Study of solar-thermal collector assisted hybrid split air conditioner

Similar documents
Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Chapter 10. Refrigeration and Heat Pump Systems

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Chapter 9. Refrigeration and Liquefaction

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

Performance Analysis of Solar Assisted Cascade Refrigeration System of Cold Storage System

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

PERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

Numerical Study on Improvement of COP of Vapour Compression Refrigeration System

Thermodynamic Calculations of Two-Stage Vapor Compression Refrigeration Cycle with Flash Chamber and Separate Vapor Mixing Intercooler

Experimental Analysis Of Vapour Compression Refrigeration System With Superheating By Using R-134a, R-12, R-717 Refrigerant

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

Design & Fabrication of Hybrid Cooler

Experimental Investigation of a Hybrid Evacuated Tube Solar Collector

FABRICATION AND COMPARISON OF SOLAR WATER HEATER WITH AND WITHOUT SEMI CIRCULAR TROUGH

(Refer Slide Time: 00:00:40 min)

International Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]

Air Conditioning System with Modified Condenser Ducts and Evaporative Cooling

REVIEW OF DESIGN OF SINGLE EFFECT SOLAR POWERED VAPOUR ABSORPTION AIR CONDITIONING SYSTEM

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852

Performance investigation of Air-conditioning system using ejector as expansion device

Week 9. Refrigeration Cycles I. GENESYS Laboratory

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning

Modified Air Cooler with Split Cooling Unit

International Journal of Informative & Futuristic Research ISSN (Online):

Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System

3. (a) Explain the working of a rotary screw compressor. [10] (b) How the capacity control is achieved in refrigerant compressor?

Global Journal of Engineering Science and Research Management

Thermodynamics I. Refrigeration and Heat Pump Cycles

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

GSJ: VOLUME 6, ISSUE 6, JUNE GSJ: Volume 6, Issue 6, June 2018, Online: ISSN

ENSC 388. Assignment #6

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

An Experimental Study on Clothes Drying Using Waste Heat from Split Type Air Conditioner

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

II. OBJECTIVE OF RESEARCH

International Journal Of Core Engineering & Management (IJCEM) Volume 2, Issue 9, December 2015

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering)

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

PLEASE READ AND FOLLOW THESE INSTRUCTIONS

Adsorption refrigeration system using waste heat

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

Performance Enhancement of Mini Refrigerator with Phase Change Materials

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

Refrigeration Cycles MOHAMMAD FAISAL HAIDER. Bangladesh University of Engineering and Technology

Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

Modelling the Performance of a Diffusion Absorption Refrigeration System

Performance Assessment of Water Cooled Condenser Refrigeration System

Waghmare Tushar Ramrao, D.S.Nakate

Thermodynamics II Chapter 5 Refrigeration

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube

AIM: TO STUDY THE PERFORMANCE OF THE DOMESTIC REFRIGERATION RIG.

Enhancement of COP in Vapour Compression Refrigeration System

Experimental Investigations of Different Types of Condensers on the Performance of Household Refrigerators

A COMPARATIVE STUDY FOR RETROFITTING OF R-12 VAPOUR COMPRESSION REFRIGERATION SYSTEM BY ECO- FRIENDLY REFRIGERANTS R-134A, R-413A, R-423A

Dhulapally, Secunderabad Subject: REFRIGERATION AND AIR CONDITIONING QUESTION BANK

Performance of an Improved Household Refrigerator/Freezer

Pressure Enthalpy Charts

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

R07. Answer any FIVE Questions All Questions carry equal marks *****

EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS

Volume 4, Issue 1 (2016) ISSN International Journal of Advance Research and Innovation

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Chapter 11 REFRIGERATION CYCLES

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

Performance Optimization of the Evaporative Condenser Design

Design and development of vapor absorption refrigeration system for rural dwellers. Adekeye, T. Oyedepo, S.O and Oyebanji, J.A

Numerical Simulation of Window Air Conditioner

we will examine only the vapour compression systems transfers to the Carnot cycle can serve as the initial model of the ideal refrigeration cycle.

