Development of centrifugal chiller and heat pump using low GWP refrigerant

Similar documents
Development of centrifugal chiller and heat pump using low GWP refrigerant

ETI-Z Series Centrifugal Chiller Applied Low GWP Refrigerant to Contribute to the Prevention of Global Warming

"ETI-Z, GART-ZE/ZEI" Centrifugal Chillers using Low-GWP Refrigerants for Full Capacity Range

High-efficiency Turbo Chiller (NART Series)

Update on Next Generation Low GWP Refrigerants for Chillers Products. Steve Kujak Director, Next Generation Refrigerant Research

Industrial Heat Pumps and Their Application Examples in Japan

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications:

High Efficiency Technologies for Small and Medium-Sized Air Conditioning Equipment Using R410A. Hitachi Appliances, Inc.

Study of R161 Refrigerant for Residential Airconditioning

R-404A Alternative with Low Compressor Discharge Temperature

Kawasaki centrifugal chiller using water as a refrigerant. Sep 26 th 2017 Kawasaki Heavy Industries, Ltd. Machinery Division Hayato Sakamoto

Scroll Chillers: Conversion from HCFC-22 to HFC-410A and HFC-407C

Current status of Japan s legislation on F-gases and RACHP using Low-GWP Refrigerants

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Selection of a refrigeration oil for the R32 refrigerant and evaluation of the compressor reliability

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

Compressor Explosion Accident at Pump-Down of Air Conditioners

International Journal of Research in Engineering and Innovation Vol-2, Issue-2 (2018),

Refrigerants & Cooling in renovation buildings

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

Chillers and Refrigerants. Purpose of Today s Presentation. Agenda. GLHN Architects & Engineers, Inc. APPA Institute Session 322 EU

Chapter 2. Alternatives to HCFCs and their Characteristics

CHAPTER 1 INTRODUCTION

R-407A R-448A R-449A

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

The analysis proceeded by adopting the ASHRAE guideline for conventional HVAC chiller applications. This guideline is summarized in Table II.

HFCs or the Old Refrigerants - what is the best Choice?

The Current Path of Refrigerants

Use of fourth generation ecofriendly refrigerants in two and three cascade refrigeration systems for reducing global warming and ozone depletion

HFO-1234yf Performance in a Beverage Cooler

Industry co-operation on Natural Refrigerant technology development Kenji Matsuda

Seminar 34 Refrigerants Today, Tomorrow, and Beyond

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

FACT SHEET 9 Large Air-Conditioning (air-to-air)

Reference Document RD-0007-E GUIDELINES FOR THE UTILIZATION OF R-404A R-452A. Page 1 of Tecumseh Products Company LLC. All rights reserved.

FACT SHEET 9 Large Air-Conditioning (air-to-air)

A Primer on HFOs. Hydrofluoro-olefins Low-GWP Refrigerants. Brett Van Horn, PhD Arkema Inc.

Brazed Plate Heat Exchanger for CO Applications

Flammability and the Low GWP Refrigerant Challenge

Midea VFD Centrifugal Chiller Technology

EVALUATION OF ALTERNATIVERS TO R404 THE MOST COMMON REFRIGERANT IN SWEDISH GROCERY STORES

A Comparison Between Refrigerants Used In Air Conditioning

DEVELOPMENT AND EVALUATION OF HIGH PERFORMANCE, LOW GWP REFRIGERANTS FOR STATIONARY AC AND REFRIGERATION

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

A: RS-45 is a non ozone depleting Drop-in replacement for R22 in most applications. A: RS-45 is a blend of R143a, R125, R134a and isobutane.

