Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Preaction Fire Protection Package General Description

Similar documents
Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Deluge Fire Protection Package General Description

Technical Data. Approvals The 1-1/2 thru 8 inch (DN40 thru DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

Worldwide Contacts.

Technical Data. Approvals The 1-1/2 in. to 8 in. (DN40 to DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

Technical Data. Working Pressure Range 20 to 250 psi (1,4 to 17,2 bar)

DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package. General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP1300. Worldwide Contacts

Model CV-1FR Riser Check Valves 2 to 12 Inch (DN50 to DN300) General Description. Installation. Technical Data. Page 1 of 6 OCTOBER 2010 TFP950

Technical Data. Installation

Design Criteria. Installation

Model A Pipe Line Strainer 3, 4, 6, 8 & 10 Inch (DN80, DN100, DN150, DN200 & DN250) 175 psi (12,1 bar) General Description.

Technical Data Approvals UL Listed and FM Approved. Refer to Tables 1, 2, and 3, as applicable.

Model ESFR-17 Early Suppression, Fast Response Upright Sprinklers 16.8 K-factor General Description

Model ESFR-25 Early Suppression, Fast Response Pendent Sprinklers 25.2 K-factor General Description

ILLUSION 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick Response, Standard Coverage General Description

The Series LFII (TY3596) Residential

Pre-Pack INTEGRATED PRE-ACTION SYSTEM

Model CHEC 8.0 K-factor Concealed Horizontal Extended Coverage Quick Response Light Hazard, Sidewall Sprinklers General Description

Model/Sprinkler Identification Number JULY, 2011 WARNINGS

Series ELO-231 Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

Series TY-B & TY-FRB, 10 mm Orifice, ISO 7/1-R3/8 Upright, Pendent, and Recessed Pendent Sprinklers Standard and Quick Response General Description

Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

Series TY-B 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General Description

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright, and Pendent Extended Coverage Light and Ordinary Hazard General Description

Series LFII Residential Sprinklers Flat-Plate Concealed Pendent 4.9 K-Factor General Description

Series LFII Residential Pendent Sprinklers 4.9 K-factor General Description

Deluge & Preac tion Systems

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations

Model QRS Electronic Accelerator (Quick Opening Device) For Dry Pipe or Preaction Systems General Description

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations

Series RFII 5.6 K-factor. Flush II Concealed Pendent Sprinklers

Model ELOC 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick and Standard Response, Extended Coverage

Sprinkler Identification Numbers

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-Factor General Description

Series LFII Residential Flush Pendent Sprinklers 4.2 K-factor General Description

Series TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard)

Model/Sprinkler Identification Numbers

DOUBLE INTERLOCK, PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC RELEASE

AQUAMIST Mist Control Center (MCC) Pump Skid Unit. General Description. Technical Data. Page 1 of 8 JANUARY 2016 TFP2270. Worldwide Contacts

5.6K Horizontal Sidewall Standard and Quick Response, Extended Coverage General Description. Model/Sprinkler Identification Numbers (SINs)

Series LFII Residential Horizontal Sidewall Sprinklers 4.4 K-factor General Description

Model WS TM 5.6 K-factor Specific Application Window Sprinklers, Horizontal and Pendent Vertical Sidewall General Description

VIZOR Electronic Dry Pipe Accelerator (EDPA) Quick-Opening Device for Dry Pipe Systems General Description

Sprinkler Identification Number (SIN) TY4234. Page 1 of 8 APRIL 2012 TFP Technical Services

Series LFII Residential Horizontal Sidewall Sprinklers 4.2 K-factor General Description

Sprinkler Identification Number TY ECLH HSW, 8.0K, 3/4"NPT

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH WET PILOT ACTUATION

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH ELECTRIC RELEASE

11.2K * Pendent Extended Coverage, Light and Ordinary Hazard General Description. Model/Sprinkler Identification Numbers (SINs) Technical Data

RAPID RESPONSE Series LFII Residential Sprinklers 4.4 K-factor Horizontal Sidewall, Dry Type Wet Pipe and Dry Pipe Systems

5.6K Pendent, Upright, and Horizontal Sidewall Standard Response, Standard Coverage General Description. Model/Sprinkler Identification Numbers (SINs)

TECHNICAL DATA OBSOLETE

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

Use this product according to this instruction manual. Please keep this instruction manual for future reference.