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

Performance Evaluation of R290 as Substitution to R22 & Mixture of Them in Vapour Compression Refrigeration System

Evacuated Tube - Solar Collector

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

CH2351 Chemical Engineering Thermodynamics II Unit V Refrigeration. Dr. M. Subramanian

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

International Journal of Research in Engineering and Innovation Vol-2, Issue-2 (2018),

EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM

Performance Evaluation of VCRS with Nested Helical Shaped Condenser by Using R134a as Refrigerant

Low GWP Refrigerants for Air Conditioning Applications

Transcription:

Study of solar-thermal collector assisted hybrid split air conditioner Chetan Brahmankar 1, Hrishikesh Bhushan 2, Akshay Ghule 3, Himanshu Ranjan 4 1,2,3,4 Dept. of mechanical engineering, Dr. D.Y Patil Institute of Technology, Maharashtra, India ---------------------------------------------------------------------***--------------------------------------------------------------------- Abstract - In this paper we used the solar thermal collector The objectives of this study are to design and integrate solar to reduce the electricity consumption of compressor. hybrid system into conventional air conditioning system, to Compressor which is the most electricity-consuming unit of air reduce air conditioning electricity consumption by up to conditioner essentially, compresses low-pressure fluid which in 45%, and to reduce electricity peak load during the day. turn gets heated. A solar collector panel can assist in heating the fluid and thus can reduce the load on the compressor, 2. EVACUATED TUBE which in turn will reduce the electricity consumption. In a typical house using air conditioners, the electricity required for cooling can be as high as 30% of the total electricity used in commercial complexes, this percentage is even higher. The study analyzed the performance of solar-thermal collector assisted hybrid split air conditioner and conventional electricity powered air conditioner, compare energy performance and evaluate energy saving due to solar-thermal collector assisted hybrid split air conditioner. Solar collector absorbs sunlight and converts to usable heat. The evacuated tube prevents the loss of heat from plate to surrounding when there is temperature difference between inside of the tube and the outside ambient air. We are able to reduce the electricity consumption of air conditioner close to 30% which in turn reduces CO 2 emission of thermal power plant. Key Words: Hybrid Air Conditioner, Evacuated tube, solar collector, Energy Saving, R410a 1. INTRODUCTION Solar energy is one of the most available forms of energy on the Earth s surface, besides; it is very promising and generous. The earth s surface receives a daily solar dose of 10E+8 KW-hr, which is equivalent to 500 000 billion oil barrels that is one thousand times any oil reserve known to man. The demand of air conditioning has greatly increased since the last decade due to the effect of climate change and global warming. High fuel price and electric tariff makes conventional air conditioner not economical in the long run. Furthermore, generating electricity from fossil fuel emits greenhouse gases and worsen the global warming. This paper presents the investigation into the feasibility of solar assisted vapour compression air conditioning system in providing thermal comfort in India. Solar energy is harvested through solar collector which provides part of compression pressure by heating the refrigerant under constant volume, thus reducing energy consumption by lowering the load on the electric compressor. A variety of technologies exist to capture solar radiation, but of particular interest of authors is evacuated tube technology. Numerous authors have noted that ETSCs have much greater efficiencies than the common FPC, especially at low temperature and isolation. For instance, Ayompe et al. Conducted a field study to compare the performance of an FPC and a heat pipe ETSC for domestic water heating system. With similar environmental conditions, the collector efficiencies were found to be 46.1% and 60.7% and the system efficiencies were found to be 37.9% and 50.3% for FPC and heat pipe ETSC, respectively. An ETC is made of parallel evacuated glass pipes. Each evacuated pipe consists of two tubes, one is inner and the other is outer tube. The inner tube is coated with selective coating while the outer tube is transparent. Light rays pass through the transparent outer tube and are absorbed by the inner tube. Both the inner and outer tubes have minimal reflection properties. The inner tube gets heated while the sunlight passes through the outer tube and to keep the heat inside the inner tube, a vacuum is created which allows the solar radiation to go through but does not allow the heat to transfer. In order to create the vacuum, the two tubes are fused together on top and the existing air is pumped out. Thus the heat stays inside the inner pipe sand collects solar radiation efficiently. Therefore, an ETSC is the most efficient solar thermal collector. An ETSC, unlike an FPC, can work under any weather conditions while it provides acceptable heat efficiency. 2.1 Why an evacuated tube solar collector (ETSC) is preferable? The single-walled glass evacuated tube is popular in Europe. Badar et al studied the thermal performance of an individual single walled evacuated tube with direct flow type coaxial piping based on analytical steady state model. Kim et al investigated the thermal performance of an ETSC with four different shaped absorbers both experimentally and numerically. Four different shapes are: finned tube (Model I), tube welded inside a circular fin (Model II), U tube welded on a copper plate (Model III) and U tube welded inside a rectangular duct.firstly, by considering only the beam radiation, the performance of a single collector tube was observed and it was found that the incidence angle has great influence on the collector 2018, IRJET Impact Factor value: 6.171 ISO 9001:2008 Certified Journal Page 2921

