Energy Impacts of Various Residential Mechanical Ventilation Strategies

Similar documents
New Construction Builders Challenge: Sealed Attic and High Efficiency HVAC in Central Florida: A Year in Review

Executive Summary: Evaluation of the Impact of Vacant Home Space Conditioning Strategies on Summer Relative Humidity, Energy, and Peak Load; Phase II

Understanding Ventilation in Hot Humid Climates by Joseph Lstiburek

Optimizing Energy Efficiency and Improved Dehumidification Performance of Variable Capacity Air Conditioning Systems

Are Residential Whole-House Mechanical Ventilation Systems Reliable Enough to Mandate Tight Homes?

Measurement of Attic Temperatures and Cooling Energy Use in Vented and Sealed Attics in Las Vegas, Nevada

Design Methodology and Economic Evaluation of Central-Fan-Integrated Supply Ventilation Systems

Dehumidification at Part Load

Closing the Gap: Getting Full Performance from Residential Central Air Conditioners. Task 4 - Develop New Climate-Sensitive Air Conditioner

Interim Report for the Period thru February 15, 2018 Submitted to Department of Business and Professional Regulations Office of Codes and Standards

BEST PRACTICE FOR THE LOCATION OF THE AIR AND THERMAL BOUNDARIES IN SMALL COMMERCIAL BUILDINGS

ENERGY SYSTEMS LABORATORY

Ventilation in Humid Climates: Data from Field Experiments

Neil A. Moyer James B. Cummings David Chasar Principal Research Engineer Program Manager Research Engineer

AN ANALYSIS OF THE RESIDENTIAL ENERGY SAVINGS FROM THE IMPLEMENTATION OF THE 2001 IECC AND 2006 NAECA APPLIANCE STANDARDS IN THE STATE OF TEXAS

Measured Duct Leakage at Operating Conditions in 48 Homes

97.501B. Prepared by: (415) Sponsored By: Final Report. Author: Presented at: ASHRAE. Meeting SF Me!

MultiFamily Ventilation Updates: ASHRAE 62.2, Best Practices and Practical Applications RESNET Conference Atlanta, GA

Energy Consumption Data Analysis Phase II Final Report

Flexible Roofing Facility: 2004 Summer Test Results

USEFUL RESOURCES: Applicability. Item o of section 150. Review-Definitions Section 101

Air Distribution Fan and Outside Air Damper Recycling Control

Residential Air Leakage (Blower Door) Testing for Florida Code Compliance

Overview. Case Study 2008 Building America Prototype ICI Showcase House. Daytona Beach, Florida. Project Team: ICI Homes, Building Science Corporation

WHOLE-HOUSE VENTILATION SYSTEMS

2006 Building Science Press All rights of reproduction in any form reserved.

Final Report. Investigation of Energy Impacts of Ducted Dehumidifier Duct Configurations and Location. DBPR Project #B21551 UCF/FSEC #

An Assessment of Building Energy Efficiency Options at Horn Island Ranger Station, Gulf Islands National Seashore

Performance and Impact from Duct Repair and Ventilation Modifications of Two Newly Constructed Manufactured Houses Located in a Hot and Humid Climate

Case Study of an Innovative HVAC System with Integral Dehumidifier. Florida Solar Energy Center Cocoa, Florida

RESNET HERS Rater Sample Test Questions 2

TESTS OF ADSIL COATING

Mechanical Ventilation : How much is enough? Can there be Too Much? Subrato Chandra Resnet Meeting 2/20/07

Residential Performance Code Methodology for Crediting Dehumidification and Smart Vent Applications Final Report

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

CITY OF DANA POINT. COMMUNITY DEVELOPMENT, BUILDING AND SAFETY Golden Lantern, Suite 209 Dana Point, CA

Effects of Air Conditioner Sizing on Energy Consumption and Peak Demand in a Hot-Dry Climate

EnergyGauge USA Release Notes

2016 BUILDING ENERGY EFFICIENCY STANDARDS RESIDENTIAL HVAC ALTERATIONS

Adding More Fan Power Can Be a Good Thing

NightCool: A Nocturnal

Comparative Summer Thermal Performance of Finished and Unfinished Metal Roofing Products with Composition Shingles

Evaluating Moisture Control of Variable Capacity Heat Pumps in Mechanically- Ventilated, Energy-Efficient Homes.

