STELLAR 2000 SINGLE PIECE AIR HANDLERS INSTALLATION INSTRUCTION Supersedes: N2Y (795) N2Y (1195)

Similar documents
INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTION

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP MODELS: TABLE OF CONTENTS LIST OF FIGURES

INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC LIST OF SECTIONS LIST OF FIGURES

INSTALLATION MANUAL SINGLE PIECE STANDARD ECM AIR HANDLERS MODELS: AHX61 SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL SINGLE PIECE NON-VARIABLE SPEED AIR HANDLERS MODELS: AHX SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL SINGLE PIECE, 3 POSITION AIR HANDLERS MODELS: AHR / AHE SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: SAFETY UIM-C-0214

INSTALLATION MANUAL LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: SAFETY

INSTALLATION MANUAL WARNING WARNING MODULAR NON-VARIABLE SPEED AIR HANDLERS MODELS: MA LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES

INSTALLATION MANUAL SINGLE PIECE NON-VARIABLE SPEED AIR HANDLERS MODELS: AHP SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL SINGLE PIECE, 3 POSITION AIR HANDLERS MODELS: AHE SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL SINGLE PIECE, 3 POSITION AIR HANDLERS MODELS: AHR SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL SINGLE PIECE VARIABLE SPEED AIR HANDLERS MODELS: AV*(C) SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL SINGLE PIECE, 4 POSITION AIR HANDLERS MODELS: AHR SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

INSTALLATION MANUAL SINGLE PIECE AIR HANDLERS MODELS: F*FP LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SAFETY UIM-B-0209

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

INSTALLATION MANUAL SINGLE PIECE AIR HANDLERS MODELS: F6FP018** - 060** TABLE OF CONTENTS LIST OF FIGURES LIST OF TABLES SAFETY UIM-B-0409

INSTALLATION INSTRUCTIONS

INSTALLATION MANUAL WARNING STANDARD PSC MODULAR MULTI-POSITION AIR HANDLERS MODELS: MP SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES

TECHNICAL GUIDE VARIABLE SPEED AIR HANDLERS DESCRIPTION FEATURES Rev. A (0105)

INSTALLATION INSTRUCTIONS

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

MODELS B1PA024, 030 AND 036

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION MANUAL WARNING WARNING FULL-CASED UPFLOW/COUNTERFLOW FOR COOLING/HEAT PUMPS FULL-CASED MULTI-POSITION FOR COOLING/HEAT PUMPS MODELS: CF

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED

INSTALLATION INSTRUCTIONS

INSTALLATION MANUAL LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: SAFETY

TECHNICAL GUIDE MODELS: MV MODULAR VARIABLE SPEED AIR HANDLERS FOR USE WITH SPLIT SYSTEM COOLING & HEAT PUMP DESCRIPTION FEATURES

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

SPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing N4C-0500

Installation Instructions

Installation Instructions

TECHNICAL GUIDE HIGH EFFICIENCY, STANDARD ECM VERTICAL WALL MOUNT AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: EWX*18-36

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

CONDENSING UNITS SPLIT-SYSTEM COOLING 1.5 TO 5 TONS INSTALLATION INSTRUCTION MODELS H*DE018 THRU H*DE060 NOMENCLATURE GENERAL LIMITATIONS INSPECTION

INSTALLATION & OPERATING INSTRUCTIONS AEM SERIES VARIABLE SPEED MULTI-POSITION ELECTRIC HEAT AIR HANDLER

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

Installation Instructions

INSTALLATION INSTRUCTIONS

CONDENSING UNITS SPLIT-SYSTEM COOLING 6-1/3 TONS INSTALLATION INSTRUCTION MODELS H*DB076 NOMENCLATURE GENERAL LIMITATIONS INSPECTION REFERENCE

INSTALLATION INSTRUCTIONS

SUBMITTAL DATA SHEET FEATURES. SPLIT-SYSTEM EVAPORATOR BLOWERS 7.5, 10, 15 & 20 TONS MODELS: NH-07 thru -20, 2-PIPE NJ-10 thru -20, 4-PIPE

Installation Instructions

Installation Instructions

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA

INSTALLATION INSTRUCTIONS

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

MODELS K2EU060A, K4EU090A, & K3EU120A

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION ACCESSORIES - FIELD INSTALLED. K5EU090 and K4EU Hz 7.5 and 10 NOMINAL TONS SUNLINE 2000 (WORLD 50 HZ)

AHG**-0B Series Hydronic Air Handling Units

INSTALLATION INSTRUCTIONS TXV Coils EBD, EBA

INSTALLATION INSTRUCTIONS TXV Coils EBU, EBA

INSTALLATION INSTRUCTIONS TXV Coils EDM, EDD, EDA

Technical Guide DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS. 7-1/2 and 10 NOMINAL TONS LA090 & LA120 SUPPLY AIR PLENUMS

TECHNICAL GUIDE SINGLE PIECE AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: F6FP DESCRIPTION FEATURES UTG-B-0409

TECHNICAL GUIDE SINGLE PIECE AIR HANDLERS DESCRIPTION FEATURES FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS

ACCESSORY INSTALLATION INSTRUCTION ELECTRIC HEAT ACCESSORY 10, 16, 26, 36 & 72

Your safety and the safety of others are very important.

