PERFORMANCE IMPROVEMENT OF SPLIT AIR CONDITIONER USING EVAPORATIVE COOLING METHOD IN THE CLIMATIC CONDITION OF GUWAHATI, ASSAM

Similar documents
Performance Improvement of Air Conditioning System using Applications of Evaporative Cooling: A Review Paper

ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS

Experimental Investigations of Different Types of Condensers on the Performance of Household Refrigerators

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

International Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014 ISSN

Reduction Of Energy Consumption in Airconditioning Systems employing direct evaporative pre-cooling of Condenser air

Modified Air Cooler with Split Cooling Unit

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852

Air Conditioning System with Modified Condenser Ducts and Evaporative Cooling

DESIGN, DEVELOPMENT AND TESTING THE

PERFORMANCE EVALUATION OF TWO STAGE AIR COOLER IN DIFFERENT SPEED

Design and Development of Combined Direct and Indirect Evaporative Cooling System

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance Optimization of the Evaporative Condenser Design

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

INTERNATIONAL JOURNAL OF APPLIED ENGINEERING RESEARCH, DINDIGUL Volume 1, No 4, 2011

Performance investigation of Air-conditioning system using ejector as expansion device

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

Enhancement of COP in Vapour Compression Refrigeration System

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid


Purdue e-pubs. Purdue University

Recent Advances in Energy, Environment and Economic Development

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

EXPERIMENTAL STUDY OF CENTRIFUGAL HUMIDIFIER FITTED IN AN INDUSTRIAL SHED LOCATED IN TROPICAL CLIMATES

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

An Experimental Study on Clothes Drying Using Waste Heat from Split Type Air Conditioner

Two Stage Indirect/Direct Evaporative Cooling

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION (VCR) BASED AIR CONDITIONING (AC) SYSTEM FOR HOT AND DRY CLIMATIC CONDITIONS IN OMAN

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

NEW GENERATION INTELLIGENT CHILLER BOOSTER, ADIABATIC PRE-COOLING SYSTEM

Low GWP Refrigerants for Air Conditioning Applications

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Performance Assessment of Water Cooled Condenser Refrigeration System

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler

Numerical Simulation of Window Air Conditioner

Design and Development of Modified Air Cooler and Storage System

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

Performance Evaluation of Evaporated Water In Cooling Towers

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

NEW GENERATION INTELLIGENT ADIABATIC PRE-COOLING SYSTEM

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

European Researcher, 2014, Vol.(75), 5-2

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Full and Partial Load Performances of RAC and CAC Heat Pump using R-32

Adsorption refrigeration system using waste heat

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

Using Evaporative Cooling Methods for Improving Performance of an Air-cooled Condenser

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

International Journal of Informative & Futuristic Research ISSN (Online):

EFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

A study of Transient Performance of A Cascade Heat Pump System

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump

EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012

*Corresponding author;

Chapter 14, Problem 27.

Design and Experimental Studies on Modified Solar Dryer

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

A Review of Different Types of Combine Cooling System

WASTE HEAT RECOVERY FROM DOMESTIC REFRIGERATOR Soma A. Biswas 1, Sandeep M. Joshi 2 1,2 Pillai College of Engineering

Performance Study on A Window Type Air Conditioner Condenser Using Alternative Refrigerant R407C

Optimum Length of a Condenser for Domestic Vapor Compression refrigeration System

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

REVIEW ON HOT GAS DEFROSTING SYSTEM FOR VAPOR COMPRESSION REFRIGERATION SYSTEM

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Solar Drying Techniques And Performance Analysis: A Review

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Heat Transfer Enhancement using Herringbone wavy & Smooth Wavy fin Heat Exchanger for Hydraulic Oil Cooling

Performance of the Variable Refrigerant Volume Air-Conditioning System. with Heat Recovery

HVAC Fundamentals & Refrigeration Cycle

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Keywords : Evaporative cooling, Saturation efficiency, Cooling capacity, Cooling pad, Cellulose, Aspen, Coconut coir. IJSER

Analysis of a Condenser in a Thermal Power Plant for Possible Augmentation in its Heat Transfer Performance