EnergyGauge USA Release Notes

Why Thermostats Matter

Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

MAD-AIR 2016 Mechanical Air Distribution and Interacting Relationships. John Tooley Advanced Energy (919)

The Unplanned Impacts On Houses By Powered Attic Ventilators

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation

b.) Technical Information:

Supplement A- Improving Forced Air Heating Systems

ASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes

Evaluation of the NightCool Nocturnal Radiation Cooling Concept: Annual Performance Assessment in Scale Test Buildings Stage Gate 1B

Relative Humidity in Schools Jim Cummings and Chuck Withers

Bill McCullough. Director ERV Products. Dallas, TX

Dwelling Ventilation Strategies, Including ASHRAE 62.2 ASHRAE Ventilation for Acceptable Indoor Air Quality

Building Codes, Ventilation Rates, and Certified Performance. Ventilation Track Comfortech 2007 St Louis, MO September 27, 2007

Passive building in Hot and Humid Climates

Modular Construction. Live/Work Urban Infill Townhome. Modular Construction. Enclosure Design. San Francisco Bay Area Net Zero Urban Infill

City of Chanhassen. Site address. Ventilation Quantity (Determine quantity by using Table R or Equation R )

ENERGY STAR V2.5 & 3 Designed to Qualify AIA Annual Convention

ASHRAE JOURNAL ON REHEAT

Experimental Evaluation of the NightCool Nocturnal Radiation Cooling Concept: Performance Assessment in Scale Test Buildings

Heat Pump Water Heaters: A Key Energy Technology for California

Food Service Technology Center

Air Distribution Systems in Conditioned Spaces i.e. Ducts in Unvented Attics

Performance Rating of Unit Ventilators

A Cost Effective Multi-Spectral Scanner for Natural Gas Detection

AHRI Guideline W (I-P) 2014 Guideline for Selecting, Sizing, & Specifying Packaged Air-to-Air Energy Recovery Ventilation Equipment

Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory

Title Page. Report Title: Downhole Power Generation and Wireless Communications. for Intelligent Completions Applications

Laboratory Evaluation of Hybrid and Advanced Water Heaters: Performance Overview in Hot Humid Climate

From Energy Guzzler to Near-Zero Energy Home: Lessons from the Phased Deep Retrofit Project

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

ENGINEERING. Edition No. 13 October 2002

Ventilation, Makeup and Combustion Air Calculations Submittal Form New Dwellings

Equipment Specifications and Required Information Quantity Rebate

In Search of the Magic Box: A Review of Crossover Conditioning/Ventilation/Dehumidification Devices on the US Market

BSC Building America High Performance Homes: Today & Tomorrow. Peter Yost Senior Building Scientist

Food Service Technology Center

FirstEnergy Program Overview

Breathe Easy With. Out. Out 54 FINE HOMEBUILDING. COPYRIGHT 2014 by The Taunton Press, Inc. Copying and distribution of this article is not permitted.

Residential Heating and Cooling Loads

Address Account # Member # Equipment Specifications Quantity Rebate. ENERGY STAR Appliances

Effects of Kitchen Ventilation on Residential Dwellings

BPI 1200 and ASHRAE Standards

Home Performance Science

Building Envelope Air Leakage Failure in Small Commercial Buildings Related to the Use of Suspended Tile Ceilings

SPLIT-SYSTEM RESIDENTIAL HEAT PUMP WITH SEPARATE DEHUMIDIFICATION OPERATING MODE

Ventilation. ASHRAE 62.2 COMPLIANCE How do we get there? Bruce Hagen ND Dept. of Commerce.

Food Service Technology Center

THERMAL VACUUM TESTS OF A FIVE WATT PSEUDO CHIP SEM-X ELECTRONIC MODULE CLAMPED IN A SATELLITE BOX

Are you Getting Your Fan Flows Right?

