SIGA-CC1 Single Input Signal Module Installation Sheet

Similar documents
Print Specification. Publication. Instructions. Specific requirements. General requirements

Signature Series Auto-Sync Output Module (CC1S)

FX-PDD Duct Smoke Detector Installation Sheet

Signature Series Component

Addressable NAC Output Module D327A

Control Relay Modules

Genesis Low Frequency (520 Hz) Horn-Strobe Installation Sheet

Booster Power Supply Manual

R-Series Remote Annunciators and Expanders Installation and Operation Guide

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

FEC403EN Installation Manual

LifeAlarm Fire Alarm Controls

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

PSN-1000 & PSN 1000(E) Installation Manual

D326A/D334A/D339A. Installation Instructions. Point Contact Modules

SC-6 Six Supervised Control Module

E-PDD Duct Smoke Detector Installation Sheet

1X-F Series Installation Manual

ATS1235 Advanced Wireless DGP on 868 MHz AM Installation Sheet

Notification Appliance Circuit Module

ECC-50/100(E) Emergency Command Center. General. Features. Emergency Voice Evacuation TYPICAL APPLICATIONS

Remote Booster Power Supply Technical Reference Manual

Product Guide. Fire Alarm Cables. Initiating Device, SLC Lines, and NAC Cables.

ECC-50/100(E) Emergency Command Center

TruVision IR Turret Camera TVT-2202/TVT-4202 Installation Guide

R Series Remote Annunciators and Expander Installation and Operation Guide

Fire Alarm Wiring. Circuit types, styles and limitations

/5121/5122 TrueAlert Power Supply Installation Instructions

ECC-50/100C. Emergency Command Center

TrueAlert Addressable Notification

Addressable Detectors & Bases

These instructions detail procedures to follow in order to avoid damage to equipment.

30.45 Electric Release PDRP-2001

Multi-Application Peripherals and Accessories

FireNET Plus Wiring Instructions

System Accessories, LCD Annunciators

KFP-CF Series Operation Manual

IDP-Zone-6 Six Zone Interface Module

ZP2 Series Operation Manual

CZ-6A Six Zone Interface Module

MMF Six Zone Interface Module

LDM Series Lamp Driver Modules For Graphic Annunciation and Control

Rev. B. TrueAlert Addressable Controller Application Manual

Remote NAC Power Supply D7038

Multiple Input and Output Modules

SAFEPATH SP40/2 D10 D35 AMP P/N P/N Installation, Testing, TONE SW Operation, and W4 Maintenance D54 SHORT

KFP-AF Series Fire Alarm Control Panel Installation Manual

(EN) RevC AS610-AS630 Outdoor Siren Installation Sheet.pdf. Remark: Rev. Date: Modif. no.

UEI-1 UNIVERSAL END-OF-LINE / ISOLATOR TESTER

Series. Access Power Controllers. Installation Guide

MODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description

Fire alarm system specification for multiple tenant retail buildings

MR-2602 Two Zone Fire Alarm Control Panel

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

Remote Booster Power Supplies

IFS SFP Tranceivers User Manual

SECTION FIRE ALARM SYSTEMS

LifeAlarm Fire Alarm Control Panels

XP6-C. Six Circuit Supervised Control Module and SYNC-1 Accessory Card

EST2. Installation and Service Manual P/N REV 07 REB 27FEB13

DS7465i. Installation Instructions. Input/Output Module

TrueAlert Non-Addressable, Multi-Candela Notification Appliances Installation Instructions

Installation Guide for models:

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

TrueAlert Addressable Notification Appliances

ANNUNCIATOR FIXED MODULE

TrueAlert Addressable Notification Appliances

SHORT CIRCUIT ISOLATOR TO NEXT COMPONENT REQUIRING POWER TO NEXT KEYPAD (** IF REQUIRED) STROBE RELAY MODULE KEYSWITCH ISOLATION MODULE STROBE

FireNET Fire Alarm Control Panel Installation Manual

June 10, 2002 DF C S2424

Fire Alarm System Fundamentals

Genesis Series Cable THE POWER OF CHOICE. Cables for Silent Knight

AL1042ULADA. NAC Power Extender. Installation Guide (See Application Guide for additional information) Rev

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

The TC-4F. Time Control Module C P/N 15972:C ECN For the Sensican 2000 Fire Alarm Control Panel

