Performance Evaluation of a Plug-In Refrigeration System Running Under the Simultaneous Control of Compressor Speed and Expansion Valve Opening

Similar documents
Exploring the Performance Characteristics of CO2 Cycles in a Breadboard-Type Test Facility

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Purdue e-pubs. Purdue University

An Experimental-Numerical Procedure to Characterize Compressor Performance under Cycling Operating Conditions of Refrigerators

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Experimental Mapping of the Thermodynamic Losses in Vapor Compression Refrigeration Systems

Low GWP Refrigerants for Air Conditioning Applications

Numerical Evaluation of Performance Curves of a High Frequency Microcompressor

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Performance Characteristics of a Refrigerator- Freezer with Parallel Evaporators using a Linear Compressor

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

An Experimental Study on the Effect of a new Defrosting Strategy on the Energy Consumption of Household Refrigerators

A New Control Approach for a Direct Expansion (DX) Air Conditioning (A/C)System with Variable Speed Compressor and Variable Speed Supply Fan

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Performance of CO2 Cycles with a Two-Stage Compressor

Theoretical and Experimental Analysis of the Superheating in Heat Pump Compressors. * Corresponding Author ABSTRACT 1.

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Pros & Cons of Using Hot-Wall Condensers in Household Refrigerators

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Experimental and Numerical Steady-State Analysis of a Top-Mount Refrigerator

Sub-Critical Operation of the CO2 Expander/ Compressor

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Optimisation Of Expansion Valve Control In Refrigeration Appliances Under Cyclic Operation

Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System

Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Efficiency of Non-Azeotropic Refrigerant Cycle

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

A Numerical and Experimental Study on Skin Condensers Applied to Household Refrigerators

Performance Measurement of R32 Vapor Injection Heat Pump System

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants

Mini Vapour Cycle System For High Density Electronic Cooling Applications

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Load Sharing Strategies in Multiple Compressor Refrigeration Systems

An Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator

Experimental comparison of a cascade refrigeration system operating with R744/R134a and R744/ R404a.

EXPERIMENTAL EVALUATION OF THE HEAT FLUXES THROUGH THE WALLS OF A DOMESTIC REFRIGERATOR

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

THE INFLUENCE OF NON-CONDENSABLE GASES ON THE THERMAL- ACOUSTIC BEHAVIOR OF HOUSEHOLD REFRIGERATORS

Compressor Capacity Control

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Experimental Study on the Performance of Twisted Capillary Tube

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

An Experimental Study on Defrosted Heaters Applied to Household Refrigerators

Effects of Oil on atranscritical Carbon Dioxide Air Conditioning Systems some experiences -

Effects of Refrigerant-Lubricant Combinations on the Energy Efficiency of a Convertible Split-System Residential Air-Conditioner

Experimental Studies on Non-Adiabatic Flow of HFC-134a Through Capillary Tubes

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Air-Cooled Heat Exchanger Performance for R410A

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Performance Characteristic and Optimization of a Simultaneous Heating and Cooling Multi Heat Pump

Experimental Investigation of a New High Temperature Heat Pump Using Water as Refrigerant for Industrial Heat Recovery

Capillary Tube and Thermostatic Expansion Valve Comparative Analysis in Water Chiller Air Conditioning

Designated vs Non-designated Areas for Condenser Subcooling

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner

R32 Compressor for Air conditioning and Refrigeration applications in China

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat Pumps Application

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Study of R161 Refrigerant for Residential Airconditioning

Experimental Research and CFD Simulation on Microchannel Evaporator Header to Improve Heat Exchanger Efficiency

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement Compressor

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

*Corresponding author;

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

A Modeling Study on the Operational Stability of a Variable Speed Direct Expansion Air Conditioning System

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Investigation of Evaporator Performance with and without Liquid Overfeeding

EXPERIMENTAL VERIFICATION OF PERFORMANCE OF CAPILLARY TUBE USING VAPOUR COMPRESSION REFRIGERATION SYSTEM

Dynamic Simulation of HFC-134a Flow Through Adiabatic and Non-Adiabatic Capillary Tubes