Site address. Ventilation Quantity (Determine quantity by using Table N or Equation 11-1) Continuous ventilation

Managing HVAC in High Performance Buildings

Energy Upgrade California Home Upgrade Offered by The Energy Network

In Search of the Magic Box: A Review of Crossover Conditioning/Ventilation/ Dehumidification Devices on the US Market

Air Change, Ventilation, and Dehumidification for Multi-family Buildings

2019 Smart Energy Existing Homes Program Manual

Transcription:

Energy Impacts of Various Residential Mechanical Ventilation Strategies Authors Robin K. Vieira, Danny S. Parker, Lixing Gu, and Michael Wichers Original Publication Vieira, R., Parker, D., Gu, L., and Wichers, M., "Energy Impacts of Various Residential Mechanical Ventilation Strategies", Sixteenth Symposium on Improving Building Systems in Hot and Humid Climates, December 15-17, 2008, in Dallas, TX. Publication Number FSEC-PF-437-09 Copyright Copyright Florida Solar Energy Center/University of Central Florida 1679 Clearlake Road, Cocoa, Florida 32922, USA (321) 638-1000 All rights reserved. Disclaimer The Florida Solar Energy Center/University of Central Florida nor any agency thereof, nor any of their employees, makes any warranty, express or implied, or assumes any legal liability or responsibility for the accuracy, completeness, or usefulness of any information, apparatus, product, or process disclosed, or represents that its use would not infringe privately owned rights. Reference herein to any specific commercial product, process, or service by trade name, trademark, manufacturer, or otherwise does not necessarily constitute or imply its endorsement, recommendation, or favoring by the Florida Solar Energy Center/University of Central Florida or any agency thereof. The views and opinions of authors expressed herein do not necessarily state or reflect those of the Florida Solar Energy Center/University of Central Florida or any agency thereof.

ENERGY IMPACTS OF VARIOUS RESIDENTIAL MECHANICAL VENTILATION STRATEGIES Robin K. Vieira, Buildings. Research Division Director Danny S. Parker Principal Research Scientist Lixing Gu Principal Research Engineer Michael Wichers Technical Specialist Florida Solar Energy Center 1679 Clearlake Rd. Cocoa, FL 32922 ABSTRACT The Building America program has been working with home builders for more than a decade using a variety of strategies for bringing fresh air into the homes. Many of these strategies utilize the central air handler fan from the HVAC system to ventilate when the system runs. Controllers can be purchased to force the air to enter for minimum periods of time or to shut off outside air dampers after some period of runtime. EnergyGauge USA, a detailed hourly residential simulation program, has been modified to simulate the various runtime strategies, as well as supply- or exhaust-only ventilation strategies and an enthalpy recovery ventilation system. This paper compares simulation results for each of these ventilation strategies. Runtime ventilation tends to bring in very little extra air. When forced to turn on for 25% of an hour, the typical HVAC fan uses significant energy making the overall energy penalty more than that from a continuous supply or exhaust fan supplying the same nominal air flow. Enthalpy recovery ventilation units tend to use more energy overall - despite the heat recovery - than supply or exhaust only ventilation systems, due to using twice as much fan energy. This paper presents simulation results for eight ventilation strategies compared to no ventilation, and it presents the changes in energy use for each. BACKGROUND The U.S. Department of Energy s (DOE) Building America s contractors have worked with many builders over the last decade to favorably incorporate mechanical ventilation systems into home construction. Typical builder concerns include the ease of installation, maintenance, and first cost. The ability to maintain comfort and moisture control at low energy costs are additional concerns. ASHRAE standard 62.2 (ASHRAE, 2007) requires that homes receive outdoor air each hour at no less than the rate specified in the following equation based on the floor area of the conditioned space and number of bedrooms: Eq. 1 Qfan = 0.01Afloor + 7.5( Nbr + 1) where Q fan = Fan flow rate (cfm) A floor = Floor area (ft 2 ) N br = Number of bedrooms; not to be less than one For example, a three-bedroom house with 2,400 square feet would require at least 54 cubic feet per minute (cfm) of outdoor air. Although ASHRAE standards may call for supplemental forced ventilation of homes, in practice few building departments are enforcing mechanical ventilation. In most Sun Belt states, only homes participating in green home or other beyond-code programs tend to have any mechanical ventilation other than spot exhaust systems. Green home programs put an emphasis on ventilation health aspects. For example, LEED for Homes requires compliance with ASHRAE Standard 62.2-2007, with some exceptions for mild climates. In humid parts of the country, the impact of adding fresh air must be properly evaluated in the HVAC design. Otherwise, the health benefits sought may be compromised since it could lead to increased moisture levels that contribute to mold growth and increased reproduction of dust mites or other allergens (Chandra, 2001). The moisture load of any fresh air design must be adequately accounted for in designing the home s comfort conditioning system with consideration for times when the sensible load is small and the air conditioner may not run. A laboratory study looked at six strategies and resulting moisture loads [Moyer et al., 2004)]. This study quantifies the energy use and humidity impacts of six commonly implemented mechanical ventilation

