Performance Analysis of a Solid Desiccant Air Dehumidifier

Similar documents
Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Indoor Air of a Double-Storey Residential House in Malaysia

Recent Advances in Energy, Environment and Economic Development

Impact of indirect evaporative air cooler type on the performance of desiccant systems

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

Principles of Active Desiccant Operation. Presented by Tom Peterson, CEO and Founder. Climate by Design International

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

Computerized Simulation of Automotive Air-Conditioning System: A Parametric Study

EXPERIMENTAL STUDY OF WATER DESALINATION BASED ON HUMIDIFICATION- DEHUMIDIFICATION PROCESS VIA HEAT PUMP

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

INDOOR HUMAN THERMAL COMFORT OPTIMAL CONTROL WITH DESICCANT WHEEL COOLING SYSTEM

Thermal Performance Enhancement of Inclined Rib Roughness Solar Air Heater

Experimental study on mass transfer comparison of two liquid desiccants aqueous solutions

A Study of Drying Uniformity in a New Design of Tray Dryer

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

ANALYSIS OF DESICCANT COOLING SYSTEM

ISSN: [Ghatol* et al., 6(12): December, 2017] Impact Factor: 4.116

Humidity Control Systems for Civil Buildings in Hot Summer and Cold. Winter Zone in China

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts

Internal flow Patterns of the Horizontal Heat Mode Closed-Loop Oscillating Heat Pipe with Check Valves (HHMCLOHP/CV)

Experimental Study of Direct Contact Condensation of Steam on Water Droplets

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

Desiccant Cooling with Solar Energy

developed, and parametric studies are conducted with the model. Based on the parameter study results, a dehumidification performance diagram is propos

K.F. Fong *, C.K. Lee, T.T. Chow

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

PERFORMANCE ANALYSIS OF A RE-CIRCULATING HEAT PUMP DRYER

Feasibility Analysis of Regeneration of Silica Gel Used in Dehumidification Process of Air Conditioning by the Condenser Waste Heat of Air Conditioner

ADVANCES IN SOLAR ASSISTED DRYING SYSTEMS FOR MARINE AND AGRICULTURAL PRODUCTS

Experimental & Analytical Investigation on Modified Solar Dryer with Recirculation of Air

Cold Storage Warehouse Dock Parametric Study

Optimization of Moisture condensation rate of Liquid Desiccant Dehumidifier through Genetic Algorithm

Heat pump and energy recovery systems

A Statistical Analysis of a Liquid Desiccant Dehumidifier/Regenerator in an Air Conditioning System

Development of a Psychrometric Test Chamber. Michael J. Swedish. Associate Professor Mechanical Engineering Department Milwaukee School of Engineering

Field Test of Combined Desiccant-Evaporator Cycle Providing Lower Dew Points and Enhanced Dehumidification

Experimental Study on Waste Heat Recovery from the Pyrolysis Stack using Heat Pipe

EXPERIMENTAL PERFORMANCE ANALYSIS OF SOLAR AIR HEATER WITH THREE DIFFERENT MODIFICATIONS IN ABSORBER PLATE

Drying of Fruits, Vegetables, Spices and Medicinal Plants with a Mixed-Mode Solar Drying System with Internal Reflectors

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

*Corresponding author;

TDSHS Air Change Requirements and the Basics of Psychrometrics. Presented by: Aric Murray December 06, 2013

Energy Consumption Reduction of AHU using Heat Pipe as Dehumidifier

Experimental Investigation to Assess the Performance of Desiccant Integrated Chilly Dryer

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Experimental study of an energy efficient hybrid system for surface drying

Experimental Performance of Solar Collector cum Regenerator for Coupling with a Liquid Desiccant Cooling System

THE PSYCHROMETRIC CALCULATOR By: Stanley F. Gallos, The Bastian-Blessing Company INTRODUCTION PROPERTIES OF THE RSES CALCULATOR

Experimental Research on Monomial Cooling Measure of Greenhouse in Summer

DESIGN AND CONSTRUCTION OF FORCED/NATURAL CONVECTION SOLAR VEGETABLE DRYER WITH HEAT STORAGE

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

Bench Top Cooling Tower H893

Development of a Sorption Assisted Air Conditioning System Driven by a Solar Air Collector

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Experimental Study on Performance of Double pipe Length on Instantaneous Air Source Heat Pump Water Heater. Yin Shaoyou 1, a

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Review on Waste Heat Recovery Techniques in Air Conditioning Application

