HVAC REPAIR/REPLACEMENT 07/18/12 SECTION HVAC - MAJOR EQUIPMENT

Similar documents
Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

A. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

UNIVERSITY OF ROCHESTER DESIGN STANDARDS NOVEMBER 1, 2013

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION EXHAUST FANS

A. Codes and Standards that are Standard at the University:

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

SECTION (15833) - HVAC POWER VENTILATORS

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems.

RetroAire Model Number: 9,000 to 36,000 Btuh (2.6 to 10.5 kw)

C. Samples for Initial Selection: For units with factory-applied color finishes.

SECTION WATER-SOURCE UNITARY HEAT PUMPS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004)

SECTION AIR HANDLING UNIT

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

1.1 This section applies to air handling units for HVAC Systems.

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork.

Modular Supply Make-Up Air Unit

Stanford University Facilities Design Guidelines SECTION DECENTRALIZED UNITARY HVAC EQUIPMENT

Direct Fired Heater Model AD Specification

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section.

Indirect Gas-Fired Make-Up Air

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

SECTION CONVECTION HEATING AND COOLING UNITS

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/

SECTION ROTARY-SCREW WATER CHILLERS

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

Modular Heating & Ventilating Unit Model IGX-HV

SECTION FAN COIL UNITS

VERTICAL STACK INNKEEPER GUIDE SPECIFICATION CGC Hybrid Heat Pump System

SKYPAK II, 3 Ton Series, gives you a

SECTION ROOFTOP REPLACEMENT AIR UNITS

MACH N-407 Heat Pump Air-Cooled Chiller

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

Direct Gas-Fired Make-Up Air

KIC Air Curtains. Technical Guide

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS

Advance Release September 2009

SECTION AIR COOLED WATER CHILLERS

BARD MANUFACTURING COMPANY, INC. W24G-W60G Gas Heat/Electric Cooling Engineering Specification Guide

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

SKYPAK II, 3 Ton Series, gives you a

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

Direct Gas-Fired Make-Up Air Models DG and DGX

MAC N-407 Air-Cooled Chiller

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM

AIR COOLED PACKAGED CHILLER

All side discharge units are having high pressure switch (LP switch- Optional) and time delay relay. Compressors are scroll type, Copeland make.

48GS HIGH-EFFICIENCY SINGLE-PACKAGE GAS HEATING/ ELECTRIC COOLING UNITS

SECTION REFRIGERATION. 1. Reciprocating Compressors (Hermetic). 2. Reciprocating Compressors (Open Drive). 3. Water Cooled Condensing Units.

SECTION COMPUTER ROOM AIR CONDITIONING SYSTEMS

SECTION AIR DOORS

SPECIFICATIONS - DETAILED PROVISIONS Section Heating, Ventilation, and Air Conditioning Equipment C O N T E N T S

Propeller Fans. Industrial And Commercial Fans Belt And Direct Drive. Your Clean Air Source!

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION REFRIGERATION

Complete HVAC Capability. Central Station Air Handling Units. Publication No. WT-CSX-0616A

RGE 13 A T - 1 A

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise Modular Climate Changer Full Spec. Prepared by: Phone Number: Prepared for:

JOB NAME: LOCATION: PURCHASER: ENGINEER: SUBMITTED TO: FOR: REFERENCE [ ] APPROVAL [ ] CONSTRUCTION [ ] SUBMITTED BY: DATE:

A. Section Common Motor Requirements for HVAC Equipment: Fan motors.

RTU. Roof Top Units 8 30 Ton. Maxi-Kool.

48TM GAS HEATING/ELECTRIC COOLING UNITS

GAS FURNACES G20RE/ G20RXE EXISTING NEG ENGINEERING DATA EXISTING NEG. Typical Applications

University of Houston Master Construction Specifications Insert Project Name

.2 Section Waste Management and Disposal.

Construction Standards Page

Series. Packaged Rooftop Units, heat pumps and Outdoor air handling Units. Features:

BARD MANUFACTURING COMPANY, INC. WG3S-WG5S 2-Stage Cooling with Gas Heat Engineering Specification Guide

Advance Product Data. Features/Benefits. 42WKN Hydronic Fan Coil Units

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

SECTION (15767) - UNIT HEATERS

Series PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS. Features:

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

BARD MANUFACTURING COMPANY, INC. W18AA-W72AB

SKYPAK II Heating & Cooling Self Contained Packages

SECTION PACKAGE AIR COOLED WATER CHILLER PART 1 GENERAL 1.01 SECTION INCLUDES. A. Chiller package. B. Charge of refrigerant and oil.