Model/Sprinkler Identification Number (SIN) Technical Data

Series DS-1 Stainless Steel Dry-Type Sprinklers 5.6K Pendent, HSW, and Extended Coverage HSW Standard and Quick Response General Description

TECHNICAL DATA. 319a. January 27, 2012

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC RELEASE

Datasheet. Dry-pipe Vacuum Sprinkler System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

Datasheet. Vacuum Double-interlock Preaction System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

TotalPac X Firecycle III Preaction Double interlock system

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEU-LECTRIC RELEASE

TotalPac X Single interlock SUREFIRE system

Installation, Operation & Service Manual

Model AV Alarm Valve With and Without Model RC-1 Retard Chamber European Conformity Valve Trim General Description

Instructions for Installation, Operation, Care and Maintenance

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description.

Model CV-1F Grooved End Swing Check Valves. General Description. Technical Data. Installation. Page 1 of 6 FEBRUARY 2016 TFP1550. Worldwide Contacts

Instructions for. Care and Maintenance 10 psi (0,7 bar) Pneumatic Supervising Pressure. Single Interlock

N2 BLAST Datasheet Preaction double interlock, Electric/Pneumatic c/w N 2 Blast Nitrogen generating system Self contained unit

CONSTRUCTION REQUIREMENTS

GASGUARD LEL 3 OPERATING & INSTALLATION MANUAL

SPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM

Technical Data. Sizes: ANSI Inches (DN) 2-1/2 (DN65), 3 (DN80), 4 (DN100), 5 (DN125), 6 (DN150), 8 (DN200), 10 (DN250)

TotalPac 3 Firecyle III Deluge Remote controlled system

N2 BLAST Datasheet SUREFIRE double interlock c/w N 2 Blast Nitrogen generating system Self contained unit

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description

N2 BLAST Datasheet Preaction double interlock, Electric/Pneulectric c/w N 2 Blast Nitrogen generating system Self contained unit

TOTALPAC2 Integrated Fire Protection System

OPERATION & INSTALLATION MANUAL

Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual

Becoming an Expert on Dry-pipe, Preaction, and Deluge Sprinkler Systems

A. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition.

Installation Manual. Expansion Module 0100 Version 1.0 EXP HBX Control Systems Inc.

WMWLB / WMWFM / WTWLB / WTWFM Series Hydronic Heating Unit

GETZ MANUFACTURING PART # CYLINDER DRYER

MaxLite LED Round Pendant Highbay Series

SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

Nitin Ventures FZE. (A Division of Nitin Fire Protection Industries Ltd.)

TMC. Installation and Operation Manual TMC. Temperature and Pressure Monitoring for Heating and Cooling Applications. Temperature Monitoring Control

BACKUP BATTERY INSTALLATION INSTRUCTIONS

Blade Series Heat Exchanger Operation and Installation

Sentry LIQUID LEVEL GAUGE MODEL 200 or 200C OWNER MANUAL REV 1.7 SEPT08 PAGE 1 OF 12

Simple On The Outside...

SEALING FIBER SEALING COMPOUND

Carbon Monoxide (CO) Detecting Ventilation Fan Controller Model 120VC Single Relay (100/25 PPM) (200/35 PPM)

Figure 1. Figure 2. See notes 1 and 2 below.