A study of Transient Performance of A Cascade Heat Pump System

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

A660 Air Conditioning Laboratory Unit

Performance of solid desiccant-based evaporative cooling system under the climatic zones of India

CHAPTER 2 EXPERIMENTAL APPARATUS AND PROCEDURES

White Paper Dehumidification in Humid Climates - A Theoretical Case Study

Effect of Parameters on Internal Flow Patterns of a Top Heat Mode Closed-loop Oscillating Heat Pipe with Check Valves (THMCLOHP/CV)

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant

Thermal Performance of a Loop Thermosyphon

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING

EXPERIMENTAL STUDY OF AIR FLOW RATE EFFECTS ON HUMIDIFICATION PARAMETERS WITH PREHEATING AND DEHUMIDIFICATION PROCESS CHANGING

Evaluation of Sorbents at Elevated Temperatures for Downhole Application

Experimental study of hybrid loop heat pipe using pump assistance for high heat flux system

Energetic vs. Exergetic Efficiency of Food Drying Via Forced Convection with and without Electrohydrodynamic Enhancement

EXPERIMENTAL INVESTIGATION OF DIRECT EVAPORATIVE COOLER WITH HEMP AND ABACA COOLING PAD MATERIAL

Measurement of internal pressure and thermal performance in a closed-loop oscillating heat-pipe with check valves (CLOHP/CV)

DESIGN, FABRICATION & PERFORMANCE ANALYSIS OF SOLAR AIR HEATER

Access from the University of Nottingham repository: %20paper_v8.

Experimental Investigation of the Padding Tower 1. for Air Dehumidifier

Specific Energy Consumption of Heat Pump Drying System

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Adding More Fan Power Can Be a Good Thing

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

Active desiccant integration with packaged rooftop HVAC equipment

Design and Experimental Studies on Modified Solar Dryer

Keywords : Evaporative cooling, Saturation efficiency, Cooling capacity, Cooling pad, Cellulose, Aspen, Coconut coir. IJSER

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

Influences of temperature of vapour-condenser and pressure in the vacuum chamber on the cooling rate during vacuum cooling

The Use Of Attic Space For Cooling and Dehumidification

GROUND COOLING OF VENTILATION AIR FOR ENERGY EFFICIENT HOUSE IN MALAYSIA: A CASE STUDY OF THE COOLTEK HOUSE

Preliminary Findings on the Performance of a New Residential Solar Desiccant Air-Conditioner

International Journal of Advance Research in Engineering, Science & Technology SOLAR HUMIDIFIER

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

EXPERIMENTAL PERFORMANCE INVESTIGATION OF SWIRLING FLOW ENHANCEMENT ON FLUIDIZED BED DRYER

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Transcription:

Performance Analysis of a Solid Desiccant Dehumidifier H. Mohamed Kamar *, N. Kamsah, K. N. A. Ku Shuib and N. A. Mufid Faculty of Mechancial Engineering, Universiti Teknologi Malaysia, 81310 Johor Bahru, JOHOR * haslinda@mail.fkm.utm.my Abstract A desiccant air dehumidification system is widely used in many applications such as refrigeration, crops drying, food industries, pharmaceutical and air-conditioning. The thermal effectiveness is often used to represent the performance of the system. Its value depends on the psychrometric properties of the incoming air and several other parameters. This article presents an experimental study to determine the thermal performance of a compact solid desiccant air dehumidifier. The effects of percent opening combination of the control valve for the process and regeneration air ducting on the thermal performances of the dehumidifier was investigated. An experimental rig was fabricated for these purposes. It consists of a solid desiccant air dehumidifier, process and regeneration air ducts, instrumentation and data acquisition system. Experimental data were acquired under a steady-state operating condition, for three cases of control valve opening combinations. It was found that the thermal effectiveness of the air dehumidifier decreases with increasing flow velocity of the process air. At a given process air flow velocity, the thermal effectiveness for case 1 is higher than that for case 3. The difference in the thermal effectiveness between the two cases becomes smaller as the process air flow velocity increases. Copyright 2015 Penerbit - All rights reserved. Keywords: dehumidifier, Solid Desiccant System, Thermal Performance 1.0 INTRODUCTION Solid desiccant air dehumidification system is widely used in many applications such as refrigeration, crops drying, food industries, pharmaceutical and air-conditioning. There are several advantages of using this system, which includes continuous operation even during off-sunshine hours that would reduce drying time due to hot and dry air [1], environmentalconscious operation, separate control of sensible and latent loads which lead to comfortable indoor air quality. In addition, the system is a heat-driven cycle, thus it has the promise of being able to use low density energy such as natural gas, waste heat and solar energy [2]. The performance of the system depends on several operating parameters, such as desiccant wheel speed, regeneration temperature, air-flow rate, wheel thickness, sector angle and desiccant loading. This article presents an experimental study to determine the thermal performance of a compact solid desiccant air dehumidifier. The effects of percent opening combination of the control valve for the process and regeneration air ducting on the thermal performances of the dehumidifier was investigated. 5