strategies one exhaust system and five supply systems compared to the base case of no ventilation system. One of these strategies incorporates energy recovery. The six systems were installed serially in a new, EnergyStar Manufactured home laboratory (MHLab) with typical whole house air tightness and simulated occupancy for 14-day periods. The MHLab, where these strategies using nominal 50 cfm airflow were implemented, is located in Cocoa, Fla. Measured air exchange for the home using tracer gases ranged form 0.20 to 0.32 air changes per hour with average outside wind speeds of two to four miles per hour. Without mechanical ventilation the home had 0.15 air changes per hour. Each of the systems tested maintained reasonable humidity control, and Moyer credits the properly sized cooling system with maintaining the control despite the outside air. The strategy with outside air brought in through the air handler with a dehumidifier maintained the humidity most consistently, but had a 200-watt energy penalty. Humidity and cost considerations have led many builders to use a runtime ventilation scheme. This involves connecting a duct from the outside to the return side of the air handler where air is brought in by the air handler when it is activated. This allows the fresh air to be easily distributed to the various rooms. The potential downside of such a system is that at peak conditions excess air may be brought in when it is least needed, and during times of year when the air conditioning system may not need to run very often the fresh air goals will not be met. In order to compensate for these potential drawbacks, control systems have been added to augment runtime ventilation. One control forces the system to turn on once per hour or every few hours in order to bring in outside air if the system has not run the required amount on its own thermostat control. The potential downside of this control scheme is that the air handler fan is used to bring in only a small amount of air and tends to draw much more power than a small supply or exhaust fan. Another control utilizes a damper that will shut off after a system has run for a specified period. This control alleviates the original downside of bringing in excess air during peak conditions and potentially reducing the size (or latent capacity in humid climates) of the air conditioning system. By itself this control system would still not bring in fresh air during times of low air conditioning operation. Combining both of these control strategies allows a system to bring in sufficient outside air on a regular basis without excessive air during peak periods. Also, the excess power of using the air handler fan can be somewhat ameliorated by the use of a variable speed fan with a more efficient brushless DC motor. ENERGY AND VENTILATION SYSTEMS The energy use of the runtime ventilation system with and without the control systems will differ. Other mechanical ventilation options use small fans that use less energy when forced to run for ventilation purpose. An exhaust-only system, such as a bath fan that will run more frequently, is fairly easy to install. The potential downside is that the negative pressure created will lead to air movement through cracks, and potentially the made-up air will come from sources (e.g., an attached garage) where air is not desirable. A supply-only system could use a small fan and have positive pressure in the home. However, distributing the air throughout the house using just a small fan is a challenge. systems have to use two fans of similar size to the supply or exhaust only options, doubling the fan energy use and also being considerably more expensive to install. They allow the maximum control of entering and exiting air as both locations are determined by the designer. In comparison, an exhaust-only system will have the make-up air delivered from the paths of least resistance which may include holes between garages or attics and the conditioned space. systems can also include a heat exchanger or enthalpy exchanger. A supply-only or exhaustonly ventilation system will tend to have less total air from the combination of the mechanical ventilation and infiltration due to the fact that unbalanced air flows are not additive. air flow results in larger ventilation rates due to the governing equation for combining forced and natural ventilation (Sherman and Modera, 1986): Eq. 2 Q total = (Q nat 2 + Q unbal 2 ) 0.5 +Q Bal where Q represents volume of air flow (cfm or m/s). SIMULATION TOOL Recently, FSEC expanded EnergyGauge USA ventilation control capabilities by adding a max-time damper control for ventilation systems. The simulation engine is DOE-2.1E Version 120. FSEC developed an algorithm in a private function of DOE- 2.1E in order to model an HVAC fan running between a specified minimum and maximum portion of an hour. Building America teams, energy raters