Sustainability of Automobile Air- Conditioning System Using Refrigerant R1234yf Instead of R134a

Experimental Investigation of a Heat Pump Assisted Fluidized Bed Dryer

Experimental Analysis of Open, Simple and Modified Greenhouse Dryers for Drying Potato Flakes under Forced Convection

Transcription:

PERFORMANCE IMPROVEMENT OF SPLIT AIR CONDITIONER USING EVAPORATIVE COOLING METHOD IN THE CLIMATIC CONDITION OF GUWAHATI, ASSAM Mr. Bashab Jyoti Phukan, S.K. Deb Assistant Professor, M.E. Department, Assam Engineering College, Guwahati Professor, M.E. Department, Assam Engineering College, Guwahati. -------------------------------------------------------------------------***------------------------------------------------------------------------- ABSTRACT - The air conditioning is concerned with controlling the temperature, humidity, and velocity of air motion in an enclosed space to maintain a comfortable environment. Coefficient of performance improvement and reduction of energy consumption occurs in an air-conditioning system when retrofitted with evaporative cooling in the condenser of split AC with a cellulose evaporative cooling pad. The COP enhancement and reduction of power consumption can be done with better performance in the climatic condition of Guwahati, Assam(hot and humid climate) due to good amount of drainage cold water coming out from evaporator (indoor) unit. Experimental work is carried out to indicate the enhancement of COP and to minimize the power consumption. Keywords: COP, Evaporative cooling, Hot and Humid, Power consumption. 1. INTRODUCTION Air conditioners are generally used in the buildings for the improvement of comfort levels. To achieve this comfort we need to consume lot of energy around the world. Worldwide buildings consume about 40% of the total energy and most this energy is utilized in the purpose of heating, ventilation and air-conditioning[1].so enhancement of COP of AC and decrease in power consumption will contribute to the reduction of global energy consumption. In an air-cooled condenser the main factor for enhancement is to reduce the average surrounding temperature. Chainarong Chaktranond and Peachrakha Doungsong [2] in their studies states that if the coil temperature of a condensing unit were raised by 1º C, the COP of the air conditioner would drop by around 3%. Hazidavalloo and Eightedari[3] and Aglawe et al.[4] performed an experimental test on a window airconditioner with evaporative cooling media around the condensing coil which results 16% decrease in power consumption. Pongsakorn et al. [5] has done experimental work on an inverter air conditioner with an evaporative cooled condenser. They experimented in multiple water spray rates and with three different temperature scales in fixed ambient temperature. They found 35% enhancement of COP at a lower water spray rate of100 L/hr. Delfani et al. [6] applied indirect evaporative cooling technique to a packaged unit air conditioner. Under local conditions, they were able to achieve an increase in a cooling load up to 75% and a reduction in electrical energy consumption of 55%. F.W Yu et al. [7] experimented that coefficient of performance (COP) can be improved by using mist to pre-cool ambient air entering the condensers. Here decrease of compressor power occurs from the reduced condenser air temperature with insignificant consumption of water and pump power associated with the mist generation. A simulation analysis of an aircooled screw chiller operating under head pressure control, shows such mist pre-cooling enables the COP to increase by up to 7.7% Tianwei Wang et al. [8] experimented of air conditioning system to increase Coefficient of Performance utilizing an evaporative cooling condenser. The results indicated an inverse relation between the condenser inlet dry bulb temperature and the COP. By using the evaporative cooling condenser to precool the air, the saturation temperature drop through the condenser increased from 2.4 0 C to 6.6 0 C. It also resulted in an increase of the mass flow rate of refrigerant that went into the evaporator. This mass increase of liquid entering the evaporator consequently resulted in the increase of COP from 6.1% to 18% and power reduction up to 14.3% on the compressor. The result reveals the relation between water consumption and compressor energy saving regarding to their costs. 2018, IRJET Impact Factor value: 6.171 ISO 9001:2008 Certified Journal Page 321