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

TECHNICAL DATA OBSOLETE

Addressable Fire Alarm Control Panel

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

EST3 Installation and Service Manual

M O D E L S F I R E G A R D M C V ADVANCE FIRE CONTROL RELEASE DEVICE

Conventional Fire Alarm Systems

TrueAlert Addressable Notification Appliances

4100U City and Relay Cards Installation Instructions

4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual

WINDOW & HVAC REPLACEMENT PEMBERTON TOWNSHIP BOE REGAN YOUNG ENGLAND BUTERA, PC PROJECT #5450E

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

1400 Direct Wire Ionization Smoke Detector

TrueAlert Multi-Candela Notification Appliances

Genesis LED G1 Series

IFS Fiber Module Installation & Operation Instructions

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays

NetworX Series NX-870E Fire Supervision Module Installation and Startup

Installation Guide for models:

good things in small packages

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING

FireShield Plus. GE Security. EST Life Safety & Communications Conventional Small Building Solutions. Conventional Fire Alarm Control Panels

The ACM-8R Annunciator Control Module

Advisor Advanced User Guide

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM

Transcription:

SIGA-CC1 Single Input Signal Module Installation Sheet Personality codes Use the personality codes described below to configure the SIGA-CC1 module. See Table 1 for listing information Table 1: Personality code listing information Code Description UL 864 CAN/ULC- S527 5 Signal - supervised output (Class B) 6 Telephone - three-state (Class B) 26 Telephone - four-state (Class B) EN 54-18 Description The SIGA-CC1 Single Input Signal Module is an addressable module that is used to connect the following circuits: Audible and visible notification appliance circuits (synchronized or unsynchronized) Speaker circuits Two-way telephone communication circuits (three-state or four-state) Upon command from the loop controller, the module connects supervised Class B signal or telephone circuits to the respective riser input. The riser input can be 24 VDC (to operate polarized audible and visible signal notification appliances), 25 or 70 VRMS (to operate audio evacuation speakers), or firefighter telephones. The module does not provide signal synchronization. To meet UL 864 requirements for horn and strobe signal synchronization, you must install a Genesis Signal Master module. The SIGA-CC1 module requires one address on the signaling line circuit (SLC). Addresses are assigned electronically. There are no address switches. Diagnostic LEDs provide visible indication of the state of the module through the cover plate: Normal: Green LED flashes Alarm/active: Red LED flashes Personality code 5: Signal - supervised output (Class B). Configures the SIGA-CC1 module as a riser selector for audible and visible notification appliance circuits or for single-channel audio circuits. The output circuit is monitored for open or shorted wiring. If a short exists, the module will not activate in order to prevent shorting the riser. The module will activate once the short is cleared. Personality code 6: Telephone - three-state (Class B). Configures the module as a riser selector for a three-state firefighter telephone. When a telephone handset is plugged into its jack or lifted from its hook, the module generates its own ring-tone signal, making a separate ring-tone riser unnecessary. The module sends this signal to the control panel to indicate the presence of an off-hook condition, and waits for the system operator to respond to the call. When the system operator responds, the ring-tone signal is disabled. Personality code 26: Telephone - four-state (Class B). Configures the module as a riser selector for a four-state firefighter telephone. Operation is the same as Personality code 6 except that the module can distinguish when a telephone is off-hook and when the circuit is shorted, which causes a trouble condition. Installation Install this device in accordance with applicable national and local codes, ordinances, and regulations. Notes The module is shipped from the factory as an assembled unit; it contains no user-serviceable parts and should not be disassembled. 2015 UTC Fire & Security Americas Corporation, Inc. 1 / 6 P/N 387022P-EN REV 12 ISS 22JUN15