MaxLite LED Vapor Tight Linear Fixture

INSTALLATION INSTRUCTIONS

Transcription:

Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Preaction Fire Protection Package General Description The Tyco Model DV-5 Red-E Cabinet is a pre-assembled fire protection valve package enclosed within a freestanding cabinet designed to occupy minimal floor space and to provide an aesthetically pleasing enclosure for a fire protection valve riser. The entire package is pre-wired and the water inlet and outlets to the valve riser are grooved to provide minimal installation time. The valve package includes the system (manual) shut-off control valve, automatic water control valve, and waterflow/supervisory switches. A built-in air compressor with associated controls provides an automatic air supply for use as either supervision or automatic water control valve actuation. Integral to the DV-5 Red-E Cabinet is a control panel and back-up batteries for providing electrical alarm, supervisory, and trouble functions. All switches within the cabinet are pre-wired to the control panel, making the electrical connections for power, detection circuits, and alarms the only remaining connections to complete the system. In addition to the control panel being integral to the DV-5 Red-E Cabinet, windows have been provided in the door for viewing the releasing panel functions and essential system pressure gauges. A lock for the control panel access door is standard, and a lock for the cabinet door is optional. Features and benefits are as follows: Aesthetically pleasing appearance Professionally assembled Internally wired Custom manufactured All gauges and panel display are externally visible Removable side panels for ease of maintenance Furniture grade rollers (4) are standard at bottom of cabinet The DV-5 Red-E Cabinet has been designed to readily incorporate 1-1/2 thru 8 inch (DN40 thru DN200) valve risers for the following types of preaction systems: Single Interlock Preaction Systems Electric Actuation Dry Pilot Actuation Wet Pilot Actuation Double Interlock Preaction System Electric/Electric Actuation Electric/Pneumatic Actuation notice The Model DV-5 Red-E Cabinets described herein must be installed and maintained in compliance with this document and with the applicable standards of the National Fire Protection Association, in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintaining their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Page 1 of 8 MAY, 2009 TFP1400

Page 2 of 8 TFP1400 Nominal Riser Size 1-1/2 (DN40) 2 (DN50) 3 (DN80) 4 (DN100) 6 (DN150) 8 (DN200) DIM Description Nominal Dimensions in Inches and (millimeters) (1) A Supply Header (1)(2) 1-1/2 (DN40) 2 (DN50) 3 (DN80) 4 (DN100) 6 (DN150) 8 (DN200) B System Discharge (1)(2) 1-1/2 (DN40) 2 (DN50) 3 (DN80) 4 (DN100) 6 (DN150) 8 (DN200) C Main Drain Header (1)(2) 3/4 NPT 3/4 NPT 1-1/4 NPT 2 NPT 2 NPT 2 NPT D Drip Funnel Drain (1)(2) 1 NPT 1 NPT 1-1/4 NPT 1-1/4 NPT 1-1/4 NPT 1-1/4 NPT E Cabinet Height 69-1/8 (1756) 69-1/8 (1756) 69-1/8 (1756) 77 (1956) 77 (1956) 80 (2032) F Cabinet Width 28-1/2 (812) 28-1/2 (812) 28-1/2 (812) 36-1/8 (918) 36-1/8 (918) 36-1/8 (918) G Cabinet Depth 20-1/2 (521) 20-1/2 (521) 20-1/2 (521) 28-1/8 (714) 28-1/8 (714) 32-1/8 (816) H Connection Dim 13-1/8 (333) 13-1/8 (333) 13-1/8 (333) 16 (406) 16 (406) 15 (381) J Connection Dim 10 (25) 10 (25) 10 (25) 14 (356) 14 (356) 15 (381) K Riser Takeout 69-3/4 (1772) 69-1/4 (1759) 67-1/4 (1708) 74-1/4 (1886) 75 (1905) 76 (1930) L Connection Dim 4-5/8 (118) 4-7/8 (124) 5-3/8 (137) 5-7/8 (149) 7 (178) 8 (203) M Connection Dim 10 (25) 10 (25) 10 (25) 14 (356) 14 (356) 15 (381) N Connection Dim 10-1/8 (257) 10-1/8 (257) 10-5/8 (270) 11-5/8 (295) 11-5/8 (295) 11-5/8 (295) P Connection Dim 4 (102) 4 (102) 4 (102) 6 (152) 6 (152) 6-1/2 (165) R Connection Dim 4-3/8 (111) 4-3/8 (111) 5 (127) 5-1/8 (130) 5-1/8 (130) 5-1/8 (130) S Connection Dim 11 (279) 11 (279) 10-1/2 (267) 12 (305) 12 (305) 13 (330) T Connection Dim 11 (279) 11 (279) 9 (229) 12 (305) 12 (305) 13 (330) (1) Pipe connections are Grooved except where noted by NPT thread designations. (2) All pipe connections except System Discharge are made internal to cabinet. G J Electrical Conduit Connections B F H J G K E P M D D M P N R L Supply Header L R N C A S T A C FIGURE 1 INSTALLATION DIMENSIONS AND REFERENCE POINTS