2.0 EXPERIMENTAL SETUP AND PROCEDURE 2.1 Description of the Experimental Apparatus The air dehumidification system experimental apparatus consists of three main sections: (1) a solid desiccant air dehumidifier unit, (2) an open-loop regeneration air duct work, and (3) an open-loop process air duct work. These are illustrated in Figure 1. Figure 1: Schematic diagram of an air dehumidifier experimental apparatus. The air dehumidifier unit is a Bry- Fluted Flat Bed (FFB) Series Compact Desiccant Dehumidifier type. The schematic diagram of the air dehumidifier unit is shown in Figure 2. It consists of a solid desiccant rotor, process air inlet and outlet, regeneration air inlet and outlet, an electrical heater and a control unit. Figure 2: Schematic diagram of the dehumidifier unit [1]. 6

The open-loop regeneration air and process air ducts were made of a 100-mm diameter PVC material. Type-K thermocouples were used to measure the dry- and wet-bulb temperatures of the air at the process air inlet and outlet ducts and also at the regeneration air inlet and outlet ducts. The thermocouples have an accuracy of ±0.3 C they were calibrated by comparing their temperature readings with temperature readings from a standard mercury-in-glass thermometer having an accuracy of ±0.2 C. A Pitot tube anemometer sensor with an accuracy of ±0.5% was placed at the process air inlet ducting to measure the air velocity. All sensors were connected to a data logger furnished with PicoLog software. 2.2 Description of the Test Procedures The experiments were conducted in a room temperature environment and all data were recorded at steady-state conditions. The experiments were carried out at different combinations of control valve opening for the process and regeneration air ducts. In this study, three cases of valve opening combination were considered. In the first case, the control valves for both process and regeneration air ducts were increased in the same amount, namely from 25% to 100%, with a 25% increment. In the second case, the control valve for the process air duct was kept at 100% opening while the valve opening for the regeneration air duct was increased from 25% to 100%, with a 25% increment. In the third case, the control valve for the regeneration air duct was kept at 100% opening while the valve opening for the process air duct was increased from 25% to 100%, with a 25% increment. In each case, the dry- and wet-bulb temperatures for both the process and regeneration air were recorded. The air flow velocity for both process and regeneration air were also recorded. All readings were acquired at a steady-state operating condition. To stabilize the air dehumidifier unit and to ensure that a steady-state condition was attained, the dehumidifier unit was turned-on for a period of 30 minutes prior to each data gathering. 3.0 PERFORMANCE ANALYSIS 3.1 Performance Parameters Common parameter used to assess the performance of a solid desiccant air dehumidifier is thermal effectiveness [3 & 4]. It is defined as the ratio between the thermal energy transferred to the process air and the thermal energy supplied by the regeneration air. Assuming that the specific heat capacity, cp of both the process and generation air is the same, the thermal effectiveness of the air dehumidifier can then be expressed as, T ηt = T T T 2 1 4 3 (1) where T1 is the dry-bulb temperature of the process entering the air dehumidifier unit, T2 is temperature of the process air leaving the dehumidifier, T3 is temperature of regeneration air leaving the heater and supplied to the desiccant wheel, and finally T4 is the temperature of the regeneration air leaving the air dehumidifier unit. 3.2 Experimental Data The experimental data are tabulated in Table 1 through Table 3, as given below. The data in Table 1 were obtained when the percent opening of the control valve for both process and 7