Numerical Simulation of a New Cooling System for Commercial Aircrafts

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Performance Evaluation of a Plug-In Refrigeration System Running Under the Simultaneous Control of Compressor Speed and Expansion Valve Opening Jackson Braz Marcinichen Federal University of Santa Catarina Leonardo C. Schurt Federal University of Santa Catarina Claudio Melo Federal University of Santa Catarina Luis A. T. Vieira Federal University of Santa Catarina Follow this and additional works at: http://docs.lib.purdue.edu/iracc Marcinichen, Jackson Braz; Schurt, Leonardo C.; Melo, Claudio; and Vieira, Luis A. T., "Performance Evaluation of a Plug-In Refrigeration System Running Under the Simultaneous Control of Compressor Speed and Expansion Valve Opening" (2008). International Refrigeration and Air Conditioning Conference. Paper 921. http://docs.lib.purdue.edu/iracc/921 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

2447, Page 1 PERFORMANCE EVALUATION OF A PLUG-IN REFRIGERATION SYSTEM RUNNING UNDER THE SIMULTANEOUS CONTROL OF COMPRESSOR SPEED AND EXPANSION VALVE OPENING Jackson B. MARCINICHEN, Leonardo C. SCHURT, Cláudio MELO, Luis A. T. VIEIRA POLO Research Laboratories for Emerging Technologies in Cooling and Thermophysics Department of Mechanical Engineering, Federal University of Santa Catarina P.O. Box 476, 88040-900, Florianópolis, SC, BRAZIL Phone: +55 48 3234 5691, e-mail: melo@polo.ufsc.br ABSTRACT This paper assesses the simultaneous influence of compressor speed and expansion valve opening on the thermodynamic performance of a plug-in (cassette) refrigeration system, running under different control strategies. Two different system configurations were investigated: (i) variable speed compressor (VSC) and capillary tube (CT); and (ii) VSC and electric expansion valve (EEV). A dual SISO (Single-Input, Single-Output) control strategy was devised based on two PI controllers, one for the compressor speed and another for the expansion valve opening. The former senses the return temperature, while the latter senses the superheating degree at the evaporator exit. It was found that the average energy consumption of the VSC/EEV when compared to the VSC/CT configuration decreased by as much as 10.1%, depending on the cassette operation regime and ambient temperature. 1. INTRODUCTION Refrigeration systems for light commercial applications are usually assembled with capillary tubes or thermostatic expansion valves and single speed compressors. More recently plug-in or cassette refrigeration systems have been introduced into the market. Although innovative in several aspects these systems are very conservative from a thermodynamic point of view. A new scenario for such systems might be the use of variable speed compressors (VSC) and electric expansion valves (EEV), both working together and under a logic provided by a smart control strategy. In this respect both the EEV and VSC would adjust themselves to allow a proper matching between the cooling load and the cooling capacity and also to guarantee proper feeding of the evaporator. Cho et al. (2006) evaluated the performance of an conditioning system varying the refrigerant charge, the compressor speed, the expansion valve opening and the internal heat exchanger (IHX) length. Carbon dioxide (CO 2 ) was used as the working fluid. It was shown that any increase in the compressor speed reduced the system coefficient of performance (COP), independently of refrigerant charge. The authors also showed that any increase in the compressor speed increased the optimum valve opening and that the system optimum discharge pressure could be attained by the simultaneous adjustment of valve opening and compressor speed. Finally, they showed that the IHX increased the cooling capacity by 6.2% and 11.9% and COP by 7.1% and 9.1% at compressors speeds of 40Hz and 60Hz, respectively. All tests were carried out under steady-state conditions without the aid of any type of controller. Pöttker and Melo (2006) studied the effect of compressor speed, valve opening and refrigerant charge on the thermodynamic performance of a HFC-134a refrigeration system. They showed that for a fixed refrigerant charge and under steady-state conditions there was a proper combination of the p compressor speed and valve opening that maximized the COP for a given cooling load. Lin and Yeh (2007) implemented a MIMO (Multi-Input, Multi-Output) control strategy in an conditioning system comprised of a VSC (0-100Hz) and a stepper motor EEV (480 pulse. It was shown that the time variation of the conditioned ambient temperature was well reproduced by the control action and that the system COP was improved. Finally, the authors claimed that with a proper control of the evaporator and condenser flow rates higher COP values would be expected.

