Transmission Line Protection End to End Testing

Similar documents
Three Terminal 230kV System Protection and Restoration at Calpine s Creed and Goose Haven Energy Centers Suisun City, California

Standard PRC 004 5(i) Protection System Misoperation Identification and Correction

Standard PRC Transmission Relay Loadability

Microgrid Fault Protection Based on Symmetrical and Differential Current Components

SDG&E Feeder Protection Philosophy:

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS

Index Arc Guard Systems. Arc Guard Systems. Arc Guard Systems Industrial Automation Supply - Tel:

CIRCUIT BREAKER FAIL PROTECTION

Electrical Energy department

SEL Arc-Flash Solutions

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS

SEL Arc-Flash Solutions

TOP R4 Unknown Operating State

Standard PRC Protection System Misoperation Identification and Correction

Heat Pump Defrost Board Replacement Kit

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

High Reliability Of Fiber Optic Amplifier For Convenient Mounting

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Standard PRC Protection System Misoperation Identification and Correction

OPERATOR S MANUAL MODEL AP15/AP15-1/AP15-2 PC-ALARM PANEL

Protection Chain IQ-Sensor + Relaiy device T420

AQ 100 Series. Arc Flash Protection System

RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control

SCR100 User Manual. Version:1.1 Date:Dec 2009

Contents. Preface. Chapter 2 Faults, types and effects The development of simple distribution systems Faults-types and their effects 7

Distribution Control Center Operator Training

Power System Protection Part 2 Dr.Prof. Mohammed Tawfeeq. Zones of Protection

Standard PRC Protection System and Automatic Reclosing Maintenance. Standard Development Roadmap

KELLOGG COMMUNITY COLLEGE INDUSTRIAL ELECTRICITY AND ELECTRONICS SPRING 2018

INSTRUCTION MANUAL and DETAILED PRODUCT SPECIFICATION TRIPLEX PUMP CONTROL SYSTEM MODEL NUMBER CPC-3. M336 Rev F. November 21, 2000.

Description (Data Point Name) Unit Size

Standard PRC-005-3(i) Protection System and Automatic Reclosing Maintenance

PGR-8800 TECHNICAL FAQ

Monitoring Devices 11/1

Major Fault Caused by Stator Winding Circuit Ring Failure

RC-101 Heat Pump Real Time Pricing System 2 Stage Heat / 1 Stage Cool

4 Channel Contact Closure SFP DIN Fiber Link System

Version 1.03 January-2002 USER S MANUAL

Carbon Monoxide Transmitter

Standard PRC-005-3(X) Protection System and Automatic Reclosing Maintenance

PRC NERC Protection System Maintenance Standard PRC-005-2

Applications and Discussions of Arc Flash Protection Relay as a Main Busbar Protection in MV Switchboards

CTT8 TEMPERATURE MONITOR DEVICE

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

RC801/803/ B 16E1 Fiber-Optic Multiplexer (Rev. M) User Manual. Raisecom Technology Co., Ltd. (04/2005)

C-Bus Pascal Automation Controller 5500PACA. Installation Instructions

HD COMMUNICATOR. Features & Benefits: Unique continuous Redundant Routing capacity. Up to 20km reach on a single copper pair.

MO n : 12JMC rév A

Standard PRC Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance

Installation, Operating and Maintenance Manual

Solid State Relays SOLITRON MIDI Current Sensing Type RJCS, RJCSR

38-SDMS-04 REV. 0 SPECIFICATION FOR ANNUNCIATOR SYSTEMS FOR PRIMARY DISTRIBUTION SUBSTATION

Residential Demand Controller Program

TEMON 4-C. Doc. N MO-0368-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 4-C OPERATION MANUAL. Microener- Copyright 2010 FW 2.1 Date Rev.