TFP1400 Page 3 of 8 SYSTEM DISCHARGE CONNECTION AUXILIARY AIR TANK SYSTEM DRAIN VALVE MAIN DRAIN VALVE LOCKING PANEL DOOR MANUAL CONTROL STATION LOCKING REMOVABLE DOOR MODEL AMD-1 AIR MAINTENANCE DEVICE MODEL DV-5 VALVE WITH DOUBLE INTERLOCK ELECTRIC/ELECTRIC PREACTION TRIM SYSTEM PRESSURE GAUGES AIR COMPRESSOR MANUAL CONTROL STATION MAIN DRAIN HEADER WATER SUPPLY HEADER MANUAL SYSTEM SHUT-OFF CONTROL VALVE DRIP FUNNEL DRAIN CONNECTION FIGURE 2 TYPICAL ASSEMBLY ARRANGEMENT (4 Inch Double Interlock Preaction System with Electric/Electric Actuation Shown) Technical Data Approvals: The 1-1/2 thru 8 inch (DN40 thru DN200) Model DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types: Single Interlock Preaction with Electric Actuation Single Interlock Preaction with Dry Pilot Actuation Single Interlock Preaction with Wet Pilot Actuation Double Interlock Preaction with Electric/Electric Actuation Double Interlock Preaction with Electric/Pneumatic Actuation The 1-1/2 thru 8 inch (DN40 thru DN200) Model DV-5 Red-E Cabinets are FM Approved with the following system types: Single Interlock Preaction with Electric Actuation Double Interlock Preaction with Electric/Electric Actuation Double Interlock Preaction with Electric/Pneumatic Actuation System Types: The Technical Data Sheets referenced in Table B provide complete details for each system type arrangement. Working Pressure Range: 20 to 250 psi (1,4 to 17,2 bar). Construction: The Red-E Cabinet is constructed of 14 gauge steel, and is free standing. The standard paint finish is bright red. The front door of the enclosure is fully hinged (and removable) to maximize access to the enclosure. All four sides of the cabinet can be removed for ease of maintenance, and furniture grade rollers at the bottom of the cabinet are standard. Internal controls that provide functions to reset a system after operation (e.g., alarm test valve, main drain valve, etc.) are individually tagged for easy identification. All prefabricated piping is Schedule 40 steel. Table A provides list of riser components and a cross reference to individual Technical Data Sheets, as well as individual component laboratory approval information. Figure 1 provides dimensional information for Red-E Cabinets, and Figure 2 illustrates the typical assembly arrangement.