2447, Page 2 Marcinichen et al. (2007) evaluated the energy consumption of a plug-in refrigeration system assembled with a VSC, running firstly at a fixed speed of 1800rpm and secondly with a variable speed to control the evaporating pressure. In both cases the EEV controlled the superheating at the evaporator exit. In the first case a drop of 8.7% in the energy consumption was found for the VSC/EEV when compared to the VSC/CT configuration. In the second case the energy consumption of the VSC/EEV was always higher than that of the VSC/CT combination. This gave a clear indication that the evaporating pressure was not a suitable parameter for use in control strategies focused on system performance. In this study the same plug-in unit tested by Marcinichen et al. (2007) was used to explore a new compressor speed control strategy, based on the cassette return temperature, which is an indirect way of balancing cooling capacity and cooling load. The VSC and EEV controllers were developed using the PI (Proportional-Integral) structure. The tests were carried out using a purpose-built calorimeter for plug-in systems, under three ambient conditions (24.0ºC/45%, 32.2ºC/65% and 40.5ºC/75%). 2. EXPERIMENTAL FACILITY 2.1 Calorimeter The calorimeter is basically composed of the following parts: i) 150mm thick wall polyurethane chamber, ii) cassete-calorimeter coupling, and iii) supply duct. An electric heater is installed in the supply duct to control the internal temperature. A variable speed fan and a damper are also installed in this duct to control the pressure drop in the loop (see Figure 1). Figure 1: Schematic of the loop All variables present in a balance of energy involving the cassette itself and the calorimeter, are controlled and measured by the experimental set-up, both under steady-state and transient conditions. The cassette cooling capacity ( Q e ) can be calculated in three distinct ways, as follows: i) Energy balance on the refrigerant side: In this case the refrigerant mass flow rate ( m ) and the refrigerant enthalpy difference between the inlet of the evaporator and the exit of the cooled compartment ( Δ h ) should be evaluated (see Equation 1 and Figure 2), = m Δh (1) Q e

2447, Page 3 Inlet evaporator temperature Cooled compartment Expansion Valve Evaporator Stabilizer Exit cooled compartment temperature Heat Exchanger From condenser To compressor Figure 2: Schematic of the refrigerant loop ii) Energy balance on the side: In this case the mass flow rate ( m ) and the temperature ( Δ T ) and humidity ratio ( Δ ) differences at the inlet and outlet of the evaporator should be measured (Equation 2), W Q = m c T + m W h (2) e p w where the symbols cp and h correspond to the constant pressure specific heat and to the saturated water vapor w enthalpy at 0 o C, respectively. iii) Energy balance in the control volume involving the calorimeter and the cassette: In this case all the energy forms flowing through the control surface should be taken into account (Equation 3), dt W +W + Q - Q f h w e = m cp (3) dt where W h is the heater power, W f is the fan power and Q w is the heat transfer rate through the chamber walls. Although any of the introduced procedures may be used to evaluate the cassette cooling capacity, the option chosen in this study was the energy balance on the refrigerant side. 2.2 Cassette The baseline cassette is comprised of a tube-fin evaporator, a helical condenser, a capillary tube-suction line heat exchanger and a variable speed compressor. The refrigerant fluid is R-134a. The modified cassette incorporates the following changes with respect to the baseline version: i) the CT was replaced by a PWM (Pulse Width Modulated) EEV and ii) the capillary tube-suction line heat exchanger was replaced by a liquid line-suction line heat exchanger. The length of the internal heat exchanger was kept equal to that of the baseline system (83cm), but the liquid line diameter was decreased in order to keep the internal volume and consequently the refrigerant charge of both systems equal. 2.3 Instrumentation A Coriolis mass flow meter was installed in the discharge line. The suction and discharge pressures were measured by absolute pressure transducers and the temperatures by T-type thermocouples. Voltage, current and power were measured by specific transducers. Specific electronic circuits, capable of converting digital into analogical signals, were developed and used to control both the VSC and the EEV. The measurement uncertainties are given in Table 1.

2447, Page 4 Table 1: Measurement uncertainties Transducer Uncertainty Transducer Uncertainty Temperature ±0.2 ºC Power ±1.5 W Pressure ±0.02 bar Energy consumption ±0.0015 kwh/month Voltage ±0.5 V Mass flow rate ±0.03 kg/h Current ±0.01 A Mass ±0.02 g 2.4 Controllers Two PI (Proportional-Integral) control structures were developed to establish the cassette return temperature and the superheating degree. These structures were implemented in a dual SISO control strategy to allow variations in the compressor speed and valve opening. It should be noted that the superheating degree was calculated from the difference between the refrigerant temperature at the exit of the cooled compartment and the refrigerant temperature at the inlet of the evaporator (see Figure 2). The controllers were designed by firstly running experiments to identify the system. In such experiments the behavior of the controlled variables was examined against stepwise changes in the compressor speed and valve opening (see examples in the Figures 3 and 4), under ambient conditions of 32.2ºC/65%. The models of the superheating degree as a function of valve opening and of the return temperature as a function of compressor speed were developed based on the studies by Hong et al. (1992), Outtagarts et al. (1997) and Aprea and Renno (2001). Figure 3: Return temperature vs. compressor speed Figure 4: Superheating vs. valve opening The first-order linear models developed are represented by equation (4) while the model parameters are given in Table 2. y( K p G( = = u( τs + 1 (4) Where: G(: process transfer function y(: Laplace transform of the superheating degree (ΔT) or of the return temperature (T r_ ), ºC u(: Laplace transform of the EEV opening (A EEV ) or of the compressor speed (N), % or rpm K p : static gain, ºC/% or ºC/rpm : time constant, s