regeneration air ducting was set at the same value, from 25% up to 100%. At each valve opening, the dry-bulb temperatures of the inlet and outlet process and regeneration air were recorded at steady-state condition. The air flow velocity was also obtained for each valve opening, using a Pitot tube apparatus. The data shown in Table 2 were obtained when the valve opening for the process air was set and maintained at 100% while the valve opening for the regeneration air was varied from 25% to 100%. Finally, the data shown in Table 3 were obtained when the control valve opening for the process air was varied from 25% to 100% while the valve opening for the regeneration air was set and maintained at 100%. Table 1: Data for similar percent opening of valve for the process and regeneration air ducts. Control Valve Opening Dry-bulb temperature ( C) Flow Velocity 25 25 32.6 47.5 62.0 46.9 6.8 5.3 50 50 33.1 47.0 61.5 47.0 7.9 5.6 75 75 33.6 46.6 60.5 46.5 8.6 5.8 100 100 30.7 45.0 61.0 45.0 9.5 6.1 Table 2: Data for 100% valve opening for the process air duct and varying percent opening for the regeneration air duct. Control Valve Opening Dry-bulb temperature ( C) Flow Velocity 100 25 30.8 49.5 61.7 42.5 9.8 4.9 100 50 31.0 48.9 61.6 43.0 9.8 5.6 100 75 30.9 47.2 61.6 44.0 9.6 6.2 100 100 30.7 45.0 61.0 45.0 9.5 6.1 Table 3: Data for varying percent opening of valve for the process air duct and 100% valve opening for the regeneration air duct. Control Valve Opening Dry-bulb temperature ( C) Flow Velocity 25 100 33 47.2 61.6 47 7.0 6.5 50 100 32.5 46.8 61.5 46.3 8.1 6.3 75 100 32.2 45.5 61.2 46.5 9.1 6.4 100 100 30.7 45.0 61.0 45.0 9.5 6.1 8

It can be observed that varying the percent opening of control valve for the process air duct directly varies the air flow velocity of the process air. Increasing the percent valve opening thus causes higher air flow velocity. 4.0 RESULTS AND DISCUSSION The thermal effectiveness of the solid desiccant air dehumidifier unit for all cases considered in this study, are shown in Table 4 through Table 6 below. Table 4: Results for similar percent opening of control valve for the process and regeneration air ducts. Control Valve Opening Flow Velocity Thermal Effectiveness 25 25 6.8 98.7 50 50 7.9 95.9 75 75 8.6 92.9 100 100 9.5 89.4 Table 5: Results for 100% control valve opening for the process air and varying percent opening for the regeneration air duct. Control Valve Opening Flow Velocity Thermal Effectiveness 100 25 9.8 97.4 100 50 9.8 96.2 100 75 9.6 92.6 100 100 9.5 89.4 Table 6: Results for varying percent opening of control valve for the process air and 100% opening for the regeneration air duct. Control Valve Opening Flow Velocity Thermal Effectiveness 25 100 7.0 97.3 50 100 8.1 94.1 75 100 9.1 90.5 100 100 9.5 89.4 The effects of flow velocity of the process air on the thermal effectiveness of the solid desiccant air dehumidifier unit (for case 1 and case 3) are illustrated in Figure 3. 9

100 98 LEGEND Case 1 Case 3 Thermal Effectiveness, 96 94 92 90 88 7 8 9 10 Velocity Figure 3: Effects of flow velocity of process air on thermal effectiveness. It can be seen that the thermal effectiveness of the air dehumidifier decreases with increasing air flow velocity of the process air. This is true for both case 1 and case 3. Also, at any given process air flow velocity, the thermal effectiveness for case 1 is higher than that for case 3. The difference in the thermal effectiveness between the two cases becomes smaller as the process air flow velocity increases. 5.0 CONCLUSION An experimental study to determine thermal effectiveness of a solid desiccant air dehumidifier unit was presented. Data were acquired at various combinations of control valve opening for the process and regeneration air. The effects of process air inlet velocity on the thermal effectiveness were examined. It was found that the thermal effectiveness of the air dehumidifier decreases with increasing air flow velocity of the process air. At any given process air flow velocity, the thermal effectiveness for case 1 is higher than that for case 3. The difference in the thermal effectiveness between the two cases becomes smaller as the process air flow velocity increases. REFERENCES [1] Misha, S., Mat, S., Ruslan, M. H., Salleh, E., &Sopian, K. (2015). Performance of a solar assisted solid desiccant dryer for kenaf core fiber drying under low solar radiation.solar Energy, 112, 194-204. [2] Chung, J. D., Lee, D. Y., & Yoon, S. M. (2009).Optimization of desiccant wheel speed and area ratio of regeneration to dehumidification as a function of regeneration temperature.solar Energy, 83(5), 625-635. [3] Daou, K., Wang, R. Z., & Xia, Z. Z. (2006). Desiccant cooling air conditioning: a review. Renewable and Sustainable Energy Reviews, 10(2), 55-77. [4] Kanoğlu, M., Çarpınlıoğlu, M. Ö., &Yıldırım, M. (2004).Energy and exergy analyses of an experimental open-cycle desiccant cooling system. Applied Thermal Engineering, 24(5), 919-932. 10