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

GAM SERIES INSTALLATION & OPERATING INSTRUCTIONS MULTI-POSITION AIR HANDLER (ELECTRIC HEAT)

AVS Series Air Handlers Installation Manual for CLASSIC SERIES SYSTEMS Models SC, SD, and SDH

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 PROVEN PERFORMANCE GENERAL FEATURING

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ)

ACCESSORY KIT INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

PL Series Premier Indoor Plenum Coils

R-410A. NJ-10 thru -20, 4-Pipe Ton, 60 Hertz TABLE OF CONTENTS LIST OF TABLES LIST OF FIGURES

AVS Air Handlers Installation Manual for Classic SC, SD, and SDH

Product Data. FH4A Fan Unit. Sizes 001 thru 004

INSTALLATION INSTRUCTION

maintenance should only be performed by a trained, qualified person. Consumer service is recommended only for filter replacement.

INSTALLATION & OPERATING INSTRUCTIONS AAC & AEC SERIES CEILING MOUNT AIR HANDLER (ELECTRIC HEAT)

Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS

B Series Multi-Position & Hydronic Air Handlers Electric or Hot Water Heat, with available Variable-Speed High Efficiency ECM Motor

Installation Instructions

Installation Instructions

Cased Aluminum Coils "Dedicated Upflow / Downflow" Convertible to horizontal with separately purchased kit

Product Data. FH4A Fan Unit. Sizes 001 thru 004

Cased Aluminum "Convertible" Coils 4TXCB003CC3HC** 4TXCB004CC3HC** 4TXCC005CC3HC** 4TXCC006CC3HC**

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

TABLE OF CONTENTS INTRODUCTION. NOTE: Read the entire instruction manual before starting the installation.

AllStyle Coil Company, LP 7037 Brittmore Houston, TX Phone Fax

EarthLinked AVN Series Air Handlers Installation Manual

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

FF1DNA, FF1DNE FAN COIL UNITS. Sizes 018, 024, 030. Form No. PDS FF1D.18.3 FEATURES FF1D

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

EarthLinked AFN Series Air Handlers Installation Manual

2/4TXCC037BC3HCA 2/4TXCB042BC3HCA 4TXCC044BC3HCA 2/4TXCC043BC3HCA 2/4TXCB048BC3HCA

SPLIT-SYSTEM CONDENSING UNITS. "HRC" Series SEER. Models H*RC018 thru H*RC060 Nominal Capacity: 18 thru 60 MBH DESCRIPTION FEATURES

Transcription:

STELLAR 2000 SINGLE PIECE AIR HANDLERS INSTALLATION INSTRUCTION Supersedes: 535.02-N2Y (795) 535.02-N2Y (1195) HEAT PUMP MODELS F1RP / F1FP018 thru 060 and COOLING MODELS F1RC / F1FC018 thru 036 035-13620 GENERAL This instruction covers the installation of the following models: F1RP / F1FP018 F1RC / F1FC018 F1RP / F1FP024 F1RC / F1FC024 F1RP / F1FP030 F1RC / F1FC030 F1RP / F1FP036 F1RC / F1FC036 F1RP / F1FP042 F1RP / F1FP048 F1RP / F1FP060 This Single Piece Air Handler provides the flexibility for installation in any upflow or horizontal application. These versatile models may be used for cooling or heat pump operation with or without electric heat. The direct-drive, 3-speed motors provide a selection of air volume to match any application. The unit can be positioned for bottom return air in the upflow position, and right or left return in the horizontal position. Top and side power wiring and control wiring, accessible screw terminals for control wiring, easy to install drain connections and electric heaters all combine to make the installation easy, and minimize installation cost. INSPECTION As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on the carrier s delivery receipt. A separate request for inspection by the carrier s agent should be made in writing. See Local Distributor for more information. Also check to be sure all accessories such as heater kits or suspension kits are available. Installation of these accessories or field conversion of the unit should be accomplished before setting the unit in place or connecting any wiring, electric heat, ducts or piping. REFERENCE This instruction should be used in conjunction with installation instructions supplied with each accessory as well as the matching outdoor section. Installer should pay particular attention to the words: NOTE, CAUTION, and WARNING. NOTES are intended to clarify or make the installation easier. CAUTIONS identifies procedure which, if not followed carefully, could result in personal injury, property damage or product damage. WARNINGS are given to alert the installer that severe personal injury, death or equipment damage may result if installation procedures are not handled properly. LIMITATIONS These units must be wired and installed in accordance with all national and local safety codes. Voltage limits are as follows: Air Handler *Normal Operating Voltage Voltage Range 208/230-1-60 (06) 187-253 *Utilization range A in accordance with ARI Std. 110. Air flow must be within the minimum and maximum limits approved for electric heat, evaporator coils and outdoor units. Entering Air Temperature Limits Wet Bulb Temp. F Dry Bulb Temp. F MIN. MAX. MIN. MAX. 57 72 65 95 * * A/C - Require Horontal Pan Accessory * FIGURE 1 -TYPICAL APPLICATIONS