2447, Page 5 Table 2: Identification test results Parameter ΔT (A EEV ) T r_ (N) K P -2ºC/% -0.0044ºC/rpm 150s 2800s The PI controllers, represented by equation (5), were designed based on the above mathematical models. The PI controller parameters are shown in Table 3. Where: u( 1 C( = = Kc. 1 + (5) e( TI s C(: controller transfer function u(: Laplace transform of the EEV opening or of the compressor speed, % or rpm e(: Laplace transform of the error in the superheating degree or in the return temperature, ºC K c : controller proportional gain, %/ºC or rpm/ºc T I : controller integral time, s Table 3: PI controller parameters PI Controller K c T I T r_ -680rpm/ºC 750s ΔT -1.5%/ºC 53s 3. CASSETTE EVALUATION 3.1 Charge determination The refrigerant charge of the VSC/CT baseline system was firstly optimized according to two distinct testing procedures: i) the optimum charge was that which minimized the energy consumption under cyclic operation conditions and ii) the optimum charge was that which minimized the supply temperature under continuous operation conditions, with a return temperature of 2ºC. The tests were carried out in an environmental chamber with the temperature controlled at 32.2 o C and the relative humidity at 65%. The compressor speed and the loop pressure drop were maintained at 3600rpm and 25Pa, respectively. Figures 5 and 6 show the results supplied by the first test procedure. Tests were carried out with a heater power of 0W. It can be seen that the optimum refrigerant charge was approximately 260g, a value that minimized the energy consumption and produced a superheating degree of 2ºC. Figure 5: Energy consumption vs. refrigerant charge Figure 6: Superheating vs. refrigerant charge

2447, Page 6 The results obtained with the second test procedure are shown in Figure 7. In this case the optimum refrigerant charge corresponded to a value of 255g, a value that minimized the supply temperature and produced a superheating degree of 1.7ºC Figure 7: Superheating and supply temperature vs. refrigerant charge The optimum refrigerant charge was therefore 30g higher than that specified by the cassette manufacturer (230g). In all the following tests a refrigerant charge of 260g was employed. 3.2 Energy consumption Energy consumption tests were carried out with the two cassette configurations, under three pre-established conditions: i) cooling load supplied by the electric heaters, ii) loop pressure drop kept at 25Pa and iii) compressor on and off temperatures of 5.6 o C and 1.7 o C, respectively. Both the cassette and the calorimeter were mounted in an environmental test chamber, where tests were carried out under the following conditions: 24ºC/45%, 32.2ºC/65% and 40.5ºC/75%. The tests were carried out using the compressor speed to control the return temperature at 3 o C and the valve opening to control the superheating degree at 6 o C. Table 4 shows the energy consumption and the runtime ratio (RTR) of the two cassette configurations running under three distinct ambient conditions. It is worth noted that the energy consumption refers only to the compressor and not to the other system components. Table 4: Energy consumption and runtime ratio (RTR) Condition Heater power (W) Compressor energy consumption (kwh/month) / RTR VSC/CT VSC/EEV Difference (%) 24ºC / 45% 40 64.27 / 59.65 67.59 / 57.76 5.17 160 88.18 / 100 84.23 / 100-4.48 32.2ºC / 65% 30 78.65 / 83.28 83.12 / 77.35 5.68 100 98.50 / 100 86.26 / 100-12.43 40.5ºC / 75% 20 100.04 / 100 87.31 / 100-12.72 It can be observed that the energy consumption of the VSC/EEV was greater than that of the VSC/CT configuration only when the compressor switched on and off (RTR smaller than 100%). Under this condition, even at the lowest compressor speed, there is no balance between cooling load and cooling capacity, which decreases the return temperature to values lower than the set point of 3 o C. When a proper balance between cooling load and cooling capacity is attained, the compressor works continuously and the energy consumption of the VSC/EEV is always lower than that of the VSC/CT configuration, with the difference increasing with the ambient temperature. Figures 8 to 11 show the time variation of the superheating degree, cooling capacity, compressor speed and power during a compressor cycle resulting from a heater power of 40W under ambient conditions of 24ºC/45%.