Evaluation of HCFC Alternative Refrigerants

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Chapter 10. Refrigeration and Heat Pump Systems

Low GWP Refrigerants for Air Conditioning and Chiller Applications

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

Solstice 452A (R-452A) Reduced GWP and Discharge Temperature for Transport Refrigeration, Plug-Ins and Condensing Units

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Japanese market and issue of Heat Pump Kenji Matsuda

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

Transitioning to Alternatives and Challenges in Japan

Positively Innovative R32 R32. Instructions for Use and Handling

Scroll Chillers Transition from HCFC-22 to HFCs

Current use of HFCs and HCFCs. Trends, alternatives and climate impact. YEREVAN, Armenia, May 18-19, International Institute of Refrigeration

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Featuring Ozone-safe HFC134a. Hitachi Centrifugal Chillers NEW. GXG-S Series GSG-S Series. Debut

Tribology Characteristics of HFO and HC Refrigerants with Immiscible Oils - Effect of Refrigerant with Unsaturated Bond -

APS Chiller Seminar. Don Brandt, CEM-AEE, BEAP-ASHRAE ASHRAE and IEEE Life Member 3/16/2017

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator

System Drop-in Tests of R-134a Alternative Refrigerants ARM-42a and R-1234ze(E) in an Air- Cooled Screw Chiller and a Water-cooled Centrifugal Chiller

Performance of an Improved Household Refrigerator/Freezer

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

The Development of Heat Pump Water Heaters Using CO 2 Refrigerant

Sustainability of Automobile Air- Conditioning System Using Refrigerant R1234yf Instead of R134a

Experimental study on automotive cooling and heating air conditioning system using CO 2 as a refrigerant

Technical Development Program

Assuring Reliability of Compressors Using HFC Refrigerants By Hideto NAKAO Mitsubishi Electric Corporation Amagasaki-City, Hyogo, Japan

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

COMPARISON OF HIGH TEMPERATURE HEAT PUMPS ON 4-TH GENERATION REFRIGERANTS

A refrigeration system for supermarkets using natural refrigerant CO 2

Sustainable Refrigerant Solutions for HVAC-R. Laurent Abbas, Wissam Rached, Brett Van Horn

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT

The Circulation Composition Characteristic of the Zeotropic Mixture R1234ze(E)/R32 in a Heat Pump Cycle

CHAPTER 1 INTRODUCTION

Oct. Newly Developed Refrigerants for Refrigeration, meeting Global Warming Regulations. Hitomi ARIMOTO / Product R&D Department, Chemicals Division

Be sustainable while protecting your business

Assessment of LPG as a possible alternative to R-12 in domestic refrigerators

Volume 4, Issue 1 (2016) ISSN International Journal of Advance Research and Innovation

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

Chillers for High Ambient Conditions: What Technologies and Fluids?

we will examine only the vapour compression systems transfers to the Carnot cycle can serve as the initial model of the ideal refrigeration cycle.

Daikin s Policy. and Comprehensive Actions on the Environmental Impact of

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS

Optimization of Capillary Tube Parameters in Vapour Compression System using Environmentally Friendly Refrigerant R1234yf

Featuring Ozone-safe HFC134a. Hitachi Centrifugal Chillers. NEW GXG-S Series GSG-S Series Debut

Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling

Evaluation and Development of Air-conditioners using Low GWP Refrigerant

Main Anthropogenic Sources of Greenhouse Gases Refrigerants

The 10 th Three Associations Meeting JRAIA. The Japan Refrigeration and Air Conditioning Industry Association. August 31, 2016.

*Corresponding author;

Transcription:

Development of centrifugal chiller and heat pump using low GWP refrigerant Abstract Ryosuke Suemitsu 1 *, Naoya Miyoshi 1, Yasushi Hasegawa 1, Kazuki Wajima 1, Yoshinori Shirakata 1, Kenji Ueda 1 1 Mitsubushi Heavy Industries Thermal Systems, Ltd., 2-1-1 Shinhama Arai-cho Takasago, Hyogo 676-8686 Japan The manufacture of HFCs has been restricted by increasingly stringent regulations, with the aim of reducing global warming. There is a need for low GWP refrigerants that can be used in air-conditioning and refrigeration equipment. The refrigerant R- 1233zd (E) has low toxicity, non-flammable, and a GWP of approximately 1, and these characteristics make it suitable for use in centrifugal chillers and heat pumps. We have developed a centrifugal chiller using R-1233zd (E). It is required that the compressor, heat exchanger, and other components are optimized, and the size of the chiller is minimized, but the specific gas volume of R-1233zd (E) is much larger than that of R-134a. We have designed a chiller whose size was almost the same as that of an R-134a chiller of between 150 and 700 tons. A COP 2% higher than that of the R-134a chiller was achieved. We also have been developing a centrifugal heat pump system using a low GWP refrigerant to heat pressurized hot water to 200 C, with a COP of 3.5. The most important criteria for refrigerant selection are low GWP, toxicity, flammability, and stability at high temperature. We will distribute a practical high temperature heat pump by 2023. 2017 Stichting HPC 2017. Selection and/or peer-review under responsibility of the organizers of the 12th IEA Heat Pump Conference 2017. Keywords: Low GWP refrigerant; R-1233zd (E); Centrifugal chiller; Centrifugal heat pump 1. Introduction In December 2015, the 21st Session of the Conference of the Parties to the United Nations (UN) Framework Convention on Climate Change (COP21) adopted the Paris Agreement, requiring each country to undertake long term action on worldwide decarbonization. For refrigeration and air conditioning equipment, the fluorinated greenhouse gases (F-gases) regulations in Europe, and the Act for Rationalized Use and Proper Management of CFCs and HFCs in Japan, were designed to reduce the environmental impacts of these gases. HFC refrigerants with high global warming potential (GWP), such as R245fa and R134a, have been replaced by new types of low GWP refrigerant. Several aspects of these low GWP refrigerants must be verified, including their physical properties, stability, toxicity, flammability, and cost effectiveness. The choice of refrigerant depends on the capacity, compressor type, operating temperature, and conditions of the refrigeration and air conditioning equipment. We have developed and manufactured a centrifugal chiller using the low GWP refrigerant R-1233zd(E), which is suitable for large capacity air conditioning systems. We also have been developing a heat pump system heating high temperature water. * Corresponding author. Tel.: +81-79-445-9774; fax: +81-79-445-9979. E-mail address: ryosuke_suemitsu@mth.mhi.co.jp.

1.1. Selection of alternative refrigerant The alternative refrigerant requires the following items to be used in the centrifugal chiller: Environmental factors: ODP 0.001, GWP 150, long term toxic exposure 800 ppm. Physical properties: Cycle efficiency equivalent to that of existing refrigerants. Design pressure not to be excessively high. Low toxicity and low flammability. Cost effectiveness. A range of double bond olefin refrigerants were considered. Table 1 shows a comparison of HFC and olefin refrigerants for chiller applications. The GWPs of the olefin refrigerants range from 0 to 1 (very low), and their cycle efficiencies are equivalent to those of the existing refrigerants. Table 1. Comparison of refrigerants for chiller applications Refrigerant HFCs Olefins R-245fa R-134a R-32 R-1234yf R-1234ze(E) R-1233zd(E) Global Warming Potential (GWP) *1 858 1300 677 <1 <1 1 Ozone Depletion Potential (ODP) 0 0 0 0 0 0 Flammability non non lower lower lower Non Toxicity toxicity low low low low low Safety class *2 B1 A1 A2L A2L A2L A1 Atmospheric lifetime 7.6 years 13.8 years 5.2 years 10.5 days 16.4 days 26 days Allowable concentration [ppm] 300 1000 1000 500 1000 800 Standard boiling point [ C] 15.1 26.1 51.7 29.4 19.0 18.3 Saturated pressure (@6 C) *3 [kpag] 32.1 260.7 879.8 283.9 167.3 39.1 Saturated pressure (@38 C) *3 [kpag] 133.1 861.9 2258 866.4 624.3 100.8 Saturated liquid density (@6 C) *3 [kg/m 3 ] 1389 1275 1034 1157 1222 1308 Saturated liquid density (@38 C) *3 [kg/m 3 ] 1302 1155 902.8 1042 1119 1231 Saturated vapor specific volume (@6 C) *3 [m 3 /kg] 0.241 0.056 0.037 0.047 0.069 0.277 Saturated vapor specific volume (@38 C) *3 [m 3 /kg] 0.075 0.021 0.014 0.018 0.026 0.091 Theoretical COP *4 6.86 6.58 6.38 6.31 6.56 6.93 *1: 5th IPCC *2: ASHRAE34 *3: RefProp Ver9.1 *4: Single stage cycle; evaporating temperature of 6 C, condensing temperature of 38 C, compressor efficiency of 90% R-1233zd(E) is non-flammable and of low toxicity. It can be used as a forming agent, and it offers availability, and cost effectiveness. Its physical properties are similar to R-245fa. However, the gas specific volume is about five times that of R-134a, requiring increased volume to accommodate the compressor, evaporator, condenser, and gas piping. Currently, centrifugal chillers use R-134a widely as refrigerants. A more advanced and compact chiller design would allow its replacement with centrifugal chillers of R-1233zd(E). 2. Design of centrifugal chiller using R-1233zd(E) We have improved the efficiency and reduced the size. 2.1. Compressor and motor Improved aerodynamic shape of compressor The compressor was designed for the large gas flow rate. Since a large gas flow rate tends to lower the adiabatic efficiency, computational fluid dynamics (CFD) analysis was performed to optimize the leading/trailing edges of the impeller, the blade angle distribution, the path form of the impeller inlet, and the form of the inlet guide vane. 2