Page 4 of 8 TFP1400 Description Model Data Sheet UL C-UL/ULC FM CSA System Shut-Off Valve, 1-1/2-2 (DN40-DN50) BBVSCS02 X (5) X (5) X (5) System Shut-Off Valve, 3-8 (DN80-DN200) BFV-N TFP1510 X X X Automatic Water Control Valve DV-5 TFP1305 X X X Actuation Trim Single Interlock (Electric) TFP1420 X X X Single Interlock (Dry Pilot) TFP1415 X X X Single Interlock (Wet Pilot) TFP1410 X X X Double Interlock (Electric/Electric) TFP1465 X X X Double Interlock (Electric/Pneumatic) TFP1460 X X X Pressure Alarm Switch PS10-2A X (6) X (6) X (6) Pressure Alarm Switch PS40-2A X (6) X (6) X (6) Control Panel (1) PFC-4410RC X (6) X (6) X (6) Automatic Supervisory Air Supply (2) G16AC812 TFP1620 X (7) X (7) Air Maintenance Device (3), Regulator Type AMD-1 TFP1221 X X X Air Maintenance Device (4), Switch Type AMD-2 TFP1231 X X X Nitrogen Maintenance Device (4) AMD-3 TFP1241 X X X (1) (2) (3) (4) (5) (6) (7) The Model PFC-4410RC is standard. The Red-E Cabinet may be ordered without an integral control panel. The Model G16AC812 is utilized to maintain supervisory air pressure in Single Interlock Preaction Systems with either Electric Actuation or Wet Pilot Actuation. The Model AMD-1 Air Maintenance Device, in addition to an Auxiliary Air Tank, is utilized as standard equipment in Single Interlock Preaction Systems with Dry Pilot Actuation, as well as Double Interlock Preaction Systems with Electric/Electric Actuation. In the case of Single Interlock Preaction Systems with Dry Pilot Actuation, two AMD-1 s are utilized to accomplish the two different pressure settings that are necessary for the system piping and the dry pilot line. In the case of Double Interlock Preaction Systems with Electric/Electric Actuation, one AMD-1 is utilized to maintain the system pressure. The Model AMD-2 Air Maintenance Device and Model AMD-3 Nitrogen Maintenance Device, as well as the Model AMD-1 Air Maintenance Device, are offered as options when the Red-E Cabinet is ordered without a built-in (i.e., air compressor) automatic air supply. Approvals under the name of Milwaukee Valve Company. Approvals under the name of Potter Electric Signal Company. Approvals for the Air Pump and Motor are under the name of General Blower Company, and the approvals for the Pressure Operated Switch are under the name of Furnas. TABLE A PRINCIPAL COMPONENTS TECHNICAL DATA SHEETS AND LABORATORY APPROVALS System Type Single Interlock, Electric Actuation Single Interlock, Dry Pilot Actuation Single Interlock, Wet Pilot Actuation Double Interlock, Electric/Electric Actuation Double Interlock, Electric/Pneumatic Actuation Refer To Following Technical Data Sheet (TFP) For Complete Operation Details TFP1420 TFP1415 TFP1410 TFP1465 TFP1460 TABLE B SYSTEM TYPES AND OPERATION

TFP1400 Page 5 of 8 ELECTRICAL POWER CIRCUITS FROM BUILDING BREAKER PANEL ONE CIRCUIT FOR RED-E CABINET AT 115 VAC, 1 AMP; ADDITIONAL CIRCUIT FOR AIR COMPRESSOR AS APPLICABLE DETECTION CIRCUITS AUDIBLE & VISUAL SIGNALING DEVICES REMOTE SIGNALS TO BUILDING FIRE ALARM PANEL ELECTRICAL WATER SUPPLY INLET FROM WATER SUPPLY PIPING MAIN DRAIN & DRIP FUNNEL DRAIN TO FLOOR DRAIN OR EQUIVALENT MECHANICAL SPRINKLER SYSTEM PIPING, AS WELL AS SPRINKLERS AND/OR NOZZLES FIGURE 3 SYSTEM DESIGN CONSIDERATIONS