535.02-N2Y LOCATION Location is usually predetermined. Check with owner s or dealer s installation plans. If location has not been decided, consider the following in choosing a suitable location: 1. Select a location with adequate structural support, space for service access, clearance for air return and supply duct connections. 2. Use hanging brackets to wall mount unit as shown below. 3. Normal operating sound levels may be objectionable if the air handler is placed directly over some rooms such as bedrooms, study, etc. 4. Precautions should be taken to locate the unit and ductwork so that supply air does not short circuit to the return air. 5. Select a location that will permit installation of a trapped condensate line to an open drain. 6. When an evaporator coil is installed in an attic or above a finished ceiling, an auxiliary drain pan should be provided under the coil as is specified by most local building codes. The coil is provided with a secondary drain it should be trapped and piped to a location that will give the occupant a visual warning that the primary drain is clogged. If the secondary drain is not used it must be capped. 7. If unit is located in an area of high humidity, ie. an unconditioned garage or attic, nuisance sweating of casing may occur. On these installations a wrap of 2" fiberglass insulation with vinyl vapor barrier should be used. 8. Proper electrical supply must be available. 9. Clearances must also be taken into consideration, and provided for as follows: a. Refrigerant piping and connections are located in the front. b. Maintenance and servicing thru the front or access side of unit with both sides and rear of unit having zero inch clearance. c. Condensate drain lines are connected in the front. d. Filter removal. e. When no electric heat is used, the unit as well as all duct work and plenum are designed for zero clearance to combustible materials. f. If Electric Heat is used, a minimum clearance of one inch must be maintained on all sides of the supply air duct and/or plenum continuously for up to 3 feet. See Figure 3. FIGURE 3 - PLENUM CLEARANCES FIGURE 2 - TYPICAL INSTALLATION 2 Unitary Products Group

HORIZONTAL DRAIN PAN INSTALLATION / CONVERSION These air handler units are supplied ready to be installed in a right hand horizontal position when a horizontal pan is factory installed. If unit requires a horizontal pan or requires left hand positioning, the unit must have the pan installed in the correct position. NOTE: Models bearing a H indicates the unit has horizontal drain pan factory installed in position A. 1. Remove blower access, coil access, and center access panels. NOTE: Conversion must be made before brazing the refrigerant connections to the coil. 2. See Figure 4, remove two (2) screws from horizontal drain pan, to remove pan from position A if factory installed. 3. Position horizontal pan, as required in either A or B position, locking it into the vertical drain pan as shown. 4. Horizontal drain pans have (4) plugged drains. Remove plugs from connections being used. NOTE: If overlooked, it can lead to a water problem later. 5. Attach horizontal pan with two (2) screws removed in step no. 2 or supplied in Horizontal Drain Pan Kit. 6. Horizontal drain cutout in the center access panel should be removed by using a utility knife (if not previously cut out). CAUTION: DO NOT TRY TO KNOCKOUT. 7. Re-position and replace access panel. 535.02-N2Y FIGURE 4 - FILTER ACCESS & DRAIN PAN CONVERSION Unitary Products Group 3