and energy analysts can now choose from a large number of potential mechanical ventilation strategies: No mechanical ventilation provided air fan air fan Both supply and exhaust air fan (Fully or partially balanced) Enthalpy recovery ventilation system Runtime ventilation where ventilation air is provided only when heating and cooling systems run (supply vent using the air handler unit) Runtime ventilation with a required minimum where the HVAC fan runs for a minimum amount of time each hour Runtime ventilation where the outside air damper will close if the air handler system has run a set amount of time during the hour A system that has a required minimum runtime and a closure for the outside air damper after a maximum amount of time run that hour A system that provides no outdoor ventilation air but does provide a set ventilation fan power (this is primarily for some reference building energy use rule sets). DOE-2 reports the fan energy in report SS-L. The SS-L report allows for separate reporting of ventilation fan energy during non-heating and noncooling hours. In order to process scoring requirements that consider the energy use of mechanical fans (HERS 2006 for instance), the ventilation fan energy used during heating and cooling hours is proportioned to heating and cooling in accordance with those energy uses in EnergyGauge USA. For allocation purposes, the fan energy used during non-heating and non-cooling hours, which DOE-2 reports on the SS-L report, is added to the total by the proportion of heating and cooling fan energy used that month. If no heating or cooling fan energy was used that month then 50% is added to each. SIMULATION RESULTS The ventilation options depicted in the previous section were run for three cities Tampa, Dallas, and St. Louis, Missouri (Farmington weather data was used). A highly efficient, tax credit eligible, threebedroom, 2,400 square-foot home was modeled with a natural air change per hour (ach) of 0.30 - ach 50 of 5.7 - infiltration rate. The St. Louis home had an additional unconditioned, windowless basement. The Tampa home had concrete block wall construction with R-5 ft 2 -hr- o F/Btu insulation. The Dallas and St. Louis homes had wood frame walls insulated to R-13 and conditioned by a SEER 14/ HSPF 8.0 Btu/Wh heat pump. Many other characteristics (note the exceptions described here) are described in a detailed report (Fairey et al., 2006). The decision was made to simulate the type of systems builders frequently use rather than systems that may be installed to guarantee the quantity and quality of air according to ASHRAE Standard 62. This study was done bringing a nominal design of 50 cfm of outside air into the home. For runtime systems that may mean far less than 50 cfm is actually added on an average basis, and examples of this will be shown in this paper. The eight ventilation options produce the results shown in Tables 1 and 2 and increased energy penalty indicated in Figures 1 and 2. These results were obtained using EnergyGauge USA, version 2.8, release 1, and the Calculate > Annual Simulation menu option. These simulations were run with the following options: No mechanical ventilation during times of natural ventilation (EnergyGauge program shuts off all mechanical ventilation during times when algorithms indicate conditions are favorable for opening windows) Auto-sizing for the HVAC system set to on. FSEC recently added the ability to separate out any mechanical fan energy each hour, including the extra time the air handler energy for runtime ventilation schemes. Another recent addition was TMY3 weather data which was used for this study.

Mechanical Ventilation Strategy Table 1. Cooling season energy use for nominal 50 cfm ventilation strategies Tampa Dallas St. Louis Mechanical Total Mechanical Total Mechanical Vent Fan Cooling Vent Fan Cooling Vent Fan kwh kwh KWh kwh kwh Total Cooling kwh None 0 3512 0 2680 0 1192 Vent, 20W 120 3825 80 2900 46 1296 Vent, 20W 120 3793 80 2878 46 1286 vent, 40W 236 4108 158 3103 90 1374 60% effective ERV, 40W 239 3923 160 2966 115 1325 Runtime Vent (RV) 0 3571 0 2740 0 1225 RV w 25% min. runtime 180 3805 170 2979 147 1426 RV with outside damper off at 25% runtime 0 3532 0 2700 0 1198 RV fixed at 25% runtime 165 3748 157 2922 137 1383 Mechanical Ventilation Strategy Table 2. Heating season energy use for nominal 50 cfm ventilation strategies Tampa Dallas St. Louis Mechanical Total Mechanical Total Mechanical Vent Fan Heating Vent Fan Heating Vent Fan kwh kwh kwh kwh kwh Total Heating kwh None 0 293 0 2157 0 5028 Vent, 20W 30 342 78 2327 100 5290 Vent, 20W 30 346 78 2344 100 5318 vent, 40W 66 455 160 2774 206 6136 60% effective ERV, 40W 61 389 156 2485 194 5571 Runtime Vent (RV) 0 294 0 2164 0 5039 RV w 25% min. runtime 107 397 282 2429 368 5377 RV with outside damper off at 25% runtime 0 294 0 2160 0 5034 RV fixed at 25% runtime 102 393 265 2410 342 5350