Certified Fibre Optic Specialist - Testing

4 & 8-POINT ANNUNCIATORS Instruction Manual

Measuring and Monitoring Relays Application Guide

Reyrolle Protection Devices. 7PG26 DAD High Impedance Current Relay. Answers for energy

Module Features are-configurable, no module jumpers to set

To: Honorable Public Utilities Board Submitted by: /s/ Douglas Draeger AGM Engineering and Operations

PERMACONN PM1030 Includes DI300. Installation Manual

Original operating instructions Safety switch with guard locking AC901S AC902S

7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management

INSTRUCTION MANUAL T119 1MN0110 REV. 0. operates with ISO9001 certified quality system

NERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1

Alarms Manual. ver.1 rev.06/'07. Enclosures to Service Manuals of: McbNET Digital TM Magnum400 TM MiniMagnum400 TM. 6) Speeder One

Standard PRC-005-X Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance

ABB Instrumentation. Specifications. COMMANDER 150 Universal Process Indicator. the 1 /8 DIN indicator to match all your display requirements

T3/E3 Fiber Optic Line Drivers

PD154 & PD158 VIGILANTE II ANNUNCIATORS Instruction Manual

Table of Contents. Protective Relays

Ground Fault Protection Improvement Study

ELECTRONIC COMMUNICATING THERMOSTAT

Residual Current Devices

Standard PRC Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance

IQ-Sense. 2/2 Introduction. 2/3 IQ-Sense photoelectric sensors. 2/5 IQ-Sense ultrasonic sensors. 2/6 4 IQ-Sense sensor module for ET 200S

17 TH APRIL 2017 Switch Board Monitoring Protecting Switchboard. Courtesy of ABB. Paul Lee

Arc Fault - Minimize damage

PRC-005. Tips and Updates. February 25th, Jonathan Hayes

DIGITIAL PROTECTION COUPLER

The next generation thermometer from the global leader

SECTION GENERATOR PARALLELING CONTROLS

ECO N DATE DESCRIPTION OF CHANGE CHG

Lecture 4 Power System Protection. Course map

DEIF A/S. Description of options. Option A4, Loss of mains protection package Automatic Gen-set Controller. Description of option

Temperatures can be displayed in degrees Celsius or degrees Fahrenheit from -100ºC to 1200ºC (-148ºF to 2192ºF).

The breaker trips at once when it is set to ON. The breaker trips in few minutes when it is set to ON.

ORION Mini-Rep INSTALLATION MANUAL

Control Panel Engineering and Commissioning Instructions

Speed and Frequency Seite 1 von 7

Danfoss gas detection units

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

5, SE GÅNGHESTER,

INSTALLATION MANUAL. G&F Manufacturing 7902 Interstate Court North Fort Myers, Florida

Electrical installation solutions for buildings Technical details Energy efficiency

Motorised Infrared Optical Beam Smoke Detector. User Guide

Appendix B. FRCC regional application of the term transmission Protection Systems

VTI MODEL itc5000 HEAT TRACING CONTROL SYSTEM OPERATIONS MANUAL

APPLICATION NOTE. Document Type. Application Note. Document Title. Date January Version DS0167/Iss 2. ESP Technical Summary

Transcription:

Transmission Line Protection End to End Testing Hands on Relay School, March 15, 2018 Chris Gallacher Protection Engineer Greg Sharpes Senior Relay Technician Mark Babin Senior Relay Technician

Presentation Agenda Why do you need Communications Aided/Based Tripping Schemes? How do you build one? Design. Are you sure it works? Testing. What can go wrong? Troubleshooting. The fun part. Lab Testing.

Why do you need Communication Aided Tripping?

Why do you need Communication Aided Tripping? Traditional step distance or time overcurrent protection is not adequate due to: System Stability Thermal Damage Protection Limitations

Line Protection without Communication Step Distance using impedance (21), definite time delayed (67) overcurrent, and time overcurrent (51) elements. Delayed Clearing at remote end of the line in either direction Zone 3 Time Zone 1 Zone 2 Substation A Substation B Zone 2 Zone 1 Time Zone 3

Line Protection without Communication 51G Time 67G1 Substation A Substation B 67G1 Time 51G

How to build a Communication Aided/Based Protection Scheme?

100% High speed clearing - Option 1 Utilize existing (single end) protection elements Impedance/Distance, Phase and/or Ground Definite and Time Overcurrent, Phase and/or Ground Traveling Wave / Rate of change (dv/dt, di/dt) Assign specific elements to bit(s)/tone(s) and transmit to the remote terminal Use local protection elements, bits/tones received from the remote end(s), and logic to either trip or restrain trip with little to no intended time delay.