535.02-N2Y Dimensions Wiring K.O. s* Refrigerant F1RP / Connections F1RC A B C J K D E F G Line Size MODEL Height Width Depth Power Control Liquid Vapor 018 40 18 14-7/8 16-1/2 5/8 024 40 18 14-7/8 16-1/2 5/8 030 40 18 14-7/8 16-1/2 3/4 036(RC) 40 18 14-7/8 16-1/2 7/8 3/4 22 18-3/8 10-3/8 7/8 3/8 036(RP) 40 21-1/2 18-3/8 20 1-3/8 3/4 042 40 21-1/2 18-3/8 20 7/8 048 50 24 7/8 060 50 24 7/8 NOTE: For all electric heat applications, ducts must be sized to match unit discharge air opening. G F J DRAIN CONNECTIONS FOR HORIZONTAL APPLICATIONS K All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request. A 4 " VAPOR OPENING LIQUID OPENING 12 1/8 " = Drain Pan Footprint MAX. FILTER LENGTH (21 inches) MAX. FILTER WIDTH (B minus 1-1/2 inches) C 3/4 REAR 3/4 1 3/8 " B D DRAIN CONNECTIONS FOR UPFLOW APPLICATIONS FILTER ACCESS E FIGURE 5 - DIMENSIONS & DUCT SIZES 4 Unitary Products Group

DUCT CONNECTIONS WARNING: Use 1/2" screws to connect ductwork to bottom of unit. Longer screws will pierce the drain pan and cause leakage. If pilot holes are drilled, drill only though field duct and unit bottom flange. NOTE: The electric heat accessory should be installed before the supply air duct is attached to the supply air openings. Air supply and return may be handled in one of several ways best suited to the installation. See Figure 5 for dimensions for duct inlet and outlet connections. The vast majority of problems encountered with combination heating and cooling systems can be linked to improperly designed or installed duct systems. It is therefore highly important to the success of an installation that the duct system be properly designed and installed. Use flexible duct collars to minimize the transmission of vibration/noise into the conditioned space. If electric heat is used non-flammable material must be used. Where return air duct is short, or where sound is liable to be a problem, sound absorbing glass fiber should be used inside the duct. Insulation of duct work is a must where it runs through an unheated space during the heating season or through an uncooled space during the cooling season. The use of a vapor barrier is recommended to prevent absorption of moisture from the surrounding air into the insulation. The supply air duct should be properly sized by use of a transition to match unit opening. All ducts should be suspended using flexible hangers and never fastened directly to the structure. This unit is not designed for non-ducted (freeblow) applications. Size outlet plenum or transition to discharge opening sizes shown in Figure 5. Duct work should be fabricated and installed in accordance with local and/or national codes. This includes the standards of the National Fire Protection Association for Installation of Air-Conditioning and Ventilating Systems, NFPA No. 90B. AIR FILTERS Air filters must be field supplied. A filter rack has been built into the unit. See Figure 4. Remove filter access bracket shown. Install proper size filter. See Table 2 for filter size. CAUTION: Equipment should never be operated without filters. SUSPENSION KITS Suspension kits are available. Models 1BH601 (unit sizes 018-042) and 1BH602 (unit size 048-060) are designed specifically for the units contained in this instruction (upflow application only). Model IMB0605, which fits all fan coil units, may also be used and is necessary for horizontal application. For installation of these accessory kits, see the instructions packed with the kit. ORIFICE SELECTION Each coil will have an orifice installed in the fitting between the liquid line connection and distributor. See Figure 6. The factory installed orifice is identified on the unit data plate. Also listed in Table 1. The orifice that is shipped with the coil is based on the most sold combination, but it may have to be changed, depending on the capacity and efficiency of the outdoor unit, elevation differences of the indoor and outdoor sections, and/or long total line lengths. An additional orifice is shipped with the outdoor unit in the literature packet for most requirements. Other sizes must be ordered from the parts department if required. ORIFICE INSTALLATION A standard orifice is pre-installed in the unit and is marked on the unit data plate. Refer to the outdoor unit instruction and application data to determine the proper orifice required for your particular system combination and piping conditions. If the orifice sizes match, nothing further is required and the refrigerant lines may be connected per the outdoor unit instruction. However, if another orifice should be used, change the orifice in the coil with the following procedure: FIGURE 6 - ORIFICE INSTALLATION WARNING: Coil is under 30 PSIG helium pressure. Relieve pressure from schrader valve on liquid line side. CAUTION: This fitting is a right-hand thread, turn counterclockwise to remove. 1. Remove the liquid line fitting using 3/4" wrenches, and remove the pre-installed orifice with a small diameter wire or paper clip. 2. Remove the new orifice from the packet and verify that it is the correct number required. Install this orifice with the rounded end toward the coil and the flat end outward per Figure 6. 3. Thread the liquid line fitting back in place on the coil. Tighten the fitting hand tight and turn an additional 1/8 turn to seal. CAUTION: Use 3/4" wrenches to turn fittings. Using pliers will cause internal damage to the fitting. TABLE 1 - INSTALLED ORIFICE SIZES 535.02-N2Y INDOOR COIL MODEL ORIFICE SIZE INSTALLED F1RP018 53 F1RP024 61 F1RP030 65 F1RP036 75 F1RP042 78 F1RP048 F1RP060 F1RC018 53 F1RC024 61 F1RC030 65 F1RC036 73 Unitary Products Group 5