efficiency. Model III had the highest efficiency with small incidence angle but the efficiency of model II became higher than model III with the increment of incidence angle. The incidence angle has negligible impacts on collector performance while considering the diffuse radiation and the shadow effects and model III is found to have the best performance for all ranges of the incidence angle. 3. Solar Hybrid Air Conditioning System ------(2) Process 3-4: Throttling and expansion An irreversible throttling process in which the temperature and pressure decrease at constant enthalpy. Process 4-1: Evaporation -----(3) An internally, reversible, constant pressure heat interaction in which the refrigerant is evaporated to a saturated vapour at state point 1 --------(4) The thermal efficiency of the cycle can be calculated as: ------(5) Figure 1. Solar Hybrid Air Conditioning System Figure 1 shows the evacuated tube solar collector is installed between the compressor and condenser. The solar collector consists of high efficient vacuum tube which provides part of compression pressure and heating by further superheating the refrigerant. The higher pressure and larger temperature difference enhance the condensation process in the condenser, resulting in high pressure liquid refrigerant. This configuration greatly reduces energy consumption by reducing the load on electric compressor. 3.1 Refrigerant Cycle During refrigeration process, the refrigerant experiences huge change in thermodynamic properties and involves heat energy transfer to the surroundings through the heat exchangers [5]. During the operation of a vapour compression refrigeration system, the following processes occurs as shown in Figure 2 Process 1-2s: Compression A reversible, adiabatic (isentropic) compression of the refrigerant. The saturated vapour at state 1 is superheated to state 2. ------(1) Figure 2. T-s diagram of vapour compression refrigeration cycle 3.2 Solar Hybrid Vapour Compression Refrigeration Cycle. The evacuated tube solar collector is installed between the compressor and condenser, providing part of compression pressure and heating by further superheating the refrigerant. Figure 5 shows the parameters of solar hybrid Process 2s-3: Condensation An internally, reversible, constant pressure heat rejection in which the refrigerant is de-superheated and then condensed to a saturated liquid at state point 3. 2018, IRJET Impact Factor value: 6.171 ISO 9001:2008 Certified Journal Page 2922

3.4 Single walled glass evacuated tube The solar collector provides part of compression pressure by heating the refrigerant under constant volume. Ideal gas law states that PV=nRT, where P is absolute pressure of gas, V is volume of gas, n is number of moles of gas, R is ideal gas constant, and T is absolute temperature of gas. During the 2 nd stage compression, V, n, and R are kept constant, deriving the ideal gas law into is the input pressure, is input temperature, is the output pressure, and is output temperature. Therefore, the higher the temperature of solar collector, the higher the pressure of refrigerant. Figure 5: Diagram of solar hybrid vapour compression refrigeration cycle Where T and S are Temperature and entropy respectively Point 1: P 1, T 1 :Evapotator Outlet Point 2: P 2,T 2 :Compressor Outlet Point 3: P 3,T 3 :Solar Plate outlet Point 4: P 4,T 4 :Condenser Inlet Point 5: P 5,T 5 : Evaporator Inlet Where, P and T are Pressure and temperature. Process 1-2: Electric AC compressor Process 2-3: Solar Collector Process 3-4: Condenser Process 4-5: Expansion valve Process Process 5-1: Evaporator Figure 3. Evacuated Tube Solar Collector Evacuated tube solar collectors consists of series of glass tubes which has the air evacuated out, creating a vacuum between the glass tube surface and absorber surface. The vacuum layer eliminates heat loss through conduction and convection, leaving radiation as the only heat loss mechanism. Figure 3. Tube evacuated solar collector consists of long copper tube which directs the refrigerant flow through the evacuated tube. This allows a greater heat exchanging area which is highly desirable due to the low thermal conductivity of refrigerant vapor. 3.3 R410a Refrigerant Because of environmental and energy efficiency concerns, the air-conditioning industry has been forced to look for alternatives to long-standing fluids such as CFC's and HCFC's and examine new technologies that will allow air conditioning systems, using the next generation of refrigerants, to be more efficient in their energy consumption than their predecessors [1]. R410A is one of the most attractive potential replacements for residential small air conditioning system. The small residential air conditioner is one of the simplest vapor compression refrigeration systems: composed only of a compressor, a condenser, an evaporator, a capillary tube and related attachments. The steady state characteristics of the R4 1 OA system as well as the R22 system are well established. Figure: 4 Cross-sectional view of evacuated tube 2018, IRJET Impact Factor value: 6.171 ISO 9001:2008 Certified Journal Page 2923

