STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD

Similar documents
C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.

B. HI Compliance: Design, manufacture, and install pumps in accordance with HI "Hydraulic Institute Standards."

HVAC BASIC MATERIAL AND METHODS 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS

SECTION SECTION DESIGN REQUIREMENTS

D. NEMA Compliance: Provide electric motors and components which comply with NEMA standards.

SECTION STEAM AND STEAM CONDENSATE SPECIALTIES

A. ASME Compliance: Fabricate and install hydronic piping in accordance with ASME B31.9 "Building Services Piping.

SECTION LABORATORY and DE-IONIZED WATER SYSTEMS STANDARD CONSTRUCTION STANDARD

D-11 OUTLINE SPECIFICATION FOR HTHW (ABOVE GRADE) HYDRONIC PIPING

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES

D-8 OUTLINE SPECIFICATION FOR HTHW HEAT EXCHANGERS

Essex County College - West Essex Campus Addition And Renovations dib # / SECTION HYDRONIC PIPING SPECIALTIES PART 1- GENERAL

University of Delaware

A. This Section includes the following domestic water piping specialties:

.2 Section Waste Management and Disposal..5 Section Performance Verification of Mechanical Piping Systems.

UFGS (May 2010) UNIFIED FACILITIES GUIDE SPECIFICATIONS

Liquid Drainers LIQUID DRAINERS

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT

Division 23 - HVAC Switzerland Beallsville K-12. Section HYDRONIC PIPING SECTION HYDRONIC PIPING PART 1 - GENERAL

Water Fuel + Air for combustion Blowdown

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings.

FM 517 San Leon, TX Toll Free: Office: (281) Fax: (281)

DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) STEAM AND CONDENSATE PIPING AND PUMPS

SECTION DOMESTIC WATER PIPING SPECIALTIES

VALVES SECTION 15100

YARWAY PROCESS THERMODYNAMIC STEAM TRAPS SERIES 40/40D AND C250/260

SECTION PLUMBING EQUIPMENT

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

Float & Thermostatic Steam Traps for efficient condensate drainage of industrial process and HVAC equipment

SECTION STEAM CONDENSATE PUMPS

Armstrong J Series Float, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual

DESIGN STANDARDS SECTION 15600

Design and Construction Standards SECTION PLUMBING EQUIPMENT

NATURAL GAS PIPING

YALE Site Specifications AIR VENT SCHEDULE

SECTION STEAM AND CONDENSATE HEATING PIPING

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

S and SF Inverted Bucket Steam Traps Installation and Maintenance Instructions

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES

1.2 CODES AND REGULATIONS A. Sprinkler system design, equipment, materials, devices, and installation shall conform to the following:

DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)

Silhouette. Feedwater Heater. Boiler Feedwater

SECTION HYDRONIC PIPING

THERMOSTATIC STEAM TRAPS

SECTION HYDRONIC PIPING

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

SPRINKLERS TABLE OF CONTENTS

Inverted Bucket Steam Traps

SECTION PLUMBING EQUIPMENT

HYDRONIC SPECIALTIES TACO AC(F)-CA 05/08/2008

13-1. Temperature Regulator

A. Operation and Maintenance Data: For pumps to include in emergency, operation, and maintenance manuals.

TABLE OF CONTENTS STEAM TRAPS INVERTED BUCKET SERIES PAGE FLOAT AND THERMOSTATIC SERIES PAGE THERMOSTATIC THERMODISC B0 26. How to Select All 107

HEAT GENERATION 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. B. Section HVAC Basic Materials and Methods

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Our Know-How. Your Peace of Mind. Steam Solutions

PhiloWilke Partnership Addendum No. 2 A/E Project No April 2016

HYDRONIC SPECIALTIES TACO MPT Tank(s) 05/30/2012. A. Multi-Purpose Tank buffer tank, air separator, and hydraulic decoupler

SECTION STEAM CONDENSATE PUMPS

Main Steam Vents. Hoffman Specialty Regulators. How to Select Steam Vents

PT15 MATERIAL : DIMENSIONS - Nominal in inches. AVAILABLE SPARES: Disc (Packet of 5) ORDERING INFORMATION: Refer to "HOW TO ORDER" page.

SECTION HEATING AND AIR CONDITIONING PIPING SYSTEMS. A. Provisions of Division 01 apply to this section. 1. Chilled Water System.