Page 6 of 8 TFP1400 Electric/Electric Actuation Model Number Horsepower Voltage (1) System Volume, Gallons (Liters) 20 psi in 30 min. Electric/Pneumatic Actuation System Volume, Gallons (Liters) 40 psi in 30 min. OL11016AC 1/6 115, 60 Hz 290 (1095) 110 (415) OL21533AC 1/3 115, 60 Hz 475 (1795) 215 (810) OL33550AC 1/2 115/230, 60 Hz 780 (2950) 335 (1260) OL435V75AC (2) 3/4 115/230, 60 Hz 950 (3595) 435 (1650) OL610V100AC (2 ) 1 115/230, 60 Hz 1430 (5410) 610 (2300) OL900V100AC (2) 1 115/230, 60 Hz 2320 (8780) 900 (3400) OL1200V200AC (2) 1-1/2 230, 60 Hz 3040 (11500) 1200 (4540) (1) Unless otherwise specified, 115 VAC, 60 Hz is provided. (2) 4, 6, and 8 Inch (DN100, 150, and 200) cabinets only. TABLE C AIR COMPRESSOR SELECTION FOR DOUBLE INTERLOCK PREACTION SYSTEM ARRANGEMENTS BASED ON SYSTEM TYPE AND SYSTEM VOLUME Design Considerations The automatic sprinklers and/or nozzles, fire detection devices, manual pull stations, and signaling devices that are to be utilized with the Red-E Cabinet must be UL Listed, ULC Listed, C-UL Listed, or FM Approved, as applicable. With reference to Figure 3, the system designer must consider and make preparations for use of a Red-E Cabinet as follows: Adequate floor space to facilitate opening of the cabinet door. Minimum ambient temperature of 40 F/4 C. Installation of a suitably sized water supply to the water supply header Port A, Fig. 1). Installation of system piping (Port B, Fig. 1) including automatic sprinklers and/or nozzles from the Red-E cabinet outlet. Installation of drains from main drain header (Port C, Fig. 1) and drip funnel header (Port D, Fig. 1). Installation of the detection system components and alarms. Determination of air compressor size for double interlock preaction systems as a function of system type and volume. Refer to Table C. Power supply to Red-E Cabinet. Separate power supply to the air compressor. Installation The Tyco Red-E Cabinet is to be installed following the directions given in the Red-E Cabinet Installer s Manual provided with the Red-E Cabinet. Instructions pertain to the following items: Placing the cabinet Connecting the system piping Electrical connections System start-up Care and Maintenance Inspection, testing, and maintenance must be performed as in accordance with the requirements of the NFPA, and any impairment must be immediately corrected. The Tyco Red-E Cabinet does not require any regularly scheduled inspection or maintenance. The riser components enclosed within the Red-E Cabinet, however, must be maintained in accordance with their applicable technical data sheet (refer to Table A). In addition, the Control Panel and Automatic Air Supply components must be maintained in accordance with their applicable instructions provided with the Red-E Cabinet. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of any authorities having jurisdiction. The installing contractor or product manufacturer should be contacted relative to any questions. Automatic sprinkler systems are recommended to be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes. notice Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection systems must first be obtained from the proper authorities and all personnel who may be affected by this decision must be notified.

TFP1400 Page 7 of 8 Limited Warranty Products manufactured by Tyco Fire Suppression & Building Products (TFSBP) are warranted solely to the original Buyer for ten (10) years against defects in material and work manship when paid for and properly installed and maintained under normal use and service. This warranty will ex pire ten (10) years from date of ship ment by TFSBP. No warranty is given for products or components manufac tured by companies not affiliated by ownership with TFSBP or for products and components which have been subject to misuse, improper installa tion, corrosion, or which have not been installed, maintained, modified or re paired in accordance with applicable Standards of the National Fire Protec tion Association, and/or the standards of any other Authorities Having Juris diction. Materials found by TFSBP to be defective shall be either repaired or replaced, at TFSBP s sole option. TFSBP neither assumes, nor author izes any person to assume for it, any other obligation in connection with the sale of products or parts of products. TFSBP shall not be responsible for sprinkler system design errors or inac curate or incomplete information sup plied by Buyer or Buyer s repre sentatives. In no event shall TFSBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect, special or consequential dam ages, including but not limited to labor charges, regardless of whether TFSBP was informed about the possibility of such damages, and in no event shall TFSBP s liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties, express or implied, including warranties of merchantability and fitness for a par ticular purpose. This limited warranty sets forth the exclusive remedy for claims based on failure of or defect in products, materials or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full extent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. Red-E Cabinet Technical Support Technical support for the Red-E Cabinet is available by calling 888-572- 4638 during regular business hours of 8:30-12:00 & 1:00-5:00 eastern time Monday through Friday. The Red-E Cabinet Technical Support should be contacted for special request cabinet configurations or electrical connection/control panel programming inquiries. An answering service will take messages outside of the regular business hours. Ordering Procedure The Part Numbers on Page 8 are provided for standard cabinets with integral control panel, built-in automatic air supply (i.e., air compressor and controls), and galvanized pipe (except supply header which is black), nipples, and fittings. The Model DV-5 Red-E Cabinet can be provided as follows as part of a special request cabinet configuration: without the control panel without built-in automatic air supply (i.e., air compressor and controls) with an optional air/nitrogen maintenance device when ordered without built-in automatic air supply with trim black pipe, nipples, and fittings, as may be desired for AFFF systems with special size air compressors for single interlock systems with 50 Hz air compressors with supervised downstream system shut-off valve - allows for easy trip testing of the system with sight flow gage - provides a visual indication of flow through the main drain with extra capacity batteries (12V 12Ah) for longer battery time and/or systems with heavy power requirements (e.g. numerous audible signaling devices) with Class A initiating appliance circuits. This option permits the connection of Class A style wiring to the initiating zones with Class A indicating appliance circuits. This option permits the connection of Class A style wiring to the indicating zones with auxiliary relay modules to provide extra dry contacts when required -up to 4 ARM-2 modules per cabinet can be added Please contact Red-E Cabinet Technical Support group for information on special request cabinet configurations.