Directional Under-reaching Transfer Trip (DUTT) Uses instantaneous elements (e.g. Zone 1, inst 50/67) to send a bit/tone to trip remote terminal(s) of the line. Substation A Substation B Zone 1 Inst Overcurrent DTT DTR Trip Breaker.. Trip Breaker DTR DTT.. Zone 1 Inst Overcurrent

Directional Under-reaching Transfer Trip (DUTT) Zone 3 Time Zone 1 DTR Zone 2 Substation A DTR Substation B Zone 2 Zone 1 Time Zone 3

Directional Under-reaching Transfer Trip (DUTT) 51G Time 67G1 DTR Substation A DTR Substation B 67G1 Time 51G

Permissive Over-reaching Transfer Trip (POTT) Uses overreaching elements (e.g. Zone 2, 67G2) to send a bit/tone giving permission to the remote terminal(s) of the line that it may trip if it too sees a fault. If all terminals agree there is a fault in the forward direction it must be on the line.

Permissive Over-reaching Transfer Trip (POTT) Simplified POTT Scheme Substation A Substation B Zone 2 Def Time Overcurrent.. PTT PTR Trip Breaker Trip Breaker PTR PTT.. Zone 2 Def Time Overcurrent

Permissive Over-reaching Transfer Trip (POTT) Simplified POTT Scheme Time Zone 2 Local AND Zone 2 Remote Substation A Zone 2 POTT Only Zone 2 POTT Only Substation B Zone 2 Local AND Zone 2 Remote Time

Permissive Over-reaching Transfer Trip (POTT) Simplified POTT Scheme Time 67G2 Local AND 67G2 Remote Substation A 67G2 POTT Only 67G2 POTT Only Substation B 67G2 Local AND 67G2 Remote Time

Permissive Over-reaching Transfer Trip (POTT) Scheme is enhanced with a reversed element (Zone 3, 67G3) to block the POTT scheme and prevent false tripping during a current reversal. Substation A Substation B Zone 2 Def Time Overcurrent.. PTT PTR Trip Breaker Zone 3 (Reverse) Zone 3 (Reverse) Trip Breaker PTR PTT.. Zone 2 Def Time Overcurrent

Permissive Over-reaching Transfer Trip (POTT) Additional enhancements: Weak end infeed Echo back b repeat

Directional Comparison Blocking (DCB) Uses a local overreaching element (e.g. Zone 2) to trip and a remote reversed element (e.g. Zone 3) to block the tripping element. Local overreaching element is briefly delayed (1-5 cycles) for communication latency, i.e. waits for a block signal

Directional Comparison Blocking (DCB) Substation A Substation B Zone 2 Def Time Overcurrent.. PU DO PU DO.. Zone 2 Def Time Overcurrent Zone 3 (Reverse) Trip Breaker Block Block Trip Breaker Zone 3 (Reverse)

Directional Comparison Blocking (DCB) Time Zone 2 Local AND NOT Zone 3 Remote Zone 3 DCB Block Substation A Zone 2 DCB Only Zone 2 DCB Only Substation B Zone 3 DCB Block Zone 2 Local AND NOT Zone 3 Remote Time

Directional Comparison Blocking (DCB) Time 67G2 Local AND NOT 67G3 Remote 67G3 DCB Block Substation A 67G2 DCB Only 67G2 DCB Only Substation B 67G3 DCB Block 67G2 Local AND NOT67G3 Remote Time

Additional Schemes Drive to lockout Used to signal to the remote end not to attempt a reclose Avoids reclosing into damaged equipment from the remote terminal Typically used for breaker failure, transformer terminated lines, or series capacitors

100% High speed clearing - Option 2 Build a current differential! Current in = Current out. Sounds easy! Communicate AC quantities to the remote terminal in near real-time and calculate the difference. The devil is in the details.

Line Current Differential Encodes the locally measured AC signal and transmits it to the remote terminal(s). Each relay must time align local and remote measurements to calculate an operate quantity. Ping Pong vs Timestamping Prevent false tripping for CT saturation and Open CT

Line Current Differential Disable differential when comm channel is bad or unstable. Long Lines charging current No PTs required Zone of protection is clearly defined

Line Current Differential Substation A Line Differential Substation B Line Differential

Communication Systems Different schemes require certain levels of communication service: Could the communication channel be effected during a fault? Does the scheme require comm during a fault to work? What is the channel latency? Is channel latency consistent? Deterministic. Is the channel latency the same in both directions? Asymmetry.