P.Martinez et al. [9] done experimental study on energy performance of a split air-conditioner by using variable thickness evaporative cooling pads coupled to the condenser. Experiments are conducted in a split air-conditioning system where the condensing unit is modified by coupling different evaporative cooling pads with variable thickness. The impact of the different cooling pads on the overall performance of the air-conditioning system is experimentally determined by measuring the airflow conditions and the energy consumption of the overall air conditioning system, including both the condenser fan and the feed water recirculation pump of the cooling pads. Experimental results show that the best COP is obtained by adding a cooling pad thickness of about 100 mm. At that point the compressor power consumption is reduced by 11.4%, the cooling capacity is increased by 1.8% and finally the overall COP is increased by10.6%. 2. WORKING PRINCIPLE OF SPLIT AC WITH DIRECT EVAPORATIVE COOLING AND INDIRECT EVAPORATIVE COOLING Split AC is assembly of two main units. Evaporator or indoor unit and Condenser or outdoor unit. Generally aircooled condensers are used in commercial split type of AC for easy and simple uses.. A strategy for improving the performance of air conditioning systems when using air-condensed units is to decrease the ambient air flow inlet temperature prior to entering the condenser coil. This is particularly useful and effective in hot, dry climates and also in regions where water scarcity influences the choice of the condensing unit and prevents the use of watercooled condensers like cooling towers. There are two methods for evaporative cooling in condensers namely direct and indirect method. In direct method water is directly injected on the condenser and provides cooling effect. This method has disadvantages of including mineral deposits and corrosion of the condenser coils. Therefore, this method has rarely been used in residential air conditioners. In the indirect method water is injected on the evaporative cooling pad which is located in the way of air over the condenser and provides cooling effect by evaporation of water. Media pads are cellulose bound cardboard structures which are crossfluted to increase the contact area between air and water. Fig.1.Schematic diagram of working of split air conditioner 2018, IRJET Impact Factor value: 6.171 ISO 9001:2008 Certified Journal Page 322

3. EXPERIMENTAL SETUP AND PROCEDURE STEP 1: (CONVENTIONAL) At first measured the ambient conditions of the air conditioner. Measurement of the temperature of evaporator exit, compressor exit, condenser exit and expander exit are taken by digital thermometer Then COP is calculated out. Further by using an ampere meter noted down the current utilised by the AC at a particular time and taking the voltage of unit as 220 V, power consumption is calculated. STEP 2: (INDIRECT COOLING) Here evaporative cooling pad is used, and placed at the backside of the outdoor unit (behind the condenser coils). The water (10.3 C) coming out of the indoor unit is made to fall through a rubber pipe on the cooling pad. Once the whole cooling pad is wet the temperature at the exit of evaporator, compressor, condenser and expander is calculated. Then COP is calculated out. Further by using an ampere meter noted down the current utilised by the AC at a particular time and taking the voltage of unit as 220 V, power consumption is calculated. STEP 3: (DIRECT COOLING) Now the cooling pad is removed. The water is allowed to fall directly on the condenser coil. Once the whole condenser coil is wet the temperature at the exit of evaporator, compressor, condenser and expander is measured. Finally the COP is calculated out. Further by using an ampere meter noted down the current utilised by the AC at a particular time and taking the voltage of unit as 220 V, power consumption is calculated. 2018, IRJET Impact Factor value: 6.171 ISO 9001:2008 Certified Journal Page 323

Fig.4. Evaporative cooling pad at back side of condenser with the connection of drain pipe 4. RESULTS AND DISCUSSION As mentioned the experiment is carried out in three steps. Direct cooling, indirect cooling with the cold drainage water and the conventional method. The results obtained in the experiments for one specific air conditioner with technical conditions as given below and the measuring equipments taken as mentioned below are considered AMBIENT TEMPERATURE OUTSIDE ROOM TEMPERATURE OF OUTLET WATER VOLTAGE OF UNIT CURRENT OF UNIT 27.6 C 10.3 C 220 V 6.8 Amp STAR RATING OF AC 3 CAPACITY OF AC 1.5 TON Table.1. Basic conditions of the AC TEMPERATURE ( CELCIUS) VOLUME 17 3.8 L 24 3.2 L 30 0.5 L Table.2 Measurement of water coming out of the indoor unit litre in 1 hour PARAMETERS TEMPERATURE,PRESSURE, ENTHALPY OF T 1, P 1, H 1 EVAPORATOR OUTLET T 2, P 2, H 2 COMPRESSOR OUTLET T 3, P 3, H 3 CONDENSER OUTLET T 4, P 4, H 4 EXPANSION OUTLET Table.3. Notation of parameters PARAMETERS UNITS TEMPERATURE (T) DEGREE CELCIUS PRESSURE (P) Bar ENTHALPY (H) KJ/Kg Table.4. Units of parameters 2018, IRJET Impact Factor value: 6.171 ISO 9001:2008 Certified Journal Page 324