Compared with systems designed for R-134a, the gas flow rate at the same impeller diameter was increased by approximately 30% and the adiabatic efficiency was improved by 3%. The volume of compressor unit was increased by approximately 40%. Direct-connected motor For R-134a, the impellers are rotated by a motor via a step-up gear, whereas in our design for R-1233zd(E), the impellers were directly mounted on the motor shaft. Since the vapor sound speed of R-1233zd(E) is lower than R-134a, the impeller diameter and the circumferential velocity is larger and the rotation speed is lower than R-134a, even if the capacity is same. The direct connected motor allows compressor unit with motor to be made more compact, and improves the performance by reducing loss as a result of eliminating the step-up gear and minimizing the number of compressor bearings. 2.2. Evaporator and condenser A shell and tube heat exchanger was adopted, and we adopted flooded type as an evaporator. Since the specific volume is larger and the differential pressure between the condenser and evaporator smaller than R-134a, the pressure drops should be cared, including (i) low temperature loss caused by refrigerant depth interrupting the evaporation, (ii) dry-out and carry-over from the liquid surface in the evaporator caused by the large gas flow, and (iii) pressure loss caused by the large refrigerant gas flow entering into the condenser. To suppress these losses, at an early stage in of the design process, we analyzed the actual chiller and measured the verification test. As a result, we achieved a smaller size and a higher performance by reducing the gas velocity in the tube bundle and arranging the tubes to control the direction of water flow. Figures 1, 2, and 3 show examples of the analysis. In the evaporator, local dry-out and carry-over were eliminated by averaging the void fraction distribution and gas velocity distribution in the tube bundle. The equivalent temperature loss due to liquid depth was suppressed by increasing the average void fraction in the tube bundle, and improved the heat exchanger. In the condenser, space was added in the tube bundle for removal of the refrigerant gas. This improved the efficiency of heat exchange with the condenser tubes. Since the evaporator pressure is below atmospheric pressure, the incoming air needed to be considered. The low velocity area was determined and a bleed pipe installed to remove these gases. Figures 4 and 5 show the performance of the heat exchanger. Compared with R-134a, the volume of the evaporator and the condenser was increased by up to 20%. The performance under the rated conditions was 10% lower for the evaporator and 20% lower for the condenser, but the improvement in the theoretical COP and the aerodynamic shape compensated for this. [ - ] Fig. 1. Void fraction distribution of evaporator 3

[m/s] [m/s] Fig. 2. Gas flow velocity distribution of evaporator [m/s] Fig. 3. Gas flow velocity distribution of condenser Fig. 4. Overall outside heat transfer coefficient of evaporator 4