535.02-N2Y NOTE: This procedure should be done within 2 minutes to keep air and contaminates from entering the coil. If the orifice cannot be replaced and the coil resealed within 2 minutes, then it should be temporarily closed to air using masking tape (short term delay) or plugging/capping (long term delay). There is no need to purge the coil if this procedure is done within the time limit. 4. Mark data plate with orifice installed. REFRIGERANT LINE CONNECTION NOTE: Confirm the orifice size before connecting lines. See the outdoor unit installation instructions for the procedure to install field supplied tubing for systems with sweat fittings. Stub adapters are available to adapt sweat connections to quick connections. Connect lines as follows: NOTE: Route the refrigerant lines to the coil in a manner that will not obstruct service access to the coil, air handling system or filter. 1. Suction line connections are made outside the center access panel. Cut off the suction line as close to the end as possible. Center access panel is recessed to assure sufficient room for brazing or it can be removed and slid over the suction line during brazing. 2. Braze the suction line. Re-attach the center access panel, if it had been removed. 3. Cut the liquid line at the groove in the bell, removing the schrader fitting. 4. Braze the liquid line. 5. Install supplied grommets on both the suction and liquid lines to complete the air seal. Lines should be sound isolated by using the appropriate hangers or strapping. When field supplied lines are used be sure to insulate the suction line only. ELECTRIC HEATERS & OPERATING CONTROLS The low voltage transformer and the fan / heater control are standard on all models and are prewired at the factory. To operate the air handler, it is necessary to field install either an electric heater kit (2HK) or a no heat power kit (2PK06700106). Factory installed electric heat is furnished with all necessary connections to operate unit. LOW VOLTAGE CONTROL CONNECTIONS The 24 volt power supply is provided by an internally wired low voltage transformer which is standard on all models. However if the unit is connected to a 208 volt power supply the low voltage transformer must be rewired to the 208 volt tap. See the unit wiring label. Field supplied low voltage wiring can exit the unit on the top right hand corner or the right hand side panel (see Fig. 5, item K). Install a 7/8" plastic bushing in the selected hole and keep low voltage wiring as short as possible inside the control box. The field wiring is to be connected at the screw terminals of the control board. Refer to Figures 9, 11, 12 and 13. NOTE: All wiring must comply with local and national electrical code requirements. Read and heed all unit caution labels. LINE POWER CONNECTIONS Power may be brought into the unit through the supply air end of the unit (top when unit is vertical) or the left side panel. Use the hole appropriate to the unit s orientation in each installation to bring conduit from the disconnect. The power lead conduit should be terminated at the electrical control box. Refer to Table 4 for wire requirements. Also see Figure 7. BLOWER SPEED CONNECTIONS All air handlers contain three speed blower motors which are prewired to the control board. Adjust blower motor speed to provide airflow within the minimum and maximum limits approved for evaporator coil, electric heat and outdoor unit. Speed tap adjustments are made at the motor terminal block, See Figure 7. Airflow data is shown in Tables 5 & 6. Higher efficiencies will be obtained if the indoor air volume is as high as possible provided the CFM does not exceed limitations and the sound level is not objectionable. Connect motor wires to motor speed tap receptacle for speed desired. See wiring label for motor wiring details. See Figure 7. FIGURE 7 - BLOWER SPEED CONNECTIONS 6 Unitary Products Group