Table.5. Experiment reading for conventional cycle TIME T 1 T 2 T 3 T 4 30 minutes 18 45 17 13 60 minutes 18 49 18 14 TIME P 1 P 2 P 3 P 4 30 minutes 8.6 18 8.35 7.44 60 minutes 8.6 19 8.6 7.66 TIME H 1 H 2 H 3 H 4 30 minutes 411.33 430 220.38 220.38 60 minutes 411.33 434 221.61 221.61 Table.6. Experiment reading of indirect evaporative cycle TIME T 1 T 2 T 3 T 4 30 minutes 10.2 34 13 8.3 60 minutes 8.4 33 13 7.4 2018, IRJET Impact Factor value: 6.171 ISO 9001:2008 Certified Journal Page 325

TIME P 1 P 2 P 3 P 4 30 minutes 6.41 13.21 7.44 6.81 60 minutes 6.50 12.87 7.44 6.31 TIME H 1 H 2 H 3 H 4 30 minutes 408.84 425 215.50 215.50 60 minutes 408.20 428 215.50 215.50 Table.7. Experiment reading of direct cooling cycle TIME T 1 T 2 T 3 T 4 30 minutes 11.4 31 12.5 8.4 60 minutes 10.4 30 12.5 7.3 TIME P 1 P 2 P 3 P 4 30 minutes 7.10 12.23 7.33 6.50 60 minutes 6.90 11.91 7.33 6.31 TIME H 1 H 2 H 3 H 4 30 minutes 409.30 421 214.40 214.40 60 minutes 409 425 214.40 214.40 CALCULATION OF COP FOR CONVENTION COOLING CYCLE- For 30 minutes- Power consumption= W =VI =220*6.8= 1.49Kw Mass flow rate = W/ (H2-H1) = 1.49/ (430-411.33) = 0.079 kg/s Refrigerating Effect =q = H1-H3 = (411.33-220.38) = 190.95 KJ/s COP = (H1-H3)/ (H2-H1) = 10.22 For 60 minutes- Power consumption= W =VI =220*6.8= 1.49Kw Mass flow rate = W/ (H2-H1) = 1.49/ (434-411.33) = 0.065 kg/s Refrigerating Effect =q = H1-H3 = (411.33-221.61) = 189.72 KJ/s COP = (H1-H3)/ (H2-H1) = 8.36 FOR EVAPORATIVE COOLING PAD CYCLE- For 30 minutes- Power consumption= W =VI =220*5.8= 1.27Kw Mass flow rate = W/ (H2-H1) = 1.27/ (425-408.84) = 0.078 kg/s Refrigerating Effect =q = H1-H3 = (408.84-215.50) = 193.34 KJ/s COP = (H1-H3)/ (H2-H1) = 11.95 2018, IRJET Impact Factor value: 6.171 ISO 9001:2008 Certified Journal Page 326