Fig. 5. Overall outside heat transfer coefficient of condenser 2.3. Subcooler In the subcooler, R-134a equipment uses a brazing type heat exchanger, but a shell and tube type was adopted to reduce pressure loss on the refrigerant liquid, as R-1233zd(E) has a smaller differential pressure. The degree of sub cooling was expected to be equal to that of R-134a equipment, and the heat capacity of the subcooler was 20 kw, for a 200 tons chiller. Space was saved by laying out the tubes in a bottom of the condenser. 2.4. Economizer In the economizer, a brazing type heat exchanger is used in R-134a equipment with a two-stage compression and one-stage expansion refrigeration cycle, but a flash tank heat exchanger and a refrigeration cycle with twostage compression and two-stage expansion was adopted, again to reduce pressure loss. A larger volume than that of the R-134a chiller is necessary for vapor-liquid separation in a self-inflation heat exchanger. However, the low design pressure allows the form of the tank to be changed freely. Space could therefore be saved by using a shared wall with the condenser shell. 2.5. Oil tank The reducing pressure of the oil tank, particularly at start-up, requires the gas phase area in the oil tank to have a larger volume, because the volume of gas emitted by the lubricant oil in the tank is greater than that of the R-134a equipment. This allowed space to be saved and the necessary capacity secured by optimizing the ratio of the oil and open space, and by combining the oil tank with the condenser. 2.6. Pipe joint The saturated vapor temperature of R-1233zd(E) is 18.3 C. The evaporator of a chiller operated under standard air conditions has negative pressure, encouraging the ingress of ambient air. This risk of air ingress was reduced by minimizing the number of joints. 3. Verification of centrifugal chiller An inverter drive centrifugal chiller was manufactured, based on the principles discussed above, and its performance was tested. Table 2 shows the specifications of the centrifugal chiller and Fig. 6 shows the test equipment. Table 2. Centrifugal chiller specifications Rated capacity 200 USRt (703 kw) 5

Chilled water temperature Chilled water flow rate Cooling water temperature Cooling water flow rate power-supply voltage Starting method 12.0 C.0 C 120.7 m3/h 32.0 C 37.0 C 139.6 m3/h 400V Inverter Figure 7 shows the performance results under the conditions presented in Table 2 and disaggregated by capacity. Under the rated capacity conditions from Table 2, the COP was found to be 6.3 and the performance was 3% better than that of the existing R-134a type of the same capacity. Table 3 compares the specifications, and Table 4 the installation area, of the developed equipment and conventional R-134a equipment. The specific volume of the refrigerant gas was approximately five times greater than that of the R-134a type, and the installation area approximately 105% that of the existing type for equipment of between 150 and 700 tons. Fig. 6. Test equipment *machine rated value = 200 USRt Fig. 7. Equipment performance 6