Hoffman Specialty General Catalog

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

C. B. Trading Corporation

B. Shop Drawings: Detail fabrication of pipe anchors, hangers, special pipe support assemblies, alignment guides, expansion joints and loops,

Installation and Testing of Inverted Bucket Steam Traps Manual

REFRIGERANT PIPING

HYDRONIC SPECIALTIES TACO AC(F)-PAX 05/15/2008

WET-PIPE SPRINKLER SYSTEMS

SECTION REFRIGERANT PIPING

ADDENDUM NO. 3 March 19, 2018

Product. Add Efficiency To Your Steam Investment... Steam Traps Drain Traps Air Vents & Eliminators Accessories Piping Assemblies Replacement Kits

SECTION HEATING BOILER FEEDWATER EQUIPMENT

Packaged Steam Fired Water Heater

SECTION (15530) - REFRIGERANT PIPING

FLO-RITE-TEMP INSTANTANEOUS WATER HEATER INSTALLATION AND ADJUSTMENT INSTRUCTIONS FOR SINGLE AND DOUBLE WALL UNITS

A. This section includes design and performance information for fire protection and suppression systems.

Yarway Repairable Drip and Tracer Steam Traps Series 751/761, 711/721, 731/741, 500/546, 460/515/D3

APT and APT14 Automatic Pump Traps. for effective condensate drainage and removal

Packaged Semi-Instantaneous Steam Fired Water Heater

INSTALLATION & MAINTENANCE MANUAL FOR QuickDraw

LIQUIDATOR 450 SERIES

UNIVERSAL STYLE STEAM TRAPS WU450 Series

ESCO. Committed. Group of Companies. to help conserve Steam Energy

Series 1140 and 1141 Temperature Regulators

Mini Pump Trap. Features: n Low maintenance - No leaking seals, impeller or motor problems reducing maintenance and downtime.

1.1 This section applies to air handling units for HVAC Systems.

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

UNDP / PAPP OFFICE BUILDING RAMALLAH HVAC WORKS

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING. A. This Section includes the following sanitary drainage piping specialties:

INSTALLATION, OPERATION

UNIVERSITY OF MISSOURI Building Hydronic Piping and Pump Systems 2017 Q3

Ratio Architects, Inc. Section Refrigerant Piping

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

CONTENTS. A. Summary. Yale University Design Standards. Valves. Change History

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - "Systems and Equipment.

Transcription:

PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is to apply the principles of this section such that the University may achieve a level of quality and consistency in the design and construction of their facilities. Deviations from these guidelines must be justified through LCC analysis and submitted to the University for approval. 1.02 References: A. ANSI/ASTM B31.1 Power Piping B. ANSI/ASTM B31.9 Building Services Piping 1.03 Requirements: A. For the purposes of this standard steam systems shall be defined as follows: 1. Low Pressure Systems: 0-15 psig and below 2. High Pressure Systems: 15-165 psig and above 3. Medium Pressure Systems: 165 psig and above B. Provide low pressure steam via a two-parallel full capacity pressure reducing stations with 75/25% pressure reducing valves (PRV s). No bypass shall be provided. C. Provide a tee in the condensate receiver vent line with plugged branch, just above the receiver, for University installation of a high-level float switch. D. Provide a capped tee in the condensate return line immediately upstream of the receiver for later use by the University. E. Provide a plugged opening on the low side of any condensate receiver, for installation of a thermo well for future temperature sensor by the University. F. Arrange the inlet piping to the condensate receiver so the University can dump condensate to floor drain before it enters the receiver. G. Avoid the use of plug valves in condensate systems. H. Provide spring-assisted, silent check valves on condensate pump discharge.

I. Avoid 3-1/2 and 5-inch diameter pipe. J. Use 316 stainless steel tubing with Swagelok fittings between the discharge of all condensate pumps and the connection at the utility tunnel. K. Provide shutoff valve between the receiver and each pump. L. Provide power to pump motors via flexible cord (not conduit) with twist-lock. M. Provide shutoff valves to isolate equipment, parts of systems, or vertical risers. N. Provide high pressure steam valve 12 and larger with an equalizing bypass valve assembly. O. Provide Flexitallic Model CG spiral-wound gaskets for steam and condensate flanged piping service. PART 2: PRODUCTS 2.01 Steam Piping: A. High pressure steam: 1. Piping shall be Schedule 80 black steel piping 2. Fittings shall be extra heavy butt-welded type. Flanges shall be 300 lb. class welding neck type. B. Low and Medium pressure steam: 2.02 Steam Specialties: 1. Piping 1 and smaller shall be Schedule 80 black steel piping. Piping 1-1/2 and larger shall be Schedule 40 black steel piping. 2. Fittings on piping 2-1/2 and larger shall be extra heavy butt-welded type. Flanges shall be 150 lb. class welding neck type. Unions shall be 150 lb. class. 3. Fittings on piping 2 and smaller shall be screwed type, class 150 malleable black iron. Unions shall be 150 lb. class. A. Pressure Reducing Valves:

1. Steam pressure reducing valves shall be Spence ED (with SECO-Weld seats) or Leslie GPS-1EP. Owner to be provided with manufacturer s recommended repair kit for each steam pressure reducing valve. Pressure reducing valves 2 inches or larger shall be flanged and less than 2 inches shall be threaded. PRV pipe and fittings shall be Schedule 80, 300 lb. class, up to and including the first downstream block valve. B. Steam Traps: 1. Inverted bucket traps are to be used only when the condensate outlet is subject to backpressure. When condensate flows by gravity from the trap, a float and thermostatic trap shall be selected. Bucket traps on high-pressure steam to be Armstrong #2011, installed in Armstrong TVS-3000-3/4 -NPT-ALL- [engineer specify]-htrap valve station or approved equal. Provide a separate gate valve installed between the trap valve station and the steam line 2. Float and Thermostatic Traps shall be ASTM A126, cast iron or semi-steel body and bolted cover for 250 psig WSP; provide access to internal parts without disturbing piping; with bottom drain plug, stainless steel or bronze bellows type air vent, stainless steel or copper float, stainless steel lever and valve assembly. F&T traps used in low pressure (15psig or less) drip applications shall be rated at 30 psig to avoid lockup in event inlet pressure exceeds 15 psig. F&T traps used in process applications (coils and vessels) shall be mounted at least 10 below the process. The installation shall also include vacuum breaker sized for the application, air vent and compound pressure gauge. 3. Thermodynamic traps are preferred over inverted bucket traps for drip applications above 30 psig when condensate flows by gravity to a receiver (the typical arrangement), prevented backpressure on the trap. 4. Install Thermostatic steam traps to drain condensate from steam radiation units, and other similar terminal heating units. Pressure balanced type with ASTM A216 WCB cast steel body and bolted or screwed cover and integral ball joint union, for 300 psig WSP; monel or stainless steel bellows, stainless steel valve and seat; Integral stainless steel strainer. Freeze-proof type with cast iron body for 300 psig WSP, bronze bellows, stainless steel valve and seat, external adjustment. Bi-metallic type with ASTM A105 forged steel body and cover, for 300 psig WSP, bi-metal element with stainless steel components, integral Type 304 stainless steel strainer screen, and ¼ inch blow down valve. 5. All trap station components (traps, valves, strainers) for clean steam system shall be of 316L stainless steel construction, body and trim. C. Steam Relief Valves:

1. Relief valves 2" and smaller shall have brass bodies and arranged for screwed connections. Such relief valves shall be Crane No. 2501 or Spirax Sarco 6010 Brass Safety Valves for steam or approved equal. Bushings shall not be used. 2. Relief valves 2-1/2" and larger shall in the case of all medium and low pressure steam piping systems be arranged for flanged inlet and screwed outlet connections. Such relief valves shall be Consolidated Type 1511 or Spirax Sarco 252, ASME Standard Cast Iron Safety Valves, or approved equal. 3. The pressure at which each relief valve shall open is designated on the Drawings. When such valves are ordered by the Contractor, he shall definitely specify the pressure at which each relief valve is to be set. Each valve shall have a metal tag attached stamped with the valve identification plus the pressure setting. D. Manual Valves: 1. Low and medium pressure isolation valves shall be ball valves, Zinc plated A-105 carbon steel body and stainless steel trim, R-PTFE seats, threaded 3-piece design for pipe sizes of 2 and under (flanged for sizes above 2 ). 2. High pressure Isolation valves shall be gate valves. E. Strainers: 1. Strainers shall be A-105 or ductile iron threaded body for pipe sizes of 2 and under (flanged for sizes above 2 ), rated for system temperature and pressure, 20-mesh stainless steel screen, with full-sized blow-off valve piped to drain. 2. Exception Strainers upstream of control valves and PRV s shall have 100-mesh stainless steel screens. F. Air Vents and Vacuum Breakers: 1. Provide automatic air vents with a pressure rating equal to system classification, but not less than 125 psig. 2. Provide shut off valve for maintenance of the air vent. 3. Locate all air vents and their discharge lines in accessible locations, preferably clustered. 4. Mount vacuum breakers between control valve and equipment, in vertical position with cap on top, and at the highest point of the circuit. 5. Large coils or equipment may require more than one vacuum breaker. 2.03 Condensate Return Pump:

A. Condensate pumping units shall be Aurora Series 220 or approved equal condensate pumping units; bronze fitted centrifugal pumps with stainless-steel shafts and Viton mechanical seals with 1750-rpm motors and cast-iron receivers. Units shall come pre-wired with mechanical alternator. Receiver shall have thermometer and sight glass. Receiver shall have a drain line to floor drain. Install condensate return pumps on housekeeping pad. B. Pumps shall be capable of pumping against downstream head under all operating conditions. C. Piping shall be Schedule 80 black steel piping. D. Fittings on piping 2-1/2 and larger shall be extra heavy butt-welded type. Flanges shall be class 150 welding neck type. E. Fittings on piping 2 and smaller shall be screwed type, class 125 black cast iron. Unions shall be 250 lb class. PART 3: EXECUTION 2.01 Pipe Testing Procedures: A. Refer to Appendix for plumbing pipe testing procedures. END OF STANDARD