TABLE 2 - PHYSICAL AND ELECTRICAL DATA 535.02-N2Y MODEL F1RP / F1RC... 018 024 030 036(RP) 036(RC) 042 048 060 Blower - Diameter x Width 9 x 6 10 x 6 10 x 8 10 x 8 10 x 8 10 x 8 11 x 10 11 x 10 Motor HP 1/4 1/4 1/3 1/2 1/2 3/4 1/2 Nominal RPM 1075 1075 1075 1075 1075 1130 Voltage 208/230 Amps Full Load 1.6 / 1.4 1.6 / 1.4 2.5 / 2.2 3.3 / 2.9 3.3 / 2.9 4.4 / 3.8 Locked Rotor 3.3 / 2.9 3.3 / 2.9 6.2 / 5.5 7.4 / 6.5 7.4 / 6.5 11.9 / 10.3 Filter 1 Type DISPOSABLE or PERMANENT Size 16 x 21 16 x 21 16 x 21 20 x 21 16 x 21 20 x 21 22 x 21 22 x 21 Shipping / Operating Weight (lbs.) - RP 87 / 92 93 / 98 100 / 105 109 / 115-115 / 121 Shipping / Operating Weight (lbs.) - RC 87 / 92 90/ /95 90 / 95-100 / 105 115 / 121 1 FIELD SUPPLIED ELECTRIC HEAT WITHOUT CIRCUIT BREAKER (2.5-10 KW) FAN CONNECTIONS FAN RELAY ELECTRIC HEAT WITH CIRCUIT BREAKER (2.5-25 KW) TRANSFORMER CONNECTIONS (HIGH VOLTAGE) 4-PIN POWER CONNECTOR 1 STAGE HEAT RELAY 24 VOLT R NO HEAT POWER KIT 5 AMP CONTROL VOLTAGE FUSE 6-PIN 24 VOLT COMMON CONNECTOR (LIMIT, 2nd and 3rd HEAT RELAY) FIGURE 8 - LINE POWER CONNECTIONS FIGURE 9 - CONTROL BOARD Unitary Products Group 7

535.02-N2Y TABLE 3 - ELECTRICAL DATA F1RP / F1RC Model 018N06 024N06 030N06 036N06 042N06 048N06 060N06 1 See Conversion Table below: 2 O.C.P. = Over-Current Protection Total Heat 1 KW Staging Factory Heater KW MBH 1st 2nd Installed Model 208 240 208 240 208 240 208 240 O.C.P. 2 2HK06500206A 1.9 2.5 6.5 8.5 1.9 2.5 - - NONE 2HK16500206A 1.9 2.5 6.5 8.5 1.9 2.5 - - BREAKER 2HK06500506A 3.8 5.0 13.0 17.1 3.8 5.0 - - NONE 2HK16500506A 3.8 5.0 13.0 17.1 3.8 5.0 - - BREAKER 2HK06500806A 5.6 7.5 19.1 25.6 3.8 5.0 1.9 2.5 NONE 2HK16500806A 5.6 7.5 19.1 25.6 3.8 5.0 1.9 2.5 BREAKER 2HK06500506A 3.8 5.0 13.0 17.1 3.8 5.0 - - NONE 2HK16500506A 3.8 5.0 13.0 17.1 3.8 5.0 - - BREAKER 2HK06500806A 5.6 7.5 19.1 25.6 3.8 5.0 1.9 2.5 NONE 2HK16500806A 5.6 7.5 19.1 25.6 3.8 5.0 1.9 2.5 BREAKER 2HK06501006A 7.5 10.0 25.6 34.1 3.8 5.0 3.8 5.0 NONE 2HK16501006A 7.5 10.0 25.6 34.1 3.8 5.0 3.8 5.0 BREAKER 2HK06500506A 3.8 5.0 13.0 17.1 3.8 5.0 - - NONE 2HK16500506A 3.8 5.0 13.0 17.1 3.8 5.0 - - BREAKER 2HK06500806A 5.6 7.5 19.1 25.6 3.8 5.0 1.9 2.5 NONE 2HK16500806A 5.6 7.5 19.1 25.6 3.8 5.0 1.9 2.5 BREAKER 2HK06501006A 7.5 10.0 25.6 34.1 3.8 5.0 3.8 5.0 NONE 2HK16501006A 7.5 10.0 25.6 34.1 3.8 5.0 3.8 5.0 BREAKER 2HK16501506A 11.3 15.0 38.6 51.2 3.8 5.0 7.6 10.0 BREAKER 2HK06500506A 3.8 5.0 13.0 17.1 3.8 5.0 - - NONE 2HK16500506A 3.8 5.0 13.0 17.1 3.8 5.0 - - BREAKER 2HK06500806A 5.6 7.5 19.1 25.6 3.8 5.0 1.9 2.5 NONE 2HK16500806A 5.6 7.5 19.1 25.6 3.8 5.0 1.9 2.5 BREAKER 2HK06501006A 7.5 10.0 25.6 34.1 3.8 5.0 3.8 5.0 NONE 2HK16501006A 7.5 10.0 25.6 34.1 3.8 5.0 3.8 5.0 BREAKER 2HK16501506A 11.3 15.0 38.6 51.2 3.8 5.0 7.6 10.0 BREAKER 2HK06500506A 3.8 5.0 13.0 17.1 3.8 5.0 - - NONE 2HK16500506A 3.8 5.0 13.0 17.1 3.8 5.0 - - BREAKER 2HK06500806A 5.6 7.5 19.1 25.6 3.8 5.0 1.9 2.5 NONE 2HK16500806A 5.6 7.5 19.1 25.6 3.8 5.0 1.9 2.5 BREAKER 2HK06501006A 7.5 10.0 25.6 34.1 3.8 5.0 3.8 5.0 NONE 2HK16501006A 7.5 10.0 25.6 34.1 3.8 5.0 3.8 5.0 BREAKER 2HK16501506A 11.3 15.0 38.6 51.2 3.8 5.0 7.6 10.0 BREAKER 2HK06501006A 7.5 10.0 25.6 34.1 3.8 5.0 3.8 5.0 NONE 2HK16501006A 7.5 10.0 25.6 34.1 3.8 5.0 3.8 5.0 BREAKER 2HK16501506A 11.3 15.0 38.6 51.2 3.8 5.0 7.6 10.0 BREAKER 2HK16502006A 15.0 20.0 51.2 68.2 3.8 5.0 11.3 15.0 BREAKER 2HK16502506A 18.75 25.0 64.0 85.3 3.8 5.0 15.0 20.0 BREAKER 2HK06501006A 7.5 10.0 25.6 34.1 3.8 5.0 3.8 5.0 NONE 2HK16501006A 7.5 10.0 25.6 34.1 3.8 5.0 3.8 5.0 BREAKER 2HK16501506A 11.3 15.0 38.6 51.2 3.8 5.0 7.6 10.0 BREAKER 2HK16502006A 15.0 20.0 51.2 68.2 3.8 5.0 11.3 15.0 BREAKER 2HK16502506A 18.75 25.0 64.0 85.3 3.8 5.0 15.0 20.0 BREAKER FOR KW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENT 208V OPERATION, MULTIPLY 240V TABULATED KW & MBH BY.751 230V 240V.918 8 Unitary Products Group