This module does not operate without electrical power. As fires frequently cause power interruption, discuss further safeguards with the local fire protection specialist. To install the module: 1. Write the address assigned to the module on the label provided, and then apply the label to the module. Remove the serial number label from the module, and then attach it to the project documentation. 2. Connect the field wires. See Wiring below. 3. Using the self-tapping screw, attach the wall plate to the module. See Figure 1. 4. Using the four machine screws, attach the wall plate and module to the electrical box. Figure 1: Installing the SIGA-CC1 module (1) (1) Compatible electrical box (2) SIGA-CC1 module (3) Wall plate Protection from transient spikes (4) #6-32 5/8 machine screw (4X) #4 1/2 self-tapping screw For installations in which the output circuit connects to electromechanical bells or horns, install a bipolar transient protector (P/N 235196P) to protect the module from transient spikes caused by switching inductive loads. Locate bells and horns at least 6 ft. (1.8 m) from the module. To install a bipolar transient protector: 1. Install the transient protector across the output circuit inside the electrical box with the module. See Figure 2. (2) (3) (4) Figure 2: Bell circuit showing bipolar transient protector placement 10 9 (1) Normal state (2) Active state Wiring (1) (2) Wire this device in accordance with applicable national and local codes, ordinances, and regulations. General wiring notes Refer to the Signature loop controller installation sheet for SLC wiring specifications. Refer to the firefighter phone installation sheet for additional details. Each terminal on the module is limited to a single conductor. Test resistors are supplied with the SIGA-CC1 to prevent trouble signals on unused circuits during installation. When connecting field wires, remove the test resistors and install a UL/ULC Listed 47 kω EOLR at the end of the circuit. The module does not support conventional smoke detectors. Riser wiring notes For maximum line impedance, refer to the installation manual for the fire alarm panel. Maximum circuit capacitance is 0.1 µf. If the riser is used for more than one notification zone, install in accordance with the survivability from attack by fire requirements in NFPA 72 National Fire Alarm and Signaling Code. Circuit and riser wiring is different when four-state firefighter telephones are installed on three-state circuits. Before replacing a SIGA-CC1 module, tag the wires to ensure correct reconnection. The SIGA-CC1 module does not supervise the riser; the fire alarm control panel provides this function. To wire the module: 1. Verify that all field wiring is free of opens, shorts, and ground faults. 2. Strip 1/4 in. (about 6 mm) from the ends of all wires that connect to the terminal block of the module. When stripping wire ends, exposing more wire may cause a ground fault; exposing less wire may result in a faulty connection. 3. Connect the field wires. See Figure 3 through Figure 5. 2 / 6 P/N 387022P-EN REV 12 ISS 22JUN15

Figure 3: Wiring diagram for NAC (personality code 5) (1)(2)(3)(4) (3)(8) (1) Signal polarity is shown when the circuit is in supervisory state. Polarity reverses when the circuit is active. (2) Supervised. (3) Power-limited unless connected to a nonpower-limited source. If the source is nonpower-limited, eliminate the power-limited mark and maintain a minimum of 0.25 in. (6.4 mm) space from powerlimited wiring. For other mounting methods, see enclosure and bracket installation sheets to maintain separation of powerlimited and nonpower-limited wiring. The wire size must be capable of handling fault current from nonpower-limited source. or Use type FPL, FPLR, FPLP, or permitted substitute cables, provided these power-limited cable conductors extending beyond the jacket are separated by a minimum of 0.25 in. (6.4 mm) space or by a nonconductive sleeve or nonconductive barrier from all other conductors. Refer to the NFPA 70 National Electrical Code for more details. (4) If using a G1-P Genesis series horn while connected to a compatible fire alarm control panel, a CDR-3 Bell Coder must be used to comply with ANSI S3.41. 47 kω EOLR. Signaling line circuit (SLC) to next device. AUX riser (to next module or riser supervisory device). (8) Power-limited regulated, power supply UL/ULC Listed for fire protective signaling systems. AUX riser (from previous device). Signaling line circuit (SLC) from previous device. Supervised and power-limited. P/N 387022P-EN REV 12 ISS 22JUN15 3 / 6

Figure 4: Wiring diagram for audio (personality code 5) (1)(2)(3)(4) (1) Signal polarity shown when the circuit is in supervisory state. Polarity reverses when the circuit is active. (2) Supervised. (3) Power-limited unless connected to a nonpower-limited source. If the source is nonpower-limited, eliminate the power-limited mark and maintain a minimum of 0.25 in. (6.4 mm) space from powerlimited wiring. For other mounting methods, see enclosure and bracket installation sheets to maintain separation of powerlimited and nonpower-limited wiring. The wire size must be capable of handling fault current from nonpower-limited source. or Use type FPL, FPLR, FPLP, or permitted substitute cables, provided these power-limited cable conductors extending beyond the jacket are separated by a minimum of 0.25 in. (6.4 mm) space or by a nonconductive sleeve or nonconductive barrier from all other conductors. Refer to the NFPA 70 National Electrical Code for more details. (4) Unshielded twisted pair. 47 kω EOLR (P/N EOL-47). Signaling line circuit (SLC) to next device. Audio riser (to next module or supervisory end of line device). (8) Unshielded twisted pair. Use shielded twisted pair when installed in the same conduit as with a telephone riser. Audio riser (from previous device). Signaling line circuit (SLC) from previous device. Supervised and power-limited. 4 / 6 P/N 387022P-EN REV 12 ISS 22JUN15