Table 3. Comparison of centrifugal chiller specifications Model Existing Developed Rated capacity 200 USRt (703 kw) Refrigerant R-134a R-1233zd(E) Chilled water temperature 12.0 C 7.0 C Chilled water flow rate 120.7 m 3 /h Cooling water temperature 32.0 C 37.0 C Cooling water flow rate 141.5 m 3 /h 139.6 m 3 /h Power consumption 115.0 kw 111.3 kw COP 6.1 6.3 Dimensions L W H 3.7 1.5 1.8 m 3.8 1.6 1.7 m Installation area 5.55 m 2 5.83 m 2 Shipping weight 3.9 ton 4.3 ton Table 4. Comparison of installation area required Rated capacity [USRt] 250 350 500 700 Existing [m 2 ] 5.55 6.30 8.36 8.82 Installation area Developed [m 2 ] 5.83 6.61 8.48 9.10 Developed/Existing 105.0% 104.9% 101.4% 103.2% 4. Development of centrifugal chiller using R-1233zd(E) The improvement in performance compared with that of the R-134a equipment suggests that this is an effective approach to reducing global warming through improved energy efficiency. The installation area was similar to that of the existing equipment, allowing its substitution. We expect that conversion to these newer refrigerants will be driven both by demand for new installations, and replacement of existing installations. 5. Design of heat pump using low GWP refrigerant Heat pumps are increasingly being used for supply of hot water and heating in the household sector, but uptake in the industrial sector has been slower. The demand for high temperature heat and reuse of waste heat is comparatively strong in the mechanical and chemical industries, and the adoption of exhaust heat recovery heat pumps offers great potential for improved energy efficiency and a reduction in CO 2 emissions. High temperature heat pump systems capable of producing pressurized hot water at 200 C with COPs of 3.5 or more are part of the research and development program of the New Energy and Industrial Technology Development Organization (NEDO). These naturally require low GWP refrigerants capable of operating at high temperatures. 5.1. Refrigerant and lubricant oil In the selection of refrigerant and lubricant oil, the operational temperature range of the heat pump must be considered. This requires the following physical properties: Stability at high temperature: Prevention of isomerism and decomposition at the operating temperature of the heat pump. Critical point: The critical temperature should be higher than the operating temperature to improve the efficiency of the cycle. Standard boiling point: At the operating temperature, the specific volume of the refrigerant gas and the design pressure of the compressor must be optimized. To reduce the design pressure at the high temperature, an appropriate standard boiling point is selected. 7

The lubricant oil must maintain its stability at high temperatures, requiring its temperature-dependent solubility in the refrigerant, viscosity, and other factors. As a first step, we investigated the replacement of R-134a with a low GWP refrigerant in an exhaust heatrecovery heat pump heating water to 90 C. In the experiments, R-1233zd(E) was selected. Table 5 compares the HFC and olefin refrigerants used in heat pumps. We evaluated the stability of R-1233zd(E) at up to 150 C. The physical properties and temperature conditions of this refrigerant can be compared with those of existing refrigerants using a drop-in test. The lubricant oil was also selected as for the heat pump using R-1233zd(E). The polyol ester (POE) oil used with HFC refrigerants is subject to hydrolysis when used with R-1233zd(E), which includes chlorine. The chlorine also serves as an extreme-pressure additive as a ferric chloride coating is formed. Mineral oil was therefore selected because of the stability of R-1233zd(E). Table 6 shows the results of accelerated thermal stability testing for the 90 C application, demonstrating stability at 200 C, but not enough for the range from 160 C to 200 C applications. We will continue testing long term stability at high temperatures. Moreover, +25% kinetic viscosity and +12% solubility were required for the bearings of heat pumps producing pressurized hot water at 160 C. Table 5. Comparison of refrigerants for heat pump use Refrigerant HFCs Olefins R-245fa R-134a R-1234ze(E) R-1233zd(E) Global Warming Potential (GWP) *1 858 1300 <1 1 Standard boiling point [ C] 15.1 26.1 19.0 18.3 Critical temperature [ C] 154.0 101.1 109.4 166.5 Saturated pressure (@30 C) *3 [MPaA] 0.178 0.770 0.578 0.158 Saturated pressure (@90 C) *3 [MPaA] 1.006 3.244 2.476 0.833 Saturated vapor specific volume (@30 C) *3 [m 3 /kg] 0.0983 0.0266 0.0328 0.1175 Saturated vapor specific volume (@90 C) *3 [m 3 /kg] 0.0176 0.0046 0.0328 0.0225 Table 6. Thermal stability testing Test condition Heat pump cycle A two-stage compression economizer cycle is used to produce water at 90 C in existing heat pump designs. However, a high temperature heat pump using the two-stage compression economizer cycle cannot achieve the target COP, 3.5. The two-stage compression bleeding cycle shown by Fig.8 was adopted instead to achieve the target COP. The bleeding cycle is highly efficient as it uses some of the refrigerant gas discharged from the low stage compressor for intermediate heating. Aerodynamic shape of compressor The compressors were designed for a high head and large volume flow rate, to reduce the number and the capacity of the compressors. CFD analysis was used to optimize the leading edge position of the splitter and the 8 Result R-1233zd(E):oil Temperature [ C] Duration [h] air/moisture [ppm] Acid Value [koh/g] 50:50 150 168 100/100 <0.01 50:50 150 168 500/100 <0.01 50:50 150 168 1000/1000 0.03 50:50 200 168 500/1000 0.02 50:50 200 336 500/1000 0.01 A heat pump is to be developed that is capable of producing the targeted range from 160 C to 200 C. Since the stability of R-1233zd(E) is poor at 200 C, suitable refrigerants and lubricant oil need to be chosen, taking account of stability, toxicity, flammability, and physical properties at the proposed operating temperatures. We have been selecting a suitable refrigerant from several candidates. 5.1. Equipment design