Energy Increase from No Vent 35.00% 3 25.00% 2 15.00% 1 5.00% -5.00% Tampa Energy Increase from No Vent 35.00% 3 25.00% 2 15.00% 1 5.00% -5.00% Dallas Energy Increase from No Vent 35.00% 3 25.00% 2 15.00% 1 5.00% -5.00% St. Louis Figure 1. Cooling Season Increase in Energy Use with Eight Ventilation Strategies

Energy Increase from No Vent 6 5 4 3 2 1 Tampa Energy Increase from No Vent 35.00% 3 25.00% 2 15.00% 1 5.00% Dallas Energy Increase from No Vent 6 5 4 3 2 1 St. Louis Figure 2. Heating Season Increase in Energy Use for Eight Ventilation Strategies

DISCUSSION Below, we help interpret the results shown in Tables 1 and 2. Continuous Ventilation Systems When an exhaust system is employed we assume that the heat from the fan s motor is also exhausted. For supply systems, we assume the heat of the fan motor is delivered to the space. Thus, the exhaust vent option uses slightly more energy for heating, but slightly less energy for cooling than the supply only system We also assumed that balanced flow required twice the fan power of unbalanced flow (40 watts vs. 20 watts) since both a supply and exhaust fan are required. Even when a 60% enthalpy recovery ventilator (ERV) is added, the energy use is greater than for an unbalanced simple supply or exhaust system. Another reason for the greater energy use is that a balanced system delivers more air as explained above in Equation 2. Runtime Ventilation Systems The runtime vent method uses the heating and cooling system fan and a purposeful, ducted return leak with a damper to bring in outside air when the system runs. Without any other controls, it only brings in fresh air during periods when heating or cooling is required. For the Dallas home, the runtime vent option only slightly increased heating and cooling energy use. Considering that we were only adding 50 cfm when the system runs, this was not surprising. For the Dallas-Fort Worth climate, the home s mechanical systems were only turned on 13% of the time. The net effect when combined with the envelope ach 50 leakage of 4.0 is vanishingly small. Computing the difference between straight natural infiltration and the total from the runtime ventilation run requires looking at the difference between the flow calculated from equation 1 and what would have otherwise occurred. Eq. 3 Q difference = Q total - Q nat Figure 3 represents the hourly Q nat and Q difference for the runtime ventilation case. The average Q difference value is 0.8 cfm. Thus, runtime venting is hardly any different, on an annual basis, than no mechanical venting. Peak summer hours for this case were as high as 12 cfm added, so for some select hours the mechanical ventilation may make a significant difference, but not on an annualized basis. Runtime ventilation is highly dependent on system size. The system size calculated yielded moderate winter runtimes as shown on the top of Figure 3. Obviously, system size will have a large impact on the impact of runtime ventilation, although the modeled systems are quite a bit smaller than what might be expected in many newer homes where systems are chronically oversized. When forced to turn on for 25% of an hour, the typical HVAC fan uses significant energy so that the overall energy penalty is more than a continuous supply or exhaust fan that, although sized for the same nominal flow, would provide more fresh air, albeit not distribute it as well. This study is a simulation study and does not evaluate the quality of a given ventilation strategy, and in practice, energy used will depend on the components and the resistance of the distribution system. On the other hand, if the runtime vent is limited with a damper to be no greater than 25% of the hour, the model predicts almost no difference in cooling or heating energy use. This is expected because the system will supply even less outside air than the simple runtime vent case shown in Figure 3, where for some hours it is adding ventilation air for much more than 25% of the hour. Finally, a sophisticated controller that maintains exactly 25% minimum and maximum runtime each hour results in a 6% (Tampa) to 16% (St. Louis) increase in cooling and a 6% (St. Louis) to 34% (Tampa) increase in heating energy use compared to no venting, or slightly less energy penalty than the simpler 25% minimum runtime. Fan Energy Use Explains Overall Energy Use Changes Examining the breakout between actual cooling, heating and fan energy use, it is apparent that most of the added energy is from the fan. Actual cooling load is only slightly larger, which is not surprising since buildings require cooling many times, such as at night when it is more comfortable outside and the added air may actually reduce cooling loads. This occurs because internal gains and solar gains create cooling loads but reduce heating loads. Fan Heat Energy is Extra Load The heating value column in Table 2 is slightly misleading as the extra fan runtime also provides heat from its motor. Table 3 shows more details for the Dallas case. Thus, the 25% minimum runtime case shows less heating (excluding fans) than the no-vent case, but the software models the extra 295 kwh of fan energy as heat. In this case, with minimal added outside air, that more than makes up for the added heating load due to extra outside air.