2447, Page 7 Figure 8: Superheating vs. time Figure 9: Cooling capacity vs. time Figure 10: Compressor speed vs. time Figure 11: Compressor power vs. time It can be seen that the VSC/EEV configuration operated with an average superheating of 6.7ºC, a value lower than that obtained with the VSC/CT configuration (8.5ºC). Furthermore the VSC/EEV produced a higher cooling capacity and operated with a smaller runtime ratio than that of the baseline system. However, the VSC/EEV compressor speed and power values were higher than those of the VSC/CT system. The net result was an increase in the energy consumption showing that the effect of a power increase surpassed the effect of a runtime ratio decrease. Table 5 shows the compressor speed and power ( W ), the cooling capacity and the system coefficient of performance c for the two cassette configurations running under ambient conditions of 32.2ºC/65%, and with a heater power of 100W. It is worth noting that the VSC/EEV configuration operated with a lower compressor speed and power, with a higher cooling capacity and consequently with a higher coefficient of performance than that of the baseline system. Table 5: Cassette performance Configuration N (rpm) W c (W) Q e (W) COP VSC/CT 2193.7 136.8 304.3 2.22 VSC/EEV 1918.5 119.9 329.1 2.75 4. CONCLUDING REMARKS The energy consumption of the VSC/EEV was higher than that of the VSC/CT configuration, when the compressor switched on and off. In this case the cooling capacity and the cooling load are not balanced against each other, which decreases the return temperature to values lower than the set point of 3 o C. When there is a proper balance between the cooling load and the cooling capacity, the compressor runs continuously and the energy consumption of the VSC/EEV is always lower than that of the VSC/CT configuration. A saving of up to 12.1% in energy

2447, Page 8 consumption was found for the VSC/EEV when compared to the VSC/CT configuration, depending on the ambient temperature. Finally, it should be mentioned that the PI controllers were designed for ambient conditions of 32.2ºC/65%, but responded quite well to the extrapolated conditions of 24 o C/45% and 40.5 o C/75%. REFERENCES Aprea, C., Renno C., 2001, Experimental Analysis of a Transfer Function for an Air Cooled Evaporator, Applied Thermal Engineering 21, pp. 481-493. Cho, H., Ryu, C., Kim, Y., 2006, Cooling Performance of a Variable Speed CO 2 Cycle with an Electronic Expansion Valve and Internal Heat Exchanger, International Journal of Refrigeration, pp. 1-8. Hong, W., Granryd, E., Kraft. H., 1992, A Pulse Width Modulation Control System for Regulating Refrigerant Flow into an Evaporator, Singapore International Conference on Intelligent Control and Instrumentation, pp. 603-607. Lin, J. L., Yeh, T. J., 2007, Modeling, Identification and Control of Air-Conditioning Systems, International Journal of Refrigeration, pp. 209-220. Marcinichen, J. B., Melo, C., Gomes, B. B., Chevarria, G. C., 2007, Analysis of the Combined Effect of Compressor Speed and Expansion Device Opening on the Thermodynamic Performance of a Cassette Refrigeration System, IV Congresso Ibérico, II Congresso Iberoamericano de Ciências e Técnicas do Frio, Porto, Portugal.(in Portuguese) Outtagarts, A., Habershill, P., Lallemand, M., 1997, The Transient Response of an Evaporator Fed Through an Electronic Expansion Valve, International Journal of Energy Research, pp. 793-807. Pöttker, G., Melo, C., 2006, Experimental Study of the Combined Effect of the Refrigerant Charge, Compressor Speed and Expansion Valve Opening in Refrigeration Systems, 11 th Brazilian Congress of Thermal Sciences and Engineering -ENCIT, paper CIT06-0448. (in Portuguese) ACKNOWLEDGEMENTS The authors are grateful to Empresa Brasileira de Compressores (Embraco S. A.) for sponsoring this research program and for technical discussions, in particular, Dr. Luciana W. da Silva. The continued support for this research program from Financiadora de Estudos e Projetos (FINEP) is also duly acknowledged.