Page 8 of 8 TFP1400 Model DV-5 Red-E Cabinet With Single Interlock Preaction System Specify: (size) Inch Model DV-5 Red-E Cabinet with (specify actuation) single interlock preaction system riser for installation in (USA or Canada), P/N (specify). Note: For assemblies intended for use in Canada, change the A to a C. Note: Assemblies intended for use in Canada are provided with Switches and a Control Panel that are ULC Listed. Note: Electric Actuation and Wet Pilot Actuation are provided standard with the Model G16AC812 Automatic Air Supply utilizing a 1/6 HP motor. Dry Pilot Actuation is provided standard with a OL11016AC (1/6 HP) Air Compressor and Auxiliary Air Tank complete with Model AMD-1 Air Maintenance Devices. 1-1/2 INCH (USA) Electric Actuation....P/N 52-816-0-1A8 Dry Pilot Actuation....P/N 52-815-0-1A1 Wet Pilot Actuation...P/N 52-814-0-1A8 2 INCH (USA) Electric Actuation....P/N 52-826-0-1A8 Dry Pilot Actuation....P/N 52-825-0-1A1 Wet Pilot Actuation...P/N 52-824-0-1A8 3 INCH (USA) Electric Actuation....P/N 52-836-0-1A8 Dry Pilot Actuation....P/N 52-835-0-1A1 Wet Pilot Actuation...P/N 52-834-0-1A8 4 INCH (USA) Electric Actuation....P/N 52-846-0-1A8 Dry Pilot Actuation....P/N 52-845-0-1A1 Wet Pilot Actuation...P/N 52-844-0-1A8 6 INCH (USA) Electric Actuation....P/N 52-866-0-1A8 Dry Pilot Actuation....P/N 52-865-0-1A1 Wet Pilot Actuation...P/N 52-864-0-1A8 8 INCH (USA) Electric Actuation....P/N 52-886-0-1A8 Dry Pilot Actuation....P/N 52-885-0-1A1 Wet Pilot Actuation...P/N 52-884-0-1A8 Model DV-5 Red-E Cabinet With Double Interlock Preaction System and Electric/Electric Actuation Specify: (size) Inch Model DV-5 Red-E Cabinet with electric/electric actuated double interlock preaction system riser with (specify model - Table C) air compressor for installation in (USA or Canada), P/N (specify). Note: For assemblies intended for use in Canada, change the A to a C. Note: Assemblies intended for use in Canada are provided with Switches and a Control Panel that are ULC Listed. 1-1/2 INCH (USA) OL11016AC...P/N 52-818-0-1A1 OL21533AC...P/N 52-818-0-1A2 OL33550AC...P/N 52-818-0-1A3 2 INCH (USA) OL11016AC...P/N 52-828-0-1A1 OL21533AC...P/N 52-828-0-1A2 OL33550AC...P/N 52-828-0-1A3 3 INCH (USA) OL11016AC...P/N 52-838-0-1A1 OL21533AC...P/N 52-838-0-1A2 OL33550AC...P/N 52-838-0-1A3 4 INCH (USA) OL11016AC...P/N 52-848-0-1A1 OL21533AC...P/N 52-848-0-1A2 OL33550AC...P/N 52-848-0-1A3 OL435V75AC............. P/N 52-848-0-1A4 OL610V100AC...P/N 52-848-0-1A5 OL900V100AC............ P/N 52-848-0-1A6 OL1200V200AC...P/N 52-848-0-1A7 6 INCH (USA) OL11016AC...P/N 52-868-0-1A1 OL21533AC...P/N 52-868-0-1A2 OL33550AC...P/N 52-868-0-1A3 OL435V75AC............. P/N 52-868-0-1A4 OL610V100AC...P/N 52-868-0-1A5 OL900V100AC............ P/N 52-868-0-1A6 OL1200V200AC...P/N 52-868-0-1A7 8 INCH (USA) OL11016AC...P/N 52-888-0-1A1 OL21533AC...P/N 52-888-0-1A2 OL33550AC...P/N 52-888-0-1A3 OL435V75AC............. P/N 52-888-0-1A4 OL610V100AC...P/N 52-888-0-1A5 OL900V100AC............ P/N 52-888-0-1A6 OL1200V200AC...P/N 52-888-0-1A7 Model DV-5 Red-E Cabinet With Double Interlock Preaction System and Electric/Pneumatic Actuation Specify: (size) Inch Model DV-5 Red-E Cabinet with electric/pneumatic actuated double interlock preaction system riser with (specify model - Table C) air compressor for installation in (USA or Canada), P/N (specify). Note: For assemblies intended for use in Canada, change the A to a C. Note: Assemblies intended for use in Canada are provided with Switches and a Control Panel that are ULC Listed. 1-1/2 INCH (USA) OL11016AC... P/N 52-817-0-1A1 OL21533AC...P/N 52-817-0-1A2 OL33550AC... P/N 52-817-0-1A3 2 INCH (USA) OL11016AC... P/N 52-827-0-1A1 OL21533AC...P/N 52-827-0-1A2 OL33550AC...P/N 52-827-0-1A3 3 INCH (USA) OL11016AC... P/N 52-837-0-1A1 OL21533AC...P/N 52-837-0-1A2 OL33550AC...P/N 52-837-0-1A3 4 INCH (USA) OL11016AC... P/N 52-847-0-1A1 OL21533AC...P/N 52-847-0-1A2 OL33550AC...P/N 52-847-0-1A3 OL435V75AC............. P/N 52-847-0-1A4 OL610V100AC...P/N 52-847-0-1A5 OL900V100AC............ P/N 52-847-0-1A6 OL1200V200AC...P/N 52-847-0-1A7 6 INCH (USA) OL11016AC...P/N 52-867-0-1A1 OL21533AC...P/N 52-867-0-1A2 OL33550AC...P/N 52-867-0-1A3 OL435V75AC............. P/N 52-867-0-1A4 OL610V100AC...P/N 52-867-0-1A5 OL900V100AC............ P/N 52-867-0-1A6 OL1200V200AC...P/N 52-867-0-1A7 8 INCH (USA) OL11016AC... P/N 52-887-0-1A1 OL21533AC...P/N 52-887-0-1A2 OL33550AC...P/N 52-887-0-1A3 OL435V75AC............. P/N 52-887-0-1A4 OL610V100AC...P/N 52-887-0-1A5 OL900V100AC............ P/N 52-887-0-1A6 OL1200V200AC...P/N 52-887-0-1A7 2009 TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446