blade angle distribution. Figs. 9 and 10 show the results. The compression ratio was larger by approximately 40% compared a compressor of chillers, the flow rate was larger by approximately 39%, and the adiabatic efficiency was improved by approximately 3.5%, for the same impeller diameter. Fig. 8. Two-stage compression bleeding cycle Fig. 9. Compression ratio of compressor Fig. 10. Adiabatic efficiency of compressor 6. Development of the heat pump using the low GWP refrigerant The heat pump capable of operating at high temperatures using low GWP refrigerants will be developed by these stages, 90 C, 160 C, 200 C. We focus to introduce a model capable of heating pressurized hot water to 9

200 C in practical applications by 2023. Heat pumps heating water to 90 C are applied for moderate high temperature, for example, cleaning and food processes. On the other hand, there are thermal demands from 160 C to 200 C in industrial applications, for example, chemical reaction and dried processes, etc. The development of refrigerants and lubricant oil will be conducted in parallel with that of the heat pump, to produce a complete heat system using the proposed heat pumps for those real processes. 7. Conclusions The development of low GWP refrigerants for use with cooling and heating equipment is essential. A centrifugal chiller was developed using R-1233zd(E), which has a GWP of 1(equivalent to CO 2). R- 1233zd(E) is a suitable refrigerant due to low GWP, nonflammable, low toxicity, cost effective for use in the centrifugal chillers of large heat source equipment. The design achieved an integrated performance better than that of an existing chiller using R-134a. The performance was improved by up to 3%, and the installation area required only an approximately 5% larger than the existing type. The refrigerant should be selected carefully to allow high temperature exhaust heat recovery. R-1233zd(E) was selected for heat pumps heating water to 90 C. The design has been complete and we are preparing for drop-in testing. For future work, the developments of heat pumps heating water to 90 C and higher temperatures are going to be carried out, with a final goal of operation at 200 C. We are going to carrying out the development through the measurement of the performance. Acknowledgements This work was supported the project of research and development of innovative practical use technologies for unused heat sources by New Energy and Industrial Technology Development Organization. References [1] Intergovernmental Panel on Climate Change (IPCC), Working Group I Contribution To The Ipcc Fifth Assessment Report Climate Change 2013, 2015. [2] ASHRAE, 2015 Addenda Supplement to ANSI/ASHRAE Standard 34-2013, Designation and Safety Classification of Refrigerants, 2015. [3] Mitsubishi heavy industries technical report, Vol52,No.4, 2015. [4] Miyoshi N et al. Development of Heat Exchanger for Centrifugal Chiller using HFO-1233zd(E), PRTEC- 15127, Proceedings of the First Pacific Rim Thermal Engineering Conference, 2016. [5] Miyoshi N et al. Centrifugal Chiller Using Hfo-1233zd(E), Jraia International Symposium 2016, 2016 [6] Kondou C, Koyama S. Thermodynamic assessment of high-temperature heat pumps using Low-GWP HFO refrigerants for heat recovery, Int J Refrig 2015;53:126 141. [7] Tomita I, Ibaraki S, Furukawa M, Yamada K. The Effect of Tip Leakage Vortex for Operating Range Enhancement of Centrifugal Compressor, ASME Turbo Expo 2012, ASME Paper No. GT2012-68947, 2012. 10