TABLE 4 - ELECTRICAL DATA F1RP / F1RC Model 018N06 024N06 030N06 036N06 042N06 048N06 060N06 2 O.C.P. = Over-Current Protection * 0 or 1 (No breaker or breaker) Field Wiring Heater Model Min. Circuit Ampacity Max. O.C.P. 2 Amps/Type Wire Size - AWG 75 C 208V 240V 208V 240V 208V 240V 2HK*6500206A 13.4 14.8 15 15 14 14 2HK*6500506A 24.9 27.8 25 30 10 10 2HK*6500806A 35.7 40.8 40 45 8 8 2HK*6500506A 24.9 27.8 25 30 10 10 2HK*6500806A 35.7 40.8 40 45 8 8 2HK*6501006A 47.1 53.8 50 60 8 6 2HK*6500506A 26.0 28.8 30 30 10 10 2HK*6500806A 36.8 41.8 40 45 8 8 2HK*6501006A 48.2 54.8 50 60 8 6 2HK16501506A 71.1 80.9 80 90 4 3 2HK*6500506A 27.0 29.7 30 30 10 10 2HK*6500806A 37.8 42.7 40 45 8 8 2HK*6501006A 49.3 55.7 50 60 8 6 2HK16501506A 72.1 81.8 80 90 4 3 2HK*6500506A 28.3 30.8 30 35 10 8 2HK*6500806A 39.1 43.8 40 45 8 8 2HK*6501006A 50.6 56.8 60 60 6 6 2HK16501506A 73.4 82.9 80 90 4 3 2HK*6500506A 2HK*6500806A 2HK*6501006A 2HK16501506A 2HK*6500506A 2HK*6500806A 2HK*6501006A 2HK16501506A 535.02-N2Y TABLE 5 - AIR FLOW DATA * (HEAT PUMP MODELS) F1RP/F1FP MODEL 018 024 030 036 042 048 060 BLOWER MOTOR SPEED 230 VOLT 208 VOLT CFM @ External Static Pressure - IWG 0.10 0.20 0.30 0.40 0.50 0.10 0.20 0.30 0.40 0.50 High 855 810 765 710 650 770 729 689 639 585 Med. 765 730 695 650 590 689 657 626 585 531 Low 645 620 590 555 505 581 558 531 500 455 High 950 910 865 835 775 855 819 779 752 698 Med. 845 815 785 745 705 760 733 706 670 634 Low 650 630 605 575 540 585 567 545 518 486 High 1,270 1,210 1,150 1,085 1,015 1,143 1,089 1,035 977 914 Med 1,050 1,040 995 930 855 941 936 895 837 770 Low 855 820 780 735 680 770 738 702 662 612 High - 1310 1250 1175 1120 1235 1179 1125 1058 1008 Med 1200 1150 1100 1040 985 1080 1035 990 936 887 Low 1060 1015 970 925 860 954 914 873 833 774 High - 1575 1500 1420 1350 1400 1418 1350 1278 1215 Med 1460 1295 1330 1260 1190 1314 1166 1197 1135 1071 Low 1250 1200 1155 1100 1050 1125 1080 1040 990 945 High Med Low High Med Low * Includes Return Air Filter and Largest Electric Heater. Unitary Products Group 9