48TF GAS HEATING/ ELECTRIC COOLING UNITS

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - "Systems and Equipment.

HEATING & COOLING SUBMITTAL The DuraPac Series Unit 559F/579F180, 216, 240, , 18, 20, and 25 NOMINAL TONS

48SS018, 024, 030, 036, 042, 048 & 060 STANDARD-EFFICIENCY COMBINATION GAS HEATING/ ELECTRIC COOLING UNITS

Submittal Data Performance Data Electrical Data

D. NEMA Compliance: Provide electric motors and components which comply with NEMA standards.

Gas-Fired Indoor and Outdoor Duct Furnaces

SECTION HEATING BOILERS

TGIF-1. Indirect Fired Heating Systems. Technical Guide for: IF Indoor Installations. IFW Outdoor Installations. Applied Air. Keeps You.

Model UDAP. Power Vented, Low Static Axial Fan Commercial/Industrial Unit Heaters DESCRIPTION STANDARD FEATURES OPTIONAL FEATURES - FACTORY INSTALLED

Industrial Space Heating Direct Gas-Fired Heating. Greenheat 50/50 Recirculation

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters.

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters.

SECTION (15733) - DEDICATED OUTDOOR AIR UNITS

Transcription:

SECTION 15300 - HVAC - MAJOR EQUIPMENT PART 1 - GENERAL 1.1 MECHANICAL GENERAL A. Section 15010 is applicable. PART 2 - PRODUCTS 2.1 FANS A. General: 1. All fans shall bear the AMCA Certified Performance Ratings Seal and U.L. Label. Some ratings shall be in accordance with AMCA Bulletin 300. Fans shall have published ratings certified by Air Moving and Conditioning Associates, Inc., (AMCA), Standard 210 and Class established by AMCA 2408-69. Fan RPM and BHP shall be selected to produce specified capacity when installed in system with accessories as indicated. Fan wheels shall be statically and dynamically balanced. 2. Belt drive fan motors shall have bases which permit adjustment of belt tension, belt guards with tachometer hole for fan shaft, and all fan motors shall have variable pitch diameter sheaves. 3. Bearings for belt drive fans other than propeller type shall have an average service life of 100,000 hours, factory lubricated and equipped with standard hydraulic grease fittings and with lubricating lines extending to outside of casing. 4. A solid state speed control on all direct drive fans shall be provided and wired under this division to allow initial balancing of fan air quantity. 5. Motors shall be as specified in Section 15010 and shall be readily accessible. Motors one (1) horsepower and larger shall be high efficiency type. B. Cabinet/Ceiling Type: 1. Housings shall be reinforced phosphatized steel. Wheels shall be true centrifugal, forward curbed design, statically and dynamically balanced. Fans shall be direct or belt drive as per schedule on drawing. 2. Where grilles are required, they shall be aluminum with white baked enamel symmetrically finished appearance. Interior surfaces of housings shall be lined with dark acoustical insulation permanently secured in place. Interior of installed unit shall not be visible when grille is in position. 3. Motors shall be shaded pole type with sleeve bearings, supported by one piece, die formed steel suspension brackets with rubber isolation dampers. 4. Terminal box shall be mounted in the housing with receptacle, plug and cord inside of the cabinet. All motors shall be suitable grounded. Motor and fan assembly shall be removable from installed ceiling ventilator. 5. Where duct flanges are required on one or both ends of fan, they shall be pre-assembled to housings. 6. Backdraft dampers shall be of integral design with aluminum damper on steel spring and foam rubber seal to eliminate chatter. 7. A speed controller on direct drive fans shall be mounted at the fan and factory wired or field wired under Division 16, between the fan and fan energizer. C. Square in-line centrifugal: 1. Fan shall be in-line duct mounted type, belt or direct drive as scheduled. Fan wheel shall be aluminum, backward inclined centrifugal type. 2. Housing shall be heavy gauge galvanized steel, square configuration with integral square duct collars. Housing shall be equipped with two removable service doors. Provide motor cover. HVAC MAJOR EQUIPMENT 15300-1