For 60 minutes- Power consumption= W =VI =220*5.8= 1.27Kw Mass flow rate = W/ (H2-H1) = 1.27/ (428-408.20) = 0.064 kg/s Refrigerating Effect =q = H1-H3 = (408.20-215.50) = 192.7 KJ/s COP = (H1-H3)/ (H2-H1) = 9.73 FOR DIRECT COOLING CYCLE- For 30 minutes- Power consumption= W =VI =220*5.5= 1.21Kw Mass flow rate = W/ (H2-H1) = 1.21/ (421-409.3) = 0.103 kg/s Refrigerating Effect =q = H1-H3 = (409.3-214.40) = 194.9 KJ/s COP = (H1-H3)/ (H2-H1) = 16.65 For 60 minutes- Power consumption= W =VI =220*5.5= 1.21Kw Mass flow rate = W/ (H2-H1) = 1.21/ (425-409.0) = 0.075 kg/s Refrigerating Effect =q = H1-H3 = (409.0-214.40) = 194.6 KJ/s COP = (H1-H3)/ (H2-H1) = 12.16 COOLING METHOD TIME COP CONVENTIONAL 30 minutes 10.22 60 minutes 8.36 EVAPORATIVE 30 minutes 11.95 60 minutes 9.73 DIRECT 30 minutes 16.65 60 minutes 12.16 Table.8. Comparison of COP 5. CONCLUSION The application of evaporative cooling in the small size refrigeration system was emphasized for regions of very hot and humid weather condition. The performance of air conditioner was experimentally investigated with and without media pad evaporative cooling on the condenser and it is found that- By applying evaporative cooling the condenser pressure of conventional AC of capacity 1.5 ton (3 star) reduces from 18 bar to 13.21bar in 30 minutes and 19 bar to 12.87 bar in 60 minutes. The pressure in the evaporator reduces from 7.44 bar to 6.81 bar in 30 minutes and 7.66 bar to 6.31 bar in 60 minutes. This pressure reduction is the indication of power reduction in the system and COP increases as following- a. In evaporative cooling method COP increases from 10.22 (conventional) to 11.95 in 30 minutes. b. In evaporative cooling method COP increases from 8.36 (conventional) to 9.73 in 60 minutes. c. In direct cooling method COP increases from 10.22(conventional) to 16.65 in 30 minutes. d. In direct cooling method COP increases from 10.22(conventional) to 12.16 in 60 minutes. 2018, IRJET Impact Factor value: 6.171 ISO 9001:2008 Certified Journal Page 327

REFERENCES [1] M. O. Abdeen, Energy, environment and sustainable development, Renewable and Sustainable Energy Reviews, vol. 12, pp. 2265 2300, 2008. [2] Chainarong Chaktranond and Peachrakha Doungsong An Experimental evaluation of energy saving in a split type air conditioner with evaporatively cooling system International transaction Journal of Engineering Management and Applied Sciences and Technologies (2010) Volume 1 No 1, 009-018. [3] E. Hajidavalloo, H. Eghtedari, Performance improvement of air-cooled refrigeration system by using evaporative cooled air condenser, International Journal of Refrigeration 33 (2010) 982 988. [4] K.R. Aglawe, M.S. Matey, N.P. Gudadhe, Experimental analysis of window air conditioner using evaporative cooling, International Journal of Engineering Research & Technology (2013). [5] Pongsakorn Sarntichartsak, Sirichai Thepa, Modeling and experimental study on the performance of an inverter air conditioner using R-410a with evaporatively cooled condenser, Applied Thermal Engineering 51 (2013) 597 610. [6] Delfani Shahram, et al., Energy saving potential of an indirect evaporative cooleras a pre-cooling unit for mechanical cooling systems in Iran, Energy and Build-ings 42 (11) (2010) 2169 2176 [7] F.W. Yu, K.T. Chan, Modelling of improved energy performance of air-cooled chillers with mist pre-cooling, International Journal of Thermal Sciences 48 (2009) 825 836. [8] Tianwei Wang, Chenguang Sheng, A.G. Agwu Nnanna, Experimental investigation of air conditioning system using evaporative cooling condenser, Energy and buildings 81 (2014) 435 443. [9] P. Martinez J. Ruiz, C.G. Cutillas, P.J. Martinez, A.S. Kaiser, M. Lucas, Experimental study on energy performance of a split air-conditioner by using variable thickness evaporative cooling pads coupled to the condenser, Applied Thermal Engineering (2016). 2018, IRJET Impact Factor value: 6.171 ISO 9001:2008 Certified Journal Page 328