Figure 3. Hourly natural and added ventilation rates for runtime vent case. Inputs were 50 cfm mechanical and 0.3 ach leakage (natural). Natural infiltration is adjusted hourly by DOE2 based on natural driving forces (e.g., wind speed). Table 3. Runtime Vent Dallas case Heating Heating Fan Mech. Vent Fan Total Heating % increase from no vent case No Vent 1860 287 0 2157 0 RV with 25% minimum 1852 295 282 2429 12.6 SUMMARY Simulation runs demonstrate that using typical mechanical ventilation control systems in highly efficient homes, with nominal 50 cfm ventilation, may increase overall cooling season energy use by 15% or more and heating season energy use by 25% or more. The fan energy use can be significant as a percentage for climates with mild seasons. ventilation systems, simulated using 40 watts of continuous energy have the highest energy use by far since balanced systems increase the amount of air more than supply or exhaust only systems and use more power. Enthalpy recovery ventilation units tend to use more energy overall, despite the heat recovery, than supply or exhaust only ventilation systems due to using twice as much fan energy. Runtime ventilation systems sized for bringing in 50 cfm of air actually bring in very little air on an average basis. For instance, there was only a 1% increase in outdoor air in a simulation for a home in Dallas. When forced to turn on for 25% of an hour, the typical HVAC fan uses significant energy so that the overall energy penalty is more than a continuous supply or exhaust fan This paper presents simulation results and does not evaluate the quality of a given ventilation strategy. The distribution of air, the actual quantity of air delivered and potential humidity levels will vary. However, this study does provide useful information for designers regarding the comparative energy use of systems.

REFERENCES ASHRAE. 2001. ANSI/ASHRAE Standard 62-2001, Ventilation for Acceptable Indoor Air Quality, Atlanta: American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. Chandra, S., & Beal, D. (2001). Preventing House Dust Mite Allergens in New Housing. ASHRAE IAQ Conference Proceedings, San Francisco, CA. Neil Moyer, Dave Chasar, Subrato Chandra and David Hoak, Assessing Six Ventilation Techniques in Hot Humid Climates, Proceedings of the 2004 Summer Study on Energy Efficiency in Buildings, Vol. 1, American Council for an Energy Efficient Economy, Washington D.C. Sherman, M.H. and Modera, M.P.,1986., "Comparison of Measured and Predicted Infiltration Using the LBL Infiltration Model," Measured Air Leakage of Buildings, ASTM STP 904, H.R. Treschel and P.L. Lagus, Eds., American Society for Testing and Materials, Philadelphia, p. 325-347 Fairey, Philip, Carlos Colon, Eric Martin, Subrato Chandra, Comparing Apples, Oranges and Grapefruit: An Analysis of Current Building Energy Analysis Standards for Building America, Home Energy Ratings and the 2006 International Energy Conservation Code, FSEC_CR_1650-06, September, 2006. ACKNOWLEDGEMENTS This work is partly sponsored by the U.S. Department of Energy (DOE), Office of Energy Efficiency and Renewable Energy, Building America Program under cooperative agreement number DE- FC26-06NT42767. Their support is gratefully acknowledged. This support does not constitute DOE endorsement of the views expressed in this paper.