3. Motor shall be isolated from the airstream, and shall be provided with external mounted junction box, disconnect switch and flexible wiring leads. 4. Provide removable inlet guard by fan manufacturer on all non-ducted fan applications. D. Centrifugal Roof Exhauster: 1. Roof exhaust fans shall be of the centrifugal, belt or direct drive type. The fan housing shall be constructed of heavy duty aluminum mounted on a rigid support structure. The shroud shall have a rolled bead and internal structural members for added strength. Install curb gasket with all curb mounted fans. 2. The fan wheel shall be of the aluminum backward curved, centrifugal type with spun inlet venturi. Motors and centrifugal wheels shall be mounted on vibration isolators. 3. Motors shall be isolated from the exhaust airstream. Air for cooling the motor shall be taken into the motor compartment form a location free from contaminants. Motors shall be readily accessible for maintenance. Motors and centrifugal wheels shall be mounted on vibration isolators. 4. A NEMA disconnect switch shall be factory installed and wired from the fan motor to the disconnect junction box. A conduit chase shall be provided for running electrical wiring through the curb cap into the power compartment. 5. Provide a backdraft damper mounted within roof curb. E. Propeller Fans: 1. Fans shall be direct or belt drive as scheduled with steel or cast aluminum blades and hub, and steel frames with formed flanges and deep spun inlet venturi. Bearing supports for belt drive shall be integral to the frame and of steel. 2. Fans shall be designed for low sound with swept, steeply pitched blades. 3. Propeller roof fans shall be as specified in 1. and 2. above, arranged for axial flow, and installed in a tall base with fan hood both constructed of galvanized steel. Hood panels shall be sloped from center point to drain and equipped with heavy gauge galvanized steel supports and ½ galvanized mesh birdscreen. 4. Propeller type fans shall have steel panel with multi-blade steel wheel, ball bearing motor with built-in thermal overload protection, direct drive, solid state speed control mounted at fan by Division 15, steel motor support, fan side guard with service access door and galvanized steel wall collar. Provide inlet and/or outlet guards where exposed in harms way. 5. Exhaust fans shall have gravity operated shutter with steel frame and aluminum blades with felt edges, coupled with tie rods. Supply fans shall have motorized damper. 6. Wall mount collar shall serve as a fan mount to metal plenum. F. In-line booster fan: 1. Fan shall be in-line type with galvanized steel housing with powder coat baked enamel finish, backward inclined centrifugal fan wheel, PSC direct drive motor, pre-wired terminal strip and integral pre-wired positive pressure sensing switch. Switch shall incorporate a delay-on-break timer cycle to maintain fan performance for intervals of 10 minutes until drying cycle is completed. 2. Fan performance shall be based on tests conducted in accordance with Home Ventilation Institute (HVI). 3. Fan shall be tested and approved buy UL and rating shall include approval for dryer exhaust and airstream temperature of at least 140ºF. 4. Basis of design is Fantech DBF 4XL, or approved equal. G. Acceptable manufacturers are Greenheck, Penn, Breidert, Loren Cook or Twin City Fan. 2.2 FILTERS A. Operating filters for rooftop units shall be 2 pleated media type, Farr 30/30, with sizes as standard for unit manufacturers. HVAC MAJOR EQUIPMENT 15300-2