535.02-N2Y TABLE 6 AIR FLOW DATA * (COOLING MODELS) F1RC/ F1FC MODEL BLOWER MOTOR SPEED 230 VOLT 208 VOLT CFM @ External Static Pressure - IWG 0.10 0.20 0.30 0.40 0.50 0.10 0.20 0.30 0.40 0.50 High 810 765 720 670 615 729 689 648 603 554 018 Med. 730 705 670 615 565 657 635 603 554 509 Low 625 605 575 535 490 563 545 516 482 441 High 925 885 850 805 750 833 797 765 725 675 024 Med. 820 800 765 720 680 738 720 688 648 612 Low 645 620 595 570 535 581 558 536 513 482 High 1205 1150 1090 1025 990 1085 1035 981 923 891 030 Med 1020 1010 960 895 825 919 909 864 805 742 Low 840 805 760 715 660 756 725 684 644 594 High 1305 1250 1195 1150 1065 1175 1125 1076 1035 959 036 Med 1225 1175 1125 1070 1000 1103 1058 1013 963 900 Low 1055 1015 980 930 880 950 914 882 837 792 * Includes Return Air Filter and Largest Electric Heater. DRAIN CONNECTIONS All drain lines should be trapped a minimum of three (3) inches, should be pitched away from unit drain pan and should be no smaller than the coil drain connection. CAUTION: Horizontal drain cutout in the center access panel should be removed by using a utility knife. DO NOT TRY TO KNOCKOUT. Route the drain line so that it does not interfere with accessibility to the coil, air handling system or filter and will not be exposed to freezing temperatures. See Figures 2, 3 and 4. NOTE: When the coil is installed in an attic or above a finished ceiling, an auxiliary drain pan should be provided under the coil as is specified by most local building codes. Coils should be installed level or pitched slightly toward the drain end. Suggested pitch should not exceed 1/4 inch per foot of coil. The coil is provided with a secondary drain that should be trapped and piped to a location that will give the occupant a visual warning that the primary drain is clogged. If the secondary drain is not used it must be capped. The drain pan connections are designed to ASTM Standard D 2466 Schedule 40. Use 3/4" PVC or steel threaded pipe. Since the drains are not subject to any pressure it is not necessary to use Schedule 40 pipe for drain lines. MAINTENANCE Filters must be cleaned when they become dirty. Inspect at least once per month. The frequency of cleaning depends upon the hours of operation and the local atmospheric conditions. Clean filters keep unit efficiency high. COIL CLEANING If the coil needs to be cleaned, it should be washed with Calgon coilclean (mix one part Coilclean to seven parts water). Allow solution to remain on coil for 30 minutes before rinsing with clean water. Solution should not be permitted to come in contact with painted surfaces. LUBRICATION The bearings of the blower motor are permanently lubricated. CONDENSATE DRAINS During the cooling season check the condensate drain lines to be sure that condensate is flowing from the primary drain but not from the secondary drain. If condensate ever flows from the secondary drain the unit should be promptly shut off and the condensate pan and drains cleaned to insure a free flowing primary drain. PROBLEM POSSIBLE CAUSE 1. No heat. Unit does not have 6-pin connector installed. 2. Limit open or not connected. Blower Runs all of the time 3. Variable speed break-out tab broken out. 4. Blower has delay on / off. Blown Fuse 1. Short to C or ground from R, Y, G, W, or O. No 24V No 2nd or 3rd stage heat TROUBLESHOOTING GUIDE 1. 4-pin connector loose. 2. Loose wire from control to transformer (24V and 230V). 3. Blown fuse on control board. 1. Check 6-pin connector and connections to panel mount relays. 10 Unitary Products Group

535.02-N2Y FIGURE 11 - COOLING ONLY - MODELS H*DB, H*DE AND H*DH FIGURE 12 - COOLING WITH ELECTRIC HEAT MODELS H*DB, H*DE AND H*DH FIGURE 13 - HEAT PUMP - MODEL E*FB, E*FC and E*FD Unitary Products Group 11

R FIGURE 14 - HEAT PUMP - MODEL E*FH Unitary Products Group P.O. Box 1592, York, Pennsylvania USA 17405-1592 Subject to change without notice. Printed in U.S.A. Copyright by York International Corporation 1995. All Rights Reserved. CPC 3M 1195.44 Code: SBY 535.02-N2Y