Figure 5: Class B telephone (personality codes 6 and 26) Three-state telephone circuit (personality code 6) (1)(2)(3) (4) (3)(8) Four-state telephone circuit (personality code 26) (1) Telephone circuit. The plus and minus symbols indicate signal polarity. (2) Supervised. (3) Power-limited unless connected to a nonpower-limited source. If the source is nonpower-limited, eliminate the power-limited mark and maintain a minimum of 0.25 in. (6.4 mm) space from power-limited wiring. For other mounting methods, see enclosure and bracket installation sheets to maintain separation of power-limited and nonpower-limited wiring. The wire size must be capable of handling fault current from nonpower-limited source. or Use type FPL, FPLR, FPLP, or permitted substitute cables, provided these power-limited cable conductors extending beyond the jacket are separated by a minimum of 0.25 in. (6.4 mm) space or by a nonconductive sleeve or nonconductive barrier from all other conductors. Refer to the NFPA 70 National Electrical Code for more details. (4) Required if the distance from the SIGA-CC1 to the phone is greater than 5 ft. Shield must be continuous, insulated, and isolated from ground, except for the connection to chassis ground in the control panel. 47 kω EOLR (P/N EOL-47). Signaling line circuit (SLC) to next device. Telephone riser (to next module or end-of-line supervisory device). (8) Use shielded twisted pair. Shields must be continuous and grounded at the panel end. Telephone riser (from previous device). Signaling line circuit (SLC) from previous device. Supervised and power-limited. (1)(2)(3) (4) (3)(8) P/N 387022P-EN REV 12 ISS 22JUN15 5 / 6

Specifications Operating voltage range Current Standby Activated Maximum line impedance Ground fault impedance Output ratings (special applications) 24 VDC 25 VRMS audio 70 VRMS audio EOL resistor value Circuit resistance EOLR Circuit capacitance Circuit designation Signaling line circuits Telephone riser circuits Notification line circuits LPCB/CPR electrical box Requirements Minimum size W H D Compatible electrical boxes Wire sizes Operating environment Temperature Relative humidity Storage temperature range 15.20 to 19.95 VDC 310 µa 135 µa Refer to the control panel installation manual 10 kω 2 A 50 W 35 W 47 kω Refer to the control panel installation manual 0.1 µf max. 47 kω (P/N EOL-47) Class A, Style 6 or Class B, Style 4 Class B, Style 4 Class B, Style Y Plastic box with cover plate, no gaps or unused holes 3.5 3.5 1.5 in. (85 85 38 mm) 2-1/2 in. (64 mm) deep dual-gang box; 4 in. square box 1-1/2 in. (38 mm) deep box with a dual-gang cover 12 to 18 AWG (1.0 to 4.0 mm²) 32 to 120 F (0 to 49 C) 0 to 93%, noncondensing 4 to 140 F ( 20 to 60 C) Regulatory information Manufacturer Edwards, A Division of UTC Fire & Security Americas Corporation, Inc. 8985 Town Center Parkway, Bradenton, FL 34202, USA Authorized EU manufacturing representative: UTC Fire & Security B.V. Kelvinstraat 7, 6003 DH Weert, Netherlands Year of manufacture The first two digits of the DATE MFG number (located on the product identification label) are the year of manufacture. FCC compliance North American standards EN 54 EU compliance CPR certificates This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. CAN/ULC-S527, UL 864 EN 54-18: 2005 Input/output devices 0832-CPR-F0840 Contact information 2002/96/EC (WEEE directive): Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon the purchase of equivalent new equipment, or dispose of it at designated collection points. For more information, see: www.recyclethis.info. For contact information, see www.est-fire.com. 6 / 6 P/N 387022P-EN REV 12 ISS 22JUN15