B. Construction filters shall be dry type fiberglass media, double wall box panel type, with sizes as standard for equipment. C. During construction, before units are placed in operation construction filters shall be installed, checked at regular intervals and replaced as necessary. No units are to be operated without filters in place. As part of system commissioning prior to start of test and balance and for final HVAC acceptance by Architect, clean operating filters shall be furnished and installed for all units. 2.3 GAS FIRED UNIT HEATERS (Closed combustion w/ power vent) A. Unit heaters are scheduled on the drawings. B. Gas fired unit heater shall have American Gas Association Certification. Heat exchanger shall be 20 gauge aluminum steel tubes welded to 18-gauge aluminized steel headers. Unit shall be separated combustion type, 80% thermal efficient with power venter and ducted combustion air intake. C. Gas valves shall be 24 volt with 100% safety shut-off on main and pilot. Units in Vehicle Maintenance Building shall have two-stage gas valves. D. Unit shall be propeller fan with drip proof motor with thermal overload protection. Unit shall be fully wired except for thermostat. E. Unit shall be equipped with spark-ignition, intermittent safety pilot with electronic flame supervision and timed lockout. Provide a wall thermostat with relay kit and guard with locking cover. F. Unit shall be furnished with 90 degree nozzles and directional louvers. G. Unit casing shall be minimum of 2-0 gauge galvanized steel with factory baked enamel finish, enclosing a propeller fan and motor as described above. H. Power venting shall be provided by flue vent fan, assembled to a sealed flue collection chamber. Furnish vertical concentric vent kit with caps and vent-box. I. Acceptable manufacturers are Reznor, Sterling, Lennox, or Carrier. 2.4 SPLIT SYSTEM DUCT FREE HEAT PUMP (Wall mounted fan coil) A. Air cooled, split system outdoor section shall be suitable for rooftop installation. Unit shall consist of a hermetic reciprocating, scroll, or rotary compressor, an air-cooled coil, propeller type blow thru outdoor fans, reversing valve, accumulator, R-410a refrigerant charge, heating mode metering device, and control box. Unit shall discharge air horizontally. Unit construction shall comply with ANSI/ASHRAE 15 and NEC. Units shall be constructed in accordance with U.L. standards. Air-cooled condenser coils shall be leak tested at 350 psig air pressure. Unit cabinet shall be constructed of galvanized steel, bonderized and coated with a baked enamel finish. Outdoor fans shall be direct drive propeller type, and shall discharge air horizontally. Outdoor fan motors shall be totally enclosed, single phase motors with Class B insulation and permanently lubricated sleeve bearings, and shall be protected by internal thermal overload protection. Fan blades shall be corrosion resistant and shall be statically and dynamically balanced. Outdoor fan openings shall be equipped with PVC coated protection grille over fan and coil. Compressor shall be equipped with oil system, operating oil charge, and motor. Internal overloads shall protect the compressor from over-temperature and over-current. Scroll compressors shall also have high discharge gas temperature protection if required. Reciprocating compressors shall be equipped with crankcase heaters. Compressor assembly shall be installed on rubber vibration isolators and shall have internal spring isolation. Coil shall be constructed of aluminum fins mechanically bonded to internally enhanced, seamless copper tubes. Refrigerant circuit components shall include brass external liquid line service valve with service gage port connections, suction line service valve with service gage connection port, service gage port connections on compressor suction and discharge lines with Schrader type HVAC MAJOR EQUIPMENT 15300-3

