important Terms Air Requirements... Appliance Location... Venting... Calculations...

Direct Vent System Required

Side by side. Cascade Venting System for RTG 199HE. Extension Set for units 3 or Installation instructions

RESULTS FROM HOUSE APPLIANCE SAFETY AND DEPRESSURIZATION TESTS CONDUCTED ON SINGLE FAMILY HOUSES UNDERGOING SOUND INSULATION

about your house Before You Start an Energy-Efficient Retrofit Mechanical Systems

AUTOMATIC MAKE-UP AIR DAMPER WITH TRANSFORMER READ AND SAVE THESE INSTRUCTIONS

Back to back. Cascade Venting System for RTG 199HE. Basic Set for units 1 and Installation instructions

101 S. George St 116 E Gas Ave York, PA York, PA (717) (717)

PROTECTING AGAINST CARBON MONOXIDE. Questions and Answers about Carbon Monoxide (CO) and CO Alarms

USER S INFORMATION MANUAL

HVAC Equipment Access Equipment Location

Inspection Checklist Mechanical Final

EARTH ADVANTAGE HVAC REQUIREMENTS

Illinois Home Weatherization Assistance Program - Field Standards Manual

INSTALLATION AND SERVICE MANUAL

Installing an exhaust system with a capacity Wood Heat

Do not use this vent pipe or fittings for venting incinerators of any kind.

USER S INFORMATION MANUAL

ASX7-4-IOM-6 J

Anticipating Depressurization Issues Due to Air Tightness and Ventilation Needs

The following are the results of the electronic ballot of the board on adopting Joint RESNET/BPI Comprehensve Energy Audit Standard Standard:

Gil Rossmiller. In the construction industry for over 30 years. ICC IRC Plumbing & Mechanical Code Development Committee

Ventilation Techniques. Topic 5 - Audio 53

Evaluate your insulation. Look for a tag in the attic that shows the R-Values of insulation in the floors, walls and ceiling.

INSTALLATION AND SERVICE MANUAL

2012 INTERNATIONAL FUEL GAS CODE VENTS

NC Department of Insurance Office of the State Fire Marshal - Engineering Division 1202 Mail Service Center, Raleigh, NC

WAP Pressure Diagnostics Procedure. Page 1

Supplement A- Improving Forced Air Heating Systems

ATTACHMENT D #1 - HVAC (OIL) - SINGLE FAMILY DWELLINGS Category C: OIL

Operating and Installation Instructions

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

74xx K. St. sample actual insp.w/photos, Edina, MN 5543x

OWNER S MANUAL PG9YAA HIGH EFFICIENCY GAS FURNACE ! WARNING SAFETY CONSIDERATIONS

SAFETY AND INSTALLATION MANUAL MODEL 8100

Energy Upgrade California Home Upgrade Offered by The Energy Network

INSTALLATION INSTRUCTIONS GUH95A & GUH92A. Warm Air Gas Furnace Upflow/Horizontal Left and Right Air Discharge

Contents Chapters 4 & 5 of the 2012 Michigan Mechanical Code CHAPTER 4, MMC: VENTILATION CHAPTER 5, MMC: EXHAUST SYSTEMS

INSTALLATION INSTRUCTIONS A95DF2V, 95G2DFV Warm Air Gas Furnace / Downflow Air Discharge Direct Vent & Non-Direct Vent

Excellent Home Inspection Services, LLC

ASX7-5-IOM-3 J

VENTING GAS APPLIANCES NFPA 54 CODE

Southern California Edison and SoCalGas Energy Upgrade California Home Upgrade. SoCalGas

INSTALLATION AND OPERATION MANUAL Model BR70/BR130

INSTALLATION INSTRUCTIONS GUH95T. Warm Air Gas Furnace Upflow/Horizontal Left Air Discharge Direct Vent & Non-Direct Vent

A95DF2V, 95G2DFV Warm Air Gas Furnace / Downflow Air Discharge Direct Vent & Non-Direct Vent

ANSI/BPI-1200-S-2015 STANDARD PRACTICE FOR BASIC ANALYSIS OF BUILDINGS

Installation Instructions DAR 1150, DAR 1220 DAR 1230, DAR 1250

Home Energy Audit. 170 Security Circle Suite 104 Athens, GA

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

An Introduction to Energy Efficient and Effective Whole-House Ventilation

Section 42. Lead Paint Risk Factor NONE WATER HEATER STORAGE GAS

TECHNICAL INFORMATION COMMUNICATION

REFERENCE GUIDE TO SUCCESSFUL BPI EXAMS

INSTALLATION INSTRUCTIONS A96US2V Warm Air Gas Furnace Upflow/Horizontal Left Air Discharge Direct Vent & Non-Direct Vent

Natural Gas Appliance Testing Action Guidelines (Non ESA/Low Income 5 )

POWER VENTER. Model: PVE Series

Ventilation, Makeup and Combustion Air Calculations Submittal Form New Dwellings

INSTALLATION INSTRUCTIONS A96UH2E Warm Air Gas Furnace Upflow/Horizontal Left Air Discharge Direct Vent & Non-Direct Vent

USER S INFORMATION MANUAL

SH, VH & SE Models. SH, VH & SE Series Heat & Energy Recovery Ventilators IMPORTANT - PLEASE READ THIS MANUAL BEFORE INSTALLING UNIT

Site address. Ventilation Quantity (Determine quantity by using Table N or Equation 11-1) Continuous ventilation

HIGH-EFFICIENCY DOWNFLOW / HORIZONTAL FURNACE INSTALLER'S INFORMATION MANUAL

Transcription:

Spray Polyurethane Foam and Open-Combustion Appliances Before applying SPF (spray foam polyurethane) insulation in an attic or crawl space it is important to determine if there are any appliances present, such as a water heater or a furnace, that are open-combustion and require a source of combustion air. Note: These same considerations apply to any air sealing modifications regardless of materials, as well as attic and crawl space modifications. BPI (see reference below) recommends performing combustion appliance safety inspections whenever 15% or more of the total building envelope is air-sealed. Open-Combustion appliances, also referred to as atmospheric-combustion appliances, draw their combustion air directly out of the room or CAZ (combustion appliance zone) it is in. When located in an attic or crawl space, they draw their combustion air directly from that space. After the open combustion appliance burns the air and fuel mixture, it sends the fumes up and out through a dedicated exhaust flue. The flue is a small diameter sheet metal duct going up and out of the appliance to the outside. The combustion process requires that open-combustion appliances exhaust a greater volume of fumes than it takes in as air. When open-combustion appliances are located in confined spaces, the volume of fresh air is limited. When the fresh air supply to the confined space is insufficient, incomplete combustion can lead to an increase in toxic fumes that need to be vented. If there is some leakage in the exhaust flue, a fraction of the exhaust fumes will accumulate in that space; toxic combustion gases (such as carbon monoxide) can then build-up inside the house. DEFINITIONS Atmospheric-Combustion Appliance: Synonymous with Open-Combustion Appliance (see below). CAZ (Combustion Appliance Zone): The room or space occupied by a combustion appliance. Combustion Appliance: Any device or system within a house that burns a mixture of fuel and air. ERV: Energy recovery ventilation. HRV: Heat recovery ventilation. Open-Combustion Appliance: A combustion appliance that relies on the natural ventilation within the space it resides (CAZ) to provide sufficient air for combustion and exhaust venting. Sealed-Combustion Appliance: A combustion appliance that is provided with a dedicated air intake duct that is directly connected to the outdoors. Spillage: Combustion gas leakage into the space occupied by a combustion appliance. Worst-Case Depressurization Test (aka, Worst- Case CAZ Test): A test which compares outdoor ambient air pressure with the air pressure in a CAZ with all of the home s exhausting appliances operating at full capacity. Exhausting appliances, in this case, include combustion appliances as well as venting appliances (bathroom vents, range vents, clothes dryer vents, etc.). Figure 1: Typical open-combustion water heater. Arrow indicates the entrance to the exhaust flue.

Figure 2: Typical open-combustion furnace co-vented with open-combustion water heater. (Requires fresh air source.) Open-combustion appliances are designed to operate efficiently in well-vented spaces. They can be installed in attics and crawl spaces, but only when these spaces are well ventilated. When SPF (or other construction material) is installed to create an unvented attic or crawl space, the source of combustion air supply is reduced minimized and or eliminated; open-combustion appliances in these spaces may then become a source of hazardous fumes and toxic gases if the exhaust flue is not well sealed. The imbalance of exhaust fumes and fresh air may not be limited to unvented attics and crawl spaces: opencombustion appliances in basements, utility rooms or other areas of the house may be affected as well when the building envelope is well-sealed with SPF. Installation of SPF changes the design of the house as a system; open-combustion appliances may now reside within spaces with a lower flow of combustion air it can no longer be assumed that opencombustion appliances will operate efficiently under these conditions. When insulating with SPF, combustion appliances (or the spaces they occupy) may need to be modified in order for the appliances to operate efficiently and meet building code requirements. SPFA supports the position of the Building Performance Institute: A preliminary and post-installation safety inspection of all combustion appliances must be completed whenever changes to the building envelope and/or heating system are part of the work scope. [BPI Technical Standards for the Building Analyst Professional 1 ] Such a safety inspection includes the following: Carbon monoxide test Draft measurement Spillage evaluation Worst-case depressurization test Caution: Combustion-appliance inspections and modifications should only be performed by professionals trained (and as appropriate, licensed) to perform these tasks. Options if the house does contain open-combustion appliances: 1) Update the open-combustion appliances- (Recommended) Replace the appliances with 90+% direct vent or sealed-combustion appliances having dedicated air supply venting. 2) Isolate the open-combustion appliances- Build a dedicated utility room or closet around the open-combustion appliances. The dedicated room must be vented to the outside of the building envelope and air-sealed and insulated from the rest of the house (in effect, the dedicated utility 1 http://www.bpi.org/web%20download/bpi%20standards/building%20analyst%20professional_2-28-05nnc-newco.pdf

room becomes outside, unconditioned space). The outside vents must be properly sized to supply the fresh air required by the appliances. 3) Change to electrical appliances- Replace open-combustion appliances with electrically-operated appliances. Figure 3: Direct Vent water heater. Sealed-combustion appliances are located close to an outside wall and vent through the wall. A double-walled vent tube functions as both air intake and exhaust flue. (No special requirements when air sealing building.) Figure 4: Powered vent on a water heater. Powered vents employ a blower to push exhaust gases out the exhaust vent pipe. Typically used for long vent runs. (No special requirements when air sealing building.)

Figure 5: Draft fan-assisted HVAC system in a crawl space. The fan is designed to pull combustion by-products out of the heat exchanger and direct them into the exhaust flue. The fan does not propel the exhaust gases up the chimney; these appliances rely on the bouyancy of the hot exhaust to rise up the flue and vent out. This appliance is open-combustion and subject to the aforementioned considerations.

Figure 6: Typical sealed-combustion HVAC system. Air supply and exhaust is through the PVC piping. (No special requirements when air sealing building.) *Photo credits Allison Bailes, Energy Vanguard