It is made from two glass tubes that are fixed at both ends.the inner tube has high efficiency of selective coating which absorbs 95% sunlight.the space between the tubes is evacuated to form an insulating vacuum.the fins of aluminium which hold the heat pipe closer to glass wall which increases transfer. The solar radiation heat flux is solved using fair weather condition radiation equations, and then solar radiation load is considered as a heat source term in the energy equation. For coated glazing, the spectral transmissivity and reflectivity at any incident angle are approximated from the normal angle of incidence. Transmissivity, is given by [8]. Chart 2: pressure vs time Where P1: suction Pressure (gauge) P3: Discharge Pressure (gauge) Reflectivity is given by 4.2 Theoretical Calculations Compressor work =h 2 -h 1 =460-422 =38 kj/kg Cooling effect = h 1 -h 4 Where: (0,$(0,)) = normal transmissivity = normal reflectivity 4. CALULATION AND RESULTS 4.1 Specification for Experimental procedure: Colling capacity 0.75ton Room specification 5.7*3.3*2.8 m 3 Reading taken at set temperature at 22ºC =422-275 =147 kj/kg Theoretical COP = 3.86 4.3 Actual calculation Actual COP = (Cooling Capacity in BThU/Hr)/ (Energy consumed in Kj/Hr) = 9000/2556= 3.714 Energy meter reading for one hour(hybrid solar AC) =2556 KJ Energy consumed by conventional 2 star AC for 1 hr = 3600 Kj Energy saving achieved = 29% 5. Energy Saving: The higher the refrigerant temperature, the higher the system energy saving, thus contributing to lower power consumption. However, the maximum energy saving is limited at 160 C of refrigerant temperature at condenser inlet. The designated condenser is unable to remove any excess heat energy from the refrigerant at temperature higher than 160 C. In short, the solar compressor provide energy saving when refrigerant temperature at condenser inlet is in the range of 69.2 C up to 160 C. At refrigerant temperature lower than 69.2 C, the energy saving is solely supported by the highly efficient DC compressor. 2018, IRJET Impact Factor value: 6.171 ISO 9001:2008 Certified Journal Page 2924

Energy savings are calculated by comparing the change in enthalpy of refrigerant through the electric compressor of both conventional and solar hybrid system. Compressor energy saving, S is given by Where is refrigerant enthalpy at electric compressor outlet foe conventional system and solar hybrid system. 6. CONCLUSION: Solar air conditioning system is a great innovation which pushes solar energy leaps ahead while promoting positive impact on the environment. The system is able to achieve up to 29% energy saving during daytime, thus significantly reduces the electricity peak load during the day. The main modifications needed are AC compressor, higher capacity condenser and evacuated tube solar collector. 7. ACKNOWLEDGMENT: I take this opportunity to express my gratitude and indebtedness to my guide Prof. Arun D Sonar, Prof. Aniket Phatangare, who has been constant source of guide and inspiration in preparing his paper. I also thankful to Everyone who helped me to completing the paper work and those who have directly or indirectly helped for completion of this Report I completing this Paper work successfully. 8. REFERENCES: [1] M. Khalaji Assadi, S. I. Gilani and T. C. Jun Yen, DESIGN a solar hybrid air conditioning compressor system,edp Sciences, 2016 [2] V Mittal,KS Kasana,NS Thakur, The study of solar absorption air-conditioning systems, November 2005 2925. [3] Masaya Okumiya, Takuya Shinoda, Makiko Ukai, Hideki Tanaka, Mika Yoshinaga, Kazuyuki Kato Toshiharu Shimizu, Performance analysis of the solar- thermal assisted air-conditioning system installed in an office building, 2011. [4] Etc Solar Collector Product o=overview, Apricus Inc - 2015. [5] M.A.Sabiha a, R.Saidur b,n, SaadMekhilef c, OmidMahiand Progress and latest developments of evacuated tube solar collectors,2014 2018, IRJET Impact Factor value: 6.171 ISO 9001:2008 Certified Journal Page 2925