fittings with brass caps, accumulator, bi-flow filter drier, and pressure relief. B. Outdoor unit operating controls and safeties shall be factory selected, assembled, and tested. The minimum control functions shall include, time delay restart, automatic restart on power failure, safety lockout, a time delay control sequence, high pressure and liquid line low pressure switches, and start capacitor and relay on single phase units without scroll compressors. Safeties shall include: System diagnostics, compressor motor current and temperature overload protection, high pressure relief and outdoor fan failure protection. Unit electrical power shall be a single point connection. Unit shall have high and low voltage terminal block connections. Liquid solenoid valve shall be included on heat pumps where required for excessive heights where recommended by manufacturer. C. Indoor direct expansion wall mounted fan coil units shall be complete with cooling/heating coil, fan, fan motor, piping connectors, electrical controls, micro processor control system, and integral wall mounting bracket, mounting hardware, and thermistor interconnection cable. The unit shall be matched with outdoor unit as scheduled on drawing. Cabinet discharge and inlet grilles shall be attractively styled, high impact polystyrene. Cabinet shall be fully insulated for improved thermal and acoustic performance. Fan shall be tangential direct drive blower type with air intake at the upper front face of the unit and discharge at the bottom front. Vertical and horizontal air sweep shall be provided. Coil shall be copper tube with aluminum fins and galvanized steel tube sheets. Fins shall be bonded to the tubes by mechanical expansion. A drip pan under the coil shall have a drain connection. Condensate pan shall have internal trap and auxiliary drip pan under coil header. The units shall use AccuRater piston refrigerant metering device in the indoor unit and outdoor unit liquid line service valve. Unit shall have filter track with factory supplied cleanable filters. Motors shall be open drip proof, permanently lubricated ball bearing with inherent overload protection. Fan motors shall be 3-speed. Controls shall consist of a microprocessor based control system which shall control space temperature, determine optimum fan speed, and run self diagnostics. Controls shall include a minimum of the following features: an automatic restart, timer function, temperature sensing controls, high discharge temperature shutdown, indoor coil freeze protection, wireless infrared remote control indoor to outdoor thermistor connection cable, fan speed control, time delay to prevent compressor restart in less than 3 minutes, automatic heating-to-cooling changeover and demand defrost. Indoor coil high temperature protection shall be provided to detect excessive indoor discharge temperature when unit is in heat pump mode. All units shall have rotatable refrigerant lines for penetration through the wall using flare connections. All units shall have flare connections. Provide a condensate pump to remove condensate from the drain pan. The lift capability of the condensate pump shall be a minimum of 10 feet. A level sensor on the condensate pan shall stop cooling operation if the level in the condensate pan is unacceptable. D. Acceptable manufacturers are Carrier, Mitsubishi, LG, Sanyo or Daikin. 2.6 VAV SYSTEMS A. General: The systems shall be bypass and changeover type in which a rooftop unit supplies either warm air or cool air. The components shall be comprised of but not limited to VAV zone dampers, bypass dampers zone temperature sensors or thermostats, microprocessor based central system controller, discharge air temperature sensors, bypass air control system (static pressure or velocity controlled) low voltage control wiring and communication bus. B. Dampers: Zone and bypass dampers shall be heavy galvanized steel or aluminum fitted with an elliptical damper blade to assure linear airflow. Round dampers shall be crimped on the leaving air end and straight on the entering end. Actuators shall be 24 VAC. HVAC MAJOR EQUIPMENT 15300-4

C. Controls: 1. Central System Controller (Master Thermostat): Microprocessor based controller shall be equipped with integral clock and shall be capable of starting / stopping equipment on a programmable schedule. Microprocessor based controller shall communicate with the zones via twisted pair; select heating or cooling mode and the number of stages for each mode based on information from zones, responds to "occupied or unoccupied" heating or cooling setpoints. 2. Zone thermostats: Solid-state sensor or thermostat to provide temperature control by modulation of the zone damper(s) and communicate cooling or heating requirement to central system controller via the twisted pair communications bus. 3. Bypass Controller: Shall utilize static pressure or velocity sensor controller to regulate the bypass damper(s) as required to maintain required airflow for proper operation of the HVAC unit. 4. Division 15 shall be responsible for wiring from circuit supplied by Division 16 to 24 volt controls transformers, 24-volt control wiring, and communication bus. E. Quality Assurance: Controls and components shall be provided by firms regularly engaged in the manufacture of such systems. Components shall be compatible in size, capacities, and characteristic to integrate with HVAC system. Start-up and commissioning of VAV system shall be assisted by employee of the equipment manufacturer. Four copies of written report assuring proper performance shall be submitted to the Architect. F. Acceptable manufacturers are Lennox/Sectra, Trane, Enviro-Tec, Airlink, Johnson Controls or Carrier. PART 3 - EXECUTION 3.1 CONTROLS AND CONTROL WIRING A. Control or safety devices furnished with equipment for field installation and wiring shall be installed and wired under Section 15900. 3.2 AIR FILTERS A. Do not operate any air distribution systems without filters in place. Construction filters shall be utilized prior to start of test and balance. Operating filters shall be installed for test and balance, and shall be checked and replaced as necessary prior to final inspection. 3.3 HVAC EQUIPMENT KNOCKOUTS AND ACCESS PLATES A. All unused holes in HVAC equipment shall be properly covered and sealed against the elements. Opening in outdoor equipment housing which are used for connection of electrical or mechanical lines shall have properly installed grommets, seals, strain clamps, or weather shields. 3.4 EQUIPMENT SUPPORTS AND PORTALS A. Refer to Section 15020 for support specifications required for mechanical equipment on the roof, concrete pads or suspended units. END OF SECTION 15300 HVAC MAJOR EQUIPMENT 15300-5