The Buddy System of Line Protection

Are you sure it works?

Testing End to end testing is designed to test logic missed by element testing and single end testing Verifies: Communication channel and addressing Comm Aided/Based Protection Logic Engineers protection settings Breaker trip and close circuits (if tripping to breaker)

End to End Testing Schemes are tested by playing faults into all relays associated with a scheme. Faults must be precisely time aligned to work properly Remember 8ms is almost a 180 degree phase shift at 60 Hz Simulated faults are usually built by the protection engineer to check specific points where misoperation could occur.

Misoperation NERC Definition 1. Failure to Trip During Fault 2. Failure to Trip Other Than Fault 3. Slow Trip During Fault 4. Slow Trip Other Than Fault 5. Unnecessary Trip During Fault 6. Unnecessary Trip Other Than Fault

NOT a Misoperation A Composite Protection System operation that is caused by personnel during on-site maintenance, testing, inspection, construction, or commissioning activities is not a Misoperation. http://www.nerc.com/files/glossary_of_terms.pdf

Typical Line Substation A Substation B Trip Trip Relay A Close Communication Channel Communication Medium: PLC, Direct Fiber, Copper, SONET, Packet Switched, etc Close Communication Channel Relay B

Typical Test Configuration Substation A Substation B Breaker Sim Breaker Sim Trip Trip Relay A Close Communication Medium: PLC, Direct Fiber, Copper, SONET, Packet Switched, etc Close Relay B Va,Vb,Vc Ia,Ib,Ic Va,Vb,Vc Ia,Ib,Ic GPS High Accuracy Clock Signal Test Set A Test Set B High Accuracy Clock Signal GPS

Faults to Run Both Phase (3LG, LL) and Ground (SLG, 2LG) Possibly different phases of the same fault if single pole tripping Phase segregated direct trip or permissive trips Fault at points where scheme is need for high speed clearing Mid line, high impedance fault. Line end

Faults to Run No-op Faults Parallel Line fault and clear (current reversal) Slow clearing faults on lines behind relay Tapped loads Pay attention to 3 phase PT location Reclosing requirements Pre-fault

Results Sequence of Events

Results Oscillography

What can go wrong?

DC Circuits and Logic Bad Breaker Status Switch on to fault Bits/Tones not the same on both ends Differing utility standards Relay is not fully isolated False trip Relay is too isolated Reclosing enable/disable or Hot Line Hold switch

AC Circuits Incorrect wiring between: Relay and test switches Test switches and test set Test Set Limitation Engineer needs to redefine faults High current test set Different phasing between utilities

Communications Comm Circuits Transmit / Receive Rolled Circuit is looped back in comm equipment Circuit was never commissioned Wrong equipment Multimode vs Single mode fiber Fiber optic transceivers Addressing Bad circuit Bit error, noise, corrupting data

Questions??

LAB Initial Wiring Power (AC plug) AC Input into Relay from Test Set 3 Phase Voltage 3 Phase Current Relay DC Inputs Breaker Status Relay AC Outputs Trip and Close Communications Fiber - Differential Channel Copper RS232 POTT / DUTT bit channel

LAB Initial Wiring Verify testing setup Is the relay seeing ABC rotation of voltage and current? Can the relay trip/close the breaker? Are the relays communicating? Differential POTT / DUTT

Protection Design Phase Elements 4 Mho Phase Distance Zone 1 Instantaneous trip (80% of line) Zone 2 POTT Keying Only (200% of line) Zone 3 POTT Reverse Blocking (200% of line) Zone 4 Traditional Zone 2 (120% of line) 20 cycle delay

Protection Design Ground Elements 4 Quadrilateral Ground Distance Zone 1 Instantaneous trip (80% of line) Zone 2 POTT Keying Only (200% of line) Zone 3 POTT Reverse Blocking (200% of line) Zone 4 Traditional Zone 2 (120% of line) 20 cycle delay

Protection Design Ground Elements con t 3 Definite Time Ground Overcurrent 67G1 Instantaneous trip (~80% of line) 67G2 POTT Keying Only 67G3 POTT Reverse Blocking